HVAC SYSTEM

Department Engineering & Document No. HVAC/EM/AHU-029


Maintenance

Area Bacterial Vaccine Page No. 1 of 2

1. Purpose: To determine the Bacterial Vaccine area, Air Handling Unit (BV-EM-AHU-029),
Room wise Grade classification, differential pressures, supply and return air grills details &
schematic air circulation of the Air Handling Units.

2. Scope: This document is applicable for Bacterial Vaccine area Air Handling Unit
(BV-EM-AHU-029), in M/s. Biovet Private Limited.

3. Description of AHU with Reference to connected room & class.

S.No Room Name Room Grade/ Differential Air Changes


No Classification Pressure /Hr
(mm/WC)
(Criteria:NLT)

1 Air Lock R003 D 0.0 To 0.5 20

2 Corridor-1 R004 D 0.5 To 1.0 20

3 Corridor-2 R019 C 1.0 To 2.0 40

4 Change Room 1 R005 C 1.0 To 2.0 40

5 Air Lock R021 C 2.0 To 3.0 40

4. List of Supply & Return Air Filters Connected to AHU Room Wise.

S.NO Room Room Supply Air Filter Return Air Filter


Name No (0.3μ) (10μ)
1 Air Lock R003 BV-EM-AHU-029-SA-001 BV-EM-AHU-029-RA-001

2 Corridor-1 R004 BV-EM-AHU-029-SA-002 BV-EM-AHU-029-RA-002


BV-EM-AHU-029-SA-003 BV-EM-AHU-029-RA-004
BV-EM-AHU-029-SA-004
3 Corridor-2 R019 BV-EM-AHU-029-SA-005 BV-EM-AHU-029-RA-005
BV-EM-AHU-029-SA-006 BV-EM-AHU-029-RA-006
BV-EM-AHU-029-SA-007 BV-EM-AHU-029-RA-007
BV-EM-AHU-029-SA-008 BV-EM-AHU-029-RA-008
4 Change R005 BV-EM-AHU-029-SA-010 BV-EM-AHU-029-RA-003
Room 1

5 Air Lock R021 BV-EM-AHU-029-SA-009 BV-EM-AHU-029-RA-009


HVAC SYSTEM

Department Engineering & Document No. HVAC/EM/AHU-029


Maintenance

Area Bacterial Vaccine Page No. 2 of 2

5. AHU Air Circulation Details:

This AHU air circulation is as follows

Capacity : 4195 CFM

Fresh Air : 10%

Re-circulation Air : 90%

Exhaust Air : NA

Total Supply Air : 100%

6. Schematic Air Circulation drawing

The schematic air circulation drawing of Air Handling Unit (BV-EM-AHU-029) is as per
following attachment.