GSC1000
Kyland ESW Configuration Manual
Rev.0
February 2014
TOSHIBA CORPORATION
Table of Contents
1. Outline ..................................................................................................................................................................... 3
2. Database Configuration .......................................................................................................................................... 3
3. Kyland ESW Configuration ..................................................................................................................................... 4
3.1 Setting KyLand ESW IP Address ............................................................................................................................ 4
3.2 SNMP Configuration ............................................................................................................................................... 6
3.3 RSTP Configuration ................................................................................................................................................ 7
3.4 Alarm Setting .......................................................................................................................................................... 8
4. SAS Setting File for KyLand ESW .......................................................................................................................... 9
-2-
6F2M1123
1. Outline
This manual describes the configuration of KyLand ESW to be applied to GSC1000 Substation Automation System
(SAS). The configuration procedure are divided into 3 three main steps as listed below.
1. SAS Database configuration
2. Kyland ESW configuration
3. Installation of SAS setting file for Kyland ESW
2. Database Configuration
Configure RingPort parameter of SAS database in Pmodel as shown by example below. Refer to System
Screen drawing to confirm the Ring LAN direction.
Set Ring_Lan_Port_No parameter as ‘Port In’ / ‘Port Out’ based on Ring LAN direction.
Set the port number of Ring LAN connection as shown by figure below.
SC-A SC-B
Ring Port7
SICOM3000 Ring Port8 SICOM3000
RingPort7 Ring Port8
(IN) (ESW-01C) (OUT) (ESW-02C)
(IN) (OUT)
-3-
6F2M1123
-4-
6F2M1123
-5-
6F2M1123
Click menu “Basic Configuration IP Address” to open IP Address configuration page.
Input IP Address, Subnet Mask and Gateway field and click Apply button.
Then select ‘Save Configuration’ menu and click ‘Save’ button to save edited IP Address.
Select “Device Management Reboot” menu and click ‘Reboot’ button to restart KyLand ESW. The IP
Address of KyLand ESW will not change until it restarted.
Select ‘Save Configuration’ menu and click ‘Save’ button to save SNMP configuration.
-6-
6F2M1123
Change protocol state to Enable and set the port priority value based on the object to be connected by
referring to priority table above as shown by figure below. After completed click Apply button.
Then select ‘Save Configuration’ menu and click ‘Save’ button to save RSTP configuration.
Set the port priority correctly according to priority table above. The priority value
will impact network performance of Substation Automation System.
-7-
6F2M1123
Unused optical
port alarm must
Enable alarm of optical be disabled
port for Ring LAN
connection by referring
to actual connection of
ESW below.
Select ‘Save Configuration’ menu and click ‘Save’ button to save Alarm configuration.
-8-
6F2M1123
4. SAS Setting File for KyLand ESW
Refer the procedure below to apply SAS setting file for KyLand ESW.
A) Preparation
Prepare SAS Individual Setting for KyLand ESW supporting.
Copy “customize” folder from Individual Setting CD to “C:/” drive.
Confirm the following SAS setting file for KyLand ESW are exist.
C:/customize/opt/sas/config/ESW_PropertyInfo.csv
C:/customize/opt/sas/config/ESW_Snmptrap.csv
C:/customize/opt/sas/config/CSCC_define.csv
-9-
6F2M1123
The confirmation dialogue will be displayed as shown by figure below. Click OK button to restart the SC
server or click Cancel button to cancel this command.
The following page will be displayed when restarting process is started. Wait until restarting process
completed.
Repeat SC mode switching (Normal Maintenance) procedures above for all SC (SC-A and SC-B).
- 10 -
6F2M1123
Set “Setting” combo box to select the drive where Individual Setting update files is located.
Select target SC to be updated. Check □SC-1 (HOST) for SC-A installation and check □SC-2 (HOST)
for SC-B installation. SC-A and SC-B can be updated together. FEP1-A/B are not necessary to be
installed.
Click ‘Revision Check button’ to confirm the version of application in SC-A and SC-B.
Click ‘Send To Computer’ button to send Individual Setting files to SC.
- 11 -
6F2M1123
Click Compare button and check the result of Individual Setting installation result. Confirm the output
string “Success” is displayed in the log. Then, click Revision Check button and confirm the version
number that displayed by IniSend dialogue same with version number of installer.
- 12 -
6F2M1123
The following page will be displayed when restarting process is started. Wait until restarting process
completed.
- 13 -
6F2M1123
Repeat SC mode switching (Maintenance Normal) procedures above for all SC (SC-A and SC-B).
- 14 -
6F2M1123
変 更 記 録 REVISIONS
変更記号
REV.MARK
ページ
変 更 箇 所 _・_ 変 更 内 容 承 認 調 査 担 当 保 管
PAGE CHANGED PLACE AND CONTENTS APPROVED CHECKED PREPARED REGISTERED
変更発行日 BY BY BY
REV.ISSUED
First Issue
0 Ilwan
Asrizal
6 Feb ‘14.
配布先 部数 発行 承 認 K. Kaneda
ISSUED
DISTRIBUTION COPY APPROVED BY 6 Feb ‘14
HEN S 1 担 当 Ilwan A.
F 保管 REGISTERED
- 15 -
6F2M1123
TOSHIBA CORPORATION
- 16 -