Power Transmission and Distribution

Siemens Belgium-Luxemburg
© Siemens AG 2006
Siemens Power Transmission and Distribution
What we have to offer

High Voltage Transformers Medium Voltage


Components, switchgear and turnkey Power transformers up to 1,300 MVA Components, switchgear and turnkey
projects for power transmission > and 765kV, distribution transformers projects for power transmission ≤
52kV (AC and DC) with oil or cast-resin insulation 52kV (AC and DC)

Energy Automation Services


Integrated control systems, protection and Network planning & consulting, asset
substation automation, telecontrol systems, maintenance and maintenance management for
power quality grids & networks, metering services
.
©
Siemens AG 2006
Page 2 28/11/2007 A.belvaux Power Transmission and Distribution
PTD Division
High Voltage overview

Air Insulated Switchgear (AIS)

ƒ Circuit-breakers
ƒ Arrestors, Bushings, Coils and
Instrument Transformers
ƒ Disconnectors

Gas Insulated Switchgear (GIS)

Highly Integrated Switchgear (HIS)

Gas Insulated Lines(GIL)

Reactive Power Compensation

High Voltage Direct Current (HVDC)


Installations

©
Siemens AG 2006
Page 3 28/11/2007 A.belvaux Power Transmission and Distribution
Products and Solutions for High Voltage
AIS – Circuit Breakers

Rated short-circuit
breaking current [kA]
80

3AT2/3 3AT4/5
63

50

40

31,5

25

3AP1 FG 3AP1 FI 3AP2 FI


0
72,5 123 145 170 245 300 362 420 550 800
Rated voltage [kV]
©
Siemens AG 2006
Page 4 28/11/2007 A.belvaux Power Transmission and Distribution
High-Voltage Circuit-Breaker
Product Characteristics

Type 3AP1 FG up to 245 kV Type 3AP1 FI up to 300 kV


ƒ For all applications: reliable ƒ Stored energy
and economical Spring Drive Mechanism
ƒ Stored energy ƒ Self compression arc
Spring Drive Mechanism quenching principle
ƒ Self compression arc ƒ Rated voltages
quenching principle up to 300 kV
ƒ Rated voltages ƒ Rated short circuit
up to 245 kV breaking current
ƒ Rated short circuit up to 50 kA
breaking current ƒ Type tested to the new
up to 50 kA IEC 62271-100
ƒ Type tested to the
new IEC 62271-100
ƒ Available for one or three
pole operation (FG/FI)
ƒ Delivered more than 50,000
breakers to more than 120
countries

©
Siemens AG 2006
Page 5 28/11/2007 A.belvaux Power Transmission and Distribution
High-Voltage Circuit-Breaker
Product Characteristics

Type 3AP1 DTC 72.5 up to Type 3AP2 FI up to 420 kV


245 kV ƒ Stored energy
ƒ One interrupter unit per Spring Drive Mechanism
pole ƒ Self compression arc
ƒ Stored energy quenching principle
Spring Drive Mechanism ƒ Rated voltages
ƒ Rated voltages up to 420 kV
up to 245 kV ƒ Rated short circuit
ƒ Rated short circuit breaking current
breaking current up to 50 kA
up to 63 kA ƒ Type tested to the
ƒ Type tested to the new IEC 62271-100
new IEC 62271-100 ƒ Easy installation and
ƒ Equipped with bushing commissioning:
type current transformers only few subassemblies
ƒ Ambient temperature range ƒ Transportation costs are
from +50° C down to -55° C minimized
with pure SF6

©
Siemens AG 2006
Page 6 28/11/2007 A.belvaux Power Transmission and Distribution
Products and Solutions for High Voltage
Arrestors, Bushings, Coils & Instrument Transformers

Arrester Coils
ƒ HV: ƒ Air Core Dry Type
AIS (Porcellain, Polymer) Reactors
& GIS; HVDC, FACTS ƒ Line Traps
ƒ MV: Distribution ƒ Arc Suppression Coils
& Traction Vehicles

Bushings Instrument Transformers


ƒ Air Core Dry Type Reactors ƒ Current Transformers
ƒ Line Traps ƒ Voltage Transformers
ƒ Arc Suppression Coils

©
Siemens AG 2006
Page 7 28/11/2007 A.belvaux Power Transmission and Distribution
Products and Solutions for High Voltage
Disconnectors & Earthing Switches from 36 kV to 800 kV

Centre Break Pantograph Vertical Break

Ur 72,5 kV – 550 kV Ur 123 kV – 420 kV Ur 123 kV – 550 kV


Ir 1250 A – 4000 A Ir 3150 A Ir 1250 A – 6300 A
Ik 31,5 kA– 63 kA Ik 50 kA Ik 31,5 kA– 63 kA

Double Break Earthing Switch Knee Type

Ur 36 kV – 800 kV Built-on Ur 123 kV – 550 kV


Ir 1250 A – 5000 A Free-standing Ir 1250 A – 400 A
Ik 31,5 kA– 63 kA Neutral point Ik 31,5 kA– 63 kA

©
Siemens AG 2006
Page 8 28/11/2007 A.belvaux Power Transmission and Distribution
Products and Solutions for High voltage
Gas Insulated Switchgear (GIS)

80

Rated short-circuit breaking current (kA)


63

50

40
HIS 8DQ1 8DR1

31,5
HIS 8DN8

25 8DQ1

8DN8 8DN9 8DQ1


0 Voltage
72.5 123 145 170 245 300 362 420 550 800 (kV)
©
Siemens AG 2006
Page 9 28/11/2007 A.belvaux Power Transmission and Distribution
Gas Insulated Switchgear (GIS)
8DN8.2 switchgear

ƒ Rated voltage up to 145 kV


ƒ Rated frequency 50 / 60 Hz
ƒ Rated power frequency
withstand voltage (1 min) up to 275 kV
ƒ Rated lightning impulse
withstand voltage (1,2/50 µs ) up to 650 kV
ƒ Rated busbar current up to 3150 A
ƒ Rated feeder current up to 3150 A
ƒ Rated breaking current up to 40 kA
ƒ Rated short-time current up to 40 kA
ƒ Leakage rate per year
and gas compartment < 0.5 %
ƒ Bay width 800 mm
ƒ Bay height 2850 mm
ƒ Bay depth 3500 mm
ƒ Bay weight 3t
©
Siemens AG 2006
Page 10 28/11/2007 A.belvaux Power Transmission and Distribution
Gas Insulated Switchgear (GIS)
8DN9 switchgear

ƒRated voltage up to 245 kV


ƒRated frequency 50 / 60 Hz
ƒRated power frequency
withstand voltage (1 min) up to 460 kV
ƒRated lightning impulse
withstand voltage (1,2/50 µs) up to 1050 kV
ƒRated busbar current up to 3150 A
ƒRated feeder current up to 3150 A
ƒRated breaking current up to 50 kA
ƒRated short-time current up to 50 kA
ƒLeakage rate per year and
gas compartment < 0.5 %
ƒBay width 1500 mm
ƒBay height 3500 mm
ƒBay depth 4700 mm
ƒBay weight 5t

©
Siemens AG 2006
Page 11 28/11/2007 A.belvaux Power Transmission and Distribution
Products and Solutions for High voltage
Highly Integrated Switchgear (HIS)

ƒ Compact
ƒ Low cost
ƒ Modular
ƒ Suitable for in- and outdoor use

Savings HIS*

Site price 60 %

Civil works 20 %

Secondary cables 35 %

Steel structures 30 %

Earthing 70 %

Erection, tests,
commissioning 70 %

* compared to air insulated switchgear


©
Siemens AG 2006
Page 12 28/11/2007 A.belvaux Power Transmission and Distribution
Domaine d’utilisation des installations
moyenne tension

Niveau de production et
Réseau de Transport

x x
Niveau de distribution primaire
x x x x x x x

Niveau de distribution secondaire


x

Basse tension

©
Siemens AG 2006
Page 13 28/11/2007 A.belvaux Power Transmission and Distribution
Medium Voltage: Overview

Primary distribution Secondary distribution Components


switchgear switchgear
Vacuum tubes
Gas-insulated (SF6 ) Gas-insulated (SF6 ) Vacuum circuit-breakers
ƒ NX PLUS C ƒ 8DH10 Vacuum contactors
ƒ NX PLUS ƒ 8DJ10/8DJ20 Other Components
ƒ 8DA/8DB
Air-insulated Air-insulated MV DC-Multifunctional
ƒ NX AIR ƒ SIMOSEC Link
ƒ NX AIR M SIPLINK
ƒ NX AIR P
ƒ SIMOPRIME
©
Siemens AG 2006
Page 14 28/11/2007 A.belvaux Power Transmission and Distribution
Medium Voltage Products for Primary Distribution
SF6-Insulated Switchgear

8DA 8DB
„ Type-tested, single-phase „ Type-tested, single-phase
encapsulation, metal-clad encapsulation, metal-clad
„ Proved design, Single „ Proved design, Double
Busbar Busbar
„ Modular design with „ Modular design with
standard enclosures standard enclosures
allows single- and double „ Busbars and busbar-
phase applications disconnectors in separate
„ More than 15 years of gas compartments
operating experience „ More than 15 years of
operating experience

Delivery Program Delivery Program


up to 40.5 kV up to 40 kA up to 4000 A up to 40.5 kV up to 40 kA up to 4000 A
©
Siemens AG 2006
Page 15 28/11/2007 A.belvaux Power Transmission and Distribution
Medium Voltage Products for Primary Distribution
Air-Insulated Switchgear (AIS)

NX AIR NX AIR M
„ Type-tested, IEC 62271-200, „ Type-tested, IEC 62271-200,
metal-clad, loss of service metal-clad, loss of service
continuity category: continuity category:
LSC 2B, partition class: LSC 2B, partition class:
PM, internal arc classification: PM, internal arc classification:
IAC A FLR ≤40 kA, 1s IAC A FLR ≤25 kA, 1s
„ Single- and double busbar „ Single- and Double Busbar
(back/back, front/front) (back/back, front/front)
„ Vacuum circuit-breaker „ Vacuum circuit-breaker
withdrawable withdrawable
„ Vacuum contactor withdrawable „ Max. renewed availability by
„ Max. renewed availability by modular design
modular design „ Selective shutdown by bushing
„ Selective shutdown by bushing type transformers and pressure
type transformers and pressure resistant compartments
resistant compartments „ Max. operating safety by
„ Max. operating safety by self- selfexplanatory logical operating
explanatory logical operating elements
elements „ Maintenance intervals > 10 years
„ Maintenance intervals > 10 years

Delivery Program Delivery Program


up to 12 kV up to 40 kA up to 2500 A 17.5 / 24 kV up to 25 kA up to 2500 A
©
Siemens AG 2006
Page 16 28/11/2007 A.belvaux Power Transmission and Distribution
Medium Voltage Products for Secondary Distribution
SF6-Insulated Switchgear

8DJ10 8DJ20
„ Type-tested „ Type-tested
„ Independent of climate „ Independent of climate
„ Maintenance-free „ Maintenance-free
„ Block-type construction, „ Block-type construction,
for 3-6 bays for 1-5 bays
„ Hermetically-sealed „ Hermetically-sealed
welded welded
switch-gear enclosures switch-gear enclosures
„ Compact and clear design „ Compact and clear design
„ No sealings „ No sealings
„ Highest Quality Level „ Highest Quality Level
„ Shortest Delivery Periods „ Shortest Delivery Periods
„ Smallest floor space for
substations

Delivery Program Delivery Program


up to 24 kV up to 25 kA up to 630 A up to 24 kV up to 25 kA up to 630 A
©
Siemens AG 2006
Page 17 28/11/2007 A.belvaux Power Transmission and Distribution
MV DC-Multifunctional Link - SIPLINK

Large-scale
power plant
Independent power producers City
(wind generators, solar plants)

Large-scale industry
with in-plant generation Consumers with
sensitive processes

Manufacturing, trade,
small industry without
in-plant generation
Hospital

New Switching Technologies for Distribution Systems


Improves Cost-Effectiveness, Availability and Power Quality
©
Siemens AG 2006
Page 18 28/11/2007 A.belvaux Power Transmission and Distribution
Medium Voltage Components
Vacuum Tubes

„ High reliability
„ Excellent field experience with more than 2
million vacuum interrupters
„ Tailormade development
„ Wide product range for any application

„ For use in
„ LV and MV circuit-breakers, load-break
switches and contactors
„ Autoreclosers
„ Transformer Tap Changers

Delivery Program
690 up to 1300 V up to 65 kA up to 2500 A
7.2 up to 40.5 kV up to 72 kA up to 6300 A
©
Siemens AG 2006
Page 19 28/11/2007 A.belvaux Power Transmission and Distribution
PTD Division
Transformers

ƒ Power
Do lor situs cum
transformersitum
habilitarum
alus causticus
ƒ Distribution
imanenter
transformers Status
with
landum exus rius
oil or cast-resin
laudanum
insulation tum.

Lorem exit vulnareus


plexus est. Vulna
pausta rhus tex, per
itum falor sit wunt.
Sit itum causticus
aurum eum et expli
ndus.Cum

©
Siemens AG 2006
Page 20 28/11/2007 A.belvaux Power Transmission and Distribution
Siemens Transformers at all Levels of
Transmission and Distribution

Generator
transformer

TLM
Shunt Siemens
HVDC reactor Transformer Life
System Management
interconnecting (condition
Phase angle transformer assessment,
regulator life-extension,
on-site-services,
monitoring, ...)
Special purpose transformers
for industrial application

System
transformer

Oil-immersed Voltage GEAFOL Traction


distribution transformer regulator cast-resin transformer transformer

©
Siemens AG 2006
Page 21 28/11/2007 A.belvaux Power Transmission and Distribution
Power Transformers

ƒ Ratings from 10 MVA up to


1.100 MVA / 1200 kV

ƒ Three-phase and single-phase

©
Siemens AG 2006
Page 22 28/11/2007 A.belvaux Power Transmission and Distribution
Distribution Transformers
GEAFOL

ƒ Cast-resin distribution
transformers

ƒ Ratings from 50 kVA up to


40MVA

ƒ Possibility for on-line


tapchanger

ƒ Static converter transformers

©
Siemens AG 2006
Page 23 28/11/2007 A.belvaux Power Transmission and Distribution
Distribution Transformers
Oil-immersed

ƒ Ratings from 50 up to 4.000 kVA

(TUNORMA and TUMETIC)

©
Siemens AG 2006
Page 24 28/11/2007 A.belvaux Power Transmission and Distribution
PTD Division
Energy Automation

ƒ Information
Do and
lor situs cum
network control
habilitarum itum
technology
alus causticus
imanenter
ƒ ProtectionStatus
and
landum exus
substation rius
auto-
laudanum tum.
mation, telecon-trol
systems, power
Lorem
quality exit vulnareus
plexus est. Vulna
pausta rhus tex, per
itum falor sit wunt.
Sit itum causticus
aurum eum et expli
ndus.Cum

©
Siemens AG 2006
Page 25 28/11/2007 A.belvaux Power Transmission and Distribution
Energy Automation
Strong products and brands on all levels

Energy Market Mgmt. System control centers


„ EMM „ Spectrum PowerCC
„ FDWH „ SINAUT Spectrum
„ PROPHET Solutions
„ AMIS
„ …
Station control & automation
Communications „ SICAM PAS
& networking „ SAT 1703 / SAT 230
„ PLC
„ Modems
RTU’s
„ SAT 1703
„ …
„ SICAM eRTU / miniRTU
Tools „ TG 805 / TG 5700

„ SICAM TOOLBOX
„ IMM Protection/Power
„ DIGSI… Quality/Bay Control
„ SIPROTEC
„ REYROLLE
„ BC 1703 ACP
„ SIMEAS

©
Siemens AG 2006
Page 26 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

LE BUT DE LA PROTECTION SELECTIVE EST:


-Assurer la continuité de service du réseau d’energie , par
élimination de l’élément défaillant et de lui seul
-Eviter des dégâts au niveau des équipements affectés par
les défauts(câbles,transformateurs…)

©
Siemens AG 2006
Page 27 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

LE SYSTEME DE PROTECTION =

TI/TP + Relais+ Disjoncteur

Sélectif,rapide,fiable

©
Siemens AG 2006
Page 28 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4 - What does it mean?

SIPROTEC 4
is a
family of numerical
Protection, Control- and
Automation Devices
from
SIEMENS

©
Siemens AG 2006
Page 29 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

O/C protection 7SJ6


Distance protection 7SA6
Line differential protection 7SD5 / 7SD6
Transformer diff. protection 7UT6
Generator protection 7UM6
Station protection 7SS52

©
Siemens AG 2006
Page 30 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

O/C protection
7SJ6

©
Siemens AG 2006
Page 31 28/11/2007 A.belvaux Power Transmission and Distribution
Time-overcurrent protection Functions

Time-overcurrent protection

Criteria for fault: overcurrent

Criteria for selectivity: time

©
Siemens AG 2006
Page 32 28/11/2007 A.belvaux Power Transmission and Distribution
Time-overcurrent protection Characteristics

Tripping characteristic of a two stage time-overcurrent


protection device - definite time

t [sec]
2.0

1.5 Tripping area

1.0

0.5

0.5 1.0 1.5 2.0 2.5 x IN


I> I>>

©
Siemens AG 2006
Page 33 28/11/2007 A.belvaux Power Transmission and Distribution
Time-overcurrent protection Characteristics

Tripping characteristic of a time-overcurrent protection device -


inverse time

t [sec]
2.0 Characteristics:
ƒ IEC
1.5 ƒ ANSI
ƒ user defined

1.0

0.5

0.5 1.0 1.5 2.0 2.5 x IN

©
Siemens AG 2006
Page 34 28/11/2007 A.belvaux Power Transmission and Distribution
Time-overcurrent protection Application

As main protection Used as:

1 Line protection
Selectivity by time-grading
x

x
x
2 Motor protection
O/C O/C O/C with short circuit- and
overload protection,
start protection,
x

start inhibit

O/C M 3 Transformer protection


for network transformers
with short circuit- and
1 2 3 overload protection,
Inrush-stabilisation

©
Siemens AG 2006
Page 35 28/11/2007 A.belvaux Power Transmission and Distribution
Time-overcurrent protection Application

Main protection as line protection

x x x x

O/C O/C O/C O/C

t = 900ms t = 600ms t = 300ms t = 0ms


b
Ttrip a
c
k
u
p

distance

Advantage: simple device,


only current transformers are necessary
Disadvantage: near infeed higher tripping time
©
Siemens AG 2006
Page 36 28/11/2007 A.belvaux Power Transmission and Distribution
Reverse Interlocking Application

O/C 1
Blocking
2 T = 50ms Outgoing protection
Energy direction t = xxms
initiates and blocks
the infeed protection
stage within 50 ms

2
O/C O/C O/C Infeed protection
+ + + gives a trip after
start start. start.
50 ms since no
M outgoing feeder has
picked up and blocked
1
the infeed protection

©
Siemens AG 2006
Page 37 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

O/C
O/Cprotection
protectionwith
withmotor
motorprotection
protection

7SJ61

ƒ Over current protection


(Phase/Earth)
ƒ Inrush Blocking
ƒ Motor Protection
ƒ Overload Protection
ƒ Unbalanced Load Protection
ƒ Auto reclosure
ƒ Trip Circuit Supervision
ƒ Breaker Failure Protection
ƒ Lock out

4 CT inputs
©
Siemens AG 2006
Page 38 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

Distance
Distanceprotection
protection

©
Siemens AG 2006
Page 39 28/11/2007 A.belvaux Power Transmission and Distribution
Why impedance protection?

Situation: Meshed network and two infeeds


Directional overcurrent time relays

0,6s 0,3s

0,6s 0,3s

0,6s 0,3s

0,6s 0,3s
non-selective trip
©
Siemens AG 2006
Page 40 28/11/2007 A.belvaux Power Transmission and Distribution
Basic principle of impedance protection

Localization of short-circuits by means of an impedance


measurement:
ƒ fault on the protected line Z1
relay A

ƒ fault outside the protected line


Z2

relay A

selectivity

©
Siemens AG 2006
Page 41 28/11/2007 A.belvaux Power Transmission and Distribution
Distance measurement (principle)

IL1 Z
ZL = RL + j XL
IL2 L

IL3 ZE = RE +j XE
IE Z
E
UL1 UL2 UL3
6 loops: 3 phase- phase loops and
3 phase- ground loops

phase- phase -loop: UL1-L2 = ZL ( IL1 - IL2)

Measured current
measured voltage

The same applies to the remaining loops

©
Siemens AG 200606.08.97
dtgerdis3
Page 42 28/11/2007 A.belvaux Power Transmission and Distribution
Distance measurement (principle)

IL1 ZL
IL2 ZL = RL + j XL
IL3

IE Z ZE = RE +j XE
E
UL1 UL2 UL3

phase-ground-loop: UL1 = ΙL1 · ( RL + j XL )- ΙE · ( RE +j XE)

ΙL1, ΙE measured current


UL1 measured voltage

The same applies to the remaining loops


©
Siemens AG 200606.08.97
dtgerdis3
Page 43 28/11/2007 A.belvaux Power Transmission and Distribution
Numerical filtered phasor measurement

1. Fast operation ⇒ Use short data window

2. High accuracy ⇒ High selectivity

3. Signal distortion does not cause delay or maloperation

©
Siemens AG 2006
Page 44 28/11/2007 A.belvaux Power Transmission and Distribution
Fourier analysis of measured values

sin 2π ⋅i
n
Sampled
measuring 0 1 2 . . . n
values
i(k −n+i) IS(k) Resulting phasor
i
I(k) = IS(k) + j⋅ IC(k)
k-n k
IC(k) I (k )
j⋅ IC(k)

ϕ
cos 2π ⋅i IS(k)
n
©
Siemens AG 2006
Page 45 28/11/2007 A.belvaux Power Transmission and Distribution
Load and short-circuit impedances

distance relay ZL
operating ZLF1
characteristic ZLF2

Fault area
X
RF RF
ZL F1 F2 ZLoad
D
ZLF2 ZF2
RR Phase - Phase Fault
ZLoad RR ≈ RF / 2
RR
ZLF1 ZF1 ing load
as
Incre Phase - Earth Fault
jL
RR ≈ RF /(1 + RE/RL)
j SC2
Fault in j SC1 R
Minimum Load Impedance:
reverse
Minimum voltage 0,9 Un
direction Load area Maximum current 1,1 In
Maximum angle ± 30°

©
Siemens AG 2006
Page 46 28/11/2007 A.belvaux Power Transmission and Distribution
Graded distance zones

Z3
∆t = grading time
time Z2 t3
Z1 t2

t1

A B C D
D1 D2 D3

distance
Grading rules:
Safety margin is 15
Z1 = 0,85 ZAB
%:
Z2 = 0,85 (ZAB + 0,85 ZBC) ƒ line error
Z3 = 0,85 (ZAB + 0,85 (ZBC + 0,85 ZCD)) ƒ CT, VT error
ƒ measuring error
©
Siemens AG 2006
Page 47 28/11/2007 A.belvaux Power Transmission and Distribution
Determination of fault direction

Fault location Where is the fault ?

Current area for Impedance area for


forward faults X forward faults
USC
ΙSC ZSC
ϕSC
ϕSC
R

ΙSC Z'SC
Current area for Impedance area for
reverse faults reverse faults

current / voltage diagram impedance diagram

The impedance also shows the direction, but ....


©
Siemens AG 2006
Page 48 28/11/2007 A.belvaux Power Transmission and Distribution
Fault detection techniques

Over-current fault detection


Voltage dependant X
over-current fault detection
U Voltage and
angle dependant
over-current
fault detection R
Impedance
fault
detection

I> Iϕ> I >> I

Not in 7SA522

©
Siemens AG 2006
Page 49 28/11/2007 A.belvaux Power Transmission and Distribution
Impedance zones of digital relays

for
Distance zones

wa
X

rds
Line
Inclined with line angle ϕ
Z5 Angle α prevents overreach of
Z4 Z1 on faults with fault
Z2 resistance that are fed from
Z1B both line ends
α
Z1
re v
ers
e

Load ϕ Load

R
Fault detection
forw
ard no fault detection polygon: the
s
largest zone determines
the fault detection
Z3
characteristic
simple setting of load
rev

encroachment area with


ers

Rmin and ϕLoad


e

©
Siemens AG 2006
Page 50 28/11/2007 A.belvaux Power Transmission and Distribution
Zone grading chart, radial feeder

Z3
Z2
A Z1 B C D

D D D Ι>> ZT
Ι>t
∆Ι

Grading according
Z1 = 0.85 ZA-B the recommendation
Z2 = 0.85 (ZA-B + 0.85 ZB-C) with the safety margin
of 15%.
Z3 = 0.85 [ ZA-B + 0.85 (ZB-C+ 0.85 ZC-D) ]
©
Siemens AG 2006
Page 51 28/11/2007 A.belvaux Power Transmission and Distribution
Ring feeder: with grading against opposite end

grading time
(s)
0.6
0.3

The same grading from both sides

©
Siemens AG 2006
Page 52 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

Line differential protection


7SD61 / 7SD52

©
Siemens AG 2006
Page 53 28/11/2007 A.belvaux Power Transmission and Distribution
Measuring Principle

I1

I5

I2

I4

I3

Kirchhoff: I1+I2+I3+I4+I5=0
©
Siemens AG 2006
Page 54 28/11/2007 A.belvaux Power Transmission and Distribution
Trip Characteristic

1 p.u. 1:1 1:1 1 p.u.


(3Y) (3Y)

IX IY

IX IY

0 6 12 0 6 12

Internal Fault
©
Siemens AG 2006
Page 55 28/11/2007 A.belvaux Power Transmission and Distribution
Trip Characteristic

IX

0 6 12 ID = I X + I Y IR = I X + I Y

ID = (+1)+ (+1) = 2 IR = +1 + +1 = 2

IY

0 3 6 12
Internal Fault
©
Siemens AG 2006
Page 56 28/11/2007 A.belvaux Power Transmission and Distribution
Trip Characteristic

Ideal internal fault


Idiff fault line (k=1) ƒ Idiff = I1
ƒ Istab = I1
ƒ fault is on fault line

internal fault
external fault or External fault
operation condition ƒ Idiff = 0
ƒ Istab = |I1|+|I2|+...|In|

security for CT deviations Istab

©
Siemens AG 2006
Page 57 28/11/2007 A.belvaux Power Transmission and Distribution
Differential Current due to CT-Saturation

i1

i2

⎟ i_diff⎟

t
T 2T 3T 4T

Differential Current may cause maloperation in case of CT-saturation

©
Siemens AG 2006
Page 58 28/11/2007 A.belvaux Power Transmission and Distribution
Current transformer saturation

Saturation during steady-state current

Saturation during offset current

©
Siemens AG 2006
Page 59 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

Line
Linedifferential
differentialprotection
protection
ƒ Current Comparison Protection for all
applications for cables and overhead
lines
ƒ Two up to six line ends
ƒ Handles transformers in the protected
zone (integrated vector group matching)
ƒ Direct connection to communication
networks
ƒ Communication via copper and ISDN
networks
ƒ Fault Locator
ƒ Fast tripping (less than 15 ms)
ƒ Automatic reclosure

©
Siemens AG 2006
Page 60 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4 Line differential protection

Configurations
Configurations

over 3 line ends

7SD52

7SD52

7SD52

©
Siemens AG 2006
Page 61 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

No
Norestrictions
restrictionsfor
forcommunication
communication
ƒ Communication with …
ƒ direct FO connection up to 100 km
ƒ digital communication network (G703, X21)
ƒ ISDN-connection
ƒ 2 or 3 wire pilot wire (twisted, screened)

FO
or
Digital
E O

7SD5
7SD5

O communication network E

or
E ISDN O
O E

or
E 2/3 wire pilot wire (Cu) O
O E

©
Siemens AG 2006
Page 62 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

Topology
Topologydetection,
detection,example
example
side 2 side 2

I2 I2 side 3

Side 3
connection to
I3 I3
I3+I1 I2 other devices

I1+I2 I3
I1 I1
I3+I1
I1+I2

side 1 side 1

ring topology Partial current summation


©
Siemens AG 2006
Page 63 28/11/2007 A.belvaux Power Transmission and Distribution
7SD52 V4.3 Line protection

Universal line protection for HV and EHV applications

ƒ Line differential protection and distance protection in one device


ƒ Comprehensive function mix for 2-6 line end applications
ƒ Any combination of DIF and DIS, as main or backup protection
ƒ Emergency / backup protection as additional backup level
ƒ Full control functionality (graphic display)

Z1B Z1

Z1 Z1B

∆I ∆I
.....11010110.....
Z< Z<

©
Siemens AG 2006
Page 64 28/11/2007 A.belvaux Power Transmission and Distribution
SIPROTEC 4

Multifunctional Protection
for
Transformers and Generators
7UT6

©
Siemens AG 2006
Page 65 28/11/2007 A.belvaux Power Transmission and Distribution
Measuring Preprocessing, Example for CT Matching (Part 1)

SN = 100MVA

UN1 = 110kV UN2 = 30kV


1000/5A 2000/5A
IP1 = 500A IP2 = 1833A
(load current) winding 1 winding 2 (load current)

IN, Trafo = 525A IN, Trafo = 1924A

measured
IS1 = 2.5A IS2 = 4.58A secondary currents
7UT512

IDiff = ?
IStab= ?

©
Siemens AG 2006
Page 66 28/11/2007 A.belvaux Power Transmission and Distribution
Method of Vector Group Determination

Side 2: Side 1:
2L1
1L1
2L2
1L2
2L3
1L3

IL1,S2 = IL1 - IL2 IL1,S1

330° Vector group is


(n * 30°) Y d 11
©
Siemens AG 2006
Page 67 28/11/2007 A.belvaux Power Transmission and Distribution
SICAM PAS
System with IEC61850 and further services

I4
DIGS Station unit
-
Web or
it SICAM PCC
Mon

62,5µ or 50µ FO

100 Mbit/s switched and redundant Ethernet ring

Ethernet-
Switch
max. 6 Ethernet
devices patch-
Stand by per Goose
cable
connection switch Message

Info
report

©
Siemens AG 2006
Page 68 28/11/2007 A.belvaux Power Transmission and Distribution