ASHIDA Electronics Pvt. Ltd.

®
Plot no. A-308, Road no. 21, Wagle Industrial Estate, Thane (W) 400604.INDIA.
0091-22-65771076/77/78, 25827524/25/26
Fax: 0091-22-2580 4262. E-mail: sales@ashidaelectronics.com

ADR132A

Operating Manual
For
ASHIDA Numerical 3 Phase
Under / Over Voltage Protection
Relay
Type: - ADR132A

REV DESCRIPTION DATE CHK. BY APPD. BY


08 Operating Manual For Ashida Numerical 3 Phase 24.03.10 VAP SMK
Under / Over Voltage Protection Relay ADR132A
User Notice

Ashida Electronics (P) Ltd. Reserve all right to make improvements in the
products described in this manual at any time and without notice. All rights are
reserved. No part of this manual may be reproduce, copied, translated or
transmitted in any form or by any means without the prior written permission of
Ashida Electronics (p.) Ltd. Information in this manual is intended to be accurate
and reliable. However Ashida assumes no responsibility for its use; nor for any
infringements of rights of third parties that may result from its use.

® ASHIDA Electronics Pvt. Ltd.


Page: 2 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
No. Topic Page No
1.0 Features 4
2.0 General 4
3.0 Protection Function 4
3.1 Over / Under Voltage Protection 5
4.0 Supervision Function 5
4.1 Self Supervision 5
5.0 Measurement & Communication Function 5
6.0 Electrical Noise Immunity 6
7.0 Setting Reliability 6
8.0 On Line Testing 6
9.0 Front Panel And Control 7
10.0 Getting Started 8
11.0 To Adjust Settings. 9
11.1 Password Settings 9
11.2 New Password 10
11.3 Unit ID 11
11.4 Trip Test 11
11.5 Under Voltage Trip setting 11
11.6 Under Voltage Time setting 11
11.7 Over Voltage Trip setting 12
11.8 Over Voltage Time setting 12
11.9 PT Secondary 12
11.10 PT Ratio 12
11.11 Trip Block 13
11.12 Ann Cont 13
11.13 Reset Delay 13
11.14 Save Settings 14
12.0 To View Fault 14
13.0 Drawing – Pickup Test Setup 17
14.0 Drawing – Time Test Setup 18
15.0 Procedure for Pickup and Time test 19
16.0 Sample Test Report 20
17.0 Technical Specification 21
18.0 Flow Chart 23
18.1 Flow Chart for Setting 23
18.2 Flow Chart to View Faults 23
19.0 Drawing - Typical External Connection 24
20.0 Drawing - Mechanical Details 25
21.0 Revision note 26

® ASHIDA Electronics Pvt. Ltd.


Page: 3 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
1.0 Features : -
• 3 Phase start connected, full Under / Over Voltage protection.
• Programmable (Non- Volatile) Setting By local keys Back - lit LCD
display for settings.
• Display of fault voltage / Load voltage.
• Wide Under voltage range – 40% to 100% (100% = bypass under
voltage element).
• Wide Over voltage range – 100% to 155% (100% = bypass over
voltage element).
• Design using DSP technology.
• Latching of fault value.
• Pass-word protection for setting.

2.0 General : -
The ADR132A is member of Ashida Numerical Relay family (Aditya Series)
design to meet demand of low and medium switchgear control. The
ADR132A is basically 3-phase Under/Over Voltage protection with Definite
Time. The ADR132A continuously monitors all 3-phase voltage, through PT
connections. The high-speed micro-controller samples this voltage sine
wave through a 12-bit A/D converter. The micro-controller performs
powerful Digital Algorithms to find out Amplitude of voltage signal, and
then this value is use for protection and metering function. All
measurement is tuned to fundamental frequency and reject all higher
harmonics present in electric supply. Each phase voltage is also
displayed on 16 x 2 LCD display for metering. The Relay is having main
three functions 1) Protection 2) Self-Supervision 3) Measurement.

3.0 Protection Function : -


The ADR132A give maximum benefit/cost ratio. The ADR132A give all the
advantage of numerical relay at affordable cost. Following is summery of
different protection functions provided by relay.

ANSI IEC Protection Function


27 - Definite Time Under Voltage Protection
59 - Definite Time Over Voltage Protection

® ASHIDA Electronics Pvt. Ltd.


Page: 4 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
3.1 Over / Under Voltage protection:-
The ADR132A has 3 sensing element, each is connected to monitor phase
to neutral voltage. The tripping voltage can be set to 40% to 100% for
under voltage and 100% to 155% for over voltage. Where 100% = rated line
to neutral voltage. The display can be programmed to display primary
voltage directly, The under voltage and over voltage sections have their
independent time setting. (1 - 10sec). The high speed CPU continuously
monitors all the three voltages inputs and compare with UV/OV setting. If
any one voltage is above OV setting or below UV setting, the CPU
calculates start timer and provides trip command, if fault persist even after
this time delay.
All the settings are password protected to prevent unauthorised change.

4.0 Supervision Function:-

4.1 Self-supervision:-
The Relay is continuously keeping track on its internal hardware and its
movement if it detects any failure of any component, it gives message on
LCD display, This feature is very useful to give pre information to avoid any
mall - operation. In such situation it uses some default setting and remains
in protection mode.

5.0 Measurement Function and communication:-


In normal condition this display shows all settings. Via keyboard the display
can be programmed to show the actual voltage across relay coil. If voltages
deviate from UV/OV settings the relay gives trip command. The type of fault
is displayed on LCD display. During the fault condition the relay
measure the fault voltage and store in non-volatile memory. The fault
voltage can be read via keyboard on LCD display Last 3 fault values
along with tripping counter can be view via keyboard. All settings are
saved in Electrically erasable read only memory and remain.

® ASHIDA Electronics Pvt. Ltd.


Page: 5 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
6.0 Electrical Noise Immunity: -
Utility and industrial environments are electrically very noisy. Electronics
protection equipment requires careful design and testing to ensure reliable
operation in switchgear. Ashida has applied its expertise and more than 35
years of experience in field of electronics design to ensure that the
ADR132A operates when required, without nuisance trips. Thanks to the
latest micro-controller technology.

7.0 Setting Reliability: -


Any numerical or digital relay in which all settings are programmable via key
board, use some internal memory to store these settings. Many relays use
internal rechargeable batteries to maintain these settings. In case of power
supply fluctuation, batteries are often unreliable, and settings get corrupted.
In such situation, the relay may mal- operate. Ashida use special non-
volatile memory technology, which do not require any power source to
maintain settings of the relay. Once the relay is programmed, it maintain the
settings more than 10 years even in the absence of any power supply. In
case if internal fault is detected in this section during the self diagnosis, then
relay gives message and take default settings stored in program memory to
avoid any mal-operation.

8.0 On Line Testing: -


The ADR132A relays are provided with online testing facility. By pressing
TEST push button (provided on front panel) the relay provide immediate trip
command. This trip command also get extended to breaker coil, thus entire
trip operation from relay to circuit breaker can be checked. This trip
command is recorded as “T” flag on LCD display. If the CB operation is un-
desirable then, pressing Bypass switch can block the relay trip command
extension to CB coil.

® ASHIDA Electronics Pvt. Ltd.


Page: 6 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
9.0 Front Panel and Control:-

ADR132A
1

3
11
4

5 7

10
8

6 9

No Legend Function
1. ON Power ‘ON’ Indicator LED.
2. PKP ‘PICKUP’ Indicator LED.
3. FAULT ‘FAULT’ Indicator LED (HR) Type.
4. TRIP ‘TRIP’ Indicator LED (SR) Type. Output element status
indicator of Trip coil or Spare coil.
5. MODE Push Button for MODE. To select setting parameter while
setting and to SAVE setting
6. INR Push Button to view the set parameters. &
To ‘Increment’ the value when the relay is in setting condition.
7. DEC Push Button to view the Fault Values. &
To ‘Decrement’ the value when the relay is in setting condition.
8. TEST Push Button for online TESTING.
9. BYPASS Push Button for BYPASSING TRIP command.
10. RESET Push Button for HARDWARE RESET of the relay.
11. LCD Display To observe setting and parameters of the relay

Push Buttons
The function of relay is controlled by the push buttons, MODE, INR, DEC, TEST,
BYPASS and RESET which are provided on the front Plate. The relay has a front
cover to keep it dust free.
At the time of setting if changes are not carried within 100s then the display will
refresh itself showing line voltages.

® ASHIDA Electronics Pvt. Ltd.


Page: 7 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
10.0 Getting Started:-
After Power ON or after pressing RESET push button the relay display
following message.

Ashida Digital
OV/UV Relay

ADR 132A V3.05


Unit ID =0001

When the PT Ratio is 1, the unit will show in terms of (V) Volts i.e.

P1 =000.0 P2 = 000.0
P3 =000.0 V

What is displayed is as follows


Relay Name – Ashida Digital OV/UV Relay
Relay Type – ADR 132A Software Revision V3.05
Relay Display – Online Voltage of (3) Three Phases P1, P2 & P3. – unit
in terms of (v) Volts.
When the PT Ratio is above 1, the unit will show in terms of (kv) Volts
i.e.

P1 =000.0 P2 = 000.0
P3 =000.0 KV

Relay Display – Online Voltage of ( 3 ) Three Phases P1, P2 & P3 units


in terms of (Kv) volts.
The relay is capable of protection as well as metering function. After
power ‘ON’ the relay will start showing actual Voltage flowing though PT.
In ASHIDA we believe in continuous improvement of our products. Also
implementing the valuable suggestions and feedback from actual user.
Whenever any relay firmware modification is done it is recorded as
version change. The relay has the facility to upgrade firmware at site, so
that customer can be benefited with latest modification.

® ASHIDA Electronics Pvt. Ltd.


Page: 8 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
11.0 To Adjusting the Settings: -
After Power ON or after pressing RESET push button the relay display
following message.

A s h id a Di g i ta l
O V / UV Rel a y

A D R 13 2 A V 3 . 05
U n i t I D = 0 0 01

P1 =000.0 P2 = 000.0
P3 =000.0 V

Now when the ‘MODE’ push button is pressed the following message is
displayed.

P a s sW o rd = 001
U s e I n r / D ec

11.1 Password :-
The INR push button is used to increment and the DEC push button is
used to decrement the value. By using this push buttons set the
Password to match the previously set password.
If any of the push button is press for more than 4 sec. the selected value
will start incrementing or decrementing with high speed. If INR push
button remains pressed then display value will roll between min. & max.
The min. is 0 and max. is 99. If DEC push button remains pressed then
display value will roll between max. & min. The max. is 99 and min. is 0.
For example if required value to be set is 25 then press INR push button
till you get reading 20, then releases the INR push button key and
increment one by one.
If the entered password matches with previously set password then we
are able enter to the other settings parameters. If not the following Error
message is shown on the display

P a s sW o rd F a il

® ASHIDA Electronics Pvt. Ltd.


Page: 9 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
Then the following message is displayed.

P1 =000.0 P2 = 000.0
P3 =000.0 V

Note: -
In case authorized person forgets the set password, then press ‘MODE’ &
‘RESET’ pushbutton simultaneously & release ‘RESET’ pushbutton.
Relay will load default value, then release ‘MODE’ pushbutton. Password
will be Reset to ‘000’ and the other settings of the relays will change to
default values.
But if entered password matches with the previously set password, then
when the MODE’ push button is pressed again the following message will
be displayed.

P a s sW o rd = 00 0
N e w P a ssW o r d

11.2 New Password :-


By using the INR push button or the DEC push button New Password
can be set.
Note:
When any changes made in the relay setting in any of the parameters the
Mode Push button should be pressed till following message is displayed
‘Save Settings’ ‘Mode for Save’. Then again press the Mode
pushbutton the relay will save the changes made and the OK message
will be displayed. Always use this procedure to save any settings that are
made.
If entered password matches with the previously set password, then
when the MODE’ push button is pressed again the following message will
be displayed.

U n i t I D = 0 01

® ASHIDA Electronics Pvt. Ltd.


Page: 10 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
11.3 Unit ID : -
By using the INR push button or the DEC push button the desired Unit
addresses can be selected. The unit addresses will vary from 00 to 255,
which means total 254 devises can be connected to single computer. The
255 address is reserved for special command.
These settings are required to communicate with the SCADA
computer.
Then when the MODE’ push button is pressed again the following
message will be displayed.

T r i p T est = 0 0 1
0 1 = N o 0 2 = Y es

11.4 Trip Test : -


By using the INR push button or the DEC push button the desired Trip
Test can be set, that is 1 or 2. In which case 1 corresponds with No and 2
correspond with Yes respectively.
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

U V % = 055
R a n ge 40 - 10 0 %

11.5 Under Voltage Trip Settings : -


By using the INR push button or the DEC push button the desired Under
Voltage Trip can be set. The under voltage Trip range will be from 40%
to 100% in steps of 1% (100%-Bypass).
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

U V Ti m e = 0 00 2
R a n ge 1 – 1 0S e c.

11.6 Under Voltage Time Settings : -


By using the INR push button or the DEC push button the desired Under
Voltage Time can be set. The under voltage Time range will be from
1Sec. to 10Sec in steps of 1Sec.

® ASHIDA Electronics Pvt. Ltd.


Page: 11 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

O V % = 105
R a n ge 100 - 1 5 5%

11.7 Over Voltage Trip Settings : -


By using the INR push button or the DEC push button the desired Over
Voltage Trip can be set. The over voltage Trip range will be from 100%
to 155%in steps of 1% (100%-Bypass).
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

O V Ti m e = 0 00 2
R a n ge 1 – 1 0S e c.

11.8 Over Voltage Time Settings : -


By using the INR push button or the DEC push button the desired Over
Voltage Time can be set. The over voltage Time range will be from
1Sec. to 10Sec in steps of 1Sec.
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

P T Se c . = 0 00 1
6 3 . 5V / 110 V / 23 0 V

11.9 PT Sec. : -
By using the INR push button or the DEC push button the desired PT
Sec. can be set 01 is 63.5V, 02 is 110V and 03 is 230V
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

P T Ra t io = 00 0 1
R a n ge 1 - 4 00 0

11.10 PT Ratio : -
By using the INR push button or the DEC push button the desired PT
Ratio can be set. The range will be from 1 to 4000 in steps of 1.

® ASHIDA Electronics Pvt. Ltd.


Page: 12 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

T r i p B loc k = 0 002
01: YES 02: NO

11.11 Trip Block: -


This setting is use to Trip block function. Normally Trip Test is required
during pre commission testing to check operation of relay and panel
wiring. By using the INR push button or the DEC push button the desired
Trip Block can be yes or no, i.e. 1 or 2. When the given set value is 2
then it will sense under voltage at zero volt, but when the given set value
is 1 then it will block under voltage tripping at zero volt (remains neutral at
zero volt).
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

A n n C o nt. = 0 0 1
S R = 1 HR = 2

11.12 ANN Contact: -


By using the INR push button or the DEC push button the desired
Annunciation Contact can be set, i.e. 1 or 2. In which, 1 corresponds with
SR (Self-Reset) and 2 correspond with HR (Hand-Reset) respectively.
The MODE’ push button is pressed again the following message will be
displayed.

R e s et Del a y = 00. 9
B y p / 0.5 - 5 .0 S ec

11.13 Reset Delay: -


By using the INR push button or the DEC push button the desired Reset
Delay can be set, i.e. Bypass or 0.5 sec to 5.0 sec in steps of 0.1sec.
Then when the ‘MODE’ push button is pressed again the following
message will be displayed.

® ASHIDA Electronics Pvt. Ltd.


Page: 13 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
S a v e S ett i n g?
M o d e f or S a ve

11.14 Save Settings : -


The relay will now ask if you would like to Save the changes made at
various setting parameters by you.
Note : In this relay all the settings are done in foreground and the relay
works in background i.e. the relay will take the new settings only after
completion of all settings and the confirmation by the user, then the relay
will use this setting for actual operation.
When the MODE’ push button is pressed again then the relay will Save
the settings made and the following message will be displayed.

OK

P1 =000.0 P2 = 000.0
P3 =000.0 V

12.0 To View FAULTS: -

P1 =000.0 P2 = 000.0
P3 =000.0 V

Now when the INR push button is pressed then following message is
displayed.

O V : P1 F : 0 001
U V : P2 T C : 0 002

Explanation:
F0001 = First Fault
OV = Over Voltage at R Phase [R Phase is taken for example]
UV = Under Voltage at Y Phase [Y Phase is taken for example]
TC = Trip Counter reading at the time of Over / Under Voltage.

® ASHIDA Electronics Pvt. Ltd.


Page: 14 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
Now if the DEC push button is pressed and the PT Ratio is 1 then
following message is displayed.

P 1 = 00 0 .0 P 2 = 0 00. 0
F 1 P3 = 000 . 0 V

Explanation:
F1 = First Fault
P1 = Voltage at R Phase.
P2 = Voltage at Y Phase.
P3 = Voltage at B Phase.
V = Units in Volts.

But if the DEC push button is pressed and the PT Ratio is more then 1
then following message is displayed.

P 1 = 0 0 0.0 P2 = 000 . 0
F1 P 3 = 00 0 . 0 KV

Explanation:
F1 = First Fault
P1 = Voltage at R Phase.
P2 = Voltage at Y Phase.
P3 = Voltage at B Phase.
KV = Units in kilovolts.

Now if the DEC push button is pressed then following message is


displayed.

O V : P1 F :00 0 1
U V : P2 TC :00 0 2

Now when the INR push button is pressed then following message is
displayed.
O V : P1 F :00 0 2
U V : P2 TC :00 0 3

Note : The Relay will display Fault 2 & Fault 3 Respectively in above order.

® ASHIDA Electronics Pvt. Ltd.


Page: 15 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
After the faults, when the INR push button is pressed then following
message is displayed.

U V : 1 00% U T : 00 1 S
O V : 1 10% O T : 01 0 S

Explanation:
UV = Set Percentage of Under Voltage.
UT = Set Time Delay for Under Voltage Tripping.
OV = Set Percentage of Over Voltage.
OT = Set Time Delay for Over Voltage Tripping.
Now when the INR push button is pressed then following message is
displayed.

P 1 = 00 0 .0 P 2= 0 00. 0
P 3 = 00 0 .0 V

® ASHIDA Electronics Pvt. Ltd.


Page: 16 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
15.0 Procedure for Pickup and Time Test.
• Connect ADR132A Relay to Variac and Timer as shown in Drawing.
• Switch ON the Relay Auxiliary supply.
Testing for B Phase Under Voltage
1. Now switch on both the sources.
2. Apply voltage 63.5VAC by varying from source 1 to terminal no 5, 7
and 6, 8. (Refer drawing)
3. Apply voltage 63.5VAC by varying from source 2 to terminal no 9
and 10. (Refer drawing)
4. Set UV Trip Percentage as per test report. (e.g. 45%)
5. Now gradually decrease the voltage by varying source 2. When it is
below the set trip percentage the relay pickups and the PKP Led
glows on front plate, this indicates pickup value.
6. For Time test set the Time Delay as per report (i.e. 5sec.)
7. Then switch ON the ARTU unit and adjust voltage to required value
by adjusting dial.
8. Switch OFF ARTU unit and reset the timer.
9. Switch ON the ARTU, which also starts timer unit. Timer unit will
stop the counting when the relay will provide the TRIP signal. Note
down the delay.
10. Repeat the same procedure for other readings.
Testing for B Phase Over Voltage
11. Set the OV percentage as per test report (i.e. for e.g. 110%)
12. Now gradually increase the voltage by varying source 2. When it is
above the set trip percentage the relay pickups and the PKP Led
glow on front plate this indicates pickup value.
13. The time testing procedure is same as above. (Point 6, 7, 8 & 9)
14. Repeat the same procedure for other readings.
For Y Phase Under / Over voltage setting keep R & B phase terminals
shorted and apply constant voltage 63VAC during testing.
For R Phase Under / Over voltage setting keep Y & B phase terminals
shorted and apply constant voltage 63VAC during testing.

® ASHIDA Electronics Pvt. Ltd.


Page: 19 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
16.0 Sample Test Report: -
Sr. No._____________________ Date:____________
Aux. Voltage :____________. P. T. : ____________.

1. Pick - up Test: : 2. Time Test: :


Keep Set Voltage at 50%

Set Under Set Time Delay Observed (Sec.)


Voltage R (V) Y (V) B (V) Delay
Trip (%) (Sec.) R Y B
45 1.0
50 5.0
55 10.0
60
65
70
75
80
85
90

Keep Set Voltage at 130%

Set Over Set Time Delay Observed (Sec.)


Voltage R (V) Y (V) B (V) Delay
Trip (%) (Sec.) R Y B
105 1.0
110 5.0
115 10.0
120
125
130
135
140
145
150

3. Insulation Test :___________ Mohm @ 1000 VDC between all terminals & body.

4. H.V. Test : @ 2000 VAC between all terminal & body for 60 sec. _______________.

Conclusion: ________________________________________________________.

® ASHIDA Electronics Pvt. Ltd.


Page: 20 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
17.0 Technical Specification :-

Sr. Specification Particulars


No.
I. Inputs : Suitable for PT secondary 63.5V / 110V / 230V Phase
neutral (To be specified.)
II. Protection Relay : For Under Voltage - 40% to 100% % in step of
Setting Range 1%. (100% = bypass)
: For Over Voltage - 100% to 155% in step of
1% (100% = bypass)
: For Under Voltage Timer - 1 – 10 sec in steps of 1sec
: For Over Voltage Timer - 1 – 10 sec in steps of 1sec
III. Pickup Voltage : Within 1.05 times of set over voltage
: Within 0.95 times of set under voltage.
IV. Resetting Voltage : Less than 90% of set value. For over voltage
: Less than 110% of set value. For under voltage
V. Time Accuracy : Within class 2.5 As per IS: 3231.
VI. Burden on PTs : Less than 1.0VA.
VII. Aux. Supply : 18 - 52VDC or 77 - 250VDC. To be specified while
ordering.
VIII. Burden on Aux. : Less than 10VA on any supply.
Supply
IX. Control Contacts : 2 NO contacts (SR) are given for Trip & Annunciation. -
Trip Duty
X. Contact Rating : Make and carry for 3sec. – 7500VA with max. 30A &
Trip Duty 660VAC/DC
: Make and carry for continuous - 1250VA with max. 5A
& 660VAC/DC
: Break AC - 1250 VA DC - 100 W resistive 50W
inductive.
XI. Operational Indicators (Flags)
ON : Green LED indicates Relay OK
: In case of following condition led become off
1. Problem in relay Hardware.
2. Auxiliary supply is not sufficient for relay operation.
FAULT : Red LED indicates the UV/OV relay fault, Hand Reset
(HR) Type.
PKP : Red LED indicates relay pickup (timer start)
TRIP : Indicates that Trip pulse is being executed. When
BYPASS switch is pressed, actual trip is not executed.
XII. Thermal Withstand : x2 times the rated voltage for 3sec.
Capacity : x1.5 Continuous

® ASHIDA Electronics Pvt. Ltd.


Page: 21 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
XIII. High Voltage Test : IEC 60255-5
: Except DC Voltage and RS485 input – 2.0 kV (RMS),
50Hz
: Only DC voltage supply and RS485 - 2.8 kV DC
: Between Open contact of TRIP / CLOSE 1.5kV (RSM)
50Hz
: Between Open contact of ALARM – 1kV (RSM) 50Hz
XIV. Impulse Voltage : IEC60255-5
Test (all circuit : 5kV (peak) 1.2 / 50us, 0.5 J, 3 positive and 3 negative
class – III) impulse at interval of 5 sec
XV. High Frequency : IEC 60255-22-1, Class III
test : 2.5 kV (peak) 1MHz , τ = 15μs 400 surges / s duration
2s
XVI. Electro static : IEC 60255-22-2 Class III and IEC 61000-4-2 class III
Discharge : 4kV/6kV contact discharge, 8kV air discharge, both
polarities 150pF, Ri 330 Ω
XVII. Irradiation with : IEC 60255-22-3 and IEC 61000-4-2 class III
radio frequency : 10V/m; 80 to 1000MHz; 80%; 1kHz AM
field, pulse-
modulated,
XVIII. Fast transient : IEC 60255-22-3 and IEC 61000-4-3, class III
interference/ bursts : 4kV; 5/50ns; 5kHz burst duration = 15ms;
: Repetition rate 300ms; Both polarities; Ri = 50Ω;
duration 1 min.
XIX. Shock Test : IEC 60255-21-2 class 1
: Semi-Sinusoidal
: 5g acceleration, duration 11ms,
: Each 3 shocks in both direction of the 3 axes
XX. Vibration Test : IEC 60255-21-1 class 1 / IEC 60068-2-6
: Sinusoidal 10 to 60Hz ±0.035 mm
: Amplitude, 60 to 150Hz, 0.5g acceleration
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal
XXI. : For Cabinet Type - MAC00101 (CSA -150)
: For Electrical Connection - APD00803

® ASHIDA Electronics Pvt. Ltd.


Page: 22 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
18.0 Flow Chart

18.1 Flow Chart for Settings

P1 = 000.0 P2 = 000.0
P3 = 000.0 V
MODE

Password = 000 Password = 000 Unit ID : 0001


MODE MODE
Use Inr / Dec New Password
MODE

UV% = 0055 Trip Test = 0002


MODE
Range = 40 - 100% 01= No 02 = Yes
MODE

UV Time = 0010s OV% = 0105


MODE
Range = 1 - 10s Range 100 - 155%
MODE

PT Sec. = 063.5 OV Time = 0001s


MODE
63.5V/110V/230V Range = 1 - 10s
MODE

PT Ratio = 0001 Trip Block = 0002


MODE
Range = 1 - 4000 01:Yes 02:No
MODE

Reset Delay =00.9 Ann Cont = 0001


MODE
Byp / 0.5-5.0sec SR = 1 HR = 2

MODE

P1 = 000.0 P2 = 000.0 Save Settings?


OK MODE
P3 =000.0 V Mode for Save

18.2 Flow Chart to View Faults

P1 = 000.0 P2 = 000.0 When PT Ratio is 1


P3 = 000.0 V P1 = 000.0 P2 = 000.0
DEC
INR F1 P3 = 000.0 V
OV : P1 F : 0001 When PT Ratio is
UV : P2 TC : 0002 more then 1
P1 = 000.0 P2 = 000.0
DEC
F1 P3 = 000.0 KV

OV : P1 F : 0001
DEC
UV : P2 TC : 0002
INR

OV : P2 F : 0002 Note : Fault 2 & Fault 3 displayed in same


UV : P2 TC : 0003 order as Fault 1.
INR

OV : P3 F : 0003
UV : P3 TC : 0003
INR

UV =100% OT = 0001S
OV = 110% UT = 0010S

® ASHIDA Electronics Pvt. Ltd.


Page: 23 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10
21.0 Revision Notes:-

Revision No. Date Revision Note


01 24.03.10 Original Revision for Software V1.0

® ASHIDA Electronics Pvt. Ltd.


Page: 26 of 26
Ref.: ADR132Am
Operating Manual For Ashida Numerical 3 Phase Under
/ Over Voltage Protection Relay ADR132A Rev. : 01 Dt. 24.03.10