STATIONS EQUIPMENT FOR RECTIFICATION/PUNCHLIST RESPONSIBLE DATE REMARKS


We can send signal up to switchgear,
Taft 750DC Feeder 2 Close Command MRT 14‐Jun‐19
1  Existing Relay has a problem
2 Magallanes Pilot Wire Pilot Wire Alarm IATECH/PLANTELLIGENT 5‐Jun‐19 There is an indication at HMI. But not in SCADA

Ayala 36 kV Switchgears Open and Close Commands  EFI/ASIAPHIL APRIL No control cable laid down from 


3 RTU to switchgear for controls, We have Feedback 

750 DC Feeder 1 Open and Close Command no feedback EFI 7‐Jun‐19 We can energize the relay. But there is no feedback


4 Guadalupe coming from switchgear. EFI to troubleshoot
No Supply of 125vdc from alarm panel to rtu
Fire and CO2 Alarm Alarm Indication EFI 5‐Jun‐19
5 for the 2 signals
6 36kV Switchgears No local indication at HMI 14‐Jun‐19
No Indication at HMI but okay in SCADA
7 12kV Switchgears No local indication at HMI IATECH/PLANTELLIGENT 14‐Jun‐19
8 189N1 problem on ethernet cable ASIAPHIL 14‐Jun‐19 No Ethernet Connection
9 189N2 problem on ethernet cable ASIAPHIL 14‐Jun‐19 No Ethernet Connection
10 Boni AT Aux Transformer Temp High, Temp Low 14‐Jun‐19
IATECH/PLANTELLIGENT HMI Indication Correct, SCADA is inverse
11 LT AC 220 LV PANEL Temp High, Temp Low 14‐Jun‐19
12 SR1 OTEMP Trip, OTEMP Alarm 14‐Jun‐19
IATECH/PLANTELLIGENT HMI Indication Correct, SCADA is inverse
13 SR2 OTEMP Trip, OTEMP Alarm 14‐Jun‐19
14 Power Meters  no Comms IATECH/PLANTELLIGENT 14‐Jun‐19 Power Meter has no comms again
15 750DC 172P1 close cmd no feedback EFI 7‐Jun‐19 No Feedback after we command, 
Ortigas
16 750DC feeder 3 (172F3) open cmd no Feedback EFI 7‐Jun‐19 We energize the relay. EFI to troubleshoot 
17 Araneta‐ Cubao 750DC feeder 4 (172F4) problem on ethernet cable ASIAPHIL 13‐Jun‐19 No Ethernet Connection
No Feedback after we command, 
GMA‐ Kamuning 750DC Feeder 2 (172F2) Close status no feedback EFI 7‐Jun‐19
18 We energize the relay. EFI to troubleshoot 
19 36kV RT1 Close and Open Commands ASIAPHIL 7‐Jun‐19 no cmd cable termination
20 36kV RT2 Close and Open Commands ASIAPHIL 7‐Jun‐19 no cmd cable termination
21 36kV RT3 Close and Open Commands ASIAPHIL 7‐Jun‐19 no cmd cable termination
Depot 

750DC 172P2 Close and Open Commands no feedback EFI 7‐Jun‐19 We can energize the relay. But there is no feedback


22 coming from switchgear. EFI to troubleshoot