DESCRIPTION:

NGR SIZING CALCULATION FOR 11MVA TRANSFORMER AT SS-1A

ISSUED FOR: RECEIVED REVISION STATES BY GPL


INFORMATION INFORMED
APPROVAL x By : APPROVED
APPLICATION (FABRICATION) APPROVED WITH COMMENTS
Date : NOT APPROVED
Date :

Revision
Nº Date Details of revision Issued Checked Approved
A 9/20/2012 FOR APPROVAL VMM GVK
No. of pages:
2

ANSFORMER AT SS-1A

Signature:

Approved Categ/Status
19260005-CAL-EL-SS-01A003

Client: SHEET NO. 2 of 2


Project: PRED / CHKD VMM/GVK
Title: NEUTRAL GROUNDING RESISTOR SIZING CALCULATIONS REV / DATE A/20-09-12

DESIGN CALCULATION FOR SIZING OF 6.6KV NEUTRAL GROUNDING RESISTOR


(FOR 17MVA, 33/6.6KV TRANSFORMER)

1 DATA
Transformer Capacity= 11 MVA
Rated Voltage= 6600 V
Full load current at 6.6KV System= 962.28 A

2 CALCULATION
2.1 The value of Neutral Grounding resistance, Zᶰ V²/(MVAx10⁶)
(To limit the fault current to full load current)
Where,
V= Line Voltage in Volts
MVA= Capacity of Transformer
Zᶰ= 3.96 Ω
Phase to ground fault current limited to
(Refer clause no: 7.2.2 Page No: 367 of IEEE Standard: 141 for low 400 A
impedence earthing of system)

2.2 The value of Neutral Grounding resistance, Zᶰ 9.53 Ω


(To limit the fault current to 400A)=

3 NGR PARTICULARS
3.1 Value of resistance= 9.53 Ω
3.2 Duration of current rating= 10 Sec

CONCLUSION
Provide, 9.53Ω, 400A/10Sec. Neutral Grounding Resistor for 6.6KV Neutral Earthing
No. of document Rev. No. of pages:
A 2

DESCRIPTION:

NGR SIZING CALCULATION FOR 17MVA TRANSFORMER AT SS-2A

ISSUED FOR: RECEIVED REVISION STATES BY GPL


INFORMATION INFORMED
APPROVAL x By : APPROVED
APPLICATION (FABRICATION) APPROVED WITH COMMENTS
Date : NOT APPROVED
Date :

Revision
Nº Date Details of revision Issued Checked Approved
A 9/20/2012 FOR APPROVAL ECB FGI
No. of pages:
2

ANSFORMER AT SS-2A

Signature:

Approved Categ/Status
19260005-CAL-EL-SS-02A003

Client: SHEET NO.


Project: PRED / CHKD
Title: NEUTRAL GROUNDING RESISTOR SIZING CALCULATIONS REV / DATE

DESIGN CALCULATION FOR SIZING OF 6.6KV NEUTRAL GROUNDING RESISTOR


(FOR 17MVA, 33/6.6KV TRANSFORMER)

1 DATA
Transformer Capacity= 17
Rated Voltage= 6600
Full load current at 6.6KV System= 1487.16

2 CALCULATION
2.1 The value of Neutral Grounding resistance, Zᶰ V²/(MVAx10⁶)
(To limit the fault current to full load current)
Where,
V= Line Voltage in Volts
MVA= Capacity of Transformer
Zᶰ= 2.5623529412
Phase to ground fault current limited to
(Refer clause no: 7.2.2 Page No: 367 of IEEE Standard: 141 for low 400
impedence earthing of system)

2.2 The value of Neutral Grounding resistance, Zᶰ 9.53


(To limit the fault current to 400A)=

3 NGR PARTICULARS
3.1 Value of resistance= 9.53
3.2 Duration of current rating= 10

CONCLUSION
Provide, 9.53Ω, 400A/10Sec. Neutral Grounding Resistor for 6.6KV Neutral Earthing
19260005-CAL-EL-SS-02A003

2 of 2
VMM/GVK
A/20-09-12

RESISTOR

MVA
V
A

Ω
Sec
No. of document Rev. No. of pages:
A 2

DESCRIPTION:

NGR SIZING CALCULATION FOR 11MVA TRANSFORMER AT ER-A

ISSUED FOR: RECEIVED REVISION STATES BY GPL


INFORMATION INFORMED
APPROVAL x By : APPROVED
APPLICATION (FABRICATION) APPROVED WITH COMMENTS
Date : NOT APPROVED
Date :

Revision
Nº Date Details of revision Issued Checked Approved
A 9/20/2012 FOR APPROVAL ECB FGI
No. of pages:
2

ANSFORMER AT ER-A

Signature:

Approved Categ/Status
19260005-CAL-EL-SS-ERA003

Client: SHEET NO. 2 of 2


Project: PRED / CHKD VMM/GVK
Title: NEUTRAL GROUNDING RESISTOR SIZING CALCULATIONS REV / DATE A/20-09-12

DESIGN CALCULATION FOR SIZING OF 11 KV NEUTRAL GROUNDING RESISTOR


(FOR 2.5 MVA, 11 KV HT DG SET)

1 DATA
HT DG Capacity= 2.5 MVA
Rated Voltage= 11000 V
Full load current at 11 KV System= 131.22 A

2 CALCULATION
2.1 The value of Neutral Grounding resistance, Zᶰ V²/(MVAx10⁶)
(To limit the fault current to full load current)
Where,
V= Line Voltage in Volts
MVA= Capacity of DG SET
Zᶰ= 48.4 Ω
Phase to ground fault current limited to
(Refer clause no: 7.2.2 Page No: 367 of IEEE Standard: 141 for low 400 A
impedence earthing of system)

2.2 The value of Neutral Grounding resistance, Zᶰ 15.88 Ω


(To limit the fault current to 400A)=

3 NGR PARTICULARS
3.1 Value of resistance= 15.88 Ω
3.2 Duration of current rating= 10 Sec

CONCLUSION
Provide, 9.53Ω, 400A/10Sec. Neutral Grounding Resistor for 6.6KV Neutral Earthing