INCOMING 132kV

OVERHEAD LINE FEED


DVC/WBSEB 132kV RADIAL SWITCHYARD MAJOR EQUIPMENT
T ZONE
WIDE BAND LINE
R HYBRID RELAYING
LA SPECS:
MCOV 92kV, 10kA, Class-III S.N EQUIPMENT DESCRIPTION RATED VOLTAGE: 120kVrms
SYMBOL QTY
LIGHTNING ARRESTOR R MCOV: 92kVrms (IEC)
3 NOS. BALANCING
(1 PER PH) UNITS
X HYBRID
TOV- 139kV(1s), 132kV(10s)
LINE (AS Max Residual Voltage with current wave 30/60μs:
TUNERS REQUIRED) T
CC/CVT WITH PLCC SYSTEM CVT / COUPLING CAPACITOR (132KV/ (HIGH 120kV NOMINAL VOLTAGE LEVEL, PORCELAIN LIGHTNING 6 NOS.
0.5kA (231kVpeak), 1kA (238kVpeak), 2kA (248kVpeak)
√3: / 110V/√3: / 110V/√3): 6600pf PASS)
NARROW BAND 1
R HYBRID TRANSFER TRIP ARRESTER (MCOV – 92kV as per IEC) Max Residual Voltage with current wave 8/20 μs:
5.0kA (268kVpeak), 10.0kA (282kVpeak), 20kA (311kVpeak), 40kA (347kVpeak)
R
CO-AXIAL CABLES Station Lightning Discharge Class - III
LINE/WAVE TRAP 145kV, 1250A/0.5mH for 3 Seconds CVT / COUPLING CAPACITOR (132KV/√3: / 110V/√3: / 110V/
2 3 NOS.
VOICE √3 / 110V/√3): 6600pf
SSB T/R
(PAX)

ISOLATOR WITH EARTH SWITCH M


145kV WAVE TRAP 1250A/0.5mH for 3 Seconds (WITH
3 POST INSULATORS COMPLETE) 3 NOS.
145kV, 1250A, 40kA FOR 3 SECS,
DOUBLE BREAK
145kV, 1250A, 40kA for 3 Secs, CENTRE POST ROTATING,
CL=0.2,
4 DOUBLE BREAK ISOLATOR WITH 1 EARTH SWITCH M 2 SETS.
30VA
TARIFF METERING PT
132kV / 3 /110V/ 3 110V/ 3 1

97
1 145kV METERING POTENTIAL TRANSFORMER 0.2 CL,
I/L 5 (132KV/√3: / 110V/√3 / 110V/√3), DUAL CORE, 30VA 3 NOS.
2

97
P1 2
CL=0.2, MAIN 145kV METERING CURRENT TRANSFORMER 30/1/1 A,
30VA 6 3 NOS.
TARIFF DUAL CORE, 0.2S CLASS, 15VA, ISF< 5.0.
CORE 1: 30/1, CL:0.2S,
15VA, ISF<5 METER
(ABT) 145kV TRAFO BAY POTENTIAL TRANSFORMER (132KV/ 1
TARIFF METERING CT 7 3 NOS.
SECURE MAKE √3: / 110V/√3: / 110V/√3: / 110V/√3), (CORE1- 0.2CL, CORE2/3-PS
ABT METER 0.2S CL, 30VA) 2
CLASS CHECK 3
CORE 2: 30/1, CL:0.2S, TARIFF
145kV TRAFO BAY CURRENT TRANSFORMER 100/1/1/1/1/1A,
15VA, ISF<5 METER 3 NOS.
8 5 CORES. CORE-2: 0.2S CLASS, CORE1,3,4,5: PS.CLASS (15VA)
(ABT)
P2 SECURE MAKE
ABT METER 0.2S
CLASS 145kV, 1600A, 40kA for 3SEC, GANG OPERATED SF6 52 1 SET
9
CIRCUIT BREAKER

132/6.6kV, 12.5MVA ONAN, 15MVA ONAF, 10%


10 IMPEDANCE, STAR/STAR OIL IMMERSED
TRANSFORMER WITH (+/-15% STEPS IN 2,5% EACH 1 NO.
SEB’s POINT OF CONTROL FOR OLTC). WITH N2 INJECTION, FIRE PREVENTION TA
SYSTEM

M
ISOLATOR WITH EARTH SWITCH
145kV, 1250A, 40kA FOR 3 SECS,
DOUBLE BREAK
INOXAP’s POINT OF CONTROL
SPARE

97
CL=3P, ENERGY AND
30VA 1 STATUS DATA
CL=3P, ONLINE RELAYING
XR BAY POTENTIAL TRANSFORMER 30VA
132kV / 3 /110V/ 3 / 110V/ 3 / 110V/ 3 TO SLDC THROUGH
97 59 27 81U/0 24 PLCC

2
KWH
DESIGN NOTES ANSI PROTECTION ELEMENTS
TRANSDUCER
(0.2S CLASS) 59 OVER VOLTAGE PROTECTION ELEMENT
3 CL=0.2,
1: ALL DIEMNSIONS ARE IN MILI-METERS UNLESS OTHERWISE SPECIFIED.
97

I/L P1 30VA
27 UNDER VOLTAGE PROTECTION ELEMENT
64R 64R
Core 1: 100/1, 87T
HV
32 16
15VA CL:PS
LV
2: THE DESIGN PARAMETERS FOR THIS SYSTEM:
KWH METERING a) NOMINAL SYSTEM VOLTAGE – 132kV (r.m.s) 81U/0 FREQUENCY (UNDER / OVER) PROTECTION ELEMENTS
MFM TRANS-
Core 2: 100/1, (A,V,kW,kVA, METER DUCERS DATA TO b) HIGHEST SYSTEM VOLTAGE – 145kV (r.m.s)
CL:0.2S, 15VA, kVAR, PF, (0.2S (AT, FT, VT, PLANT DCS 24
ISF<5 HZ) CLASS) PFT & (BUYER”S c) PF (50Hz) WITHSTAND VOLTAGE – 275kV (peak) EXCITATION (VOLTS/HERTZ) PROTECTION ELEMENT
KWHT) d) IMPULSE WITHSTAND VOLTAGE – 650kV (peak)
SCOPE)
50N/ 67/ TRANSFORMER DIFFERENTIAL PROTECTION ELEMENT
XR BAY CURRENT TRANSFORMER
Core 3: 100/1, 50/51
51N 67N
68 e) MAX FAULT LEVEL WITHSTAND – 40kA for 3 seconds. 87T
15VA, CL:PS
f) NOMINAL CREEPAGE SISTANCE – 31mm/kV
64R TRANSFORMER LV SIDE GROUND FAULT PROTECTION ELEMENT
Core 4: 100/1, 87L LV
15VA, CL:PS
3: THE FOLLOWING MINIMUM CLEARANCES AS PER IS-10118 ARE ADOPTED:
Core 5: 100/1, SPARE a) BETWEEN PHASES – 1300mm 50/51 INSTANTANEOUS AND IDMT PHASE OVER CURRENT PROTECTION ELEMENT`
15VA, CL:PS b) BETWEEN PHASE TO EARTH – 1300mm
50N/
P2 INSTANTANEOUS AND IDMT NEUTRAL OVER CURRENT PROTECTION ELEMENT`
4: MINIMUM SAFETY WORKING CLEARANCE (IE RULES “RULE-64”): 4000mm 51N
CIRCUIT BREAKER 52 86-1 67/ DIRECTIONAL PHASE AND NEUTRAL OVER CURRENT PROTECTION ELEMENT`
79 50LBB 5: CONNECTION TYPE FOR: 132kV SWITCHYARD 67N
145kV, 1600A,GANG OPERATED SF6 86-2 LEVEL FROM FGL CONDUCTOR TYPE
CIRCUIT BREAKER a) MAIN GANTRY BUS – 9300mm – SINGLE ACSR ‘ZEBRA’ 64R TRANSFORMER HV SIDE GROUND FAULT PROTECTION ELEMENT
40kA for 3 seconds HV
MCOV 92kV, 10kA, Class-III b) EQUIPMENT INTERCONNECTION – 4600mm – SINGLE ACSR ‘ZEBRA’
XR BAY LIGHTNING ARRESTER c) EARTH/SHIELD WIRE – 11300mm – 7/3.15 mm G.I
68 BLOCKING ELEMENT

6: ALL THE EQUIPMENT AND STRUNG BUSSES WITHIN THE SUBSTATION WILL BE
51G SENSITIVE EARTH FAULT PROTECTION ELEMENT
PROTECTED FROM LIGHTNING STROKE BY MEANS OF EARTH/SHIELD WIRE
15(ONAN) / 20(ONAF) MVA
132/6.6KV (GANTRY TOWERS – LM)
Z=10% 49 TRANSFORMER THERMAL PROTECTION ELEMENT
1 No. 63 63 63
POWER TRANSFORMER NCT 50/1,
ON-LOAD T.C BZ TC PD
+12.5% IN STEPS OF
CL=PS, 15VA 7: LOCATION AND QUANTITY OF LIGHTNING MASTS SHALL BE FINALISED AFTER
49O 49W 71 DATA COMMUNICATION ELEMENT (WITH OUR PLANT DCS)
2.5% TA OIL
DETAILED CALCULATION OF LIGHTNING PROTECTION. 16
2 Nos.
WITH N2 INJECTION SYSTEM
7 RUNS OF 11KV(E) XLPE 1Cx630Sq.mm AL.
NCT 1000/1,
CL=PS, 15VA
8: FOR LIGHTNING SHIELDING, EARTHING, ILLUMINATION AND JUNCTION BOXES 79 CB RECLOSING PROTECTION ELEMENT
CABLE (3PHx2/PH)+1 SPARE) HAS TO BE
TERMINATED INSIDE THE MAIN INCOMER OF MV P1 WITH CONTROL CABLING DETAILING WILL BE DONE DURING DETAILED
SWITCHBOARD (APPROXIMATELY 100MTRS
FROM THE TRANSFORMER SECONDARY
2000/1 CL=PS, 20VA ENGINEERING. LIGHTING CONTROLLER WITH GEO-TIMER HAVING BATTERY 50L LOCAL CB BACKUP PROTECTION ELEMENT
P2
TERMINAL BOX). ALL CABLES BURRIED IN HUME 51G BACKUP WILL BE PROVIDED. BB
PIPES (SUPPLY OF HUME PIPES – INOXAP). TAKE
1KMS OF THIS CABLE WITH 6x2=12 END UPSTREAM
TERMINATIONS INTERLOCK 86 LOCKOUT RELAY ELEMENT
9. THE DC POWER SYSTEM WILL COMPRISE OF 220VDC, 160AH SMF VRLA 2V
CELLS BATTERY BANK. 63BZ BUCKHOLZ RELAY PROTECTION
TO MV SW.BOARD
7.2kV, 2000A, VCB PROTECTION RELAY
63
40kA for 3s
ONLINE TAP-CHANGER PRESSURE DEVICE SIGNAL PROTECTION
TC
63 TRANSFORMER MAIN TANK PRESSURE DEVICE SIGNAL PROTECTION
PD
49O OIL TEMPERATURE SIGNAL PROTECTION ELEMENT

49W WINDING TEMPERATURE SIGNAL PROTECTION ELEMENT

71
OIL LEVEL SWITCH SIGNAL PROTECTION ELEMENT
OIL

87L TRANSMISSION LINE DIFFERENTIAL PROTECTION ELEMENT

TITLE: USED ON: 2015-BARJ


132KV EHV RADIAL SUBSTATION OWNERS GROUP: ELECTRICAL
RELEASE PURPOSE: PRELIMINARY
SINGLE LINE DIAGRAM FOR UPCOMING ASU REFERENCE : IE RULES
0 -- PRILIMINARY ISSUE 05-08-2016 SC SC ASM INOX AIR PRODUCTS PRIVATE LIMITED
7TH FLOOR CEEJAY HOUSE, DR.ANNIE BASANT ROAD, WORLI,MUMBAI - 400018
AT BARJORA (W.B) PROJECT : 2015-BARJ DOC.NO.: 2015-BARJ-EHV-SLD-01
REV CN NO. REVISION DESCRIPTION DATE BY CHK’D APP’D SCALE NONE SHEET 1 OF 1