You are on page 1of 1

Notes

1. THIS DRAWING IS NOT TO BE SCALED. WORK TO


FIGURED DIMENSIONS ONLY.

2. THIS DRAWING IS TO BE READ IN CONJUNCTION


WITH ALL RELEVANT SERVICES, ARCHITECTURAL,
AND STRUCTURAL DRAWINGS.

3. THIS IS NOT AN INSTALLATION DRAWING, NOR A


CO-ORDINTAION DRAWING.

4. PIPEWORK IN UNHEATED AREAS SHALL BE TRACE


HEATED FOR FROST PROTECTION

Legend
TMV THERMOSTATIC MIXING VALVE

IV ISOLATION VALVE

IV(NC) NORMALLY CLOSED ISOLATION VALVE

NRV NON RETURN VALVE

WH01 IN LINE ELECTRIC INSTANTANEOUS WATER


HEATER 15L

WH02 UN-VENTED ELECTRIC WATER HEATER

EXPANSION VESSEL

PRV PRESSURE REDUCING VALVE


ROOF
DRAIN OFF VALVE
RISER DOC

N_P004 BCWS

HOT WATER SERVICE

AVB CAT 5 WATER SERVICE

EXTENT OF TRACE HEATING ON HOT


SOLENOID VALVE OPERATED BY
WATER SUPPLY PIPEWORK
AUTOMATIC WATER HYGIENE
CAPPED FLUSH CONTROL SYSTEM
OFF EXPANSION RELIEF VALVE TO DRAIN
LCWS
CONNECTION 28Ø
FOR PRESSURE TEMPERATURE SAFETY VALVE
FUTURE SOLENOID VALVE OPERATED BY PTSV
DRAIN
AUTOMATIC WATER HYGIENE
NEAR RISER NEAR RISER FLUSH CONTROL SYSTEM ANTI-VACUUM AND AIR RELEASE VALVE
AVB
FIFTH FLOOR S_P003 S_P004 FOURTH FLOOR
15Ø SOLENOID VALVE

4N_D001 AUTOMATED STAINING 4N_D002 MANUAL STAINING DCV IV


AVB AVB EXTERNAL TRACE HEATING

DRAIN FLUSH
AUTOMATIC
AUTOMATIC AUTOMATIC 3S_D006 MICROTOMY 3S_D008 PROCESSING PIR PRESENCE DETECTOR
DFT SINK

DFT SINK

WASHER

STAINER
DRAIN FLUSH DRAIN FLUSH 22Ø 22Ø

GLASS
FC SINK POLISHER DCV DOUBLE CHECK VALVE
DOWNFLOW
SINK SINK TABLE CV
VIA TUNDISH VIA TUNDISH SINGLE CHECK VALVE

28Ø DCV DCV M


IV POLISHER METER
IV IV IV IV IV
DRAIN DRAIN
C.F. COLD FEED
DOC DOC DOC 28Ø IV IV IV IV IV IV CPR COPPER
22Ø COLD WATER SERVICES
DCV IV CWS
FOURTH FLOOR FA FROM ABOVE
DOC DOC DOC HL HIGH LEVEL
28Ø HWS HOT WATER SERVICES
CAPPED LOW LEVEL
LL
OFF DCV IV MDPE MEDIUM DENSITY POLYETHYLENE
LCWS THIRD FLOOR
MWS MAINS WATER SERVICE
CONNECTION DOC 22Ø 15Ø
28Ø 22Ø S SINK
FOR TB TO BELOW
FUTURE 28Ø 35Ø 35Ø 28Ø 28Ø 28Ø TO ABOVE
TA
35Ø 22Ø WATER CLOSET
PRV PRV WC
35Ø WHB WASH HAND BASIN
CV CV 2S_D006 CV CV DCV DCV 15Ø 2S_D003 22Ø 2S_D008 FROZEN
22Ø DFT DOWN FLOW TABLE
CUT-UP 22Ø NON GYNAE SECTION
22Ø 28Ø 22Ø 28Ø 28Ø FC FUME CUPBOARD
STR STR

DRAIN FLUSH

DRAIN FLUSH
AUTOMATIC

AUTOMATIC
MSC MICRO-BIOLOGICAL SAFETY
SINK SINK SINK SINK SINK SINK SINK SINK SINK SINK SINK SINK SINK SINK CABINET

MSC SINK

MSC SINK

MSC SINK

MSC SINK
WASHER

WASHER

WASHER

STAINER

STAINER

STAINER

STAINER
GLASS

GLASS

GLASS
NRV NRV IV IV
NRV

SINK
NRV
THIRD FLOOR

28Ø IV IV IV IV IV IV IV IV IV IV IV IV IV IV IV IV
CAPPED VIA TUNDISH
OFF DCV IV
IV IV IV
LCWS IV IV IV IV IV IV IV IV IV IV
DOC VIA
CONNECTION
FOR IV IV IV IV IV IV IV IV IV IV IV IV TUNDISH
DOC DOC DOC DOC 42Ø 35Ø DOC DOC DOC
FUTURE
15Ø 22Ø 22Ø 15Ø
35Ø
SECOND FLOOR

22Ø PRV PRV 22Ø

1S_D006 DCV DCV 1S_D001 BT


SLUICE ROOM
STR STR
SECOND FLOOR
22Ø IV IV SINK
PRV DCV STR IV
1N_D001 AUTO RRL 22Ø SINK SLUICE POLISHER
AUTOMATIC AUTOMATIC AUTOMATIC
DRAIN FLUSH DRAIN FLUSH DRAIN FLUSH HATCHING INDICATES HOT
WATER PIPEWORK TO BE TRACE NRV
SINK HEATED IV IV
VIA TUNDISH VIA TUNDISH VIA TUNDISH
22Ø

15Ø

IV IV IV
35Ø
WH02 IV
DOC 22Ø 42Ø 35Ø DOC
15Ø 15Ø
IV

FIRST FLOOR
DOC DOC DOC
22Ø 22Ø
22Ø PRV PRV
FIRST FLOOR
28Ø 0S_D001 DCV DCV 0S_D007 ISH PREP LAB 0S_D010 POC
SAMPLER 22Ø
PRV DCV STR IV
STR STR
0SN_D009 IHC LAB
IV IV SINK
AUTOMATIC
DRAIN
FLUSH STAINER STAINER SINK SINK DFT SINK SINK

35Ø 35Ø
42Ø 35Ø
15Ø

15Ø

15Ø

15Ø

15Ø

VIA TUNDISH NRV NRV NRV NRV


IV
IV IV IV IV IV IV IV IV IV IV
15Ø 15Ø 15Ø IV WH02 WH02 IV WH02 IV IV IV IV WH02
DOC 15Ø DOC DOC DOC
M M
15Ø 22Ø
IV IV
GROUND FLOOR GROUND FLOOR
35Ø
COLD WATER SUPPLY, WATER TANK ROOM 54Ø 54Ø 54Ø
22Ø IV DCV STR PRV
IV
REFER TO DWG '8090' SAFTY BS_D001 WET & FORMALIN STORE
STR 28Ø T P VALVE
VENT VENT AAV
54Ø POINT OF CONNECTION BY CONTROLS
IV IV PRV DFT SINK
PURIFIED WATER SYSTEM
IV INSTALLERS. REFER TO DWG
POTABLE POTABLE P No. 60WS-E-LGL-DR-XX-8092 35Ø EXPANSION NRV
FS WATER WATER FS IV IV
VESSEL
IV
STORAGE STORAGE BUFFER FOR HEATING IV IV
TANK TANK SYSTEM IV WH02
VESSEL REFER TO
IV IV DRG '6094
DOC
54Ø LCWS/BS/01 IV LONDONGUILD LTD
DOC DOC STR DCV IV IV ELECTRICAL CONTRACTORS
ESTABLISHED 1989
IV PRV IV PHE The Palmerston Centre
DOC
Oxford Road
BASEMENT Harrow
BASEMENT Middlesex
HA3 7RG
Tel: 020 8424 8122
Fax: 020 8424 8588

NORTH WING / WALPORT HOUSE SOUTH WING / GOLDBEATERS HOUSE


ISG

60 WHITFIELD STREET

PUBLIC HEALTH SERVICES


LABORATORY WATER
SCHEMATIC

Copyright c 2016 LONDON GUILD Ltd.