You are on page 1of 3

Test Report for Cooling

Systems of 300MVA
TRANSFORMER Customer: MEW
400/132/11kVFUNAITEES‘Z’
Contract No MEW/C/4372-2011/2012 Project Name
SS
System 300MVA TRANSFORMER Transformer No 300MVA-TRF-1
HHI
Author / Prepared Resp. Dept. Date Lang. Doc.kind Page/No.of pages
Rev.
T&C Dept MEW 12.04.2015 En 0 TR Page 1 of 3

COOLING FANS AND PUMPS MOTOR COIL RESISTANCE AND CURRENT MEASUREMENT:

1.Fan Motor Details:

Make : HYUNDAI
Volts : 415V
Amps : 1.1A
RPM : 960

Fan Motor Test:


Supply Voltage to Fan Motor RY: 416V YB: 416V BR:413V

Direction of
Motor Running Current in Amps Motor Coil Resistance in Ohms
Fan No Rotation Remarks
RØ YØ BØ RØ YØ BØ Forward
FAN-1 0.779 0.763 0.770 49.2 49.2 49.9 OK

FAN-2 0.745 0.751 0.759 49.2 49.0 48.8 OK

OK
FAN-3 0.730 0.731 0.745 48.7 49.4 49.0
OK
FAN-4 0.716 0.714 0.725 48.5 48.7 48.9
OK
FAN-5 0.738 0.739 0.744 48.6 48.7 48.9
OK
FAN-6 0.737 0.732 0.740 48.6 49.2 49.0
FAN-7 OK
0.739 0.733 0.736 48.5 48.7 49.1
FAN-8 OK
0.761 0.763 0.762 49.7 49.2 49.3
FAN-9 OK
0.730 0.723 0.733 49.2 49.6 49.4
FAN-10 OK
0.738 0.730 0.736 49.3 50.0 49.4
FAN-11 OK
0.749 0.743 0.742 49.9 50.0 49.6
FAN12 OK
0.734 0.722 0.726 49.6 49.4 49.5

TESTED BY HHI MEW-WITNESSED MEW-APPROVED


NAME: NAME: NAME:

SIGN: SIGN: SIGN:

DATE: DATE: DATE:


Test Report for Cooling
Systems of 300MVA
TRANSFORMER Customer: MEW
400/132/11kVFUNAITEES‘Z’
Contract No MEW/C/4372-2011/2012 Project Name
SS
System 300MVA TRANSFORMER Transformer No 300MVA-TRF-1
HHI
Author / Prepared Resp. Dept. Date Lang. Doc.kind Page/No.of pages
Rev.
T&C Dept MEW 12.04.2015 En 0 TR Page 2 of 3

Direction of
Motor Running Current in Amps Motor Coil Resistance in Ohms
Fan No Rotation Remarks
RØ YØ BØ RØ YØ BØ Forward
FAN-13 0.741 0.743 0.739 49.0 49.0 49.1 OK

FAN-14 0.759 0.754 0.758 49.6 49.3 49.3 OK

OK
FAN-15 0.712 0.720 0.716 49.5 49.5 49.7
OK
FAN-16 0.731 0.735 0.739 49.4 49.1 49.8
OK
FAN-17 0.766 0.759 0.761 49.8 49.6 49.4
OK
0.760 0.762 0.759 49.7 49.2 49.3
FAN-18
FAN-19 OK
0.726 0.725 0.729 49.2 49.6 49.4
FAN-20 OK
0.751 0.749 0.746 49.3 50.0 49.4
FAN-21 OK
0.758 0.753 0.756 49.9 50.0 49.6
FAN-22 OK
0.761 0.766 0.763 49.6 49.4 49.5
FAN-23 0.761 0.764 0.765 49.0 49.0 49.1 OK

FAN-24 OK
0.756 0.763 0.763 49.6 49.3 49.3
FAN-25 OK
0.758 0.769 0.722 49.5 49.5 49.7
FAN-26 OK
0.748 0.750 0.761 49.4 49.1 49.8
FAN-27 OK
0.766 0.760 0.763 49.8 49.6 49.4
FAN28 0.727 0.726 0.725 49.7 49.2 49.3 OK

FAN-29 OK
0.759 0.755 0.760 49.2 49.6 49.4
FAN-30 OK
0.744 0.749 0.750 49.3 50.0 49.4

TESTED BY HHI MEW-WITNESSED MEW-APPROVED


NAME: NAME: NAME:

SIGN: SIGN: SIGN:

DATE: DATE: DATE:


Test Report for Cooling
Systems of 300MVA
TRANSFORMER Customer: MEW
400/132/11kVFUNAITEES‘Z’
Contract No MEW/C/4372-2011/2012 Project Name
SS
System 300MVA TRANSFORMER Transformer No 300MVA-TRF-1
HHI
Author / Prepared Resp. Dept. Date Lang. Doc.kind Page/No.of pages
Rev.
T&C Dept MEW 12.04.2015 En 0 TR Page 3 of 3

Direction of
Motor Running Current in Amps Motor Coil Resistance in Ohms
Fan No Rotation Remarks
RØ YØ BØ RØ YØ BØ Forward
FAN-31 0.740 0.738 0.742 49.5 49.5 50.1 OK

FAN-32 0.758 0.759 0.762 49.2 49.0 49.5 OK

OK
FAN-33 0.755 0.760 0.762 49.5 49.6 49.9
OK
FAN-34 0.711 0.715 0.720 49.5 49.5 50.2
OK
FAN-35 0.759 0.762 0.765 49.5 49.6 49.9

4.Pump Motor Test

Direction of
Motor Running Current in Amps Motor Coil Resistance in Ohms
Fan No Rotation Remarks
RØ YØ BØ RØ YØ BØ Forward
PUMP-1 2.257 2.239 2.243 27.7 27.6 27.7 OK

PUMP-2 2.301 2.303 2.311 27.6 27.6 27.6 OK

OK
PUMP-3 2.302 2.300 2.320 27.5 27.6 27.5
OK
PUMP-4 2.328 2.306 2.341 27.4 27.5 27.5
OK
PUMP-5 2.301 2.291 2.305 27.5 27.6 27.5

TEST EQUIPMENTS USED:

SI.NO EQUPMENT NAME MAKE SL.NO CAL,DUE DATE

1 DIGITAL MULTIMETER FLUKE 25520407 23.09.2015


2 LEAKAGE TESTER KYORITSU 8182877 18.11.2015

TESTED BY HHI MEW-WITNESSED MEW-APPROVED


NAME: NAME: NAME:

SIGN: SIGN: SIGN:

DATE: DATE: DATE: