You are on page 1of 2

Product note

Kabeldon cable termination for GIS and TRF, 84 kV


APEGA 84

Cable termination suitable as a fixed 1

connection point in a gas-insulated


switchgear, a transformer without 2
3
a separate cable box or where the
cable box is filled with transformer oil. 4
5
Designed to meet the requirements of 6
internationally accepted standards. 7
8
9

10
11

1. Top fitting 9. Earth clamp


Made from silver-plated brass. The earth clamp is made from tin-plated brass and clamped
with stainless steel bolts. The earth clamp has a rated cross
2. Top bolt/conductor connection section of 300 mm².
Made from aluminium or tin-plated copper.
10. Cable clamp
3. Insulator Made from aluminium alloy. The clamp secures the cable in
Made from epoxy with an integrated screen interruption. a fixed position.

4. Filling compound 11. Corona shield


Polybuthene oil, volume: 6 liters (expansion vessel included). Corona shield for transformer (TRF) applications, made of
aluminium with surface insulation coating.
5. Stress relief cone
Premolded stress relief cone designed for geometric field
control.
Main technical data
6. Pressure ring Electrical data, IEC standard 60840 Voltage kV
Made from stainless steel (bolts are not included). Highest voltage for equipment, Um 84
Rated voltage, U 72.5
7. Flange Value of U0 for determination of test voltage 42
Made from aluminium alloy. Heating cycle voltage test, 2U0 85
Partial discharges test <5pC, 1.5U0 65
8. Box body Switching impulse voltage test NA
Made from aluminium alloy. Lighting impulse voltage test, BIL + 380
AC voltage test, 2.5U0 105
Measurement of loss factor, U0 42
Dimensions in mm
120
Ø 270

Ø 12 (8x)

583

Ø 217

Document ID: 7ABA102623


Ø 300

Pressure ring.
Laboratory for product testing. APEGA installation.

~446

For GIS. For TRF.

CST 84 CBT 84 RE-APEGA OKT DMT


Corona shield for TRF Contact bolt for TRF Re-assembly kit. Stress cone Kit for optical fibers in Top fitting removal
installation. installation. is included. Top bolt must be screen. kit.
ordered separately.

Common specifications Cable range


Classifications HV GIS/TRF Prepared insulation Ø (mm) 25–66
Net weight, complete termination, kg ~54 Conductor Cu/Al (mm²) 185–2000
Rated frequency, Hz 50/60 Oversheath Ø (mm) 85
Max inclination, degrees No limitations
Dimensions according to IEC 62271–209 (GIS) Packaging Net weight Gross weight Dimensions
Dimensions according to EN 50299 (TRF) kg kg mm
Box 1, termination parts 31 38 600 x 400 x 420
Routine test Box 2, insulator 23 24 800 x 370 x 270
Epoxy insulator according to EN 50089 Dimensions and weights may vary as products occasionally have different packaging.
Filling compound:
- Dielectric strength according to IEC 60156 Optional equipment Designation
- Water content test according to Karl Fischer method Corona shield for TRF installation CST 84
Leakage test on flange Contact bolt CBT 84
Visual and dimensional check is perfomed on the stress relief cone Re-assembly kit RE-APEGA
Visual inspection is performed on all parts of the termination Kit for optofiber in screen OKT
Top fitting removal kit DMT 1
Storage Earthing kit JSA
When stored in original, unopened packaging at temperatures Screen connection kit SCK
in the range of -30°C to 30°C:

− The stress relief cone has a shelf life of ten years from date
of manufacture. For additional information, please contact:
www.abb.com/cableaccessories
− Tapes and grease have a shelf life of five years.
− Metal hardwares have no shelf life limit.
© Copyright 2014 ABB. All rights reserved.
The insulating oil shall be stored in original, unopened pack- Specifications subject to change without notice.

aging at temperatures in the range of 5°C to 45°C. The shelf


life is ten years from date of manufacture.