Initiating Devices
Conventional
Call Point
Technical Manual
Note
i Do not install, operate, and maintain this product before fully reading this
manual.
1 Introduction
The TPB-10 is available in three models:
• TPB-10R – red fire alarm push button
• TPB-10Y – yellow extinguishing activating push button
• TPB-10B – blue abort / hold
2 Compatibility
The TPB-10 is compatible with the following control panels:
• All TSA-1000 models
• TSA-1000X
• TSA-200; TSA-200XT; and TSA-200X
• All GSA-1000 models
• GSA-2B
The TPB-10 is compatible with Telefire's ADR-3000 Analog Addressable Control Panel
when used with an ADR-812 or ADR-818 Input module.
3 Installation
Planning of quantity and location of call points shall be done according to the local codes
and regulations and in accordance to the planning consultant's requirements.
EN 54 EN 54 Requirement
In some countries local interpretation of EN 54 requires the installation of call
points in a dedicated zone.
3.2 Installation
3.2.1 Control Panel Configuration (TSA-1000 / TSA-1000X Only)
Configure the input zone as type d (detector zone) for a detector and manual alarm call
point zone if local codes and regulations allow for this.
Configure the input zone as type p (push button input) for a dedicated TPB-10R zone.
Configure the input zone as type p (push button input) for a dedicated TPB-10Y input.
Include the TPB-10Y input in the control panel's extinguishing matrix
– Page 1 of 3 –
TPB-10
© 1999 – 2014 Telefire Fire & Gas Detectors Ltd Revision 1.01 October 2014
Configure the input zone as type h or H (extinguishing hold input), for a dedicated
extinguishing hold, as required.
Configure the input zone as type A (extinguishing abort input) for a dedicated abort
input.
Please refer to the TSA-1000 / TSA-1000X technical manual for a detailed description of
programming and configuration.
3.2.2 Location
The TPB-10 is designed to protect indoor fire risk areas, except environments where
smoke, steam, dust, or corrosive gasses are present under normal conditions.
Observe NFPA 72 guidelines and local fire codes when installing the TPB-10.
UL UL Requirement
Smoke call points are not to be used with call point guards unless the
combination has been evaluated and found suitable for that purpose.
3.3 Post-Installation
Test the push button to ensure that it operates properly and verify that it is included in
the appropriate matrices as specified by the planning consultant.
– Page 2 of 3 –
TPB-10
© 1999 – 2014 Telefire Fire & Gas Detectors Ltd Revision 1.01 October 2014
4 Specification
Dimensions (W / H / D) ................................................. 70 / 100 / 100 mm
Weight .......................................................................... 240 gr.
Operating Temperature range....................................... -10°C – +60°C (14°F – 140°F)
Operating Voltage (supplied by control panel)............... 24Vdc
Maximum Current Consumption.................................... 0 µA (quiescence mode)
125 mA (Alarm)
Local Indication Local red LED (light-emitting diode) turns on upon alarm.
All values are nominal. Specifications are subject to change without prior notice
5 Certification
Telefire’s TPB-10 Conventional Call Point complies with the following approvals:
• EN 54 Compliant
• UL 38 Compliant
• GOST 60065 Certified
• IS 1220 Certified