AL-ANDALOSIA FOR AIR OUTLETS

FIRE DAMPERS
CONSTRUCTION AND SPECIFICATIONS:

FRAME : 20 ga. galvanized steel


BLADE : 22 ga. Galvanized steel blades
With interlocking Joints.
FUSIBLE LINK: U. L. Approved fuse.
Standard 160°F (others
Available)
MIN. SIZE : 4”W x 4” H
MAX. SIZE : 40”W x 48” H
FOR HORIZONTAL TYPE UNITS:
(Specify if Horizontal Mounted)
BLADE LOCK : 16 ga. Galvanized steel blade
lock.
SPRING : Stainless steel closure springs
For Horizontal type units.

- 1-
AL-ANDALOSIA FOR AIR OUTLETS

CONSTRUCTION AND SPECIFICATIONS:

Frame : 18 Ga (1.25mm) galvanized steel frame (all welded).


Blades : 24 Ga (0.7 mm) interlocking type galvanized steel.
Fusible link : U.L Listed standard 165 Fº fusing temperature.
(Other temperatures available on request)
Mounting : Vertical & horizontal mounting positions.
Fire rating : 1 ½ hour rated for use in 1 hour or 2 hour partitions.
Springs : Stainless steel constant force closure springs.
Sealing : Stainless steel side seals.
Finish : All steel parts with galvanized mill finish.
Single section : minimum size 6" D inch
Maximum size 36"D inch.
Free area 100% of Nominal.
Recommended for low – medium – high air velocities.

Note: Dampers for larger than maximum single section sizes shown above are assembled
from equal size single section dampers, W and H dimensions furnished approximately ¼"
under size.

- 2-
AL-ANDALOSIA FOR AIR OUTLETS

Frame : 18 Ga (1.25mm) galvanized steel frame (all welded).


Blades : 24 Ga (0.7 mm) interlocking type galvanized steel.
Fusible link : U.L Listed standard 165 Fº fusing temperature.
(Other temperatures available on request)
Mounting : Vertical & horizontal mounting positions.
Fire rating : 1 ½ hour rated for use in 1 hour or 2 hour partitions.
Springs : Stainless steel constant force closure springs.
Sealing : Stainless steel side seals.
Finish : All steel parts with galvanized mill finish.
Single section : minimum size 6"x6" W x H inch
Maximum size 40"x36" W x H inch.
Free area 100% of Nominal.
Recommended for low – medium – high air velocities.

Note: Dampers for larger than maximum single section sizes shown above are assembled
From equal size single section dampers, W and H dimensions furnished
Approximately ¼" under size.

- 3-
AL-ANDALOSIA FOR AIR OUTLETS

SERIES FIRE DAMPER SIZING CHART


H or D FIRE DAMPER MODELS
Dimension(in) FD-A P(in) FD-B 0(in) FD-C 0(in)
6 1 7-7/16 8-5/8
7 1-1/4 8-5/8 9-3/4
8 1-1/4 9-5/8 10-3/4
9 1-1/2 10-7/8 12-3/64
10 1-1/2 11-7/8 13-1/32
11 1-3/4 13-1/8 14-5/16
12 1-3/4 14-1/8 15-5/16
13 1-3/4 15-1/8 16-9/32
14 2 16-3/8 17-9/16
15 2 17-3/8 18-9/16
16 2 18-3/8 19-9/16
17 2-1/4 19-5/8 20-3/4
18 2-1/4 20-5/8 21-3/4
19 2-1/2 21-7/8 23-1/32
20 2-1/2 22-7/8 24-1/64
21 2-3/4 24-3/32 25-9/32
22 2-3/4 25-3/32 26-1/4
23 2-3/4 26-3/32 27-9/32
24 3 27-3/8 28-9/16
25 3 28-3/8 29-9/16
26 3 29-3/8 30-1/2
27 3-7/32 30-5/8 31-3/4
28 3-7/32 31-5/8 32-3/4
29 3-1/2 32-7/8 34-1/64
30 3-1/2 33-7/8 35
31 3-1/2 34-7/8 36-1/64
32 3-3/4 36-1/16 37-1/4
33 3-3/4 37-5/64 38-1/4
34 4 38-3/8 39-1/2
35 4 39-3/8 40-1/2
36 4 40-5/16 41-1/2
37 4-1/4
38 4-1/4
39 4-1/4
40 4-1/2

- 4-
AL-ANDALOSIA FOR AIR OUTLETS

MULTIPLE ASSEBLIES

Two or more units can be arranged in complete multiple assembly where required.
Blade closed position .

- 5-
AL-ANDALOSIA FOR AIR OUTLETS

FIRE DAMPERS INSTALLATION INSTRUCTIONS

INSPECTION
Before installing, make sure:
The unit

• Has not been damaged in shipping.


• Is the model and size specified.
If there are discrepancies, check with the job superintendent before installing.

The installation site


• Is the correct size.
• Is straight, plumb and clean. The mounting
Surface should be as level as possible.
- 6-
AL-ANDALOSIA FOR AIR OUTLETS
INSTALLATION

Secure to the collar or sleeve with ¼” dia. Bolts and nuts, or back tack welding with beads ½” (+, -)
¼” in

Length, or with #10 sheet metal screws, or with 3/16” steel pop rivets. Fasteners or weld beads
should be 6 to 8 in. on centers.

The collar shall be on the same gauge or heavier than the duct sleeve to which it is attached.

Gauges shall conform to SMACN A or ASHRAE duct standards.

When the following duct collar connections are used, the minimum gauge of the collar shall be
16ga. On Dampers not exceeding 36” wide by 24” high and 14ga. On large dampers.

1. Angle reinforced standing steam.


2. Angle reinforced pocket lock.
3. Companion angles.
4. Metal fasteners spaced a minimum of 16” on center.

Secure angles to collar only so as to frame the wall opening. Angles shall be a minimum of 1 ½” x
1 ½” x 14 ga. Fasten to collar only using the same means as required for fastening the damper to
the collar. Damper Shall have a clearance of 1/8” per foot on height and width, and angles shall
Increase in size proportionately, so that there will be a minimum of 1” of overlap
On the partition. At light see the duct sleeve connections which may be used on all systems.

- 7-