MLFB: 7UT6121*!B001BA0
Parameter set version: V04.04.04
Device path: C:\Documents and Settings\admin\Desktop\02-Site
Work\CONFIGURATION\Hamedan_\P7DI\GV\SD\0000000e
Author:
Creation date: 21.09.08 15:54:49
Last modified: 23.06.10 15:09:55
Operating mode: Offline
Comment:
Setting values in: Secondary value description
PRINT - CONTENTS
1 Device Configuration 3
2 Configuration - short (column-oriented) 4
2.1 Binary inputs 4
2.2 Binary outputs 4
2.3 LEDs 4
2.4 System interface 4
3 General Device Settings 5
3.1 Group Device; Group General 5
4 Power System Data 1 6
4.1 Group Power System Data 1; Group Power System 6
4.2 Group Power System Data 1; Group Transformer 6
4.3 Group Power System Data 1; Group CT's 6
4.4 Group Power System Data 1; Group Breaker 6
5 Settings groups 7
5.1 Group Differential Protection; Group General 7
5.2 Group Differential Protection; Group I-Diff 7
5.3 Group Differential Protection; Group Characteristic 7
5.4 Group Differential Protection; Group Inrush 2.HM 7
5.5 Group Differential Protection; Group Restr. n.HM 7
5.6 Group Restricted Earth Fault Protection; Group General 8
5.7 Group Restricted Earth Fault Protection; Group Settings 8
5.8 Group Measurement Supervision; Group General 8
5.9 Group Measurement Supervision; Group Balance I S1 8
5.10 Group Measurement Supervision; Group Balance I S2 8
Page 1 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15
Page 2 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15
1 Device Configuration
No. Function Scope
0103 Setting Group Change Option Disabled
0105 Protection Object 3 phase Transformer
0106 Number of Sides for Multi Phase Object 2
0107 Number of Ends for 1 Phase Busbar 7
0108 I7-CT connected to Side 1
0112 Differential Protection Enabled
0113 Restricted earth fault protection Side 1
0117 Cold Load Pickup Disabled
0120 DMT / IDMT Phase Disabled
0121 DMT / IDMT Phase Pick Up Characteristic Definite Time only
0122 DMT / IDMT 3I0 Disabled
0123 DMT / IDMT 3I0 Pick Up Characteristic Definite Time only
0124 DMT / IDMT Earth Disabled
0125 DMT / IDMT Earth Pick Up Characteristic Definite Time only
0127 DMT 1Phase Disabled
0140 Unbalance Load (Negative Sequence) Disabled
0141 Unbalance Load (Neg. Sequ.) Characteris. Definite Time only
0142 Thermal Overload Protection Disabled
0143 Thermal Overload Protec. Characteristic classical (according IEC60255)
0170 Breaker Failure Protection Disabled
0181 Measured Values Supervision Enabled
0182 Trip Circuit Supervision Disabled
0186 External Trip Function 1 Disabled
0187 External Trip Function 2 Disabled
Page 3 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15
2.3 LEDs
LEDs No. Group Information Type Configuration
1 05671 Diff. Prot Differential protection TRIP OUT L
2 05821 REF Restr. earth flt.: TRIP OUT L
6 00140 Supervision Error with a summary alarm OUT U
6 00160 Supervision Alarm Summary Event OUT U
7 00311 P.System Data 2 Fault in configuration of the Protection OUT U
Page 4 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15
Page 5 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15
Page 6 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15
5 Settings groups
5.1 Group Differential Protection; Group General
No. Settings Value Group
1201 Differential Protection ON A
1205 Increase of Trip Char. During Start ON A
1206 Inrush with 2. Harmonic Restraint ON A
1207 n-th Harmonic Restraint OFF A
1211A Diff-Prot. with meas. Earth Current S1 NO A
Page 7 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15
Page 8 of 8