BUS-1
BUS COUPLER
89A
89B
BUS-
BUS-2
89C
89T
89E
FEEDER-1 FEEDER-2
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Make sure that the Circuit Breaker of the Line which was taken on
Bus Coupler is in OPEN condition.
Hand trip the Bus Coupler Circuit Breaker.
Open the Under Hung Isolator of the Line which was taken on Bus
Coupler.
Open the Bus-2 Isolator of the Line which was taken on Bus
Coupler.
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Close the Isolators before and after the Circuit Breaker of the Line
which was taken on Bus Coupler.
Close the Bus-1 Isolator of the same Line.
Close the Circuit Breaker of the same line to energise the Line.
Open the Bus-2 PT Isolator.
Open Bus-1 and Bus-2 Isolators of Bus Coupler Bay.
Ascertain the selection of proper Bus Zone selection of the bay in
the Bus Bar scheme.
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
BUS-
BUS-1
BUS COUPLER
89A
89B
BUS-
BUS-2
TRANSFE R BUS
COUPLER
89C
89D
BAY3 BAY4 BAY5
BAY1 BAY2 TRANSFER BUS BAY6 BAY7 BAY8
Make sure that the Circuit Breaker of the Bay which was taken on
Transfer Bus Coupler is in OPEN condition.
Hand trip the Transfer Bus Coupler Circuit Breaker.
Open the Isolators 89D and 89A or 89B (which ever was closed) in
the transfer Bus Coupler bay.
Put the Protection Transfer switch in the Panel of the bay which was
taken on Transfer Bus to NORMAL position.
Close the Isolators 89C and 89A or 89B (which ever required) in the
Bay which was taken on Transfer Bus.
Close the Circuit Breaker of the Bay to energise the Bay.
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Put the Protection Transfer switch in the Panel of the bay which is to
be taken on Transfer Bus to INTER position.
Close 89A or 89B (which ever was closed in the bay which is to be
taken on Transfer Bus) and 89D Isolators of Transfer Bus Coupler
Bay.
Close the Transfer Bus Coupler Circuit Breaker and energise Transfer
Bus.
In the Bay to be taken on Bus Coupler, Close the 89D Isolator.
Put the Protection Transfer switch in the Panel of the bay which is to
be taken on Transfer Bus to TRANSFER position.
Hand trip the Bay Circuit Breaker. (In some sub station schemes, the
Bay Circuit Breaker will trip once the Protection Transfer switch is put
to TRANSFER position).
Open the Isolators 89C and 89A or 89B (which ever was closed) in
the Bay which is to be taken on Transfer Bus.
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Put the Protection Transfer switch in the Panel of the bay which was
taken on Transfer Bus to INTER position.
Close the Isolators 89C and 89A or 89B (which ever required) in the
Bay which was taken on Transfer Bus.
Close the Circuit Breaker of the Bay.
Hand trip the Transfer Bus Coupler Circuit Breaker.
Open the Isolators 89D and 89A or 89B (which ever was closed) in
the transfer Bus Coupler bay.
Put the protection Transfer switch in the Panel of the bay which was
taken on Transfer Bus to NORMAL position.