Professional Documents
Culture Documents
h i g h l i g h t s
Measured the potential of pipeline steel under direct current (DC) densities.
Quantified the accelerated corrosion rate of the steel under DC interference.
Determined the shift of cathodic protection potential in the presence of DC.
Determined the electrolyte alkalinisation caused by DC stray current.
a r t i c l e i n f o a b s t r a c t
Article history: In this work, corrosion of an X52 pipeline steel at various direct current (DC) densities was investigated in
Received 6 February 2017 an extracted soil solution by potential and pH measurements, weight-loss testing and optical microscopy.
Received in revised form 19 April 2017 It was found that the DC stray current could polarize, either anodically or cathodically, the steel at the
Accepted 5 May 2017
anodic and cathodic zones, respectively, resulting in accelerated corrosion of the steel and the cathodic
Available online 17 May 2017
reduction of dissolved oxygen. The CP potential was not maintained at the applied value under the DC
interference, and was shifted to positive and negative directions in the anodic and cathodic zones, respec-
Keywords:
tively. The pipeline suffered from both anodic and cathodic DC interferences. The steel in the anodic zone
Pipeline steel
Corrosion
cannot be protected, at least not fully protected, by the CP from corrosion. The solution alkalization in the
Direct current interference cathodic zone would be further enhanced due to the combined effect of DC and CP on cathodic reaction.
Cathodic protection The implications of the DC interference on pipeline integrity were discussed.
Solution pH Ó 2017 Elsevier Ltd. All rights reserved.
1. Introduction current sources, the pipeline would suffer from accelerated corro-
sion, resulting in the so-called AC or DC corrosion [6–15].
Stray current refers to the electric current flowing through con- The DC corrosion of buried pipelines is similar to classic corro-
ductive paths other than the intended ones [1]. Corrosion of metals sion mechanism, i.e., current flows from anode to cathode through
can be caused by the stray current interference [2]. In the 1960s, the soil electrolyte by ionic conductivity and from cathode to
Schwalm and Sandor [3] determined that the stray current, includ- anode through the pipeline by electrons [16]. At the anode, the
ing both alternating current (AC) and direct current (DC) ones, was pipe steel oxidizes; and at the cathode, hydrogen evolution or
able to accelerate corrosion of buried pipelines. The stray current the oxygen reduction occurs. Thus, steel corrosion occurs at the
can be categorized into dynamic or static ones based on the fact anode, with no corrosion attack at the cathode. The corrosion
whether the amplitude and direction of the current change over kinetics obeys Faraday’s law, i.e., 1 ampere of DC discharge from
time [4,5]. Generally, the static stray current interference that a a pipeline may consume 10 kg of steel within one year [17]. Gener-
pipeline is subject to is generated by outside current sources, such ally, the DC can cause more serious corrosion than AC on pipeline
as high-voltage AC or DC powerlines, DC rectifiers, etc. The steels. McIntosh [18] demonstrated that the corrosion of steels
dynamic current interference is mostly from the orbital transport under AC interference of 60 Hz is about 1% of that induced by an
system, i.e., city transit systems. When collocated with the stray equivalent amount of DC. Moreover, the DC corrosion is localized
in nature. Corrosion reaction occurs at the anode where the pipe
steel is exposed to soil due to local breakage of external coatings,
which can result in dramatic consequences on pipelines [19,20].
⇑ Corresponding author.
E-mail address: fcheng@ucalgary.ca (Y.F. Cheng).
http://dx.doi.org/10.1016/j.conbuildmat.2017.05.024
0950-0618/Ó 2017 Elsevier Ltd. All rights reserved.
676 S. Qian, Y.F. Cheng / Construction and Building Materials 148 (2017) 675–685
Different from AC corrosion, there have been limited investiga- the DC circuit was ON. In other words, the potential would deviate from the applied
CP potential under the DC effect (i.e., the potential of the steel did not automatically
tions on DC corrosion of pipelines, including parametric effects and
adjust itself to the applied CP potential). The potential of the steel electrode under
the mutual interference of DC with cathodic protection (CP) [21– various DC densities was measured through a Gamry Reference 600 electrochemical
24]. For example, the CP criterion recommended by NACE Interna- system. The recorded potential of the steel included both the applied CP potential
tional to protect underground steel structures from corrosion and the potential shift under DC stray current. All potentials in this work were con-
attack is a cathodic potential of 850 mV vs. copper sulfate elec- verted to CSE to be consistent with the industry use.
During testing, the test cells were continuously purged with air to maintain the
trode (CSE) [25]. However, the presence of DC interference can
constant dissolved oxygen content in the solution. A dissolved oxygen sensor was
decrease the effectiveness of CP by shifting the applied CP potential used to monitor the content of dissolved oxygen, which was 7.7 ppm. A pH meter
from the designed value. There has been so far rare understanding (Oaklon Acorn) was installed to monitor the solution pH at the anodic and cathodic
of the quantitative relationship between DC current density and cells. To ensure the reproducibility of the measured data, each test was conducted
three time.
the CP potential shift.
The DC corrosion of buried pipelines has attracted increasing
2.3. Weight-loss testing
attention recently along with the design and construction of
high-voltage DC (HVDC) power lines, which are usually located Prior to weight-loss testing, steel coupons were weighed by an electronic bal-
in energy corridors where oil/gas pipelines are buried. This is par- ance with an accuracy of 0.1 mg. They were immersed in the soil solution under
ticularly true in Alberta, Canada, where the proposed HVDC lines the corrosion potential of the steel and two CP potentials, i.e., 850 mV vs. CSE
are adjacent to energy pipelines over a long distance. Obviously, and 1000 mV vs. CSE, respectively, and varied DC current densities. To ensure
reproducibility of the testing results, three parallel coupons were used at each
investigations of DC corrosion of pipelines not only improve our
condition.
understanding to this important phenomenon, but also meet After testing, the corrosion products formed on the steel surface were removed
immediate industry and society needs for safe and reliable design carefully by both mechanical and chemical methods according to ASTM G1-03 [26].
of energy infrastructure. Light scraping and scrubbing was used to remove tightly adherent corrosion prod-
ucts, and a descaling solution containing 500 mL HCl, 3.5 g hexamethylenete-
In this work, corrosion of an X52 pipeline steel at various DC
tramine and 500 mL distilled water was used in chemical removal procedure. The
current densities was investigated in an extracted soil solution cleaning process was repeated several times to remove corrosion products thor-
by potential and pH measurements, weight-loss testing and optical oughly. After rinsing with distilled water and alcohol, the steel coupons were dried
microscopy. The effect of DC current density on both anodic and and weighed again. The weight change under specific testing conditions was
cathodic reactions was determined. The shift of CP potential under recorded. The corrosion rate (mm/year) of the steel was calculated from the
weight-loss measurements and the testing time.
DC interference was measured. The mechanistic aspects about the
accelerated pipeline corrosion and reduced CP effectiveness in the
2.4. Surface characterization
presence of DC interference were analyzed. The implications of the
DC interference on pipeline integrity were discussed. After 48 h of testing in the soil solution at various DC current densities and/or
CP potentials, the steel electrodes were removed from the solution, and rinsed with
2. Experimental deionized water. The surface morphology of the steel was observed by an optical
microscope.
2.1. Specimen and solution
Fig. 1. Schematic diagram of the experimental setup for DC corrosion testing on X52 steel specimen in the extracted soil solution, where WE, RE and CE refer to working
electrode, reference electrode and counter electrode, respectively, and SCE is saturated calomel electrode. The DC parameters to be tested are also included.
recorded before the DC is applied. The new potential is generally solution pH in the cathodic zone increases (tends to be more alka-
less negative than the initial corrosion potential in the period from line) with the increase of the DC current density (Fig. 5b).
0 to 1200 s.
Fig. 4 shows the steady-state DC-ON potential of the X52 steel
electrode in anodic and cathodic zones, respectively, in the soil 3.3. Corrosion rate and morphology of the steel under various DC
solution as a function of DC current density. It is seen that, in the current densities
anodic zone, the potential becomes less negative with the increas-
ing DC current density; while in the cathodic zone, the potential is Fig. 6 shows the corrosion rate determined by weight-loss test-
more negative at higher DC current densities. ing of X52 steel after 48 h of immersion in the soil solution as a
function of DC current density. It is seen that the corrosion rate
of the steel increases with the DC current density. For example,
3.2. Solution pH at anodic and cathodic zones under various DC in the absence of DC, the steel corrodes in the aerated soil solution
various densities at a corrosion rate of about 0.4 mm/y. At a DC current density of 5
A/m2 and 10 A/m2, the corrosion rate is increased to 6.5 mm/year
Fig. 5 shows the solution pH in the anodic and cathodic zones, and 12.5 mm/year, respectively.
respectively, as a function of DC current density. It is seen that, Fig. 7 shows the optical views of the morphology of the steel
in the anodic zone, the solution pH drops (tends to be more acidic) electrodes after 48 h of testing in the soil solution under various
with the increasing DC current density (Fig. 5a). However, the DC current densities. In the absence of DC, the steel electrode
678 S. Qian, Y.F. Cheng / Construction and Building Materials 148 (2017) 675–685
-0.2 -0.3
0.1 A/m2 (a)
0.5 A/m2
10 A/m2 -0.4
-0.4 1 A/m2
2 A/m2
5 A/m2
5 A/m2
-0.6 -0.5
2 A/m2 10 A/m2
1 A/m2
0.5 A/m2
-0.8 0.1 A/m2
-0.6
-0.9
-1.4 0 2 4 6 8 10 12
0 500 1000 1500 2000 2500 3000 3500 4000
DC current density (A/m2)
Time (s)
-0.7
Fig. 2. Time dependence of the potential of X52 steel electrode in the anodic zone at
various DC current densities in the soil solution. (b)
-0.8
-0.9
Time (s)
DC application. The steady-state DC-ON potential, i.e., the steel
Fig. 3. Time dependence of the potential of X52 steel electrode in the cathodic zone
at various DC current densities in the soil solution.
potential under both CP and DC, is less negative with the increasing
DC current density. When the DC is stopped at the 2400th s, the
potential drops, but does not recover to the initial CP potential val-
shows a bright, clear view, and corrosion products are not visible ues. Generally, the new steady-state DC-OFF potential is more neg-
on the steel surface. At the small DC current density of 0.1 A/m2, ative than the applied CP potential, especially at high DC current
the morphology of the steel electrode is similar to that in the densities, as shown in Fig. 8a and b.
absence of DC. With the increase of the DC current density, the Fig. 9 shows the time dependence of the potential of X52 steel
steel surface becomes dark, and corrosion products can be seen electrode at CP potentials of 850 mV vs. CSE and 1000 mV vs.
on the steel surface obviously. Moreover, as the DC current density CSE in the cathodic zone at various DC densities in the soil solution,
increases, the electrode surface turns darker and more corrosion respectively. It is seen that, similar to the potential records mea-
products are present on the surface. Generally, the DC application sured on the steel without CP application in Fig. 3, the potential
induces uniform corrosion on the steel. of the steel is shifted negatively under DC in the cathodic zone.
The DC-ON potential, i.e., the potential of the steel under both CP
and DC application, becomes more negative with the increasing
3.4. DC corrosion testing on the steel under CP at various DC current DC current density. When the DC is stopped, the potential of the
densities steel increases rapidly and gradually reaches a relatively stable
value, which is approximately close to the initially applied CP
Fig. 8 shows the time dependence of the potential of X52 steel potential.
electrode under CP potentials of 850 mV vs. CSE and 1000 mV Fig. 10 shows the potential of the X52 steel electrode at corro-
vs. CSE in the anodic zone at various DC densities in the soil solu- sion potential and varied CP potentials in the soil solution as a
tion, respectively. Prior to DC application, the steel is at the applied function of DC current density. It is seen that, in the anodic zone,
CP potential. Similar to the potential records in the absence of CP in the DC shifts the CP potential applied on the steel positively. At
Fig. 2, the potential of the steel cannot be maintained at the applied individual DC current densities, the steel without CP has the least
CP potential, and is shifted towards the positive direction upon the negative DC-ON potential, and the steel applied at 1000 mV vs.
S. Qian, Y.F. Cheng / Construction and Building Materials 148 (2017) 675–685 679
9.0 CSE has the most negative potential. In the cathodic zone, the DC is
(a) able to shift the CP potential applied on the steel more negatively
as the DC current density increases. At individual DC current den-
8.5 sities, the steel without CP application has the most negative
potential, and that applied at 1000 mV vs. CSE of CP has the least
8.0 negative potential.
Fig. 11 shows the solution pH in the anodic and cathodic zones
as a function of DC current density when the steel is at varied
pH
7.5 potentials. It is seen that, with the increase of the DC current den-
sity, the solution pH decreases and increases in the anodic and
cathodic zones, respectively. This is similar to those observed in
7.0 the absence of CP application in Fig. 5. At individual DC current
densities, the CP application could elevate the solution pH in both
6.5 the anodic and cathodic zones, compared to those measured in the
absence of CP in Fig. 5.
Fig. 12 shows the corrosion rate of the steel at corrosion poten-
6.0 tial and under CP potentials of 850 mV vs. CSE and 1000 mV vs.
0 2 4 6 8 10 12 CSE, respectively, determined by weight-loss testing after 48 h of
2
DC current density (A/m ) immersion in the soil solution as a function of DC current density.
Generally, the corrosion rate of the steel increases with the DC cur-
9.0 rent density. At individual DC current densities, the corrosion rate
(b) decreases if CP is applied on the steel. Moreover, the more negative
CP potential (i.e., 1000 mV vs. CSE) causes a smaller corrosion
rate. It is noted that, at a small DC current density of 1 A/m2, the
8.5 corrosion rate of the steel exceeds 1 mm/year even when the CP
of 850 mV vs. CSE is applied. The industry-acceptable corrosion
rate of pipelines is usually less than 0.1 mm/year [27]. Only when
the CP potential is shifted negatively to 1000 mV vs. CSE, the cor-
pH
4. Discussion
14
4.1. Accelerated corrosion of pipelines in the presence of DC
interference
12
Corrosion rate (mm/year)
2 A/m2 5 A/m2
10 A/m2
Fig. 7. Optical views of the morphology of steel electrodes after 48 h of testing in the soil solution under various DC current densities.
tively, in the soil solution, while the corrosion potential of the X52 When the DC is removed, the potential is gradually recovered
pipe steel is approximately 800 mV vs. CSE. Thus, the DC greatly back to the steady-state value which is generally identical to the
polarizes, either anodically or cathodically, the steel at the anodic initial corrosion potential prior to DC application in the anodic
and cathodic zones, respectively. As a result, both the steel dissolu- zone (Fig. 2). This indicates that the DC accelerated corrosion is
tion (corrosion) and the cathodic reduction of dissolved oxygen are reversible under the present testing condition. Although the DC
accelerated in the presence of DC interference. Moreover, new application can cause the drop of solution pH in the anodic zone
steady-state potentials are established at the DC-ON levels, indi- (Fig. 5a), the pH values of the solution in the anodic zone before
cating that the steel corrodes at a new state with a high corrosion and after application of the highest DC current density of 10 A/
rate, as confirmed by the weight-loss measurements and corrosion m2 are still in the near-neutral pH range (changing from 7.7 to
morphology observations in Figs. 6 and 7. 6.4). The potential of the steel does not change greatly in the neu-
S. Qian, Y.F. Cheng / Construction and Building Materials 148 (2017) 675–685 681
-0.2 -0.2
(a) 0.1 A/m2 (a)
0.5 A/m2
-0.4
-0.4 1 A/m2
10 A/m2
2 A/m2 Corrosion DC-ON DC-OFF
-1.4 -1.6
0 500 1000 1500 2000 2500 3000 3500 4000 0 500 1000 1500 2000 2500 3000 3500 4000
Time (s) Time (s)
-0.2 -0.2
(b) 0.1 A/m2 (b)
0.5 A/m2 -0.4
-0.4 1 A/m2
-0.6
5 A/m2
-0.6 10 A/m2 Corrosion DC-ON DC-OFF
10 A/m2
-0.8 potential potential potential
5 A/m2
2 A/m2
-0.8
1 A/m2 -1.0 0.1 A/m2
2 0.5 A/m2 1 A/m2
0.5 A/m 0.1 A/m2
-1.0 0.1 A/m2
-1.2 2 A/m 2 0.5 A/m2
5 A/m2
1 A/m2
Corrosion DC-ON DC-OFF 2 A/m2
-1.2 -1.4
potential potential potential 5 A/m2
10 A/m2
10 A/m2
-1.4 -1.6
0 500 1000 1500 2000 2500 3000 3500 4000 0 500 1000 1500 2000 2500 3000 3500 4000
tral pH range. If the DC current density is sufficiently large and the shifted to the positive and negative directions in the anodic and
anodic solution pH drops greatly to make the solution to be acidic, cathodic zones, respectively, as seen in Figs. 8–10. For example,
it is expected that the steady-state DC-OFF potential of the steel prior to DC application, the steel is at the CP potential of
would be different from the original corrosion potential. 850 mV vs. CSE and 1000 mV vs. CSE, which are both effective
However, after the DC is stopped, the potential at the cathodic for corrosion protection, as seen in Fig. 12. At the DC current den-
zone does not return to the original corrosion potential. Generally, sity of 1 A/m2, the ‘‘true” potential of the steel is changed to about
the steel is at a new steady state with a less negative potential in 750 mV vs. CSE and 880 mV vs. CSE, respectively, which are less
the cathodic zone, as seen in Fig. 3. Thus, the DC effect on the negative than the applied CP potential values. As a result, the CP at
cathodic zone is irreversible under the testing condition. The DC 850 mV vs. CSE is not able to protect the steel from corrosion, and
drives the cathodic reduction of dissolved oxygen to produce the corrosion rate of the steel increases to about 1 mm/year
hydroxyl ions, elevating the solution pH. For example, the cathodic (Fig. 12). When the DC current density is up to 10 A/m2, the CP
solution pH increases from 7.7 to 8.6 upon the application of the potential of 1000 mV vs. CSE losses its ability for corrosion pro-
largest DC current density of 10 A/m2 in this work. The steel is tection because the ‘‘true” potential of the steel in the presence
expected to be in a relatively more stable state in the new alkaline of DC is about 650 mV vs. CSE only, where the corrosion rate is
environment, even after the DC is removed. Thus, the DC corrosion up to approximately 4 mm/year. The steel under the applied CP
of pipelines would cause local alkalization of the solution through at 850 mV vs. CSE has a corrosion rate of about 9.3 mm/year at
production of OH- by cathodic reaction. The degree of alkalization the DC current density of 10 A/m2. Thus, the steel in the anodic
depends on the value of DC current density. zone is not protected, at least not fully protected, by the CP from
corrosion in the presence of DC interference. The steel corrosion
at the anodic zone depends on both the DC current density and
4.2. Adverse effect of DC interference on CP performance the applied CP potential. As illustrated in Fig. 14b, when the
applied CP potential, such as 850 mV vs. CSE, is not sufficient to
This work also demonstrates that, in the presence of DC, the offset the DC-induced anodic polarization, corrosion would occur
applied CP potential on the steel cannot be maintained, and is in the anodic zone. Unless the CP potential is sufficiently negative
682 S. Qian, Y.F. Cheng / Construction and Building Materials 148 (2017) 675–685
-0.3 8.5
(a) (a) Corrosion potential
-0.4 -850 mV vs. CSE
8.0 -1000 mV vs. CSE
-0.5
Potential (V vs. CSE)
-0.6
7.5
pH
-0.7
-0.8 7.0
-1.1 6.0
0 2 4 6 8 10 12 0 2 4 6 8 10 12
DC current density (A/m2) DC current density (A/m ) 2
-0.7 10.5
(b) (b) Corrosion potential
Corrosion potential
-0.8 -850 mV vs. CSE
-850 mV vs. CSE 10.0 -1000 mV vs. CSE
-1000 mV vs. CSE
-0.9
Potential (V vs. CSE)
-1.0 9.5
-1.1
pH
9.0
-1.2
-1.3 8.5
-1.4
8.0
-1.5
-1.6 7.5
0 2 4 6 8 10 12 0 2 4 6 8 10 12
2 2
DC current density (A/m ) DC current density (A/m )
Fig. 10. Potential of the X52 steel electrode at corrosion potential and varied CP Fig. 11. Solution pH in the anodic (a) and cathodic (b) zones as a function of DC
potentials as a function of DC current density in the soil solution (a) anodic zone, (b) current density when the steel is at varied potentials.
cathodic zone.
14
(i.e., 1000 mV vs. CSE) so that the steel becomes cathodically Corrosion potential
polarized even in the presence of DC interference, the steel can 12 -850 mV vs. CSE
be protected from corrosion, as shown in Fig. 14c. -1000 mV vs. CSE
Corrosion rate (mm/year)
2
4.3. Implications on pipeline integrity under DC interference
0.1 A/m2
0.5 A/m2
1 A/m2
2 A/m2
5 A/m2
10 A/m2
Fig. 13. Optical views of morphology of the steel that is at corrosion potential (left) and CP potentials of 850 mV vs. CSE (middle) and 1000 mV vs. CSE (right), respectively,
after 48 h of testing in the soil solution at various DC current densities.
of that in the absence of DC interference. The accelerating corro- cause alkalinisation of the electrolyte remaining at the cathodic
sion at the anode could result in rapid perforation of the pipelines zone, i.e., the coating defect where the DC current flows into the
at the coating defect. Second, the presence of DC stray current can pipeline steel. Although corrosion would not occur locally, the
684 S. Qian, Y.F. Cheng / Construction and Building Materials 148 (2017) 675–685
Fig. 14. Schematic diagram of the mechanistic model to illustrate the electrochemical reactions occurring in the anodic and cathodic zones under DC interference (a) in the
absence of CP, (b) CP potential of 850 mV vs. CSE, (c) CP potential of 1000 mV vs. CSE and the DC current density is smaller than 1 A/m2.
In the presence of DC interference, the applied CP potential on [8] A. Pourbaix, P. Carpentiers, R. Gregoor, Detection and assessment of alternating
current corrosion, Mater. Perf. 39 (2000) 34–37.
the pipeline steel cannot be maintained, and is shifted to the pos-
[9] A. Brenna, S. Beretta, F. Bolzoni, M. Pedeferri, M. Ormellese, Effects of AC-
itive and negative directions in the anodic and cathodic zones, interference on chloride-induced corrosion of reinforced concrete, Const. Build.
respectively. As a result, the steel in the anodic zone cannot be pro- Mater. 137 (2017) 76–84.
tected, at least not fully protected, by the CP from corrosion. The [10] L.V. Nielsen, Role of Alkalization in AC Induced Corrosion of Pipelines and
Consequences Hereof in Relation to CP Requirements, Corrosion 2005, NACE
solution alkalization in the cathodic zone would be further International, Houston, USA, 2005.
enhanced by the combined effect of DC and CP on cathodic reduc- [11] H. Xiao, S.B. Lalvani, A linear model of alternating voltage-induced corrosion, J.
tive reaction. Electrochem. Soc. 155 (2008) C69–C74.
[12] L. Xu, X. Su, Z. Yin, Y. Tang, Y. Cheng, Development of a real-time AC/DC data
The DC stray current causes anodic and cathodic interferences acquisition technique for studies of AC corrosion of pipelines, Corros. Sci. 61
on the buried pipelines at the same time. For the anodic interfer- (2012) 215–223.
ence, the DC current results in accelerated corrosion to the steel, [13] L. Xu, X. Su, Y. Cheng, Effect of alternating current on cathodic protection on
pipelines, Corros. Sci. 66 (2013) 263–268.
which presents an essential threat to the integrity of the pipeline. [14] E. Ghanbari, M. Iannuzzi, R. Lillard, The mechanism of alternating current
For the cathodic interference, the dominant effect is the increased corrosion of API grade X65 pipeline steel, Corrosion 72 (2016) 1196–1210.
pH of the local solution, which potentially causes disbonding of the [15] L. Bertolini, M. Carsana, P. Pedeferri, Corrosion behaviour of steel in concrete in
the presence of stray current, Corros. Sci. 49 (2007) 1056–1068.
coating. [16] F. Brichau, J. Deconinck, T. Driesens, Modeling of underground cathodic
protection stray currents, Corrosion 52 (1996) 480–488.
[17] C. Andrade, I. Martinez, M. Castellote, Feasibility of determining corrosion
Acknowledgements rates by means of stray current-induced polarisation, J. Appl. Electrochem. 38
(2008) 1467–1476.
This work was supported by Eyes High Doctoral Recruitment [18] D. McIntosh, Grounding where corrosion protection is required, IEEE Trans.
Indu. Appl. (1982) 600–607.
Scholarship at the University of Calgary – Canada. [19] D. Jones, Effect of alternating current on corrosion of low alloy and carbon
steels, Corrosion 34 (1978) 428–433.
[20] P.M. Scott, Environmentally induced cracking, Construct. Build. Mater. 4
References (1990) 98–106.
[21] I. Metwally, H. Al-Mandhari, A. Gastli, Z. Nadir, Factors affecting cathodic-
[1] S. Papavinasam, R.W. Revie, Uhlig’s Corrosion Handbook, Wiley, New York, NY, protection interference, Eng. Ana. Boundary Elements 31 (2007) 485–493.
2000. [22] I. Metwally, H. Al-Mandhari, A. Gastli, A. Al-Bimani, Stray currents of ESP well
[2] B. Martin, A history of stray current corrosion, Corros. Mater. 31 (2006) 12–14. casings, Eng. Ana. Boundary Elements 32 (2008) 32–40.
[3] L. Schwalm, J. Sandor, Stray current-the major cause of underground plant [23] S. Srikanth, T. Sankaranarayanan, K. Gopalakrishna, B. Narasimhan, T. Das, S.K.
corrosion, Mater. Perf. 6 (1969) 31–36. Das, Corrosion in a buried pressurised water pipeline, Eng. Failure Ana. 12
[4] W. Li, The monitor and control system of stray current corrosion in metro, (2005) 634–651.
Urban Mass Transit. 4 (2003) 48–52. _
[24] K. Zakowski, W. Sokólski, Numeric method of IR elimination from
[5] Y. Song, X. Wang, R. He, C. He, X. Wang, Status in research on stray-current measurement results of potential of underground pipelines in the zone of
corrosion of buried steel pipelines, Corros. Prot. 8 (2009) 003. interaction of stray currents, Corros. Sci. 41 (1999) 2213–2222.
[6] A. Fu, Y. Cheng, Effects of alternating current on corrosion of a coated pipeline [25] NACE Standard RP0169-2002 Control of external corrosion on underground or
steel in a chloride-containing carbonate/bicarbonate solution, Corros. Sci. 52 submerged metallic piping systems, NACE, 2002.
(2010) 612–619. [26] ASTM Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test
[7] D. Kuang, Y. Cheng, Understand the AC induced pitting corrosion on pipelines Specimens, ASTM International, 2011.
in both high pH and neutral pH carbonate/bicarbonate solutions, Corros. Sci. [27] J.R. Davis, Corrosion: Understanding the Basics, ASM International, 2000.
85 (2014) 304–310.