- DENSIDAD DE MUROS :
Datos
Sobrecarga : 0.25 Ton /m2
Sobrecarga Azotea : 0.10 Ton /m2
Aligerado , e = 0.20 m 0.30 Ton /m2
Acabados : 0.10 Ton /m2
Viga Solera : Base 0.15 m
Altura 0.30 m
Peso Especifico del Concreto 2.40 Ton /m3
Peso Especifico del Muro 1.90 Ton /m3
f'm 65.00 kg/cm2 650.00 Ton/m2
Ec 2170000.00 Ton/m2
Em 325000.00 Ton/m2
n 6.68
∑ Lt
= 0.08
Area Total
Z*U*S*N
= 0.03
56
Según fórmula se obtiene: 0.08 ≥ 0.03
250 Kg /m2 Lados X 6.00 m
100.00 Kg /m2 Y 10.80 m
300.00 Kg /m2 Area Total X*Y 64.8 m2
100.00 Kg /m2
15.00 cm Z (Lima, Zona 3) 0.40
30.00 cm U Uso: Vivienda 1.00
2400.00 kg /m3 S Factor de suelo 1.00
1900.00 kg /m3 N N° de pisos 4.00
650000.00 kg/m2
217000.00 kg/cm2
Sobrecarga
P.Espcf. Peso Muro (Ton) Peso Losa (Ton) Peso Acab. (Ton) Peso Solera (Ton)
(Ton/m2)
1.90 3.04 1.93 0.64 0.55 0.25
1.90 1.93 2.00 0.67 0.35 0.25
1.90 2.45 1.51 0.50 0.45 0.25
1.90 1.93 2.13 0.71 0.35 0.25
1.90 3.04 4.75 1.58 0.55 0.25
1.90 1.93 2.13 0.71 0.35 0.25
1.90 2.39 2.83 0.94 0.12 0.25
1.90 3.04 2.62 0.87 0.55 0.25
1.90 1.78 0.70 0.23 0.32 0.1
1.90 2.45 1.51 0.50 0.45 0.25
∑ de Pesos: 23.97 22.11 7.37 4.05
Area en Planta
Conforme!!
Piso Típico Azotea Piso Típico Servicio Azotea Servicio
P.D + P.L P.D + P.L
P.Viva(Ton) P.Viva(Ton) P.D (Ton) P.L (Ton) P.D (Ton) P.L (Ton)
(Ton) (Ton)
1.61 0.64 6.16 1.61 7.77 6.16 0.64 6.81
1.67 0.67 4.95 1.67 6.61 4.95 0.67 5.61
1.26 0.50 4.91 1.26 6.16 4.91 0.50 5.41
1.78 0.71 5.12 1.78 6.90 5.12 0.71 5.83
3.96 1.58 9.93 3.96 13.89 9.93 1.58 11.52
1.78 0.71 5.12 1.78 6.90 5.12 0.71 5.83
2.36 0.94 6.28 2.36 8.64 6.28 0.94 7.22
2.18 0.87 7.09 2.18 9.27 7.09 0.87 7.96
0.23 0.23 3.04 0.23 3.27 3.04 0.23 3.27
1.26 0.50 4.90 1.26 6.16 4.90 0.50 5.40
18.07 57.50 75.57 57.50 7.37 64.87
Límites de Norma E070
Total Muro Esfuerzo de Compresión 0.2*f'm*(1-(h/35e)^2)
Nº Pisos P.D + P.L
Típicos
Azotea
(Ton)
σ (Ton/m2) (Ton/m2)
97.50 conforme
97.50 conforme
97.50 conforme
97.50 conforme
97.50 conforme
97.50 conforme
97.50 conforme
97.50 conforme
97.50 conforme
97.50 conforme