SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.

10 15:10:15

HAMEDAN Factory final / 230KV / 7UT612 V4.0

MLFB: 7UT6121*!B001BA0
Parameter set version: V04.04.04
Device path: C:\Documents and Settings\admin\Desktop\02-Site
Work\CONFIGURATION\Hamedan_\P7DI\GV\SD\0000000e
Author:
Creation date: 21.09.08 15:54:49
Last modified: 23.06.10 15:09:55
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS
1 Device Configuration 3
2 Configuration - short (column-oriented) 4
2.1 Binary inputs 4
2.2 Binary outputs 4
2.3 LEDs 4
2.4 System interface 4
3 General Device Settings 5
3.1 Group Device; Group General 5
4 Power System Data 1 6
4.1 Group Power System Data 1; Group Power System 6
4.2 Group Power System Data 1; Group Transformer 6
4.3 Group Power System Data 1; Group CT's 6
4.4 Group Power System Data 1; Group Breaker 6
5 Settings groups 7
5.1 Group Differential Protection; Group General 7
5.2 Group Differential Protection; Group I-Diff 7
5.3 Group Differential Protection; Group Characteristic 7
5.4 Group Differential Protection; Group Inrush 2.HM 7
5.5 Group Differential Protection; Group Restr. n.HM 7
5.6 Group Restricted Earth Fault Protection; Group General 8
5.7 Group Restricted Earth Fault Protection; Group Settings 8
5.8 Group Measurement Supervision; Group General 8
5.9 Group Measurement Supervision; Group Balance I S1 8
5.10 Group Measurement Supervision; Group Balance I S2 8

Page 1 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15

5.11 Group Measurement; Group Measurement 8

Page 2 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15

1 Device Configuration
No. Function Scope
0103 Setting Group Change Option Disabled
0105 Protection Object 3 phase Transformer
0106 Number of Sides for Multi Phase Object 2
0107 Number of Ends for 1 Phase Busbar 7
0108 I7-CT connected to Side 1
0112 Differential Protection Enabled
0113 Restricted earth fault protection Side 1
0117 Cold Load Pickup Disabled
0120 DMT / IDMT Phase Disabled
0121 DMT / IDMT Phase Pick Up Characteristic Definite Time only
0122 DMT / IDMT 3I0 Disabled
0123 DMT / IDMT 3I0 Pick Up Characteristic Definite Time only
0124 DMT / IDMT Earth Disabled
0125 DMT / IDMT Earth Pick Up Characteristic Definite Time only
0127 DMT 1Phase Disabled
0140 Unbalance Load (Negative Sequence) Disabled
0141 Unbalance Load (Neg. Sequ.) Characteris. Definite Time only
0142 Thermal Overload Protection Disabled
0143 Thermal Overload Protec. Characteristic classical (according IEC60255)
0170 Breaker Failure Protection Disabled
0181 Measured Values Supervision Enabled
0182 Trip Circuit Supervision Disabled
0186 External Trip Function 1 Disabled
0187 External Trip Function 2 Disabled

Page 3 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15

2 Configuration - short (column-oriented)


2.1 Binary inputs
nothing allocated

2.2 Binary outputs


BO No. Group Information Type Configuration
1 05821 REF Restr. earth flt.: TRIP OUT U
2 05671 Diff. Prot Differential protection TRIP OUT U
4 00511 P.System Data 2 Relay GENERAL TRIP command OUT U
4 05671 Diff. Prot Differential protection TRIP OUT U
4 05821 REF Restr. earth flt.: TRIP OUT U

2.3 LEDs
LEDs No. Group Information Type Configuration
1 05671 Diff. Prot Differential protection TRIP OUT L
2 05821 REF Restr. earth flt.: TRIP OUT L
6 00140 Supervision Error with a summary alarm OUT U
6 00160 Supervision Alarm Summary Event OUT U
7 00311 P.System Data 2 Fault in configuration of the Protection OUT U

2.4 System interface


nothing allocated

Page 4 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15

3 General Device Settings


3.1 Group Device; Group General
No. Settings Value Group
7110 Fault Display on LED / LCD Display Targets on every Pickup All

Page 5 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15

4 Power System Data 1


4.1 Group Power System Data 1; Group Power System
No. Settings Value Group
0270 Rated Frequency 50 Hz All
0271 Phase Sequence L1 L2 L3 All
0276 Unit of temperature measurement Degree Celsius All

4.2 Group Power System Data 1; Group Transformer


No. Settings Value Group
0240 Rated Primary Voltage Side 1 230.0 kV All
0241 Starpoint of Side 1 is Solid Earthed All
0242 Transf. Winding Connection Side 1 Y (Wye) All
0243 Rated Primary Voltage Side 2 63.0 kV All
0244 Starpoint of Side 2 is Solid Earthed All
0245 Transf. Winding Connection Side 2 D (Delta) All
0246 Vector Group Numeral of Side 2 11 All
0249 Rated Apparent Power of the Transformer 125.00 MVA All

4.3 Group Power System Data 1; Group CT's


No. Settings Value Group
0201 CT-Strpnt. Side1 in Direct. of Object YES All
0202 CT Rated Primary Current Side 1 800 A All
0203 CT Rated Secondary Current Side 1 1A All
0206 CT-Strpnt. Side2 in Direct. of Object YES All
0207 CT Rated Primary Current Side 2 1200 A All
0208 CT Rated Secondary Current Side 2 1A All
0230 Earthing Electrod versus Terminal Q7 All
0232 CT Rated Primary Current I7 800 A All
0233 CT Rated Secondary Current I7 1A All
0235 Factor: Prim. Current over Sek. Curr. I8 60.0 All

4.4 Group Power System Data 1; Group Breaker


No. Settings Value Group
0280A Minimum TRIP Command Duration 0.15 sec All
0283 Clos. Breaker Min. Current Thresh. S1 0.04 A All
0284 Clos. Breaker Min. Current Thresh. S2 0.04 A All

Page 6 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15

5 Settings groups
5.1 Group Differential Protection; Group General
No. Settings Value Group
1201 Differential Protection ON A
1205 Increase of Trip Char. During Start ON A
1206 Inrush with 2. Harmonic Restraint ON A
1207 n-th Harmonic Restraint OFF A
1211A Diff-Prot. with meas. Earth Current S1 NO A

5.2 Group Differential Protection; Group I-Diff


No. Settings Value Group
1221 Pickup Value of Differential Curr. 0.20 I/InO A
1226A T I-DIFF> Time Delay 0.00 sec A
1231 Pickup Value of High Set Trip 8.0 I/InO A
1236A T I-DIFF>> Time Delay 0.00 sec A

5.3 Group Differential Protection; Group Characteristic


No. Settings Value Group
1241A Slope 1 of Tripping Characteristic 0.30 A
1242A Base Point for Slope 1 of Charac. 0.00 I/InO A
1243A Slope 2 of Tripping Characteristic 0.70 A
1244A Base Point for Slope 2 of Charac. 2.28 I/InO A
1251A I-RESTRAINT for Start Detection 0.10 I/InO A
1252A Factor for Increasing of Char. at Start 1.0 A
1253 Maximum Permissible Starting Time 5.0 sec A
1256A Pickup for Add-on Stabilization 7.00 I/InO A
1257A Duration of Add-on Stabilization 15 Cycle A

5.4 Group Differential Protection; Group Inrush 2.HM


No. Settings Value Group
1261 2nd Harmonic Content in I-DIFF 15 % A
1262A Time for Cross-blocking 2nd Harm. 3 Cycle A

5.5 Group Differential Protection; Group Restr. n.HM


No. Settings Value Group
1271 n-th Harmonic Content in I-DIFF 30 % A
1272A Time for Cross-blocking n-th Harm. 0 Cycle A
1273A Limit IDIFFmax of n-th Harm.Restraint 1.5 I/InO A

Page 7 of 8
SIMATIC HAMEDAN Factory final / 230KV / 7UT612 V4.0/7UT612 23.06.10 15:10:15

5.6 Group Restricted Earth Fault Protection; Group


General
No. Settings Value Group
1301 Restricted Earth Fault Protection ON A

5.7 Group Restricted Earth Fault Protection; Group


Settings
No. Settings Value Group
1311 Pick up value I REF> 0.15 I / In A
1312A T I-REF> Time Delay 0.00 sec A
1313A Slope of Charac. I-REF> = f(I-SUM) 0.00 A

5.8 Group Measurement Supervision; Group General


No. Settings Value Group
8101 Current Balance Supervision ON A
8102 Phase Rotation Supervision OFF A

5.9 Group Measurement Supervision; Group Balance I S1


No. Settings Value Group
8111 Current Balance Monitor Side 1 0.50 A A
8112 Balance Factor for Current Monitor S1 0.50 A

5.10 Group Measurement Supervision; Group Balance I S2


No. Settings Value Group
8121 Current Balance Monitor Side 2 0.50 A A
8122 Balance Factor for Current Monitor S2 0.50 A

5.11 Group Measurement; Group Measurement


No. Settings Value Group
7601 Calculation of Power with V setting A

Page 8 of 8