Anchorage design is assessed according to ACI 318 Appendix D which is exclusively based on the

strength approach (LRFD). Please follow the LRFD guidelines to assess the anchorage
Ft
Utt = Rnt
= 655.9 %
min( Ω
,ϕNcb )
where:
Rnt
= 111.2 kN Tension resistance
Ω


Uts = min(Rnv ,Rnb )
= 0.0 %
where:
Rnv
= 0.0 kN Shear resistance
Ω

Rnb = 1.2lc tFu ≤ 2.4dtFu


Rnb = 174.2 kN
where:
400.0
Fu = Specified minimum tensile strength of the connected material
MPa

Clear distance, in the direction of the force, between the edge of the hole and the edge of the
lc = 70 mm
adjacent hole or edge of the material

t= 19 mm Thickness of connected material

d= 19 mm Nominal diameter of the fastener

Ω= 2.00 Safety factor

A
ϕNcb = ϕψ3 24√fc′ h1.5
ef A
N
= 12.0 kN
No

where:
AN = 25613 mm2 Concrete breakout cone area for group

ANo = 52441 mm2 Concrete breakout cone area for single anchor

fc′ = 27.6 MPa Concrete compressive strength

ψ3 = 1.00

hef = 76 mm Depth of embedment

ϕ= 0.70 Resistance factor

A
ϕVcbg = ϕ A v ψ5 ψ6 ψ7 Vb = 0.0 kN
vo

Vb = 7( dl )0.2 √d0 √fc′ c1 1.5 = 0.0 kN


0

where:
Av = 0 mm2 The total breakout shear area for a single anchor

Avo = 0 mm2 The area of the full shear cone

ψ5 = 1.00

ψ6 = 1.00

30/05/2019 17:25:23 p. m. 1/2


ψ7 = 1.00 A modifier to reflect the capacity reduction when side cover limits the size of the breakout cone

c1 = 0 mm The edge distance in the direction of load

fc′ = 27.6 MPa Concrete compressive strength

l= 0 mm The embedment depth

d0 = 0 mm The rod diameter

ϕ= 0.00 Resistance factor

30/05/2019 17:25:23 p. m. 2/2