You are on page 1of 8

Medium voltage motors

Generators Bus duct


InsulGard Switchgear Cable terminations

Maximize
your uptime
Why InsulGard?
Economics and safety
Insulation failures cost time
and money. What’s even
more damaging is that
insulation failures lead to
arc flash events, equipment
failure, unscheduled outages
or, worst of all, accidents
involving personnel.

2 EATON InsulGard
Mitigate your risk
Eaton’s InsulGard system predicts insulation failures before they occur.

How does it work? Eliminate periodic scheduling


of downtime to perform
By measuring partial discharge
tests and time-based
activity in medium voltage
maintenance that lead to
equipment, InsulGard provides
customer inconvenience
intelligence about the wellness
of electrical insulation, enabling The InsulGard predictive
better decision-making for relay revolutionized predictive
managing electrical assets maintenance practices by
and increasing safety for introducing one continuous,
plant personnel. online partial discharge
(PD) monitoring system
designed for the following
What is the payback? medium voltage applications:
The average cost of motors, • Generators
generators and switchgear
can range from $100k to many
• Motors
millions, and if a station is • Switchgear
shut down, that loss can be
catastrophic. In addition, buying • Unit substation dry-type
equipment is only part of the transformers
expense of replacing it. • Bus duct
• Cable connections
Protect your investment Continuous eliminates the
In many circumstances, chances of failures occurring
InsulGard back InsulGard can double the between periodic test events.
equipment’s life span. Online eliminates the
inaccuracies of offline tests.
InsulGard can maximize InsulGard also reduces the
your uptime level of expertise required to
analyze PD data with user-
InsulGard is a more economical
friendly software.
alternative for maintaining
electrical power equipment.

Proven history
Thousands of InsulGards are
protecting assets all over the
world.

InsulGard front

EATON InsulGard 3
Resistive Temperature Device Coupling capacitors available Radio Frequency Current
(RTD) sensor for monitoring from 5 to 38 kV Transformer (RFCT) for partial
existing RTDs in stator windings discharge detection

InsulGard technology works for you


24 hours a day, 7 days a week, 365 days Cable or Bus

a year—reliable support you can count on Motor


or
Generator
The InsulGard system detects The predictive relay works as
partial discharge activity online, a single, local device or in a R R R R R R
with the entire electrical system communication network with T T T T T T
D D D D D D

energized—no offline testing multiple devices.


Line Jumper Cable or Cable Shield
necessary. It analyzes radio Directly Bolted to Bus
The most commonly used (If Applicable)
frequency (RF) signals emitted
sensors include coupling
by the partial discharge pulses RFCT
capacitors and radio frequency
and measures pulse quantity
current transformers (RFCTs). Coupling

RG58 Coax
and magnitude, then correlates Capacitors
For rotating machinery, such RG58 Coax
the data to temperature,
as generators and motors, RFCT input
humidity and various other CC1 input
additional sensing technologies Protective CC2 input
electrical system dynamics. If Relay CC3 input
are available. RTD1 input
PD levels exceed programmable RG58
Coax
RTD2 input
RTD3 input
set points, alerts are initiated. For sites with pre-existing RTD4 input
RTD5 input
With or without alerts, you can sensors, the InsulGard predictive InsulGard RTD6 input
RTD Module
quickly view or analyze trends relay is fully compatible and (Optional)
Max. 15 Channels

using InsulGard software. can be instantaneously


commissioned.
Typical rotating machine application

Features and benefits


• Advanced filters and three
noise algorithms provide
clarity in the PD signal,
which leads to quicker
and easier diagnostics
• InsulGard can operate in
a lower RF bandwidth of
1–20 MHz. This bandwidth
provides a broader sensing
range for identification of
more partial discharge
activity that higher band-
widths can miss completely

4 EATON InsulGard
Corona damage on the Damage to bus caused by 34.5 kV potential transformer–
motor windings air gaps within bus support tracking

InsulGard is the ideal advanced-warning solution


Where can the InsulGard system be used?

Generators and motors Switchgear and unit substation


dry-type transformers
Available sensors for rotating Used alone or in combination, Problems that partial discharge
machinery include coupling the PD sensors, along with analysis can detect within Available sensors for
capacitors and RFCTs. The sensors for humidity, load and rotating equipment include: switchgear include coupling
traditional sensor of choice is temperature, connect to the capacitors and RFCTs.
• Early stages of insulation
the coupling capacitor; with InsulGard predictive relay for
deterioration Coupling capacitors detect
this sensor alone, InsulGard monitoring, data collection and
partial discharges within cubicles
technology provides much analysis. • Sparks in voids and
and typically connect to the
broader coverage of the stator between windings
InsulGard is also compatible load side of the feeder breakers
winding when compared with
with variable frequency drives • Corona on end windings or on the main bus.
the competition. An optional
and can be used on motors
RTD module takes advantage of RFCTs identify partial discharges
running between 3 and 400 Hz.
a third PD sensing technology related to the feeder cables
that dramatically increases the and connect around the cable
coverage of the stator winding shields. The same sensors apply
for maximum coverage. to power center transformers,
cable terminations and bus ducts.
Problems that partial discharge
analysis can detect within
switchgear apparatus include:
• Discharges in air gaps
(between bus and support
window, for example)
Breaker Breaker Breaker Breaker Breaker Breaker
Cubicle 1 Cubicle 2 Cubicle 3 Cubicle 4 Cubicle 5 Cubicle 6
• Surface tracking (on
supporting isolator or
bus insulation surface)
• Sparks within insulation voids
• Insulation problems in
cable terminations and
connected equipment
• Poor electrical connections
L1 L2 L3 (floating potentials)
• Defective current transformers
Legend MV Power Circuit Breaker and potential transformers
52
RFCT • Incoming bus ducts
Coupling
Capacitors Switchgear Cable Cable
Compartment Shields

Sensor Selection Guideline


• RFCT—One for Every Feeder Breaker
• Coupling Capacitors—One Set for
Every 3 to 4 Cubicles Load Cables or Bus

Typical switchgear application

EATON InsulGard 5
InsulGard software

InsulGard software allows for extensive data analysis from simple automated reporting to in-depth analysis by experts.
This image shows the history and outcome of maintenance efforts, which resulted in a not very successful rewinding of a 13.8 kV motor.
PD activity in two locations grew higher than before rewinding.

Very aggressive PD was found as a result of several InsulGard alarms triggered on 11/14–11/16, 2011.
PD grew rapidly in the 6 weeks between October 19 and November 16 when it was discovered.
It could have had dramatic consequences if it had been left undetected.

6 EATON InsulGard 
Simplified PD remote monitoring process
Eaton’s Remote Monitoring and Diagnostic services add considerable The accumulated data is summarized for viewing using Eaton’s
value to continuous online monitoring investment at a remarkably Online Viewing Portal where customers may access data trends
low cost. Traditionally, data collection and data analysis for partial and monthly reports. Report format is single page with stop light
discharge has been cumbersome and extremely difficult for untrained (red, yellow or green) designations to quickly assess the monitored
professionals. Eaton’s Remote Monitoring service eliminates these equipment’s health. Behind the scene is a team of world-renowned
concerns by communicating directly to PD monitors using Ethernet or PD expert engineers reviewing any anomalies. A designated engineer
cellular modems. Data encryption, VPN connection and secure tunnels will contact the customer directly with recommendations before the
provide reliable, safe and secure connection to the monitors. The data PD leads to a catastrophic event. If there are ever any concerns or
is collected daily from the units and screened for alarms. questions regarding the InsulGard PD detection system, experts are
available with instantaneous access to all current data.

Motors, generators, switchgear or Remote monitoring back office


bus ducts with partial discharge
monitors (PDM) Alarms
Acknowledgement
Escalation

PDM Cell
Secure Web
Modem
Portal
Secure
Database
VPN

PDM Cell
Modem Cell Provider

Expert
Analysis and
Recommendations
PDM PDM Cell
Modem

Simplified PD process

Communications and connectivity


There are three communication ports available.

RS-485 RS-485 Modbus RTU RS-485 Modbus Network


RS-485 optically isolated interface based on ModbusT RTU
protocol allows remote device configuration and
data downloading. InsulGard can be networked with an
existing Modbus network, allowing for up to 231
addressable devices.

Direct USB connection USB to Laptop


The device USB port is used for local communications
between the InsulGard and a computer through a
USB A/B cable.

Ethernet connection
There are several functions available through the Ethernet
port, including webpage display, FTP upload or download and
operation as a virtual serial port.

Communications options

EATON InsulGard 7
InsulGard’s onboard webpage

InsulGard’s on-board webpage provides a quick overview of status and PD levels. It is accessed using a standard Web
browser over Ethernet.

For technical specifications and


additional information, please
contact your local Eaton
representative or visit our
website at Eaton.com/pd

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122 USA
Eaton.com

© 2015 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. BR02713001E / Z16028 All other trademarks are property
January 2015 of their respective owners.

You might also like