FIRST ANGLE PROJECTION ALL DIMENSIONS ARE IN MM

2 3 4 5 6 7 8 9 10 11 12

CT-DETAILS
GENERATOR TRANSFORMER
A A
150MVA,230/11kV
C.T. Qty LOCATION RATIO ACC. BURDEN ALF/ Vk> Ie< Rct AT PURPOSE
ONAN/ONAF/OFAF,YN d1, Z=12.5 % = =
ON 150MVA BASE, OCTC+5 % TO -5% NO. CLASS ISF 75°C=<

- - -
IN STEPS OF 2.5% ON HV SIDE
WALL FRAME GEN. BUSDUCT
CT-1 3 (NEUTRAL SIDE)
9000/5A PS 250Rct+325V 150mA AT VK/2 PROTECTION

1000A CT-2
3
GEN. BUSDUCT
(NEUTRAL SIDE)
9000/5A 0.2 50VA < 5.0
= - - - METERING

-
152KArms FOR 3
WALL FRAME WITH SEAL
OFF BUSHING
SEC.(403KAp) CT-3
3
GEN. BUSDUCT
(NEUTRAL SIDE)
9000/5A PS - - 250Rct+250V 150 mA AT VK/2 PROTECTION

CT-12
P1 CT-4
3
GEN. BUSDUCT
(NEUTRAL SIDE)
9000/5A PS - - 250Rct+250V 150mA AT VK/2 - PROTECTION
B

CT-13
CT-14
CT-5 3
GEN. BUSDUCT
(PHASE SIDE)
9000/5A PS
- - 250Rct+250V 150mA AT VK/2 - PROTECTION

10000 A P2
UNIT AUX TRANSFORMER
CT-6
3
GEN. BUSDUCT
(PHASE SIDE)
9000/5A PS - - 250Rct+250V 150mA AT VK/2
- PROTECTION

-
82KArms FOR
3SEC.(217KAp) 16 MVA,11/6.9kV
Z=10%,OLTC/ONAF,Dyn11,
CT-7
3
GEN. BUSDUCT
(PHASE SIDE)
9000/5A 0.2 50VA < 5.0
= - - METERING

CT-8
3
GEN. BUSDUCT
(PHASE SIDE)
9000/5A 0.2 50 VA < 5.0
= - - - METERING

-
C C

CT-10 1 GEN NG CUBICLE 600-400/5A 1.0 40VA < 5.0


= - - METERING

P2 LAVT CUBICLE CT-12


3
GEN. BUSDUCT
UAT TAP OFF
1000/1A PS - - 40Rct+125V 30mA AT VK/2 - PROTECTION

CT-13 3 GEN. BUSDUCT


UAT TAP OFF
1000/1A 5P 10VA 20
- - - METERING

CT-8 LA 12kV,10kA CT-14


3 GEN. BUSDUCT
UAT TAP OFF
9000/5A PS - - 250Rct+325V 150mA AT VK/2 - PROTECTION
It must not be used directly or indirectly in any way detrimental to the interest of the company.
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED

CT-7 12kV,0.25 µF
D D
CT-6 FS VT1 MCB 3
GENERATOR SYNCHRONISING
CT-5
FS VT2 MCB 2
AVR (AUTO CHANNEL)
COPYRIGHT AND CONFIDENTIAL

FS VT3 MCB 1

Fold-4
PERFORMANCE TESTING
VT DETAILS Fold-4

GENERATOR #1/2/3/4
VT NO. RATIO
CAT-1 BURDEN ACCURACY CLASS LOCATION QTY.
E E

APPROVED
11000 110 V
3P/0.5
VT-1 60VA/60VA LAVT CUBICLE 003
3 3

Checked and
11000approved
110 V with regard to the 3P/0.5 003
VT-2 60VA/60VA LAVT CUBICLE
P2 LEGEND 3
system requirements
and/or the11000
3
overall110
and/or main dimensions
arrangement. The Contractor
VT-3 V 60VA 0.2 LAVT CUBICLE 003
CT-4 CURRENT TRANSFORMER 3 for design
is responsible 3 calculation, detail
CT-3 dimensions and operability.
F F

CT-2 SEAL OFF BUSHING

ROOF BUSHING CT-1


P1 RUBBER BELLOW
EARTHING Signature: Date:
2008.01.08
N.G.CUBICLE RUBBER BELLOW
for 10:31:52 +
NEUTRAL GROUNDING Unterschrift 01'00'
TRANSFORMER N.G.RESISTOR FLEXIBLE CONNECTION
nicht bestätigt
G 0.455 OHM WITH TAPS AT G
11kV/240, AN, 1 PHASE,
35 kVA (CONT.) BASED 80,85 & 90%.
ON 5 MIN.DUTY CYCLE CT-10 R
240V, 400A FOR 5 MIN. NATIONAL ELECTRICITY CORPORATION (NEC)
ROOF BUSHING THE REPUBLIC OF THE SUDAN
4x125MW KOSTI THERMAL POWER PLANT

FICHTNER
FOR APPROVAL ONLY
STATUS

H
NOTE- DISTRIBUTION
DEPT NAME SIGN
CODE DRN S.K.SHRIVASTAVA
DESN ASHIM KUMAR
C CHD ASHIM KUMAR

1. ALL CTs & VT ARE OF EPOXY RESIN CAST RING TYPE WITH APPD V.K.MEHTA

TITLE
CLASS OF INSULATION AS 'B' CLASS.
I DEPT. SCALE DRAWING NO.
SIGN

1 2 3 4 5 6 7 8 9 10 DATE SHEET REV. 02


Fold-3

Fold-2

Fold-1