You are on page 1of 12

Solar Energy xxx (2016) xxx–xxx

Contents lists available at ScienceDirect

Solar Energy
journal homepage: www.elsevier.com/locate/solener

Operational power performance of south-facing vertical BIPV window


system applied in office building
Hyo Mun Lee a, Jong Ho Yoon a,⇑, Seung Chul Kim a, U. Cheul Shin b
a
Department of Architecture Engineering, Hanbat National University, Daejeon, Republic of Korea
b
Department of Architecture Engineering, Daejeon University, Daejeon, Republic of Korea

a r t i c l e i n f o a b s t r a c t

Article history: The purposes of this study are to analyze the power efficiency of BIPV system under actual operating con-
Received 31 January 2016 dition and to reveal the factors of performance decrease through annual monitoring of the south-facing
Received in revised form 20 July 2016 vertical BIPV window system (the capacity of 10.6 kWp) whose performance was affected by partial
Accepted 30 July 2016
shading.
Available online xxxx
The study first investigated the monthly PR of each inverter to verify what caused the decrease in
power performance by analyzing PR variation. Then, the shading analysis was performed using a simu-
Keywords:
lation to analyze the capture loss of measured power performance and ultimately to find out the effect
Building integrated photovoltaic system
a-Si thin film solar cell
by partial shading components such as small overhang louvers of each floor, obstructions of adjacent
Transparent BIPV window building, and nearby hillock.
Partial shading The one-year measurement of the power performance showed that the annual average reference yield
Performance ratio (PR) was 2.15 h/day and the final yield was 1.52 h/day; moreover, it was analyzed that the annual average
Capture loss capture loss was 0.49 h/day and the system loss was 0.14 h/day. Monthly average reference yield in sum-
mer (between April and August) showed only 1.28 h/day which was 54% lower than the other seasons
with average 2.77 h/day. The annual average of PR was 0.69 (the monthly maximum of 0.77 and mini-
mum of 0.58); the average PR in the summer with low reference yield was 0.64, while the average PR
for other seasons was 0.73. Whereas monthly variation of LS (system loss) did not show big difference
of under 9%, monthly LC (capture loss) highly varied with fluctuation. These primarily arise from the
effect of the partial shading and vertically installed angle of south-facing BIPV modules.
The BIPV system consisted of four arrays and installed on the same south façade. However, the power
performance analysis per array showed that each array had different performances. The arrays located
above the facade had the highest PR, from 0.74, 0.75, 0.66, and 0.62 respectively in order. In addition,
LS and LC analysis of each array showed that there was performance difference mainly by LC, due to
the influence of an adjacent building located in the south.
The analysis using the simulation showed the adjacent building did not cast any shading but affected
on decrease in diffuse solar radiation whose amount was depending on the array location. When it comes
to the lowest array, nearly 7% of annual insolation was blocked by front building. The shading analysis,
furthermore, revealed that the overhang louvers caused a partial shading problem in spite of short extru-
sion of 40 mm depth all through the year, and particularly, showed a big effect during summer because of
high solar altitude. The extruded louvers caused decrease in 4.5% of average insolation loss over the year.
Ó 2016 Elsevier Ltd. All rights reserved.

1. Introduction electrical load matching. In non-residential buildings, since the


electric power consumption accounts for a big part of total energy
New and renewable energy systems in the zero energy building consumption, there still exist a difficulty in reducing energy by
are regarded as the final stage of a technical application to manage energy conservation and energy efficient technologies. Thus, the
residual load, and these play an important role in thermal and new and renewable energy systems are getting more desirable in
the non-residential building, particularly in view of electricity
generation.
⇑ Corresponding author. Building integrated photovoltaics (BIPV) systems, which also
E-mail address: jhyoon@hanbat.ac.kr (J.H. Yoon). serves as building envelope material itself, can be a leading

http://dx.doi.org/10.1016/j.solener.2016.07.056
0038-092X/Ó 2016 Elsevier Ltd. All rights reserved.

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
2 H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx

Nomenclature

PV photovoltaic YA array yield


BIPV building integrated photovoltaic EA;d daily net energy from array
STC Standard Test Condition PO nominal power at STC
PR performance ratio PL load power
POA plane of array Yf final yield
IAM incident angle modifier EL;d daily net energy from load
Yr reference yield gLOAD load efficiency
HA;d daily global irradiation in POA LC capture loss
GI total irradiation, in POA
LS system loss
sr time interval

technology in terms of managing the argument of cost and effi- 2014; Yoon et al., 2011; Masa-Bote et al., 2014; Eke et al., 2015;
ciency issues. Recently, numerous market researches forecasted Drift et al., 2012; Ding et al., 2015). The main purpose of this
the rapid expansion of BIPV and PV market. The world PV market research is to investigate the power efficiency of BIPV system
is expected to grow total global installed solar capacity from under actual operation and to determine the factors of perfor-
229 GW in 2015 to 600 GW in 2020 (Solar Power Energy, 2016). mance decrease. The investigation was carried out by measuring
The Installed capacity of BIPV was 0.3 GW in 2012 and the market annual electricity generation of the BIPV systems, installed in office
expects to expend a compound annual growth rate (CAGR) of building as a south-faced vertical curtain wall and affected by par-
18.70% per year, which will result in the capacity of 1.2 GW in tial shading.
2019 (Transparency Market Research, 2016). Although current
market share of BIPV is only 1.2% in solar energy market, it is 2. Methodology
expected to go up to 9.0% in 2017 (Philip and Kerry-Ann, 2012).
Meanwhile, the size of BIPV market in South Korea is still small BIPV is a concept to economically increase the energy efficiency
at the moment, which is between 3 MW and 5 MW. However, of buildings not only by replacing existing construction material
according to the recent research, the size of BIPV market is but also by generating electricity with PV module. This system is
expected to highly increase in the year 2017, up to 100 MW (SNE usually installed on the external surface of building unlike general
Research, 2012). stand-alone PV system or PV plants that only aims to produce elec-
The regulation for obliging newly constructed public buildings tricity. Therefore, BIPV system has a high possibility of efficiency
to apply certain proportion of new and renewable energy system decline due to the factors such as the shading effect by installation
took effect from 2004, and consequently many BIPV buildings are angle and surrounding obstructions and the temperature increase
being supplied to the public in South Korea. Different from PV of PV module. The efficiency decline is more so for BIPV module
Power plants, most of BIPV modules are applied to a building installed on the vertical wall.
envelope such as roof, wall and windows. Therefore, variables such Accordingly, this research investigated the power generation
as installation angle, shading and solar cell temperature become and performance degradation of BIPV system, which was installed
key factors limiting power efficiency. Over the past 10 years of to replace curtain wall of an office building. Using the measured
its early stage of application, BIPV system required a great deal data, this research analyzed the power generation of the BIPV sys-
of work to establish guidelines for the BIPV design and construc- tem and the performance of each array.
tion (German Solar Energy Society, 2005). To do so, the research selected factors that can cause perfor-
In recent years, many theoretical and experimental studies have mance decline by investing surrounding environmental conditions,
been conducted to determine how to maximize the benefits from and calculated valid insolation that reached the array by simula-
the BIPV systems in terms of PV power generation, payback time tion. Finally, the research analyzed the decline of power generation
and thermos-physical properties for the reduction of cooling load by calculating the PR of BIPV system through estimation of valid
in the buildings (Li et al., 2009; Mercaldo et al., 2009; Sun et al., insolation. The PR, which is defined by the ratio between the refer-
2012; Lu et al., 2010; Zogou et al., 2011; Han et al., 2010; ence yields on STC (Standard Test Condition) and the final yield
Baetens et al., 2012; Tiwari et al., 2011; Sadineni et al., 2012). during actual operation, can be differentiated into subcategory of
In addition, in order to maximize the benefits, not only the effi- system losses and capture losses. Transformation loss in the inver-
cient design, installation and construction of the BIPV system is ter is a major reason of system losses. In addition, other diverse
important, but also the verification to ensure the power generation reasons are: thermal capture loss of the module in the operation
with maximum efficiency in operation is significant. These are temperature, wiring, string diode, low insolation loss, partial shad-
especially necessary for BIPV systems whose power generation ing loss, dust and containments loss, snowing loss, irregular insola-
efficiency is affected by many factors. To sum up, investigation of tion condition, solar cell mismatch, MPPT failures loss, inefficient
actual power yield of BIPV systems in various installations are system configuration and system failures account for capture
needed to maximize benefits. losses. This study referred to the IEC guideline 61724 (IEC, 1988)
The previous experimental study on operational power perfor- to calculate power yield performance using measured power yield
mance focuses on analyzing annual power yield and PR by collect- data (see Fig. 1).
ing the long-term monitoring data of BIPV system installed on
external wall or rooftop (Eke et al., 2013; Lee et al., 2014; Essah  Reference yield (Yr)
et al., 2015; Sanchez et al., 2015; Wittkopf et al., 2012). Further-
P 
more, an experimental study on temperature, shading effect, and
HA;d day GI
solar incidence angle have been carried out, which are the ele- Yr ¼ ¼ sr  ½h=d ð1Þ
ments influencing the performance of BIPV system (Maturi et al., GI;ref GI;ref

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx 3

Fig. 1. Schematic illustration of power loss factors in BIPV system.

 Array yield (YA) of south facade BIPV system is 10.56 kWp and each array has
P 
2.64 kWp of capacity with 55.85 m2 of PV module area (see
EA;d day P L
YA ¼ ¼ sr  ½h=d ð2Þ Table 1). The specification of each BIPV module and inverter are
PO PO shown in Tables 2 and 3 respectively. Fig. 4 shows the array and
 Final yield (Yf) inverter configuration of whole BIPV system.
P 
Meanwhile, the influential elements that can give a partial
EL;d day P L
Yf ¼ ¼ ¼ Y A  gLOAD ½h=d ð3Þ shading effect around the south facade BIPV system were: an adja-
PO PO cent building with a nearly similar building height located about
 Capture loss (LC) 8 m away from the south facade of the building; the low hillock
LC ¼ Y r  Y A ½h=d ð4Þ located in the east side; and 40 mm extruded louvers above each
BIPV module. Fig. 5 represents the adjacent building and the
 System loss (LS) louvers.
LS ¼ Y A  Y f ½h=d ð5Þ
 Performance ratio (PR) 4. Measured power generation of BIPV system
Yf
PR ¼ ½ ð6Þ Fig. 6 compares monthly vertical irradiation from Korea Meteo-
Yr
rological Administration (KMA) in Daegu and from the BIPV site.
Since local KMA measures only global horizontal irradiance, the
3. Overview of BIPV window system vertical irradiation was calculated using Trnsys. The results
showed that the local irradiation form KAM was higher than the
The building for the investigation was a five-story office build- measurement from BIPV site and difference rate was between
ing in Daegu, South Korea, that was built in September 2011. The 8.95% and 34.91%. The difference was the biggest in winter,
BIPV system applied to the south and east facade of building as ver- between November and February, which was average difference
tical curtain wall, and this research focused only on the BIPV sys- rate of 22.53%. The discrepancy of measured irradiation between
tem applied on the south facade. Fig. 2 is an exterior view seen KMA and BIPV site was mainly due to different measurement loca-
from the southeast side of building, while Fig. 3 is the view of tion and the effect of surrounding environments such as the adja-
installed BIPV system seen inside. As shown in Fig. 2, when the cent building and hillock.
facade of each floor was divided into 4 sections (Fancoil area In order to investigate the operational power performance of
+ Vision area + Daylighting area + Spandrel area), typical tinted BIPV system, this study utilized measured data for a year (from
(blue color) double glazing window systems only applied to the Sep 2012 to Aug 2013). Fig. 7 illustrates daily average power gen-
vision area and transparent BIPV window systems applied to the eration and conversion efficiency of a power conditioning system
other three remaining areas. The type of transparent BIPV module (PCS). The AC power generation in March and October was
was a-Si thin film solar cell that has 10% transmittance of visual 24.91 kW h/day and 26.64 kW h/day respectively with high insola-
light. The installed BIPV window was a double glazing window tion on the vertically installed BIPV system. In contrast, since inso-
consisting of 10 mm a-Si BIPV module glass + 12 mm Air gap lation was low on the BIPV system in Jun and July, the AC power
+ 6 mm clear glass. generation was 7.29 kW h/day and 6.97 kW h/day respectively;
Total 240 BIPV modules applied to south facade with four arrays the daily average AC power generation for the year was
and inverters. The size of unit BIPV module is 0.95 m  0.98 m. 16.08 kW h/day. Conversion efficiency of PCS was between
Each array consists of five serial and twelve parallels. Total capacity 87.08% (in July) and 93.07% (in January), and annual average of

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
4 H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx

Fig. 2. External view of the BIPV system in the office building.

Fig. 3. Internal view of the BIPV window system.

Table 1 Table 2
Description of BIPV window system. Specification of a-Si BIPV module.

Location [latitude/longitude] Daegu [35.1/128.37] Electrical data (STC)


Tilt angle Vertical (90°) Maximum power (Pmax) 44 W
PV orientation Due south Open circuit voltage 91.8 V
PV module type a-Si thin film (10% Transmittance) Short circuit current 0.97 A
Install capacity (south) 10.6 kWp Voltage at Pmax (Vmpp) 59.6 V
Current at Pmax (Impp) 0.74 A
Module efficiency 6.3%
Temperature coefficients
PCS was 90.96%. The results show that both conversion efficiency Power 0.35%/°C
of PCS and power generation were high in winter. Open circuit voltage 0.39%/°C
Fig. 8 shows the results of the monthly final yield, capture loss Short circuit current 0.056%/°C

(LC), and system loss (LS) of BIPV System, and Fig. 9 shows monthly
PRs that were calculated at a ratio of final yield to reference yield.
The results showed that the annual average reference yield was (between April and August) was only 1.28 h/day, which was 54%
2.15 h/day and the final yield was 1.52 h/day; meanwhile, the lower than other season with average 2.77 h/day.
annual average capture loss was 0.49 h/day and the system loss Next, the annual average of PR was 0.69 (the maximum of 0.77
was 0.14 h/day. Monthly average reference yield in summer and the minimum of 0.58). The average PR in summer (between

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx 5

Table 3 average was 0.80 for the system that was installed during the past
Specification of inverter. few years and had improved performance (Norman et al., 2014).
Input data When it comes to PR in previous researches, the majority of
Maximum PV power 3300 Wp the results were from the cases such as power plant, PV installa-
Operating PV voltage range 190 Voc  600 Voc tion with optimized angle, and a few examples of BIPV applied on
MPPT voltage range 170 Voc  500 Voc
Max PV current 16 A
rooftop, etc. Especially, there are very few examples of detailed
PR analysis of BIPV system installed on the outer wall or rooftop
Output data
Maximum continuous power 3000 W
as a building window system. According to the IEA research
Maximum efficiency 94.5% describing the power performance of 14 examples applied on
Euro efficiency 93.0% facade and 12 examples applied on slope roof, the PR range of
Operating line frequency 59.3 Hz facade was between 0.61 and 0.84 (the average 0.72) and the
Nominal line voltage 220 V, 1Phase
PR range of slope roof was between 0.67 and 0.86 (the average
Line current (max)/line >0.99
0.74).
Fig. 10 is the diagram of monthly PR change for each array. PR
analysis result of each array showed that array-3 and array-4 con-
April and August) with low reference yield was 0.64 and the aver- nected to the array at the upper part of building facade had similar
age PR for the other seasons was 0.73. The annual average of LC annual monthly PR variation. Annual average PR of array-3 and
was 0.23 (the maximum of 0.34 and the minimum of 0.17), and array-4 outstandingly remained 0.74, although the PR value
the annual average of LS was 0.06 (the maximum of 0.09 and the dropped below 0.7 from May to July when incidence angle is high.
minimum of 0.05). Whereas monthly variation of LS did not show This value is not that different from the average PR value of instal-
big difference under 9% in Fig. 7, monthly LC highly varied with lation examples of general PV system and shows normal power
fluctuation. It may arise primarily from the effect of partial shading performance level.
and incidence angle of vertically installed south-facing BIPV Whereas array-1 and array-2 connected to the array at the
modules. lower part of building facade, affected by the shading effect of
Meanwhile, according to the previous researches (Ayompe south adjacent obstruction building and eastern hillock just beside
et al., 2011; Chokmaviroj et al., 2006; Congedo et al., 2013; the building, showed dramatic operational degradation compared
Ghiani et al., 2013; Khatib et al., 2013; Kymakis et al., 2009; to array-3 and array-4. Annual average PR of the array-1 which
Micheli et al., 2014; Mondol et al., 2006; Okello et al., 2015; locates the lowest was 0.62, showing 16%lower operational degra-
Padmavathi et al., 2013; Sharma et al., 2013; Sidrach et al., 1998; dation than that of the upper one (array-4). Even though the PR
Ueda et al., 2009), the PR range of general PV system from 2001 itself fluctuated especially during the summer season, the differ-
to 2014 was between 0.67 and 0.87 (the average 0.77) depending ence gap of monthly average PRs between array-1 and array- 4
on the installation type and condition, type of solar cell, and showed almost same
installed year and so on. According to a latest research from IEA Fig. 11 illustrates the monthly variations of each array’s LC (cap-
(IEA, 2016), the PR range was between 0.60 and 0.95 and the ture loss) and LS (system loss). Speaking of PR performance by its

Fig. 4. Array and inverter configuration of the BIPV window system.

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
6 H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx

Fig. 5. View of partial shading components around the BIPV system.

Fig. 6. Irradiation analysis of KMA Data and Monitoring Data.

Fig. 7. Monthly power generation and PCS efficiency.

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx 7

Fig. 8. Monthly power yields and losses of the BIPV window system.

Fig. 9. Monthly PR variation of the BIPV window system.

Fig. 10. Monthly PR variation of 4 each array.

LS and LC, system loss with the inverter remained steadily below the capture loss tends to show the greatest loss in the summer
0.1, and the four inverters showed only minor difference. However, around in July, and the loss also increased in winter. To sum up,
capture loss almost followed the same variation of the previous PR this study estimated that the loss was due to the shading by lou-
value, which concludes that the difference in performance effi- vers with high incidence angle in summer and the shade of adja-
ciency mostly results from the capture loss. Seasonal variation of cent obstruction buildings in winter.

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
8 H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx

Fig. 11. Monthly LC and LS variation of 4 each array.

5. Analysis of partial shading effect each array was split into fine grid having 0.45 m distance, and
the insolation decrease by shading effect was assessed through
To disaggregate the complex effect of shading components such the calculation of annual cumulative direct and diffuse solar radi-
as small overhang louvers of each floor and obstructions of adja- ation that reach each subdivision.
cent building or hillock beside the building in BIPV site, shading The influence of the obstruction with and without the adjacent
analysis result using Autodesk Ecotect Analysis (Autodesk, 2016) building is shown in Fig. 13. Reduction ratio of irradiation varied
and Solmetric SunEye 210 (Solmetric Corporation, 2016) measur- over the year and the ratio was dependent on installed height of
ing Equipment is used to estimate the geometric effect of the cap- the arrays. Array-1 and Array-4 showed decrease in irradiation of
ture loss in measured power performance. 3% and 0.34% respectively for the year, which indicated Array-1
lost approximately 10 times higher irradiation than Array-4. Based
5.1. Front adjacent building on Array-1, irradiation loss by the adjacent building was between
1.56% (in July) and 5.5% (in January).
In order to find out the influence of shading effect by the 40 mm The variation of irradiation affected by the adjacent building
extruded louvers and adjacent building, this research compared was divided into direct and diffuse components. There is no shad-
and analyzed the insolation reaching each array surface using Eco- ing effect of direct solar radiation by adjacent building during the
tectÒ. To do so, both the array-1 located in the lowest side of the whole year, but the shading effect of diffuse solar radiation by
facade and the array-4 located in the uppermost side of the facade adjacent building differs from the location of BIPV arrays. Array-1
were evaluated as shown in Fig. 12. The BIPV module surface of (the lowest side of BIPV) shows 6.89% loss of annual surface

Fig. 12. Model view of Ecotect for shading analysis of adjacent building.

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx 9

Fig. 13. Partial shading effect of Total irradiation by the adjacent building.

insolation by front building, whereas array-4(the uppermost side) 5.2. Extruded louvers
shows just 0.81% loss. The monthly decrease rate of diffuse solar
radiation by the adjacent building was uniform all year round. Fig. 15 shows monthly cumulative solar radiation on the south
Fig. 14 shows the calculated diffuse solar radiation that reaches facade surface in cases with and without of 40 mm extruded lou-
the south facade surface in cases with and without the southern vers. Annual average insolation of 3.54 kW h/m2.month is blocked
adjacent building. Array-1, located in the lowest side, showed the by the 40 mm extruded louvers during every month. The insolation
highest diffuse radiation decrease of 6.89% and Array-4, located of 4.8 kW h/m2.month and 4.3 kW h/m2.month are blocked in May
in the highest side, showed the lowest decrease of 0.81%. Array-2 and June respectively that has high solar altitude. Finally, 4.1% of
and Array-3 showed diffuse radiation decrease of 4.73% and total insolation is blocked by the 40 mm extruded louvers over
2.62% respectively. To sum up, amount of diffuse radiation influ- the year.
enced by the adjacent building decrease when PV array is placed Fig. 16 illustrated influences of the partial shading by 40 mm
lower side. This decrease in diffuse radiation of each array was louvers to direct and diffuse solar radiation. While 3.2% of diffuse
due to different sky component of each array by the adjacent build- radiation is blocked evenly every month over the year, direct solar
ing. In addition, it turned out that the different PR of each array in radiation shows decreases due to the louvers by 20.1% in June,
Section 4 resulted from the building. 13.3% in May, and 16.7% in July respectively that have high solar

Fig. 14. Partial shading effect of diffuse irradiation by the adjacent building.

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
10 H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx

Fig. 15. Partial shading effect by extruded louvers.

Fig. 16. Partial shading effect of direct and diffuse irradiation by the 40 mm extruded louvers.

altitude angle. As shown in the previous analysis result, the louver have low solar altitude, and did not change between April and
or overhang located next above the BIPV module has a consider- September.
able influence on the power generation despite its short extruded According to the analysis with sun-path diagram, hillock
length, as solar altitude is high during summer especially on a blocked some irradiation before 8 AM between October and March.
lower latitude location. Thus, the study investigated proportion of cumulative irradiation
before 8 AM to total cumulative irradiation in each month based
on the measured insolation; the analysis result is shown in Table 5.
5.3. Adjacent hillock
The average rate of irradiation loss before 8 AM between October
and March was 0.19% in comparison to annual average, demon-
The influence of hillock adjacent to the eastern side was ana-
strating that the adjacent hillock affected the total irradiation but
lyzed using instrument as it was difficult to carry out accurate
did not influence on overall power generation.
modeling through the simulation program. Measurement was
done in the central point of the entire module connected to
array-1. The equipment used can measure the time that cast sha- 5.4. IAM (Incidence Angle Modifier)
dow from any object by projecting the surrounding to the sunpath
diagram through a fisheye lens. The shading effect by hillock The incidence angle is a measure of deviation from the direct
located at the eastern side of the building was evaluated through solar radiation to the PV panel surface. The incidence angle is
the geometric shading analysis using sun-path diagram. The directly involved in the determination of the radiation incident
monthly calculated solar access was shown in Table 4. Solar access on the surface of the PV device. Therefore, the incidence angle
decreased by maximum of 4% between October and March that affects the amount of solar radiation transmitted through the

Table 4
Calculated monthly solar access of adjacent hillock.

% 1 2 3 4 5 6 7 8 9 10 11 12 Avr
Solar access 96 97 99 100 100 100 100 100 100 98 96 96 98

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx 11

Table 5
Monthly blocked irradiation percentage of adjacent hillock.

1 2 3 4 5 6 7 8 9 10 11 12
2
Measured Irradiation (kW h/m ) 1889.5 2717.3 4002.3 1652.7 1430.6 926.6 1221.1 1126.1 2671.0 4206.7 2438.0 2606.8
Blocked irradiation (kW h/m2) 0.00 0.55 29.13 0.00. 0.00 0.00 0.00 0.00 0.00 54.39 5.80 0.00
Irradiation reduction percentage (%) 0.00 0.02 0.73 0.00. 0.00 0.00 0.00 0.00 0.00 1.29 0.24 0.00

protective cover and converted to electricity by the cell. In general, The decline of BIPV system performance was investigated con-
the higher incidence angle, the more amount of reflected radiation sidering the surrounding environmental elements: 40 mm
from the cover. Significant effects of inclination occur at incidence extruded louver, southern adjacent building, and eastern adjacent
angles greater than 65 degree (De Soto et al., 2006). Accordingly, hillock. It was calculated that an annual average of 4.1% of irradia-
the monthly irradiation loss was calculated considering the trans- tion was blocked by the 40 mm louvers. The monthly diffuse solar
mittance by incidence angle. radiation loss was about 3.2% over the year, but the direct solar
The study first calculated variations of the transmittance to radiation showed increase by 20.1% in summer with high solar alti-
direct solar radiation, and then applied the IAM (De Soto et al., tude. In addition, each array showed variation in irradiation loss by
2006). To do so, the measured global solar radiation was separated the adjacent building in the south.
into direct and diffuse solar radiation. In order to calculate loss Reduction ratio of irradiation varied over the year and the ratio
rate, the hourly solar radiation loss and its rate for a year was dependent on installed height of the arrays. Array-1 and
(8760 h) were calculated and finally the monthly rate of solar radi- Array-4 showed decrease in irradiation of 3% and 0.34% respec-
ation loss was calculated, which is illustrated in Fig. 17. tively for the year, which indicated Array-1 lost approximately
The annual average irradiation decreased by 5.68% due to 10 times higher irradiation than Array-4. The influence of the adja-
change of incidence angle, and the highest monthly irradiation loss cent building was investigated on direct and diffuse radiation com-
was about 8.17% in May. It was assumed that the highest irradia- ponents. While direct radiation loss was not observed, diffuse
tion loss occur in June due to the highest solar altitude resulting radiation decreased by the adjacent building. Reduction ratio of
in high IAM, but in fact this occurs in May. Since June and July diffuse radiation was constant over the year, but was different
are a rainy season in Korea, the proportion of direct solar radiation depending on installed height: 6.86% in Array-1, 4.73% in Array-
was lower than the other months. 2, 2.62% in Array-3, and 0.81% in Array-4. This decrease in diffuse
radiation of each array was due to different sky component of each
array by the adjacent building. In addition, it turned out that the
6. Conclusion different PR of each array resulted from the building. The investiga-
tion of shading by hillock showed trivial influence between Oct.
This research performed an analysis on the performance of BIPV and Mar. and thus hillock affected little or no influence on the BIPV
System equipped with real-time measurement system, and ana- performance.
lyzed the influence of factors on performance decline. The mea- The irradiation decrease by the incidence angle showed an
sured power generation performance of BIPV system showed annual average loss of 5.68% and the maximum monthly loss
annual average PR of 0.69, capture loss of 0.23, and system loss occurred not in June that has high solar altitude but in May with
of 0.66. When it comes to the performance of each array, the PR the monthly loss of 8.17%; this is because proportion of the direct
of array-3 and array-4 installed on the upper part of south facade solar radiation decreases in June due to rainy season.
surface was 0.75 and 0.74 respectively, and array-1 and array-2 In general, most BIPV window systems are vertically installed
located in the lower part was 0.62 and 0.66 respectively. This indi- and thus there is a high possibility of shading effect due to the
cated that arrays performance varies depending on the installed adjacent buildings, vegetation, and structures in the downtown
height in spite of the same direction. area. As demonstrated by this research, louver with a short

Fig. 17. Variation of monthly measured irradiation and IAM corrected irradiation.

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056
12 H.M. Lee et al. / Solar Energy xxx (2016) xxx–xxx

extrusion length of 40 mm affects a power performance decline. Lee, J.B., Park, J.W., Yoon, J.H., Baek, N.C., Kim, D.K., Shin, U.C., 2014. An empirical
study of performance characteristics of BIPV (Building Integrated Photovoltaic)
Therefore, it is important to correctly identify and respond to the
system for the realization of zero energy building. Energy 66, 25–34.
external environmental conditions to minimize irradiation loss Li, D.H.W., Lam, T.N.T., Chan, W.W.H., Mak, A.H.L., 2009. Energy and cost analysis of
and secure the performance of BIPV system in the design stage. semi-transparent photovoltaic in office buildings. Appl. Energy 86, 722–729.
In addition, it is important to prevent the shading effect on array Lu, L., Yang, H.X., 2010. Environmental payback time analysis of a roof-mounted
building-integrated photovoltaic (BIPV) system in Hong Kong. Appl. Energy 87,
even by a small design element, and it is necessary to make an 3625–3631.
effort to increase the irradiation by improving the building facade Masa-Bote, D., Caamaño-Martín, E., 2014. Methodology for estimating building
design in regions where high incidence angle change occur over integrated photovoltaics electricity production under shadowing conditions
and case study. Renew. Sustain. Energy Rev. 31, 492–500.
the year like South Korea. Finally, when using excellent perfor- Maturi, L., Belluardo, G., Moser, D., Del Buono, M., 2014. BiPV system performance
mance PV module with diffuse solar radiation, the performance and efficiency drops: overview on PV module temperature conditions of
loss by adjacent building must be considered in the design stage. different module types. Energy Procedia, Proceedings of the 2nd International
Conference on Solar Heating and Cooling for Buildings and Industry (SHC 2013)
48, 1311–1319.
Acknowledgements Mercaldo, L.V., Addonizio, M.L., Noce, M.D., Veneri, P.D., Scognamiglio, A., Privato, C.,
2009. Thin film silicon photovoltaics: architectural perspectives and
technological issues. Appl. Energy 86, 1836–1844.
This work was supported by the Korea Institute of Energy Tech- Micheli, D., Alessandrini, S., Radu, R., Casula, I., 2014. Analysis of the outdoor
nology Evaluation and Planning (KETEP) and the Ministry of Trade, performance and efficiency of two grid connected photovoltaic systems in
Industry & Energy (MOTIE) of the Republic of Korea (No. northern Italy. Energy Convers. Manage. 80, 436–445.
Mondol, J.D., Yohanis, Y., Smyth, M., Norton, B., 2006. Long term performance
2015301013032).
analysis of a grid connected photovoltaic system in Northern Ireland. Energy
Convers. Manage. 47, 2925–2947.
References Nordmann, T., Clavadetscher, L., van Sark, W., Green, M., others, 2014. Analysis of
Long-Term Performance of PV Systems. IEA Task 13 Report.
AUTODESK, 2016. Autodesk Ecotect Analysis. URL <http://usa.autodesk.com/ Okello, D., van Dyk, E.E., Vorster, F.J., 2015. Analysis of measured and simulated
ecotect-analysis/> (accessed 1.13.16). performance data of a 3.2 kWp grid-connected PV system in Port Elizabeth,
Ayompe, L.M., Duffy, A., McCormack, S.J., Conlon, M., 2011. Measured performance South Africa. Energy Convers. Manage. 100, 10–15.
of a 1.72 kW rooftop grid connected photovoltaic system in Ireland. Energy Padmavathi, K., Daniel, S.A., 2013. Performance analysis of a 3 MWp grid connected
Convers. Manage. 52, 816–825. solar photovoltaic power plant in India. Energy Sustain. Develop. 17, 615–625.
Baetens, R., De Coninck, R., Van Roy, J., Verbruggen, B., Driesen, J., Helsen, L., Saelens, Philip, Drachman, Kerry-Ann, Adamson, 2012. Building-Integrated Photovoltaics 
D., 2012. Assessing electrical bottlenecks at feeder level for residential net zero- BIPV and BAPV : Market Drivers and Challenges, Technology Issues, Competitive
energy buildings by integrated system simulation. Appl. Energy, Smart Grids 96, Landscape, and Global Market Forecasts, PikeResearch research report.
74–83. Sadineni, S.B., Atallah, F., Boehm, R.F., 2012. Impact of roof integrated PV orientation
Chokmaviroj, S., Wattanapong, R., Suchart, Y., 2006. Performance of a 500 kWP grid on the residential electricity peak demand. Appl. Energy 92, 204–210.
connected photovoltaic system at Mae Hong Son Province, Thailand. Renew. Sánchez, E., Izard, J., 2015. Performance of photovoltaics in non-optimal
Energy 31, 19–28. orientations: an experimental study. Energy Build. 87, 211–219.
Congedo, P.M., Malvoni, M., Mele, M., De Giorgi, M.G., 2013. Performance Sharma, V., Chandel, S.S., 2013. Performance analysis of a 190 kWp grid interactive
measurements of monocrystalline silicon PV modules in South-eastern Italy. solar photovoltaic power plant in India. Energy 55, 476–485.
Energy Convers. Manage. 68, 1–10. Sidrach-de-Cardona, M., López, L.M., 1998. Evaluation of a grid-connected
De Soto, W., Klein, S.A., Beckman, W.A., 2006. Improvement and validation of a photovoltaic system in southern Spain. Renew. Energy, Renew. Energy Energy
model for photovoltaic array performance. Sol. Energy 80, 78–88. Efficiency, Policy Environ. 15, 527–530.
Ding, Y., Young, M., Zhao, Y., Traverse, C., Benard, A., Lunt, R.R., 2015. Influence of SNE Research, 2012. BIPV Technology and Market Forecast (2009–2015) – 2nd
photovoltaic angle-dependence on overall power output for fixed building Version, SNE Research Report.
integrated configurations. Sol. Energy Mater. Sol. Cells 132, 523–527. Solmetric Corporation, 2016. Solmetric Suneye 210 Series Users Guide [WWW
Drif, M., Mellit, A., Aguilera, J., Pérez, P.J., 2012. A comprehensive method for Document]. URL <http://resources.solmetric.com/get/Solmetric%20SunEye%
estimating energy losses due to shading of GC-BIPV systems using monitoring 20200%20Series%20Users%20Guide_en.pdf> (accessed 1.13.16).
data. Sol. Energy 86, 2397–2404. Solar Power Energy, 2016. Global Market Outlook For Solar Power 2016–2020, Solar
Eke, R., Demircan, C., 2015. Shading effect on the energy rating of two identical PV Power Report.
systems on a building façade. Sol. Energy 122, 48–57. Sun, L., Lu, L., Yang, H., 2012. Optimum design of shading-type building-integrated
Eke, R., Senturk, A., 2013. Monitoring the performance of single and triple junction photovoltaic claddings with different surface azimuth angles. Applied Energy,
amorphous silicon modules in two building integrated photovoltaic (BIPV) Energy Solutions for a Sustainable World, Special Issue of International
installations. Appl. Energy 109, 154–162. Conference of Applied Energy, ICA2010, April 21–23, 2010, Singapore 90, pp.
Essah, E.A., Rodriguez Arguelles, A., Glover, N., 2015. Assessing the performance of a 233–240.
building integrated BP c-Si PV system. Renewable Energy, Sustainable Transparency Market Research, 2016. Building Integrated Photovoltaic Market:
Development in Building and Environment (SuDBE) 2013 73, 36–45. Shifting Preference of Consumers towards Energy Generation from Renewable
German Solar Energy Society, 2005. Planning and Installing Photovoltaic Systems: A Resources to Drive Market, Transparency Market Research Report.
Guide for Installers, Architects, and Engineers. Earthscan Publications Ltd. Tiwari, G.N., Mishra, R.K., Solanki, S.C., 2011. Photovoltaic modules and their
Ghiani, E., Pilo, F., Cossu, S., 2013. Evaluation of photovoltaic installations applications: a review on thermal modelling. Appl. Energy 88, 2287–2304.
performances in Sardinia. Energy Convers. Manage. 76, 1134–1142. Ueda, Y., Kurokawa, K., Kitamura, K., Yokota, M., Akanuma, K., Sugihara, H., 2009.
Han, J., Lu, L., Yang, H., 2010. Numerical evaluation of the mixed convective heat Performance analysis of various system configurations on grid-connected
transfer in a double-pane window integrated with see-through a-Si PV cells residential PV systems. Solar Energy Materials and Solar Cells. In: 17th
with low-e coatings. Appl. Energy 87, 3431–3437. International Photovoltaic Science and Engineering Conference 93, pp. 945–
IEA, 2016. IEA PVPS Task 13 Performance Database. URL <77.245.18.90> (accessed 949.
1.15.16). Wittkopf, S., Valliappan, S., Liu, L., Ang, K.S., Cheng, S.C.J., 2012. Analytical
IEC61724:1998, 1988. Photovoltaic System Performance Monitoring Guidelines for performance monitoring of a 142.5 kWp grid-connected rooftop BIPV system
Measurement, Data Exchange, and Analysis. in Singapore. Renew. Energy 47, 9–20.
Khatib, T., Sopian, K., Kazem, H.A., 2013. Actual performance and characteristic of a Yoon, J.-H., Song, J., Lee, S.-J., 2011. Practical application of building integrated
grid connected photovoltaic power system in the tropics: a short term photovoltaic (BIPV) system using transparent amorphous silicon thin-film PV
evaluation. Energy Convers. Manage. 71, 115–119. module. Sol. Energy 85, 723–733.
Kymakis, E., Kalykakis, S., Papazoglou, T.M., 2009. Performance analysis of a grid Zogou, O., Stapountzis, H., 2011. Energy analysis of an improved concept of
connected photovoltaic park on the island of Crete. Energy Convers. Manage. 50, integrated PV panels in an office building in central Greece. Appl. Energy 88,
433–438. 853–866.

Please cite this article in press as: Lee, H.M., et al. Operational power performance of south-facing vertical BIPV window system applied in office building.
Sol. Energy (2016), http://dx.doi.org/10.1016/j.solener.2016.07.056

You might also like