Professional Documents
Culture Documents
entitled
Evaluation of Indoor Air Quality in Four Nursing Home Facilities in Northwest Ohio
by
Hope Tebbe
Submitted to the Graduate Faculty as partial fulfillment of the requirements for the
Occupational Health
________________________________________
April Ames PhD, CIH, Committee Chair
________________________________________
Victoria Steiner, PhD, Committee Member
________________________________________
Farhang Akbar-Khanzadeh PhD, CIH, Committee
Member
________________________________________
Sheryl Milz, PhD, CIH, Committee Member
________________________________________
Amanda Bryant-Friedrich, PhD, Dean
College of Graduate Studies
May, 2017
Copyright 2017, Hope Marie Tebbe
This document is copyrighted material. Under copyright law, no parts of this document
may be reproduced without the expressed permission of the author.
An Abstract of
by
Hope Tebbe
Submitted to the Graduate Faculty as partial fulfillment of the requirements for the
Masters of Science Degree in
Occupational Health
May 2017
Indoor air quality (IAQ) is considered one of the top five environmental risks to
the public’s health. Older adults are more vulnerable to health complications associated
with indoor air contaminants because of their decreased immune system and age-
associated health problems, as well as the fact that they spend up to 95 percent of their
time indoors.
Area air sampling was conducted in the nursing home section of four long term
care facilities, three days at each facility (12 days total). Particle concentrations (PM2.5,
PM10, Total Particulate matter (TPM), Ultrafine Particles (UFP), temperature, and
humidity were measured. Two minute samples were collected during seven Sampling
Sessions. Up to nine indoor locations were sampled, representing the various occupied
spaces in each nursing home, along with an outside location for comparison.
differences (p<0.001) in PM concentrations and UFP counts. One Facility had higher
iii
Location demonstrated significant differences (p<0.001) in PM concentrations and UFP
counts. In general, the highest UFP and PM concentrations were seen in the kitchen,
satellite kitchen, and hair salon, especially at times when the staff and residents were
active in these rooms. Significant differences were seen in UFP counts (Facilities 1 and
3) and PM2.5 (Facility 2) by Sampling Session. The highest concentrations were found for
the Sampling Sessions in the mid-morning and mid-afternoon which were during peak
guidelines, this may be appropriate for older residents who prefer a warmer temperature.
While most median particle values were below ASHRAE guidelines, maximum values
did exceed occasionally in the hair salon and kitchen at all facilities. Various indoor
Sampling Location PM concentrations or UFP counts exceeded the outdoor levels at all
four facilities. Although the median PM values did not exceed the ASHRAE standards it
is unknown whether older adults may still experience significant health complications
with these PM concentrations. In addition staff who spend extended amount of times in
the kitchen and hair salon could be exposed to higher levels of PM. IAQ in hospitals and
similar environments, such as nursing homes, may require a higher level of care because
iv
This thesis is dedicated to my parents: for their endless love, support and encouragement;
Thank you, Dr. Ames, for your long hours of review, support, and assistance, who
without I never would have pursued my career in Occupational Health and Safety. Your
guidance and encouragement are likely responsible for the completion of this paper and
program.
Thank you, Dr. Steiner, for your assistance in coordinating the facilities and for
Thank you, Erin Messerly, Sarah Mancuso, and Megan Benner for your assistance
in gathering data.
Thank you to the members of my committee for your participation with this
thesis; Dr. Akbar-Khanzadeh, Dr. Milz, Dr. Valigosky and Dr. Ames, for all the
education leading up to this; you have been a teacher, a motivator, and an inspiration.
Thank you to NIOSH/CDC for the scholarship that provided me with this
education.
v
Table of Contents
Acknowledgements .............................................................................................................v
1 Introduction .............................................................................................................1
1.2 Significance........................................................................................................2
vi
2.6 Control of IAQ ................................................................................................11
3 Methods .................................................................................................................18
4 Results ...................................................................................................................27
vii
4.5.5 Comparison by Sampling Location and Facility .............................61
5 Discussion .............................................................................................................95
viii
5.5 Indoor versus Outdoor Comparisons ..............................................................97
6 Conclusions .........................................................................................................104
References ........................................................................................................................106
ix
List of Tables
4.8 Descriptive Statistics, All Indoor Locations by Sampling Session, Facility 1 ......68
4.9 Descriptive Statistics, All Indoor Locations by Sampling Session, Facility 2 ......70
4.10 Descriptive Statistics, All Indoor Locations by Sampling Session, Facility 3 ......71
4.11 Descriptive Statistics, All Indoor Locations by Sampling Session, Facility 4 ......72
x
4.20 ANOVA by Sampling Location, Facility 3 ...........................................................85
xi
List of Figures
xii
4-17 Ultrafine Particles (pt/cm3) by Sampling Location and Facility ...........................62
4-21 Median Ultrafine Particles (pt/cm3) by Sampling Session and Facility ................74
4-23 Median PM10 Concentration (mg/m3) by Sampling Session and Facility .............76
xiii
List of Abbreviations
OA ..............................Outside Air
OEL ............................Occupational Exposure Limit
OSHA.........................Occupational Safety and Health Administration
RH ..............................Relative Humidity
xiv
List of Symbols
º .................................Degrees
< ................................Less than
% ................................percent
a.m. .............................Morning
C .................................Celsius
F .................................Fahrenheit
L/min ..........................Liter/minute
Max ............................Maximum
mg/m3 .........................Milligrams per Cubic Meter of Air
Min .............................Minimum
n..................................Number
p.m. ............................Evening
pt/cm3 .........................Particles per Cubic Centimeters of Air
μg ...............................Micrometers
μg/m3 ..........................Micrometers per Cubic Meter of Air
xv
Chapter 1
Introduction
1.1 Overview
The Environmental Protection Agency (EPA) defines indoor air quality (IAQ)
as “the air quality within and around buildings and structures, especially as it relates to
the health and comfort of building occupants” (EPA, 2016a). It has been shown that air
pollutants are commonly two to five times higher indoors compared to outdoors and
sometimes 100 times greater than outdoor levels (EPA, 2015). It is estimated that 96
percent of homes in the United States (US) have at least one problem with IAQ.
IAQ is a priority environmental health concern due to the fact the US population
spends so much time indoors and the health effects that can arise from exposure to these
pollutants (EPA, 2016). Indoor air contaminants can cause acute or chronic health
problems (Bentayeb et al., 2015; Bentayeb et al., 2013; Maio et al., 2015). Previous
research has associated acute health problems such as headache, nausea and respiratory
infection to the quality of the indoor air (Curtis et al., 2006). Chronic health effects of
poor IAQ may include systemic problems such as anemia, heart problems, decreased
1
lung elasticity, and even cancer (Pecingina & Popa, 2014).
Particulate matter (PM) is a mixture of small particles and droplets in the air that
combustion, use of cleaning products, and biological contaminants such as pollen, dust
and fungi. Common PM include dust, dirt, cigarette smoke, soot, or smoke. PM tends to
be higher on warmer days (Katsouyanni, et al., 1993). Relative humidity (RH) has been
exposure has been linked to heart attacks, aggravated asthma, decrease in lung function,
irregular heartbeat, premature death in people with heart or lung disease, and increases in
respiratory symptoms such as irritation of the air way, coughing, and difficulty breathing
(Bernstein et al., 2008; Bentayeb et al., 2015; Curtis et al., 2006; Bentayeb et al., 2013).
Populations most sensitive to PM are people with lung disease, children and older adults
(EPA, 2016b).
1.2 Significance
In 2014, older adults over the age of 65 comprised 14.5 percent of the US
population (46.2 million Americans), but are projected to more than double to 98 million
systems, increasing the demand for care, services and technologies to prevent and treat
chronic conditions associated with old age. Older adults spend up to 95 percent of their
time indoors and have reduced outdoor activities. As a result, there is potentially more
Wolterbeek, & Almeida, 2014; Bernstein et al., 2008). Older adults are a susceptible
population due to: 1) having a compromised immune system; 2) decreased lung function
2
with a predisposition for respiratory infections; and, 3) age-associated health problems
Almeida, 2014). Older adults are sensitive to short-term PM exposure with a higher risk
of hospitalization and death (EPA, 2017). Recent studies have found that PM levels may
be elevated in nursing homes and this can cause acute and chronic health effects
Limited studies have been conducted related to the indoor environment and long-
term care facilities. These studies have been performed primarily in other countries or in
large urban areas. The quality of nursing home care has been found to be different
between rural and non-rural nursing homes (Lutfiyya, Gessert and Lipsky, 2013).
Nursing homes are measured on a five-star scale from the Centers for Medicare and
Medicaid Services (CMS) nursing home compare website, a publicly available federal
may have an impact on the quality of the indoor environment. The age of the facility
levels in nursing homes can assist in determining the potential exposure of older adults to
indoor air pollutants. Understanding the PM levels in nursing homes may allow
3
1.4 Hypotheses
airborne particle (PM2.5, PM10 and TPM) concentrations and Ultra Fine Particle
Facility 4).
airborne particle (PM2.5, PM10 and TPM) concentrations and UFP counts
airborne particle concentrations (PM2.5, PM10 and TPM) and UFP counts
evening activity).
1.5 Objectives
Identify four long term care facilities and conduct a walkthrough at each;
Perform air sampling for airborne particle (PM2.5, PM10 and TPM)
TPM) and UFP counts between Facilities, Sampling Locations and Sampling
Sessions;
4
Determine if indoor airborne particle concentrations (PM2.5, PM10 and TPM)
and UFP counts indoors are below outdoor concentrations and counts; and,
ASHRAE 2010.
5
Chapter 2
Literature Review
The EPA defines indoor air quality as “the air quality within and around buildings
and structures, especially as it relates to the health and comfort of building occupants”
(EPA, 2016a). Air quality testing in homes across the United States estimated that 96
percent of homes had at least one problem with IAQ. Up to 85 percent had high levels of
particulates and bioaerosols and up to 71 percent were filled with odors and potentially
The most important environment that relates to human health is the indoor
environment because people spend as much at 90 percent of their time indoors (Sundell,
2004). In addition, air pollutants inside are two to five times higher than outside and
sometimes as high as 100 times greater compared to outside air (Hess-Kosa, 2011; EPA,
can be harmful and/or directly or indirectly induce changes on health (Pecingina & Popa,
2014). According to the World Health Organization (WHO, 2016) polluted air is linked
6
even death. Poor air quality has been shown to exacerbate chronic respiratory diseases,
Over the past few decades there has been a decrease in outdoor pollution but an
increase in indoor pollution (Mendes et al., 2013). As people built shelters for living, they
also brought pollutants into their living space (Perez-Padilla, Schilmann, & Riojas-
Rodriguez, 2010). In the 1950’s, the focus on air quality became prominent in the United
States when dealing with industrial air pollution. In the 1960’s, the term environment
changed to a focus on ambient air and industrial surroundings. This caused a shift from
examining all air quality to IAQ. Awareness of IAQ became a concern in the 1970s after
the energy crisis. New requirements for buildings, such as insulated windows, caused
scientists began to understand that crowded buildings could be causing health problems.
Subsequently, the first ventilation standards were initiated (Lillard, 2005). Research is
lacking in the area of IAQ and the health impacts it has older adults, a vulnerable
IAQ problems arise from interactions between the building materials, activities
that occur in the building, climate and the building occupants (Kike-Parsis, 2004). These
problems may arise from inadequate temperature, poor ventilation systems, indoor air
contaminants, or from insufficient outdoor air intake (EPA, 2016a). In general, the types
of pollutants that may affect IAQ are biological, chemical, particles and aerosol
pollutants. Biological pollutants include bacteria, fungi, pollen, and animal dander.
emissions from floor or wall coverings. Particles and aerosols are solids and liquids
7
suspended in air, from dust, construction, smoking, or combustion (EPA, 2016b). For the
purposes of this study, the stressors discussed will include particulate matter, ultrafine
Particulate matter (PM) is a mixture of small particles and droplets in the air that
can cause health problems if inhaled. Some PM are visible while others are not, except
under a powerful electron microscope. The most common sizes are PM0.1 (< 0.1
micrometers), PM2.5 (< 2.5 micrometers), and PM10 (< 10 micrometers). Total particulate
matter (TPM) is all respirable particles. Smaller particles have the greatest health concern
because they can travel deep in the lungs and cause heart and lung disease (Oberdörster,
2000).
The populations most affected by PM exposure are people with lung disease,
children, and older adults (Liu, et al., 2008). Indoor particle events are elevated PM levels
for short periods of time usually caused by a source such as cooking. Particle events have
been associated with an increase in acute health outcomes (Long, Suh, & Koutrakis,
Ultrafine particles are particles that are less than 100 nanometers aerodynamic
diameter in size (Oberdörster, 2000). Ultrafine particles are much smaller than cellular
structures and have been associated with adverse health effects because of how deeply
they can penetrate the lungs (Oberdörster, 2000; Peters, et al., 1997).
8
2.3 Indoor PM Sources
addition, PM can be from general activities such as walking and flailing one’s arms,
which may recirculate particles (Long, Suh, & Koutrakis, 2000); Diapouli et al., 2011).
Research completed by Monn et al. (1997) showed that human activity accounted for
high indoor levels of PM and that cooking on a gas stove had the largest impact on
cooking, smoking or cleaning (Abt et al., 2000). The main source of UFPs is traffic
(Sajani et al., 2015). A tenfold increase in UFPs has been found with cooking (Wallace et
al., 2004). Higher concentrations have been observed during frying and lower during
boiling (Zhang, Ramirez, & Zhu, 2010). It has been suggested that peak concentrations of
UFPs may be more important for determining health effects than long-term average
concentrations (Garrett et al., 1998). It has been shown that outdoor-generated PM2.5 and
UFPs seem to penetrate indoors but PM10 does not (Diapouri et al., 2011). In the absence
maintaining good IAQ (Davis, et al., 2016). Thermal comfort is affected by air
9
and the rate of air exchange (Ormandy and Ezratty, 2012). Relative humidity (RH) is the
amount of water vapor that the air is holding compared to the amount it can hold at a
specific temperature (Spengler, Samet, & McCarthy, 2001). Temperature and RH have
been shown to increase concentrations of air pollutants because of the dense air holding
Health effects related to poor IAQ depend upon several factors: the effect of each
2010). Indoor air contaminants can cause acute or chronic health problems. Acute health
effects are usually from short-term exposure at higher concentrations, whereas chronic
health effects are often long-term exposure at lower concentrations (EPA, 2016c). Acute
health effects have been correlated with peak particle events (Long, Suh, & Koutrakis,
2000); Diapouli et al., 2011). Acute health concerns of exposure to PM are respiratory
issues such as wheezing and coughing (Bentayeb et al., 2015; Bentayeb et al., 2013; Maio
increased asthma and COPD (Bentayeb et al., 2013; Saldiva, et al., 2002; Curtis et al.,
2006). PM exposure has been linked to premature death in people with heart or lung
disease, heart attacks, a decrease in lung function, and irregular heartbeat (Bernstein et
al., 2008; Bentayeb et al., 2015; Curtis et al., 2006; Bentayeb et al., 2013). PM exposure
has been linked to an increase in hospital admissions (Bernstein, et al., 2008). Research
by Peters et al. (1997) showed that when there were high levels of UFPs people who had
asthma had a decrease in peak respiratory flow. Early signs of atherosclerosis and
10
systemic oxidative stress have also been associated with exposure to UFPs (Araujo et al.,
associated with an increased risk of coronary artery disease, asthma, and admissions to
the hospital for respiratory related illnesses (Dales, Liu, & Wheeler, 2008; Bentayeb et
al., 2008).
Aging may lead to a compromised immune system and decreased lung functions,
with a predisposition for respiratory infections. As people age, they also tend to have an
increased incidence of chronic respiratory diseases such as COPD and asthma. Older
adults are sensitive to short-term PM exposure with a higher risk of hospitalization and
death (EPA, 2017). One way to help with the control of these acute and chronic illnesses
is to better understand the health consequences associated with IAQ (Bentayeb, et al.,
2013).
temperature as well as younger, healthy adults and they can have difficulty controlling
body temperature. Older adults tend to prefer it warmer than other individuals, around
25C in the summer and 23C in the winter (Davis, McGregor, & Enfield, 2016). Older
adults also have decreased perspiration making it difficult to cool the body (Klenk,
Becker, & Rapp, 2010). Temperature and RH have been linked to several health issues
wheezing and an increase in hospital admissions among older adults (Davis, et al., 2016).
indoor environment. Ventilation is the process of supplying a building or room with fresh
11
air (EPA, 2016a). The purpose of ventilation in buildings is to provide healthy air by
diluting and removing pollutants from a building (Etheridge & Sandber, 1996). Elements
of building ventilation include ventilation rate and air flow direction and distribution. The
ventilation rate is the amount of outdoor air that is provided into a given area. Airflow
direction is the overall direction the air is flowing in the building, which should be from a
clean to a dirty environment. Air distribution ensures air is distributed evenly, instead of
into only one area (Atkinson, et al., 2009). According to the Occupational Safety and
Health Administration (OSHA), ventilation is the most important engineering control for
maintaining and improving IAQ. Inadequate ventilation and poor maintenance was the
main issue in over 50 percent of IAQ investigations conducted by the National Institute
for Occupational Safety and Health (NIOSH) (OSHA, 1999). Knowing and controlling
common indoor air pollutants can help decrease the risk of indoor health concerns (EPA,
2016a). Other methods of controlling IAQ are to eliminate the source of the pollution,
conserve energy, use energy efficient appliances, and choose environmentally friendly
There are few established national or mandatory limits for indoor air quality
has guidelines to help monitor and control a healthy living environment: Standard 55,
Thermal Environmental Conditions for Human Occupancy, and Standard 62, Ventilation
12
The purpose of ASHRAE Standard 55 is “to specify the combinations of indoor
space environment and personal factors that will produce thermal environmental
to 82F) in summer and 20 to 25.5C (68 to 78F) in winter. Clothing selection accounts for
ASHRAE Standard 62 recommends pollutants in indoor air should not exceed the
EPA’s National Ambient Air Quality Standards (NAAQS) levels. The NAAQS are used
to protect the public health from six criteria pollutants, including particulate matter (EPA,
2016a). This equates to a maximum exposure limit for PM10 of 0.15 mg/m3 for a 24-hour
mean. EPA NAAQS for PM2.5 is 35 μg/m3 for a 24-hour mean (EPA, 2016b).
Currently, there are no standards or guidelines for UFPs. While threshold limits
for UFPs are under discussion, a challenge is determining the appropriate exposure
(TLV), those are primarily intended for industrial environments (Burton, 2017). Over the
years, Burton has compiled data suggested by agencies or associations such as OSHA,
ASHRAE, NIOSH, WHO and EPA regarding “typical,” and “trigger” conditions. A
depending on professional judgement (Burton, 2017). The trigger condition for PM2.5 is
13
2.8 Long Term Care Environments
In many countries, the aging population is a major challenge. In 2014, older adults
over the age of 65 comprised 14.5 percent of the United States population (46.2 million
Americans), but are projected to more than double to 98 million in 2060 (Administration
on Aging, 2015). Population aging puts pressure on health systems, increasing the
demand for care, services and technologies to prevent and treat chronic conditions
associated with old age. Annually, 8,357,100 people receive support from five main long-
term care services; home health agencies (4,742,500), nursing homes (1,383,700),
hospices (1,244,500), residential care communities (713,300) and adult day service
centers (273,200) because of a chronic illness or disabling condition (CDC, 2013). The
average person spends up to 90 percent of their time indoors, but many older adults have
reduced outdoor activities and may spend more time indoors. As a result, they may
may impact indoor air quality in nursing homes and elderly care centers. Mendes et al.
(2014) completed a study examining how windows, walls and ceiling, type of ventilation,
air conditioner status, and roof lining affected PM, carbon dioxide, temperature, and RH
within elderly care centers. PM10 was affected by the types of window, sealants, and
types of window frames used. PM2.5 was affected by insulation, ventilation type, and
flooring. The number of building occupants, ventilation type, wall insulation type, roof
lining, window types and frames, glass type, and flooring affected temperature. Relative
humidity was affected by building occupancy, wall insulation, roof lining, ventilation
14
type, window types, and flooring. Overall the building design and occupancy greatly
Little research has been completed in regards to older adults and their exposure to
IAQ contaminants. The following section will discuss the indoor air quality research that
A pilot study done by Williams, Creason, Zweidinger et al. (2000) was conducted
Baltimore, MD. The elderly subjects were sedentary and spent 96 percent of their time
inside. Results suggested PM2.5 was the dominant outdoor size fraction. Findings
indicated elderly subjects were compliant with wearing personal samplers to measure PM
matter exposure with an elderly population. Part one examined daily 24-hour integrated
PM2.5 and PM10 from residential central indoor, individual apartment and residential
outdoor and ambient monitoring locations (Williams, Suggs, Zweidinger et al., 2000).
The average daily central indoor and individual apartment PM concentrations were
approximately 10 μg/m3. The mean outdoor and ambient PM2.5 concentrations were 22
outdoor PM penetration rather than typical generating activities such as cooking and
tobacco smoking.
15
Part two of the Baltimore study examined the variability of 24-hr personal PM
exposure among the elderly population (Williams, Suggs, Creason, et al., 2000). Subjects
reported spending 92 percent of their time within the retirement center, 76 percent in their
apartment and 16 percent inside other people’s apartments. The mean of the daily PM2.5
personal concentrations was 12.9 μg/m3. Residents rarely left these facilities because they
offered many internal amenities. This fact, along with the low activity level of the
A study done by Rhodes et al. (2001) evaluated personal PM2.5 and PM10
exposure and the indoor and outdoor concentrations at three different retirement centers
(one in Baltimore and two in Fresno) over winter and summer months. Overall, the levels
of PM2.5 and PM10 were lower inside compared to levels outside, suggesting the Heating,
Ventilation, and Air Conditioning (HVAC) system was effective in removing particles
from the environment. There were higher concentrations of PM10 indoors compared to
PM2.5. Higher concentrations of PM2.5 were found indoors during the summer, when the
windows were open. However, PM10 levels remained consistent throughout the seasons,
suggesting PM10 does not penetrate through open doors and windows. The most
activities such as cooking and walking on the carpet, the type of HVAC unit, and how
exposure to indoor air pollutants in living rooms and bedrooms in elderly care centers.
PM of different sizes (0.3-0.5, 0.5-1, 1-2.5, 2.5-5, and 5-10 µg), carbon monoxide and
carbon dioxide were evaluated. Residents spent approximately 95 percent of their time
16
indoors, with 57 percent in the bedroom and 30 percent in the living room. PM was
significantly higher in the living room compared to the bedroom. It was observed that
older adults performed more tasks that could promote the re-suspension of particles in the
living room. In addition, there were peaks in PM levels in the living room area during
meals. In general, there were higher levels of air contaminants during the winter
Mendes et al. (2014) examined indoor air pollutants, including PM2.5 and PM10,
conducted in the dining room, drawing room, medical offices, and bedrooms. PM2.5
exceeded EPA NAAQS standards in winter and summer. Among indoor areas, levels of
PM2.5 were highest in the drawing rooms and were affected by ventilation characteristics.
PM10 levels were higher in the dining room and the drawing room. PM10 was affected by
window characteristics, suggesting PM10 can enter the building more readily with open
independent ventilation system, the adjacent hallway and outside the building) within
three nursing homes were monitored for carbon monoxide, carbon dioxide, respirable
suspended particulate matter, nicotine and solanesol. Compared to the adjacent hallways
and outdoors, concentrations of air contaminants (except CO2) were significantly higher
17
Chapter 3
Methods
3.1 Overview
Air sampling was conducted at four long term care facilities in Ohio. The focus of
the air sampling was in the nursing home section of the care facilities. Two of the
facilities selected were older buildings, while two were newer buildings. The sampling
occurred in up to nine indoor Sampling Locations, one outdoor smoking location (if
present) and one outdoor Sampling Location for comparison purposes at each facility.
Measurements were collected during seven time periods (Sampling Sessions) throughout
the day, representing baseline and peak activities. Indoor and outdoor air was sampled for
particulate matter (PM2.5, PM10, and TPM), ultrafine particle counts, temperature and
Facilities, Sampling Locations and Sampling Sessions. Comparisons were made between
Particle concentrations at various sizes were measured using TSI DustTrak DRX
Aerosol Monitor (Model 8533); ultrafine particulate counts were measured with a TSI P-
18
Trak Ultrafine Particle Counter (Model 8525), and temperature and humidity were
measured using a TSI Q-Trak Indoor Air Quality Monitor (Model 7575 (TSI, Inc.,
Shoreview, MN).
The DustTrak DRX (Figure 3.1) simultaneously measures mass and size fraction
corresponding to PM2.5, PM10 and TPM. The instrument uses a 90º light scattering laser
photometer which provides the mass concentration of a photometer and size resolution of
an optical particle counter. The pump flow rate is 3.0 L/min with a flow accuracy of ±5%
of the factory set point, internal flow controlled. The aerosol concentration range is 0.001
to 150 mg/m3 and the particle size range is 0.1 to 15 µm. The resolution of the instrument
The TSI P-Trak Plus Model 8525 measured the number of ultrafine particles per
cubic centimeter of air (pt/cm3). An ultrafine particle has a diameter less than 0.1 µm.
The P-Trak provides one second averages of ultrafine particulate matter in pt/ cm3. The
P-Trak’s has a sampling range from 0 to 50,000 pt/cm3. The P-Trak is able to capture and
measure ultrafine particles ranging from 0.02μm - 1μm in aerodynamic diameter. The
19
flow rate for the unit is approximately 100 cm3/min. The unit uses an isopropyl alcohol
wick to grow UFP into larger, easier to count droplets. The instrument was zeroed prior
IAQ probe. Temperature was measured using a thermistor sensor with a range of 32 to
140°F (0 to 60°C). The accuracy was ±1.0°F (0.5°C) and the resolution was 0.1°F
(0.1°C). The response time was 30 seconds. Relative humidity was measured using a
thin-film capacitive sensor with a range of 5 to 95 percent. The accuracy was ±3%
relative humidity and the resolution was 0.1% relative humidity. The response time was
20 seconds. Both temperature and relative humidity affect PM. A dry environment may
allow for more re-suspension of PM and skin becomes drier, which may lead to more
PM.
20
Figure 3-3: TSI Q-Trak Plus Model 7575.
3.3 Facilities
Data were collected at four long term care facilities during fall of 2016. Data
collection occurred at each facility on two days during the week and one day on the
weekend, for a total of three days at each facility. All facilities were located in northwest
Ohio. Facility 1 was a two-story building constructed in 1992 and the nursing home had
32 beds. Data at Facility 1 were collected indoors on the second floor and outdoors at
ground level. Facility 2 was a one-story building constructed in 1966 with 54 beds in the
nursing home. Data at Facility 2 were collected on the first floor. Facility 3 was a two-
story building constructed in 1930, with 29 beds in the nursing home. Data at Facility 3
were collected on both the first and second floor indoors and on the ground level
outdoors. Facility 4 was a one-story building constructed in 2013 and the nursing home
had 60 beds. All indoor and outdoor data were collected on the first floor at Facility 4.
21
3.3.1 Sampling Locations
Each Facility was sampled on 3 separate days for a total of twelve sampling days.
There were multiple fixed Sampling Locations sampled throughout the facilities, nine
1. Activity Room: Art and crafts that occur in these rooms, such as ceramics,
5 percent of the residents’ time may be spent in the dining room areas
2012; Ozkaynak et al., 1996); PM2.5 and ultrafine particles are both
2004);
22
6. Satellite Kitchen: Although smaller in size, this location is believed to
have indoor air similar to the kitchen which may be elevated since cooking
al., 1996);
7. Community Space: Almost all of the residents’ time may be spent in the
9. Hair Salon: Reported to have high PM levels due to the use of hair
11. Outdoors: Research has shown that as the PM outside increases so does
Sampling times were selected in an attempt to collect data during potential high
activity and a time of minimal activity for the baseline. The seven time windows
23
1. Baseline: approximately 6:00-7:00 a.m.;
community spaces;
activities.
instructions. The DustTrak and P-Trak were zeroed using a zero filter before and after
each sampling event. All instruments were placed on a rolling cart at approximately
breathing height while sitting (3.5 feet). The inlets of all instruments were placed away
from all walls and corners and faced the center of the room where the occupants were
located during sample collection. Each instrument was programmed to collect a 2-minute
average sample, which were displayed on the screens of each instrument. The resulting
24
values were documented on a sampling form and saved in the instrument memory. One
form was used to document all sampling data including location, time, temperature,
the area, and activities being performed (cooking, eating, playing games) during sampling
was documented. Outdoor samples were taken outdoors away from doors or traffic. Any
dust or gravel from parking lots) were documented. Weather conditions were also
recorded.
each indoor location. Information collected included: physical description, primary use,
occupancy, square footage, flooring type, wall construction, number of windows, any
evidence of water damage and any odors. General information about the remodeling,
heating, ventilation and air conditioning at each facility was obtained from each facility
manager.
All data were downloaded and exported into excel from TrakPro, the TSI
instrument software. Data were merged into one SPSS file for analysis.
Sampling Session. The distribution of the particle data was not normally distributed and
this data was log transformed. Analysis of variance (ANOVA), a parametric test, was
25
used to determine whether there were any statistically significant differences between the
Session). The Tukey honestly significant difference (HSD) post hoc test, a conservative
Resulting data were compared to indoor air quality guidelines related to comfort
26
Chapter 4
Results
4.1. Overview
A total of four facilities were sampled three separate days over Fall of 2016. Up to
nine indoor locations were sampled, representing the various occupied spaces in each
nursing home. An Outdoor smoking location was sampled when available. An Outdoor
This chapter will present the results of the sampling, descriptive and statistical
tests by Facility, Sampling Location and Sampling Session. The particle, temperature and
relative humidity levels measured were all within the working range of associated
instruments. The distribution of the particle data was not normally distributed.
Descriptive data presents the median, minimum and maximum. Statistical tests were
in 2015. The facility was located in a suburban area away from major traffic. The nursing
home section was on the second floor with 32 beds. The nursing home was dry wall and
all rooms were carpeted except the kitchen (vinyl tile), rehab/exercise room (hardwood),
27
and hair salon (vinyl tile). The facility allowed pets; however, domesticated animals were
only present one day over one Sampling Session. The housekeeping schedule was 7:00
a.m. to 3:30 p.m. each day and included changing linens, vacuuming, washing dishes,
Facility 1 had twelve air handling units (AHUs) on the roof that operated
continuously. Associated filters are replaced quarterly. The nursing home recirculated air
in all areas except the satellite kitchen, which used 100 percent outside air (OA).
rehabilitation center was added in 2009. The facility was located in an urban area on a
busy street. The nursing home section had 54 beds. The entire nursing home section of
the facility was dry wall and the flooring was vinyl tile. The facility did not allow
resident pets. The housekeeping schedule was 7:00 a.m. to 4:00 p.m. each day and
included mopping, sweeping, changing linens, washing dishes, and cleaning the
bathrooms.
Facility 2 had 6 AHUs on the roof that were continuously operated using 100
percent OA. Associated pleated filters were changed monthly. A boiler system provided
heat at the facility and was operational during the last two days of sampling.
Facility 3 was a two-story building constructed in 1930. The facility was located
in a urban area away from major streets. The nursing home section was on the second
floor and had 29 beds, while the hair salon, activities room, rehab/exercise space, and
kitchen were located on the first floor. The nursing home section of the facility was dry
wall. Vinyl tile was present in the kitchen, hair salon, rehab/exercise room, and satellite
;kitchen; wood flooring was present in the activities room; while the remainder of the
28
facility was carpeted. Residents were permitted to have pets; however, none were present
during sampling. In addition, birds were present in a glass cage on the first floor and a
resident cat roamed the space on the first floor. The facility was cleaned each day by the
staff and included changing linens, vacuuming, washing dishes, sweeping, and cleaning
the bathrooms.
Facility 4 was a one-story building constructed in 2013 and the most recent
remodeling event occurred 2015. The facility was located in a rural area surrounded by
agricultural fields. There was a major highway less than a mile away from the facility.
The nursing home section had 60 beds. The facility had an open concept, with the
community space and dining room all in one shared space. Vaulted ceilings were present
in the shared open space. The entire facility was dry wall and carpeted except for the
kitchen. Although the facility does allow pets, none were present during sampling. The
housekeeping schedule was 7:00 a.m. to 3:30 p.m. each day and included changing
Facility 4 had 16 AHUs on the roof using 100 percent outside air. Associated
29
4.3. Descriptive Statistics All Indoor Locations by Facility
Table 4.1 shows the descriptive statistics for all indoor locations by Facility. The
number of sampling points by Facility ranged from 115 to 155. Differences in sampling
number were due to the number of indoor locations sampled and accessibility. The
temperature ranged from 64.3 to 80.9F in the four facilities, while relative humidity
ranged from 15.5 percent to 74.8 percent. The highest median count of ultrafine particles
(10,546 pt/cm3) was in Facility 2. The median concentration of particulate matter was
highest in Facility 2: PM2.5 (0.012 mg/m3), PM10 (0.013 mg/m3) and TPM (0.02 mg/m3).
30
Table 4.1: Descriptive Statistics All Indoor Locations by Facility
Descriptive statistics were calculated separately for each Sampling Location. The
median, minimum and maximum values for each location and all facilities are presented
in Table 4.2. The highest indoor median of ultrafine particles in all facilities was seen in
the Satellite Kitchen (14,101 pt/cm3; min-max 1,493-315,108 pt/cm3), followed by the
31
Community Space (9,099 pt/cm3; min-max 2,978-49,641 pt/cm3) and Hair Salon (8,711
pt/cm3; min-max 2,627-51,026 pt/cm3). The lowest indoor median UFP was seen in the
The Hair Salon had the highest indoor median concentration of PM2.5 (0.021
mg/m3; min-max 0.003-0.16 mg/m3), PM10 (0.024 mg/m3; min-max 0.006-0.403 mg/m3)
and TPM (0.032 mg/m3; min-max 0.010-0.595 mg/m3), followed by the Community
Space, PM2.5 (0.013 mg/m3; min-max 0.001-0.032 mg/m3), PM10 (0.016 mg/m3; min-max
0.001-0.04 mg/m3) and TPM (0.025 mg/m3; min-max 0.016-0.051 mg/m3). The
Rehab/Exercise Room had the lowest indoor median concentration of PM2.5 (0.005
mg/m3; min-max 0.001-0.025 mg/m3), PM10 (0.006 mg/m3; min-max 0.001-0.028 mg/m3)
and TPM (0.009 mg/m3; min-max 0.001-0.083 mg/m3). The Outdoor median
concentrations of PM2.5, PM10 and TPM were 0.011 mg/m3, 0.014 mg/m3, and 0.015
mg/m3 respectively, which were lower than the highest median indoor concentrations.
The indoor median temperature ranged from 73.3F in the kitchen to 77.2F in the
Community Space and the indoor median relative humidity ranged from 33.1 percent in
the Satellite Kitchen to 50.7 percent in the Community Space. The median Outdoor
temperature was 53.3F, while the median Outdoor relative humidity was 53.6 percent.
32
Table 4.2: Descriptive Statistics by Sampling Location, All Facilities
Rehab
Activity Private Dining Satellite Community Community Hair Outdoor
/Exercise Kitchen Outdoors
Room Room Room Kitchen Space Space 2 Salon Smoking
Room
n 63 73 78 83 63 62 83 20 27 82 42
UFP (pt/cc)
Median 2,421 2,529 2,603 4,764 5,234 14,101 3,413 9,099 8,711 5,167 5,547
Min 366 399 362 440 517 1,493 410 2,978 2,627 773 1,671
Max 18,807 57,945 17,099 93,790 314,083 315,108 75,521 49,641 51,026 66,849 39,739
PM2.5 (mg/m3)
Median 0.006 0.007 0.005 0.008 0.010 0.01 0.007 0.013 0.021 0.011 0.014
Min 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.006 0.003 0.001 0.001
Max 0.101 0.028 0.025 0.034 0.028 0.117 0.033 0.032 0.160 0.078 0.082
PM10 (mg/m3)
Median 0.010 0.010 0.006 0.010 0.011 0.012 0.009 0.016 0.024 0.014 0.016
Min 0.002 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.006 0.001 0.002
Max 0.142 0.037 0.028 0.038 0.039 0.162 0.038 0.040 0.403 0.126 0.100
TPM (mg/m3)
Median 0.016 0.016 0.009 0.015 0.015 0.014 0.014 0.025 0.032 0.015 0.018
Min 0.003 0.001 0.001 0.002 0.001 0.001 0.001 0.016 0.010 0.001 0.002
Max 0.153 0.052 0.053 0.051 0.068 0.169 0.046 0.051 0.595 0.129 0.102
Temperature (F)
Median 75.6 76.4 74.5 74.7 73.3 74.2 74.4 77.2 75.8 53.3 62.2
Min 69.9 69.9 69.6 70.1 69.2 64.3 71.2 76.5 71.9 29.3 26.8
Max 80.4 79.9 78.8 79.0 77.2 78.8 78.4 79.0 80.9 77.5 77.4
Relative Humidity (%)
Median 39.2 34.9 35.4 35.6 40.3 33.1 34.2 50.7 47.0 53.6 56.0
Min 16.6 16.3 15.5 18.3 22.1 19.2 17.7 39.2 25.7 27.6 40.5
Max 57.5 55.9 74.8 57.9 56.4 53.7 56.1 57.4 55.0 85.1 89.0
33
4.5. Descriptive Statistics by Sampling Location and Facility
Descriptive statistics were calculated by Sampling Location for each Facility. The
tables and figures by Sampling Location and Facility are summarized in Sections 4.5.1 to
4.5.4.
The median, minimum and maximum values for each Sampling Location at
Facility 1 are presented in Table 4.3. Figures 4-1 to 4-4 present boxplots graphically
illustrating the UFP counts and PM concentrations by Sampling Location for Facility 1.
Outliers are values that are 1.5 times the interquartile range and extreme values are values
that are 3 times the interquartile range. The number of sampling points by room ranged
The highest indoor median counts of ultrafine particles in Facility 1 were in the
Satellite Kitchen (12,663 pt/cm3; min-max 2,723-57,120 pt/cm3), followed by the Dining
Room (4,764 pt/cm3; min-max 440-93,970 pt/cm3) and Hair Salon (4,607 pt/cm3; min-
max 2,950-4,819 pt/cm3). The lowest indoor median count for ultrafine particles was in
the Private Room (1,781 pt/cm3; min-max 399-9,338 pt/cm3). The Outdoor median UFP
The Hair Salon had the highest indoor median concentrations of PM2.5 (0.026
mg/m3; min-max 0.025-0.16 mg/m3), PM10 (0.023 mg/m3; min-max 0.031-0.403 mg/m3)
and TPM (0.044 mg/m3; min-max 0.037-0.595 mg/m3), followed by the Satellite Kitchen,
PM2.5 (0.017 mg/m3; min-max 0.002-0.117 mg/m3), PM10 (0.021 mg/m3; min-max 0.002-
0.162 mg/m3) and TPM (0.023 mg/m3; min-max 0.002-0.169 mg/m3). The Activity
Room, Private Room, Rehab/Exercise Room and Community Space had the lowest
34
median concentration of PM2.5 (0.004 mg/m3; min-max 0.001-0.025 mg/m3). The
Rehab/Exercise Room and Community Space had the lowest median concentration of
PM10 (0.005 mg/m3; min-max 0.001-0.027 mg/m3), while the Rehab/Exercise Room had
the lowest median concentration of TPM (0.006 mg/m3; min-max 0.001-0.029 mg/m3).
mg/m3), PM10 (0.006 mg/m3; min-max 0.002-0.031 mg/m3) and TPM (0.006 mg/m3; min-
max 0.002-0.033 mg/m3) were lower than the highest and lowest median indoor
concentrations at Facility 1.
The indoor median temperature at Facility 1 ranged from 73.5F in the Satellite
Kitchen to 80.1F in the Hair Salon. The indoor median relative humidity ranged from
34.2 percent in the Activity Room to 51.7 percent in the Hair Salon. The median Outdoor
temperature was 50.1F, while the median Outdoor relative humidity was 61.4 percent.
35
Table 4.3: Descriptive Statistics by Sampling Location, Facility 1
Rehab/
Activity Private Dining Satellite Community Outdoor
Exercise Hair Salon Outdoors
Room Room Room Kitchen Space Smoking
Room
n 21 21 21 21 20 21 3 21 21
UFP (pt/cm3)
Median 1654 1781 3254 4764 12663 2521 4607 3628 5203
Min 366 399 362 440 2723 410 2950 1656 2215
Max 9084 9338 12271 93790 57120 42852 4819 7354 15829
PM2.5 (mg/m3)
Median 0.004 0.004 0.004 0.006 0.017 0.004 0.026 0.003 0.004
Min 0.001 0.001 0.001 0.001 0.002 0.001 0.025 0.001 0.001
Max 0.015 0.015 0.025 0.034 0.117 0.017 0.16 0.029 0.025
PM10 (mg/m3)
Median 0.008 0.006 0.005 0.008 0.021 0.005 0.032 0.006 0.005
Min 0.003 0.001 0.001 0.001 0.002 0.001 0.031 0.002 0.002
Max 0.019 0.023 0.027 0.038 0.162 0.018 0.403 0.031 0.029
TPM (mg/m3)
Median 0.018 0.012 0.009 0.018 0.023 0.012 0.044 0.006 0.006
Min 0.009 0.001 0.001 0.002 0.002 0.001 0.037 0.002 0.002
Max 0.038 0.038 0.029 0.051 0.169 0.024 0.595 0.033 0.032
Temperature (F)
Median 77.1 77.3 76.1 76.1 73.5 75.8 80.1 50.1 49.0
Min 72.9 72.7 72.1 72.6 64.3 71.2 79.3 29.3 26.8
Max 80.4 79.8 78.8 78.6 76.1 78.4 80.9 74.0 76.4
Relative Humidity (%)
Median 34.2 34.3 35.0 34.8 42.4 36.1 51.7 61.4 61.2
Min 16.6 17.1 15.5 18.3 19.2 17.7 51.1 27.6 40.5
Max 50.8 50.0 48.9 50.5 52.8 54.4 52.5 85.1 89.0
36
o
= outliers; * = extreme values
37
o
= outliers; * = extreme values
38
o
= outliers; * = extreme values
39
o
= outliers; * = extreme values
40
4.5.2. Descriptive Statistics by Sampling Location, Facility 2
The median, minimum and maximum values for each Sampling Location at
Facility 2 are presented in Table 4.4. Figures 4.5 to 4.8 graphically illustrate UFP counts
The highest indoor median UFP count in Facility 2 was in the Kitchen (70,790
pt/cm3; min-max 5,466-314,083 pt/cm3) followed by the Dining Room (16,647 pt/cc;
min-max 5,063-89,107 pt/cm3). The lowest indoor UFP was in the Rehab/Exercise Room
(2,294 pt/cm3; min-max 1,186-17,099 pt/cm3). The Outdoor median UFP was 6,369
pt/cm3.
The Hair Salon had the highest indoor median concentration of PM2.5 (0.021
mg/m3; min-max 0.009-0.056 mg/m3), PM10 (0.024 mg/m3; 0.011-0.120 mg/m3) and
TPM (0.03 mg/m3; min-max 0.014-0.188 mg/m3), followed by the Kitchen and
Space for PM10 (0.016 mg/m3; min-max 0.001-0.040 mg/m3) and Community Space for
TPM (0.025 mg/m3; min-max 0.016-0.051 mg/m3). The Rehab/Exercise Room had the
mg/m3), PM10 (0.006 mg/m3; min-max 0.005-0.015 mg/m3), and TPM (0.009 mg/m3;
min-max 0.005-0.029 mg/m3). The outdoor median concentrations of PM2.5, PM10 and
TPM were 0.014 mg/m3, 0.015 mg/m3, and 0.016 mg/m3 respectively, which were lower
The indoor median temperature ranged from 72.8F in the kitchen to 77.2F in
Community Space and the indoor median relative humidity ranged from 47.4 percent in
41
the Dining Room to 50.8 percent in the Private Room. The median Outdoor temperature
was 65.5F, while the median Outdoor relative humidity was 54.0 percent.
42
Table 4.4: Descriptive Statistics by Sampling Location, Facility 2
Rehab/
Activity Private Dining Community Community Outdoor
Exercise Kitchen Hair Salon Outdoors
Room Room Room Space 1 Space 2 Smoking
Room
n 21 19 20 21 21 20 20 12 21 21
UFP (pt/cm3)
Median 4794 10645 2294 16647 70790 16298 9099 13395 6369 6543
Min 2320 2721 1186 5063 5466 5020 2978 4016 1714 1671
Max 18807 57945 17099 89107 314083 75521 49641 51026 10403 39739
PM2.5 (mg/m3)
Median 0.010 0.011 0.005 0.012 0.013 0.013 0.013 0.021 0.014 0.017
Min 0.005 0.006 0.003 0.008 0.007 0.006 0.006 0.009 0.003 0.002
Max 0.101 0.028 0.013 0.033 0.028 0.033 0.032 0.056 0.033 0.082
PM10 (mg/m3)
Median 0.011 0.013 0.006 0.014 0.015 0.015 0.016 0.024 0.015 0.018
Min 0.006 0.009 0.005 0.009 0.008 0.006 0.001 0.011 0.005 0.004
Max 0.142 0.037 0.015 0.035 0.039 0.038 0.040 0.120 0.041 0.100
TPM (mg/m3)
Median 0.019 0.020 0.009 0.020 0.020 0.020 0.025 0.030 0.016 0.019
Min 0.011 0.012 0.005 0.009 0.010 0.008 0.016 0.014 0.005 0.004
Max 0.153 0.047 0.029 0.038 0.068 0.046 0.051 0.188 0.049 0.102
Temperature (F)
Median 75.8 76.0 75.0 75.0 72.8 74.0 77.2 76.0 65.5 67.0
Min 72.5 74.7 69.6 71.7 70.6 71.2 76.5 75.6 44.6 48.3
Max 76.9 77.0 76.5 77.5 74.7 75.3 79.0 78.2 77.5 77.4
Relative Humidity (%)
Median 48.7 50.8 50.7 47.4 50.4 49.0 50.7 48.5 54.0 49.0
Min 43.1 36.3 40.6 37.1 40.3 38.5 39.2 39.5 38.7 42.7
Max 57.5 55.9 74.8 57.9 56.4 56.1 57.4 55.0 74.7 69.8
43
o
= outliers; * = extreme values
44
o
= outliers; * = extreme values
45
o
= outliers; * = extreme values
46
o
= outliers; * = extreme values
47
4.5.3. Descriptive Statistics by Sampling Location, Facility 3
The median, minimum and maximum values for each Sampling Location at
Facility 3 are presented in Table 4.5. Figures 4.9 to 4.12 present boxplots graphically
The highest indoor median UFP count in Facility 3 was in the Satellite Kitchen
(8,525 pt/cm3; min-max 1,493-315,108 pt/cm3), followed by the Dining Room (3,148
pt/cm3; min-max 1,387-88,232 pt/cm3). The lowest indoor median UFP was in the Private
Room (2,330 pt/cm3; min-max 798-4,251 pt/cm3). The Outdoor UFP was 6,840 pt/cm3.
The Hair Salon had the highest median concentration of PM2.5 (0.020 mg/m3; min-
max 0.003-0.055 mg/m3), PM10 (0.023 mg/m3; min-max 0.006-0.105 mg/m3) and TPM
(0.039 mg/m3; min-max 0.010-0.188 mg/m3) followed by the Satellite Kitchen: PM2.5
(0.011 mg/m3; min-max 0.003-0.033 mg/m3), PM10 (0.014 mg/m3; min-max 0.004-0.042
mg/m3) and TPM (0.016 mg/m3; min-max 0.004-0.051 mg/m3). The Rehab/Exercise
Room had the lowest median concentration of PM2.5 (0.003 mg/m3; min-max 0.002-0.025
mg/m3), PM10 (0.004 mg/m3; min-max 0.002-0.028 mg/m3), and TPM (0.005 mg/m3;
min-max 0.002-0.035 mg/m3). The outdoor median concentrations of PM2.5, PM10 and
TPM were 0.007 mg/m3, 0.009 mg/m3, and 0.010 mg/m3 respectively.
The indoor median temperature ranged from 72.6F in the Activity Room to 77.2F
in the Private Room. The indoor median relative humidity ranged from 21.0 percent in
the Rehab/Exercise Room to 37.2 percent in the Hair Salon. The median Outdoor
temperature was 53.3F, while the median Outdoor relative humidity was 47.0 percent.
48
Table 4.5: Descriptive Statistics by Sampling Location, Facility 3
Rehab/
Activity Private Dining Satellite Community
Exercise Kitchen Hair Salon Outdoors
Room Room Room Kitchen Space
Room
n 21 20 21 21 21 21 21 9 21
UFP (pt/cm3)
Median 2384 2330 2395 3148 2957 8525 2499 7359 6840
Min 892 798 625 1387 1309 1493 992 2627 2996
Max 9509 4251 8283 88232 47826 315108 9215 29661 66849
PM2.5 (mg/m3)
Median 0.004 0.006 0.003 0.005 0.008 0.011 0.005 0.020 0.007
Min 0.002 0.002 0.002 0.002 0.002 0.003 0.002 0.003 0.003
Max 0.019 0.026 0.025 0.028 0.027 0.033 0.025 0.055 0.049
PM10 (mg/m3)
Median 0.006 0.010 0.004 0.008 0.011 0.014 0.007 0.023 0.009
Min 0.002 0.004 0.002 0.003 0.003 0.004 0.004 0.006 0.004
Max 0.021 0.031 0.028 0.030 0.028 0.042 0.026 0.105 0.054
TPM (mg/m3)
Median 0.008 0.018 0.005 0.013 0.013 0.016 0.013 0.039 0.010
Min 0.003 0.007 0.002 0.005 0.004 0.004 0.007 0.010 0.004
Max 0.035 0.052 0.035 0.033 0.039 0.051 0.035 0.188 0.057
Temperature (F)
Median 72.6 77.2 74.1 74.8 73.6 74.0 75.3 73.6 53.3
Min 69.9 73.8 71.0 71.1 69.2 70.9 72.2 71.9 32.0
Max 75.6 79.9 75.5 77.9 77.2 78.8 77.9 74.6 62.8
Relative Humidity (%)
Median 24.3 22.4 21.0 29.6 36.1 31.0 25.1 37.2 47.0
Min 19.1 16.3 15.9 18.4 22.8 24.0 18.2 25.7 27.7
Max 49.8 46.2 50.2 54.7 55.1 53.7 47.0 49.5 70.4
49
o
= outliers; * = extreme values
50
o
= outliers; * = extreme values
51
o
= outliers; * = extreme values
52
o
= outliers; * = extreme values
53
4.5.4. Descriptive Statics by Sampling Location, Facility 4
The median, minimum and maximum values for each Sampling Location at
Facility 4 are presented in Table 4.6. Figures 4.13 to 4.16 present boxplots that
graphically illustrate UFP counts and PM concentrations by location for Facility 4. The
The highest indoor median UFP in Facility 4 was in the Satellite Kitchen (20,706
pt/cm3; min-max 524-5,792 pt/cm3) and Kitchen (3,847 pt/cm3; min-max 517-56,937
pt/cm3). The lowest indoor median UFP was in the Private Room (2,142 pt/cm3; min-max
The Hair Salon had the highest indoor median concentration of PM2.5 (0.015
mg/m3; min-max 0.015-0.027 mg/m3), PM10 (0.018 mg/m3; min-max 0.015-0.033 mg/m3)
and TPM (0.022 mg/m3; min-max 0.018-0.066 mg/m3), followed by the Rehab/Exercise
Room, PM2.5 (0.010 mg/m3; min-max 0.001-0.020 mg/m3), PM10 (0.018 mg/m3; min-max
0.001-0.022 mg/m3) and TPM (0.022 mg/m3; min-max 0.001-0.053 mg/m3). The Satellite
Kitchen and Community Space had the lowest indoor median concentration of PM2.5
(0.007 mg/m3; min-max 0.001-0.026 mg/m3), the Community Space had the lowest
median concentration of PM10 (0.007 mg/m3 min-max 0.001-0.016 mg/m3), and the
Satellite Kitchen had the lowest median concentration of TPM (0.005 mg/m3; min-max
0.001-0.028 mg/m3). The outdoor median concentrations of PM2.5, PM10 and TPM were
The indoor median temperature ranged from 71.6 F in the Private Room to 74.5F
in the Satellite Kitchen. The indoor median relative humidity ranged from 24.5 percent in
54
the Community Space to 39.1 percent in the Hair Salon. The median Outdoor
temperature was 46.8F, while the median Outdoor relative humidity was 52.3 percent.
55
Table 4.6: Descriptive Statistics by Sampling Location, Facility 4
Rehab /
Private Dining Satellite Community
Exercise Kitchen Hair Salon Outdoors
Room Room Kitchen Space
Room
n 13 16 20 21 21 21 3 19
UFP (pt/cm3)
Median 2142 4312 3758 3847 20706 3718 3321 4573
Min 420 524 519 517 3742 622 2822 773
Max 7478 5792 6284 56937 222691 38734 8711 11041
PM2.5 (mg/m3)
Median 0.008 0.010 0.008 0.008 0.007 0.007 0.015 0.015
Min 0.001 0.001 0.001 0.001 0.001 0.001 0.015 0.001
Max 0.020 0.020 0.015 0.022 0.026 0.016 0.027 0.078
PM10 (mg/m3)
Median 0.008 0.011 0.008 0.009 0.008 0.007 0.018 0.015
Min 0.001 0.001 0.001 0.001 0.001 0.001 0.015 0.001
Max 0.023 0.022 0.016 0.028 0.027 0.016 0.033 0.126
TPM (mg/m3)
Median 0.013 0.019 0.011 0.014 0.010 0.011 0.022 0.016
Min 0.003 0.001 0.002 0.001 0.001 0.002 0.018 0.001
Max 0.043 0.053 0.031 0.034 0.028 0.018 0.066 0.129
Temperature (F)
Median 71.6 73.0 72.5 73.3 74.5 73.4 72.8 46.8
Min 69.9 72.6 70.1 70.8 73.2 72.1 72.8 36.7
Max 73.9 73.9 79.0 74.6 76.9 73.9 72.9 60.1
Relative Humidity (%)
Median 27.5 25.1 26.2 26.1 28.5 24.5 39.1 52.3
Min 24.0 21.6 22.3 22.1 23.7 19.5 38.5 29.5
Max 42.3 38.8 43.4 41.1 40.8 38.2 39.1 77.5
56
o
= outliers; * = extreme values
57
o
= outliers; * = extreme values
58
o
= outliers; * = extreme values
59
o
= outliers; * = extreme values
60
4.5.5. Comparison by Sampling Location and Facility
Figures comparing the median particulate matter by Sampling Location for each
Facility are presented in Figures 4.17 to 4.20. In general, the median UFPs were highest
in Facility 2, with the highest counts being in the Kitchen or Satellite Kitchen in each
Facility. In all four Facilities, indoor PM2.5, PM10, and TPM were highest in the Hair
61
Figure 4-17: Ultrafine Particle (pt/cm3) by Sampling Location and Facility
62
Figure 4-18: PM2.5 Concentrations (mg/m3) by Sampling Location and Facility
63
Figure 4-19: PM10 Concentrations (mg/m3) by Sampling Location and Facility
64
Figure 4-20: TPM Concentrations (mg/m3) by Sampling Location and Facility
65
4.6. Descriptive Statistics by Sampling Session
A total of seven Sessions were sampled daily at each Facility and Sampling
Session 1: baseline;
Session 5: mid-afternoon;
The indoor median, minimum and maximum values for each Sampling Session,
all Facilities are presented in Table 4.7. At all Facilities, Session 1, the baseline, had the
lowest median concentrations across all particulate sizes. Indoor median UFP counts
were lowest in Sampling Session 1 (2,934 pt/cm3; min-max 362-264,716 pt/cm3) and
Sampling Session 1: PM2.5 0.007 mg/m3 (min-max 0.001-0.024 mg/m3); PM10 0.008
mg/m3 (min-max 0.001-0.026 mg/m3); and TPM 0.013 mg/m3 (min-max 0.001-0.039
mg/m3). The highest indoor median particle concentrations for PM2.5 were during
Sampling Session 6 (0.01 mg/m3; min-max 0.001-0.16 mg/m3); PM10 during Sampling
Session 5 (0.013 mg/m3; min-max 0.001-0.118 mg/m3); and, TPM during Sampling
66
The median indoor temperature was lowest during Sampling Session 1 (73.6F)
and highest during Sampling Session 7 (75.2F). The median indoor relative humidity was
The indoor median, minimum and maximum values for each Sampling Session, at
Facility 1 are presented in Table 4.8. Session 1, the baseline, had the lowest median
concentrations across all particulate sizes. Indoor median UFP counts were lowest in
Sampling Session 1 (1,756 pt/cm3; min-max 362-14,627 pt/cm3) and highest in Sampling
67
The lowest indoor median concentrations of particulate matter were during
0.004mg/m3 (min-max 0.001-0.015 mg/m3); and TPM 0.007 mg/m3 (min-max 0.001-
0.038 mg/m3). The highest indoor median particle concentrations for PM2.5 were during
Sampling Session 5 (0.007 mg/m3; min-max 0.001-0.077 mg/m3); PM10 during Sampling
Session 5 (0.011 mg/m3; min-max 0.002-0.118 mg/m3); and, TPM during Sampling
The median indoor temperature was lowest during Sampling Session 1 (75.5F)
and highest during Sampling Session 5 (76.8F). The median indoor relative humidity was
Table 4.8: Descriptive Statistics, All Indoor Locations by Sampling Session, Facility 1
68
4.6.3. Descriptive Statistics by Sampling Session, Facility 2
The indoor median, minimum and maximum values for each Sampling Session, at
Facility 2 are presented in Table 4.9. Indoor median UFP counts were lowest in Sampling
The lowest indoor median concentrations of PM2.5 (0.011 mg/m3; min-max 0.005-
0.024 mg/m3) and PM10 (0.013 mg/m3; min-max 0.005-0.026 mg/m3) were seen during
Sampling Sessions 1, 3, and 4, while the lowest indoor median TPM was during
Sampling Session 1 at 0.017 mg/m3 (min-max 0.005-0.032 mg/m3). The highest indoor
median particle concentrations were observed during Sampling Session 6 for all particles
sizes: PM2.5 (0.019 mg/m3; min-max 0.004-0.101 mg/m3); PM10 (0.022 mg/m3; min-max
The median indoor temperature was lowest during Sampling Session 1 (74.4F)
and highest during Sampling Session 7 (76.4F). The median indoor relative humidity was
69
Table 4.9: Descriptive Statistics, All Indoor Locations by Sampling Session, Facility 2
Session 1 Session 2 Session 3 Session 4 Session 5 Session 6 Session 7
n 20 22 21 23 23 23 22
UFP (pt/cm3)
Median 6276 11887 8144 10569 9298 15871 12452
Min 2300 1536 1602 1186 1537 1346 1588
Max 264716 89107 263316 195100 314083 233300 86127
PM2.5 (mg/m3)
Median 0.011 0.012 0.011 0.011 0.014 0.019 0.012
Min 0.005 0.003 0.004 0.004 0.004 0.004 0.005
Max 0.024 0.022 0.024 0.024 0.086 0.101 0.056
PM10 (mg/m3)
Median 0.013 0.013 0.013 0.013 0.018 0.022 0.014
Min 0.005 0.005 0.005 0.005 0.001 0.005 0.006
Max 0.026 0.029 0.027 0.039 0.092 0.142 0.12
TPM (mg/m3)
Median 0.017 0.02 0.02 0.019 0.02 0.031 0.019
Min 0.005 0.006 0.008 0.008 0.005 0.007 0.007
Max 0.032 0.04 0.035 0.068 0.097 0.153 0.188
Temperature (F)
Median 74.4 75.2 74.7 75.2 75.3 75.9 76.4
Min 69.6 72.1 71.2 71.3 71.8 71.6 71.3
Max 77.4 77.5 77.2 77.5 79 78.1 78.2
Relative Humidity (%)
Median 50.5 51.8 52.3 49.5 49.2 48.7 48.2
Min 36.3 37.1 38.4 39.5 41.4 41.8 41.1
Max 74.8 56.2 55.2 53.7 56.4 52.8 54
The indoor median, minimum and maximum values for each Sampling Session, at
Facility 3 are presented in Table 4.10. Indoor median UFP counts were lowest during
Sampling Session 4 (1,955 pt/cm3; min-max 625-53,268 pt/cm3) and highest in Sampling
Sampling Session 1: PM2.5 0.003 mg/m3 (min-max 0.002-0.023 mg/m3); PM10 0.005
mg/m3 (min-max 0.002-0.024 mg/m3); and TPM 0.007 mg/m3 (min-max 0.003-0.039
mg/m3). The highest indoor median particle concentrations were observed during
Sampling Session 3 for all particles sizes: PM2.5 (0.009 mg/m3; min-max 0.002-0.03
70
mg/m3); PM10 (0.013 mg/m3; min-max 0.003-0.042 mg/m3); and, TPM (0.021 mg/m3;
The median indoor temperature was lowest during Sampling Session 1 (73.1F)
and highest during Sampling Sessions 6 and 7 (74.8F). The median indoor relative
humidity was lowest in Session 7 (24.0 percent) and highest in Session 1 (32.6 percent).
Table 4.10: Descriptive Statistics, All Indoor Locations by Sampling Session, Facility 3
The indoor median, minimum and maximum values for each Sampling Session, at
Facility 4 are presented in Table 4.15. Indoor UFP median counts were lowest in
71
The lowest indoor median concentrations of particulate matter were during
Sampling Session 7: PM2.5 0.005 mg/m3 (min-max 0.001-0.02 mg/m3); PM10 0.007
mg/m3 (min-max 0.001-0.02 mg/m3); and TPM 0.009 mg/m3 (min-max 0.002-0.025
mg/m3). The highest indoor median particle concentrations were observed during
Sampling Session 5 for all particles sizes: PM2.5 (0.012 mg/m3; min-max 0.001-0.027
mg/m3); PM10 (0.014 mg/m3; min-max 0.001-0.033 mg/m3; and, TPM (0.016 mg/m3;
The median indoor temperature was lowest during Sampling Session 1 (72.1F)
and highest during Sampling Sessions 4-6 (73.4F). The median indoor relative humidity
was lowest in Session 3 (25.5 percent) and highest in Session 5 (31.4 percent).
Table 4.11: Descriptive Statistics, All Indoor Locations by Sampling Session, Facility 4
72
Figures 4.21 to 4.24 present the particulate matter by Facility for all indoor
locations over the Sampling Sessions. The UFPs were highest at Facility 2 over all
Sampling Sessions. In general, all PM sizes were higher at Facility 2, over all Sampling
Sessions. Facilities 1-3 generally start with the lowest UFP counts and PM values with
73
Figure 4.21: Median Ultrafine Particles (pt/cm3) by Sampling Session and Facility
74
Figure 4.22: Median PM2.5 Concentration (mg/m3) by Sampling Session and Facility
75
Figure 4.23: Median PM10 Concentration (mg/m3) by Sampling Session and Facility
76
Figure 4.24: Median TPM Concentration (mg/m3) by Sampling Session and Facility
77
4.7. ANOVA by Facility
The distribution of the particle data was not normally distributed and the data
were log transformed. While the Shapiro-Wilk test suggested the transformed data were
not normally distributed, the standard deviation of the data was less than half of the
mean. As such, the transformed data were analyzed by parametric statistics. An alpha of
Table 4.12 shows the results of the ANOVA by Facility. There was a statistically
significant difference between facilities for UFP (p<0.001), PM2.5 (p<0.001), PM10
(p<0.001) and TPM (p<0.001). Therefore, for each of the particle sizes, at least two of
Tukey post hoc was performed to identify pairwise differences by Facility for
UFP and PM. Table 4.13 presents the Tukey post hoc between Facilities. Facility 2 was
significantly different from Facility 1, Facility 3 and Facility 4 for UFPs and all PM sizes.
78
Table 4.13: Tukey by Facility
The following sections present the results of ANOVA by Sampling Locations and
Facilities.
Table 4.14 shows the results of the ANOVA by Sampling Location at all
all Facilities for UFP (p<0.001), PM2.5 (p<0.001), PM10 (p<0.001) and TPM (p<0.001).
Therefore, for each of the particle sizes at least two of the Sampling Locations at all
Tukey post hoc was performed to identify pairwise differences by Facility for
UFP and PM. Table 4.15 presents the Tukey post hoc by Sampling Location at all
Facilities. In general, many significant pairwise differences were found between indoor
locations and the Hair Salon for PM. In addition, the Rehab/Exercise space was
79
significantly different from Community Space 2 for all PM sizes. UFPs had the most
80
Table 4.15: Tukey by Sampling Location, All Facilities (continued)
Table 4.16 shows the results of the ANOVA by Sampling Location at Facility 1.
for UFP (p<0.001), PM2.5 (p<0.001), PM10 (p<0.001) and TPM (p<0.001). Therefore, for
each of the particle sizes at least two of the Sampling Locations at Facility 1 were
Table 4.17 presents the Tukey post hoc by Sampling Location at Facility 1. In
general, many significant pairwise differences were found between indoor locations and
81
the Hair Salon and indoor locations and the Satellite Kitchens for PM. UFPs
demonstrated significant differences between indoor locations and the Satellite Kitchen
and the Activity Room and Private Room compared to the Dining Room.
82
4.8.3. ANOVA by Location, Facility 2
Table 4.18 shows the results of the ANOVA by Sampling Location at Facility 2.
for UFP (p<0.001), PM2.5 (p<0.001), PM10 (p<0.001) and TPM (p<0.001). Therefore, for
each of the particle sizes at least two of the Sampling Locations at Facility 2 were
Table 4.19 presents the Tukey post hoc by Sampling Location at Facility 2. In
general, significant pairwise differences for PM were found between all indoor locations
and the Rehab/Exercise Room. UFP had the most pair wise differences by location.
83
Table 4.19: Tukey by Sampling Location, Facility 2
84
4.8.4. ANOVA by Location, Facility 3
Table 4.20 shows the results of the ANOVA by Sampling Location at Facility 3.
for UFP (p<0.001), PM2.5 (p<0.001), PM10 (p<0.001) and TPM (p<0.001). Therefore, for
each of the particle sizes at least two of the Sampling Locations at Facility 3 were
Table 4.21 presents the Tukey post hoc by Sampling Location at Facility 3. In
general, many significant pairwise differences were found between indoor locations and
the Hair Salon at Facility 3. UFPs showed significant differences between the Satellite
Kitchen and all other indoor locations except the Hair Salon, as well as, the Activity
Room, Private Room and Rehab/Exercise Room and the Hair Salon.
85
Table 4.21: Tukey by Sampling Location, Facility 3
86
4.8.5. ANOVA by Location, Facility 4
Table 4.22 presents the results of the ANOVA by Sampling Location for Facility
4. There was a statistically significant difference for UFP (p<0.001) and PM2.5 (p=0.032).
Table 4.23 presents the Tukey post hoc by Sampling Location at Facility 4 for
UFP and PM2.5. Significant pairwise differences were found between indoor locations
and the Satellite Kitchen at Facility 4. Although a significant difference was indicated by
ANOVA for PM2.5, no pairwise differences were found by Tukey post hoc test.
87
Table 4.23: Tukey by Sampling Location, Facility 4
UFP PM2.5
Location 1 Location 2 (pt/cm3) (mg/m3)
p-value p-value
Rehab/Exercise Room 0.968 0.929
Dining Room 0.978 1.000
Kitchen 0.693 1.000
Private Room Satellite Kitchen <0.001 1.000
Community Space 0.877 0.995
Hair Salon 0.927 0.750
Outdoors 0.802 0.598
Dining Room 1.000 0.776
Kitchen 0.998 0.799
Satellite Kitchen <0.001 0.537
Rehab/Exercise Room
Community Space 1.000 0.387
Hair Salon 0.999 0.988
Outdoors 1.000 0.999
Kitchen 0.993 1.000
Satellite Kitchen <0.001 1.000
Dining Room Community Space 1.000 0.999
Hair Salon 0.997 0.633
Outdoors 0.999 0.319
Satellite Kitchen <0.001 1.000
Community Space 1.000 0.997
Kitchen
Hair Salon 1.000 0.653
Outdoors 1.000 0.332
Community Space <0.001 1.000
Satellite Kitchen Hair Salon 0.051 0.500
Outdoors <0.001 0.139
Hair Salon 1.000 0.413
Community Space
Outdoors 1.000 0.080
Hair Salon Outdoors 1.000 0.999
Bold=statistically significant
Table 4.24 shows the results of the ANOVA by Sampling Session for all
Facilities. Statistically significant differences were found for ultrafine particles (p=0.015)
88
and TPM (p=0.007) which indicates at least two of the Sampling Sessions were
Table 4.25 presents the Tukey post hoc by Sampling Session at all Facilities for
UFP and TPM. Significant pairwise differences were found between Sampling Session 1
and Sampling Session 2 (p=0.003) for UFPs and Sampling Session 1 and Sampling
89
Table 4.25: Tukey by Sampling Session, All Facilities
UFP TPM
Location 1 Location 2 pt/cm3 mg/m3
p-value p-value
Session 2 0.003 0.142
Session 3 0.191 0.008
Session 4 0.716 0.540
Session 1
Session 5 0.651 0.009
Session 6 0.446 0.037
Session 7 0.584 0.334
Session 3 0.767 0.951
Session 4 0.198 0.986
Session 2 Session 5 0.256 0.956
Session 6 0.448 0.998
Session 7 0.339 1.000
Session 4 0.968 0.544
Session 5 0.984 1.000
Session 3
Session 6 0.999 0.999
Session 7 0.994 0.798
Session 5 1.000 0.558
Session 4 Session 6 0.999 0.840
Session 7 1.000 1.000
Session 6 1.000 0.999
Session 5
Session 7 1.000 0.810
Session 6 Session 7 1.000 0.967
Bold=statistically significant
Table 4.26 shows the results of the ANOVA by Sampling Session and Facility.
There was a statistically significant difference between Sampling Sessions for UFP at
90
Table 4.26: ANOVA by Sampling Session Facilities 1-4
Table 4.27 presents the Tukey post hoc by Sampling Session at Facility 1 for
UFP. Significant pairwise differences were found between Sampling Session 1 and
UFP
Location 1 Location 2 pt/cm3
p-value
Session 2 <0.001
Session 3 0.001
Session 4 0.101
Session 1
Session 5 0.262
Session 6 0.359
Session 7 0.137
Session 3 0.992
Session 4 0.230
Session 2 Session 5 0.071
Session 6 0.044
Session 7 0.153
Session 4 0.653
Session 5 0.330
Session 3
Session 6 0.236
Session 7 0.528
Session 5 0.999
Session 4 Session 6 0.994
Session 7 1.000
Session 6 1.000
Session 5
Session 7 1.000
Session 6 Session 7 0.999
Bold=statistically significant
91
Table 4.28 presents the Tukey post hoc by Sampling Session at Facility 2 for
PM2.5. No significant pairwise differences were found between Sampling Sessions using
Tukey.
PM2.5
Location 1 Location 2 mg/m3
p-value
Session 2 0.999
Session 3 0.999
Session 4 1.000
Session 1
Session 5 0.950
Session 6 0.260
Session 7 0.866
Session 3 1.000
Session 4 1.000
Session 2 Session 5 0.699
Session 6 0.068
Session 7 0.534
Session 4 1.000
Session 5 0.747
Session 3
Session 6 0.087
Session 7 0.587
Session 5 0.768
Session 4 Session 6 0.088
Session 7 0.608
Session 6 0.845
Session 5
Session 7 1.000
Session 6 Session 7 0.947
Bold=statistically significant
Table 4.29 presents the Tukey post hoc by Sampling Session at Facility for UFPs.
Significant pairwise differences were found between Sampling Session 2 and Sampling
92
Table 4.29: Tukey by Sampling Session, Facility 3
UFP
Location 1 Location 2 pt/cm3
p-value
Session 2 0.081
Session 3 0.871
Session 4 1.000
Session 1
Session 5 1.000
Session 6 0.996
Session 7 1.000
Session 3 0.676
Session 4 0.055
Session 2 Session 5 0.026
Session 6 0.281
Session 7 0.106
Session 4 0.829
Session 5 0.681
Session 3
Session 6 0.995
Session 7 0.920
Session 5 1.000
Session 4 Session 6 0.993
Session 7 1.000
Session 6 0.966
Session 5
Session 7 0.999
Session 6 Session 7 0.999
Bold=statistically significant
NAAQS levels. The PM10 maximum exposure limit for a 24-hour mean is 0.15 mg/m3
and PM2.5 is 0.035 mg/m3 for a 24-hour mean (EPA, 2016). In general, the median PM
levels were not above the ASHRAE recommended concentrations. However, maximum
PM concentration all four facilities exceeded the recommended levels. The maximum
PM2.5 and PM10 concentration in the hair salon exceeded the ASHRAE recommended
concentrations at all facilities. The maximum PM2.5 and PM10 concentration exceeded
ASHRAE recommended concentrations in the Satellite Kitchen and Hair Salon at Facility
to 28C (74 to 82F) in summer and 20 to 25.5C (68 to 78F) in winter. Indoor relative
median temperatures were within ASHRAE winter guidelines in all facilities and
locations except at Facility1 in the hair salon. There were numerous occasions that the
never exceeded ASHRAE summer guidelines in all Facilities and Sampling Locations.
94
Chapter 5
Discussion
5.1 Overview
Data were collected at four facilities over three separate days during Fall of 2016.
PM (PM2.5, PM10, TPM, and UFP), temperature, and RH were measured in up to nine
indoor locations and an outdoor location for comparison. The data analyses showed that
there were significant differences between Facilities, Sampling Locations, and Sampling
Results showed that there were significant differences between Facilities. Overall,
Facility 2 had higher UFP and PM levels compared to the other three Facilities. This was
consistent in all rooms except the rehab/exercise room which was constructed in 2009
and included a brand-new HVAC system. This Facility was the only one without any
recent remodeling.
One possible reason for the higher particles at Facility 2 is that this facility had a
higher number of residents who tended to be younger and more mobile. This is consistent
with a study by Monn et al. (1997) which showed that one of the highest contributors to
increased PM levels was human activity. In addition, Facility 2 had the poorest ratings on
95
the Center of Medicare and Medicaid Services nursing home compare website (Medicare,
2017).
Only Facility 2 had outdoor smoking permitted by the residents. A prior study in
Ohio found ETS related air contaminants, including respirable suspended particulate
area were above outdoor concentrations and most indoor location concentrations.
elevated UFP and PM concentrations. This Facility is located in a more urban setting and
near a road with higher counts of vehicular traffic, compared to the other facilities.
Vehicle exhaust is a common source of PM and UFP. Indoor PM and UFP levels have
been correlated with outdoor levels and this Facility uses 100 percent outdoor air.
Differences between indoor Sampling Locations were found for UFP and all PM
significant for UFP and PM2.5. In general, the highest UFP and PM concentrations were
found in the kitchen, satellite kitchen, and hair salon. Wallace et al. (2004) showed that
there was a tenfold increase in UFP concentrations when cooking occurred and a study by
Williams, Creason, Zweidinger, et al. (2000) showed that hair products and cooking
increase PM levels.
In general, the bedroom had lower levels of PM than the activities room,
community space, and dining room. Other studies have found that the bedroom had lower
96
PM levels due to decreased movement and activity (Almeida-Silva, Wolterbeek, and
Almeida, 2014).
Finally, the lowest UFP and PM concentrations were seen in the rehab/exercise
room. This could because it was used the least compared to the other indoor locations.
Facility 2 had the highest UFP and PM concentrations across Sampling Sessions
or different times of the day. As expected, the lowest concentrations tended to occur
during Sampling Session 1 which was a baseline measurement before residents awoke
and started their day. PM levels were highest during Sampling Session 3 (10:00 to 11:00
a.m.) and Sampling Session 5 (1:30-2:30 p.m.) which were peak times of activity for the
residents. During these times cooking and cleaning also occurred by facility staff.
The UFP counts and PM concentrations for the indoor locations were compared to
the counts and concentrations outdoors. Table 5.1 presents the indoor mean UFP counts
concentrations. Facility 1 had the most indoor locations whose levels exceeded the
outside air. This could be because it is the only facility that did not use any outdoor air to
Research has not consistently shown that indoor or outdoor PM levels are higher
in nursing homes. However, all other studies looked a fewer indoor locations (patient
room, activities room, and dining room). This research study had varied results
97
Table 5.1: Indoor/Outdoor Median PM by Location and Facility
Indoor Median Concentration ≥ Outside Median Concentration
Indoor Location
UFP (pt/cm3) PM2.5 (mg/m3) PM10 (mg/m3) TPM (mg/m3)
Facility 1
Activity room
Private room
Rehab/Exercise room
Dining Room
Satellite kitchen
Community Space
Hair Salon
Facility 2
Activity room
Private room
Rehab/Exercise room
Dining Room
Kitchen
Community Space
Community Space 2
Hair Salon
Facility 3
Activity room
Private room
Rehab/Exercise room
Dining Room
Kitchen
Satellite kitchen
Community Space
Hair Salon
Facility 4
Private room
Rehab/Exercise room
Dining Room
Kitchen
Satellite kitchen
Community Space
Hair Salon
98
5.6 Comparison to Guidelines
There are few established national or mandatory limits for indoor air quality
contaminants, however, there are guidelines. All median PM levels were compared to the
ASHRAE Standard 62 which recommends that levels do not exceed the EPA standard in
order to protect public health. This equates to a maximum exposure limit for PM2.5 of
0.035 mg/m3 for a 24-hour mean and PM10 of 0.15 mg/m3 for a 24-hour mean (EPA,
2016b).
While we have OSHA PEL and ACGIH TLV values, those are primarily intended
for industrial environments (Burton, 2017). The standard of care for IAQ in hospitals and
similar environments, such as nursing homes, should be at a higher level because of the
health effects (Gunderson, 2016). Burton has compiled data for “typical” or “trigger,”
conditions (Burton, 2017). The trigger condition for PM2.5 is >0.015 mg/m3 and TPM is
>0.050 mg/m3.
Table 5.2 compares all Sampling Locations to the ASHRAE recommendation for
PM2.5 and PM10 and the trigger conditions for PM2.5 and TPM. Overall, the median PM
levels did not exceed the ASHRAE recommendations. The PM2.5 maximum
concentrations exceeded ASHRAE guidelines in the satellite kitchen, hair salon, and
activities room. The PM10 maximum concentrations exceeded ASHRAE guidelines in the
satellite kitchen and hair salon. This can be attributed to salon/hair products and the
cooking that occurs in these locations, both of which are known to be sources of PM.
The maximum concentrations for PM2.5 met the recommended trigger conditions
in every indoor location. In addition, the TPM maximum concentrations met the trigger
99
conditions in all facilities in various locations. This indicates that even though PM levels
do not exceed the ASHRAE recommendations, there are conditions that suggest further
ASHRAE winter guidelines. Thermal comfort normally differs for staff and elderly with
the staff generally comfortable in cooler temperature and the elderly in warmer
100
Table 5.2: Indoor Median and Max PM by Location and Facility
Compared to Guidelines and Trigger Levels
ASHRAE Trigger Conditions ASHRAE Trigger
Indoor Location PM2.5 PM2.5 PM10 ConditionsTPM
0.035 mg/m3 >0.015 mg/m3 0.15 mg/m3 >0.05 mg/m3
Facility 1
Median Max Median Max Median Max Median Max
Activities room
Private room
Rehab/Exercise room
Dining Room
Kitchen
Satellite Kitchen
Community Space
Hair Salon
Facility 2
Median Max Median Max Median Max Median Max
Activities room
Private room
Rehab/Exercise room
Dining Room
Kitchen
Community Space 1
Community Space 2
Hair Salon
Facility 3
Median Max Median Max Median Max Median Max
Activities room
Private room
Rehab/Exercise room
Dining Room
Kitchen
Satellite Kitchen
Community Space
Hair Salon
Facility 4
Median Max Median Max Median Max Median Max
Private room
Rehab/Exercise room
Dining Room
Kitchen
Satellite Kitchen
Community Space
Hair Salon
101
5.7 Limitations
The two minute Sampling Sessions are a limitation of this study. However, Long,
Suh, and Koutrakis (2000) showed that when long periods of sampling occur, peak levels
of PM are often missed suggesting that short sampling periods can be beneficial. Their
research showed that peak PM levels have been related to an increase in acute health
effects.
previous study in nursing homes and PM exposure showed that area sampling resulted in
essentially the same value as personal sampling (Williams, Creason, Zweidinger et al.,
2000).
Another limitation was that indoor and outdoor locations were sampled in a fixed,
rather than random order. While the initial intent was to sample in random order for each
Sampling Session, it was not conducted due to the fact that locations were far apart from
each other and could not all be sampled in the time allotted.
There were only 3 days of sampling per facility which provides limited data.
Another limitation is that samples were only collected during one season of the year (i.e.
fall). Prior research has shown that there are different levels of PM during different
5.8 Recommendations
This research shows that there are differences in PM concentrations and UFP
counts between facilities, location, and time of day. This research study provided pilot
data of what occurs in the nursing home section of four long term care facilities. It is
102
recommended that integrated sampling be performed in a smaller number of locations,
which are suggested problem areas such as the hair salon, kitchen, satellite kitchen, and
activities room. Future research should also consider the importance of sampling PM
fact the staff might be present in the locations that have higher PM concentrations. This
may offer a better understanding of particle levels throughout the day. Finally, it is
103
Chapter 6
Conclusions
The results showed that the highest median PM concentrations and UFP counts
were in Facility 2. A statistically significant difference between Facilities was seen for all
PM levels (PM2.5, p<0.001); PM10, p<0.001); and TPM, p<0.001) and UFP counts
(p<0.001). The null hypothesis “there will be no statistically significant difference in the
3-day median airborne particle (PM2.5, PM10 and TPM) concentrations and Ultra Fine
Particle (UFP) counts indoors between Facilities (Facility 1, Facility 2, Facility 3, Facility
4)” is rejected.
The results showed that the highest median indoor PM concentrations and UFP
counts were in the hair salon and kitchen at all Facilities. A statistically significant
difference between indoor Sampling Locations was seen for all PM levels (PM2.5,
p<0.001); PM10, p<0.001); and TPM, p<0.001) and UFP counts (p<0.001) at all
Facilities. The null hypothesis “there will be no statistically significant difference in the
3-day median airborne particle (PM2.5, PM10 and TPM) concentrations and UFP counts
between indoor Sampling Locations (activity room, rehab/exercise room, dining room,
104
The results showed PM concentrations and UFP counts were highest during
Sampling Session 3 (10:00 to 11:00 am) and Sampling Session 5 (1:30-2:30 pm). A
statistically significant difference between Sampling Sessions was seen for all TPM
(p=0.015) and UFP (p=0.007) at all facilities, while no significant difference between
Sampling Sessions was seen for PM2.5 (p=0.304) or PM10 (p=0.101). The null hypothesis
concentrations (PM2.5, PM10 and TPM) and UFP counts indoors between Sampling
Session (baseline, morning meal time, mid-morning activity, mid-day meal time, mid-
105
References
Abt, E., Suh, H.H., Catalano, P. and Koutrakis, P. (2000). Relative contribution of
outdoor and indoor particle sources to indoor concentrations. Environ. Sci.
Technol., 34, 3579–3587.
Administration on Aging. (2014, October 7). Retrieved from Administration for
Community Living: http://www.aoa.acl.gov/Aging_Statistics/index.aspx
Akbar-Khanzadeh, F., Windom, S., & Golbabaei, F. (2011). Designating smoking room
to control environmental tobacco smoke in nursing homes. International Journal
of Occupational Hygiene, 3(1), 1-5.
Almeida-Silva, M., Wolterbeek, H. T., & Almeida, S. M. (2014). Elderly exposure to
indoor air pollutants, Atmospheric Environment, 85, 54-63.
Annesi-Maesano, I., Norback, D., Zielinski, J., Bernard, A., Gratziou, C., Sigsgaard, T.,
& Viegi, G. (2013). Geriatric study in Europe on health effects of air quality in
nursing homes (GERIE study) profile: Objectives, study protocol and descriptive
data. Multidisciplinary Respiratory Medicine, 8(1), 71.
ANSI/ASHRAE Standard 55R (2010) Thermal environmental conditions for human
occupancy. American Society of Heating, Refrigerating and Air-Conditioning
Engineers Inc.: Atlanta
Araujo, J. A., Barajas, B., Kleinman, M., Wang, X., Bennett, B. J., Gong, K. W., & Nel,
A. E. (2008). Ambient particulate pollutants in the ultrafine range promote early
atherosclerosis and systemic oxidative stress. Circulation Research, 102(5), 589-
596.
Arundel, A. V., Sterling, E. M., Biggin, J. H., & Sterling, T. D. (1986). Indirect health
effects of relative humidity in indoor environments. Environmental Health
Perspectives, 65, 351.
Atkinson, J., Chartier, Y., Silvia, C. L. P., Jensen, P., Li, Y., & Seto, W. H. (Eds.).
(2009). Natural ventilation for infection control in health-care settings. World
Health Organization.
Bentayeb, M., Norback, D., Bednarek, M., Bernard, A., Cai, G., Cerrai, S., & Nasilowski,
J. (2015). Indoor air quality, ventilation and respiratory health in elderly residents
living in nursing homes in Europe. European Respiratory Journal, ERJ-00824.
106
Bentayeb, M., Simoni, M., Norback, D., Baldacci, S., Maio, S., Viegi, G., & Annesi-
Maesano, I. (2013). Indoor air pollution and respiratory health in the elderly.
Journal of Environmental Science and Health, Part A, 48(14), 1783-1789.
Bernstein, J. A., Alexis, N., Bacchus, H., Bernstein, I. L., Fritz, P., Horner, E., & Reijula,
K. (2008). The health effects of nonindustrial indoor air pollution. Journal of
Allergy and Clinical Immunology, 121(3), 585-591.
Broich, A. V., Gerharz, L. E., & Klemm, O. (2012). Personal monitoring of exposure to
particulate matter with a high temporal resolution. Environmental Science and
Pollution Research, 19(7), 2959-2972.
Burton, J. (2017, February). Using triggers to avoid IAQ problems. The Synergist.
Retrieved from: http://synergist.aiha.org/201702-using-triggers-to-avoid-iaq-
problems
Center for Disease Control and Prevention (2013). Long-Term Care Services. Retrieved
from: http://www.cdc.gov/nchs/data/nsltcp/long_term_care_services_2013.pdf
Chronic respiratory diseases. (2016). Retrieved June 20, 2016, from World Health
Organization (WHO): http://www.who.int/respiratory/en/
Crowder, J., Flick, C., Giliam, R., Klesch, L., Simpson, I., & Smimova, Y. (2007).
AirAdvice state of our indoor air. AirAdvice.
Curtis, L., Rea, W., Smith-Willis, P., Fenyves, E., & Pan, Y. (2006). Adverse health
effects of outdoor air pollutants. Environment International, 32(6), 815-830.
Dales, Liu, & Wheeler. (2008). Quality of indoor residential air and health. Canadian
Medical Association Journal 179.2, 147-152.
Davis, R. E., McGregor, G. R., & Enfield, K. B. (2016). Humidity: A review and primer
on atmospheric moisture and human health. Environmental Research, 144, 106-
116.
Diapouli, E., Eleftheriadis, K., Karanasiou, A. A., Vratolis, S., Hermansen, O., Colbeck,
I., & Lazaridis, M. (2011). Indoor and outdoor particle number and mass
concentrations in Athens. Sources, sinks and variability of aerosol parameters.
Aerosol and Air Quality Research, 11(6), 632-642.
Environmental Protection Agency. (2016a, July 15). Introduction to Indoor Air Quality
Retrieved July 20, 2016, from EPA: https://www.epa.gov/indoor-air-quality-
iaq/introduction-indoor-air-quality
Environmental Protection Agency. (2016b, July 1). Particulate matter (PM) basics.
Retrieved January 20, 2017, from https://www.epa.gov/pm-pollution/particulate-
matter-pm-basics
107
Environmental Protection Agency (2016c, May 16). Volatile organic compounds' impact
on indoor air quality. Retrieved January 20, 2017, from EPA:
https://www.epa.gov/indoor-air-quality-iaq/volatile-organic-compounds-impact-
indoor-air-quality
Environmental Protection (2017, January 13). Agency Climate Impacts on Human
Health. Retrieved March 25, 2017, from Environmental Protection Agency:
https://www.epa.gov/climate-impacts/climate-impacts-human-health#Air
Etheridge, D. W., & Sandberg, M. (1996). Building ventilation: theory and measurement
(Vol. 50). Chichester: John Wiley & Sons.
Garrett, M. H., Hooper, M. A., Hooper, B. M., & Abramson, M. J. (1998). Respiratory
symptoms in children and indoor exposure to nitrogen dioxide and gas
stoves. American Journal of Respiratory and Critical Care Medicine, 158(3),
891-895.
Gunderson, E. C. (2016). The IAQ investigator's guide: A guide to the principles,
techniques, and resources available for professional indoor air quality
investigations. Fairfax, VA: American Industrial Hygiene Association.
Hess-Kosa, K. (2010). Indoor air quality: Sampling methodologies. CRC Press.
Katsouyanni, K., Pantazopoulou, A., Touloumi, G., Tselepidaki, I., Moustris, K.,
Asimakopoulos, D., & Trichopoulos, D. (1993). Evidence for interaction between
air pollution and high temperature in the causation of excess mortality. Archives
of Environmental Health: An International Journal, 48(4), 235-242.
Kike-Parsis, A. (2004). Indoor air quality: Part 1- What is it. Retrieved from Medscape:
http://www.medscape.com/viewarticle/494503_4
Klenk, J., Becker, C., & Rapp, K. (2010). Heat-related mortality in residents of nursing
homes. Age and Ageing, 39(2), 245-252.
Laiman, R., He, C., Mazaheri, M., Clifford, S., Salimi, F., Crilley, L. R., & Morawska, L.
(2014). Characteristics of ultrafine particle sources and deposition rates in
primary school classrooms. Atmospheric Environment, 94, 28-35.
Lehnert, M., Pesch, B., Lotz, A., Pelzer, J., Kendzia, B., Gawrych, K., & Mattenklott, M.
(2012). Exposure to inhalable, respirable, and ultrafine particles in welding
fume. Annals of Occupational Hygiene, 56(5), 557-567.
Lillard, S. (2005, June). Stachybotrys chartarumthe best and most complete. Retrieved
August, 2016, from http://www.mold-help.org/content/view/429.com
Liu, L. S., Box, M., Kalman, D., Kaufman, J., Koenig, J., Larson, T., & Wallace, L.
(2003). Exposure assessment of particulate matter for susceptible populations in
Seattle. Environmental Health Perspectives, 111(7), 909.
108
Long, C. M., Suh, H. H., & Koutrakis, P. (2000). Characterization of indoor particle
sources using continuous mass and size monitors. Journal of the Air & Waste
Management Association, 50(7), 1236-1250.
Lutfiyya, M. N., Gessert, C. E., & Lipsky, M. S. (2013). Nursing home quality: A
comparative analysis using CMS nursing home compare data to examine
differences between rural and nonrural facilities. Journal of the American Medical
Directors Association, 14(8), 593-598.
Maio, S., Sarno, G., Baldacci, S., Annesi-Maesano, I., & Viegi, G. (2015). Air quality of
nursing homes and its effect on the lung health of elderly residents. Expert Review
of Respiratory Medicine, 6, 671-673.
Medicare (2017). Find and compare nursing homes | Nursing home compare. (2017).
Retrieved April 03, 2017, from Medicare.gov:
https://www.medicare.gov/nursinghomecompare/search.html
Mendes, A., Pereira, C., Mendes, D., Aguiar, L., Neves, P., Silva, S., … Teixeira, J. P.
(2013). Indoor air quality and thermal comfort – results of a pilot study in elderly
care centers in Portugal.Journal of Toxicology and Environmental Health. Part
A, 76(0), 333–344.
Mendes, A., Bonassi, S., Aguiar, L., Pereira, C., Neves, P., Silva, S., & Teixeira, J. P.
(2014). Indoor air quality and thermal comfort in elderly care centers. Urban
Climate, 14, 486-501.
Monn, C. H., Fuchs, A., Högger, D., Junker, M., Kogelschatz, D., Roth, N., & Wanner,
H. U. (1997). Particulate matter less than 10 μm (PM10) and fine particles less
than 2.5 μm (PM2. 5): Relationships between indoor, outdoor and personal
concentrations. Science of the Total Environment, 208(1-2), 15-21.
Nazaroff, W. W. (2004). Indoor particle dynamics. Indoor Air, 14(s7), 175-183.
Oberdörster, G. (2000). Pulmonary effects of inhaled ultrafine particles. International
Archives of Occupational and Environmental Health, 74(1), 1-8.
Ormandy, D., Ezratty, V. (2012). Health and thermal comfort: from WHO guidance to
housing strategies. Energy Policy, Elsevier 49, 116–121.
OSHA. (1999). OSHA Technical Manual (OTM) Indoor Air Quality.
Özkaynak, H., Xue, J., Weker, R., Butler, D., & Koutrakis, P. (1996). Particle TEAM
(PTEAM) Study: Analysis of the Data. NASA, (19980007226).
Pecingina, I.-R., & Popa, R.-G. (2014). Air Pollutants and the effects of on the human
body. Annal of "Constantin Brancusi" University of Tarju-Jui. Engineering
series, 213-218.
109
Perez-Padilla, R., Schilmann, A., & Riojas-Rodriguez, H. (2010). Respiratory health
effects of indoor air pollution [Review article]. The International Journal of
Tuberculosis and Lung Disease, 14(9), 1079-1086.
Peters, A., Wichmann, H. E., Tuch, T., Heinrich, J., & Heyder, J. (1997). Respiratory
effects are associated with the number of ultrafine particles. American Journal of
Respiratory and Critical Care Medicine, 155(4), 1376-1383.
Rhodes, C. E., Lawless, P. A., Evans, G. F., Sheldon, L. S., Williams, R. W., Vette, A. F.,
& Walsh, D. (2001). The relationships between personal PM exposures for elderly
populations and indoor and outdoor concentrations for three retirement center
scenarios. Journal of Exposure Science and Environmental Epidemiology, 11(2),
103.
Saldiva, P. H., Clarke, R. W., Coull, B. A., Stearns, R. C., Lawrence, J., Murthy, G. K., &
Godleski, J. J. (2002). Lung inflammation induced by concentrated ambient air
particles is related to particle composition. American Journal of Respiratory and
Critical Care Medicine, 165(12), 1610-1617.
Sajani, S. Z., Ricciardelli, I., Trentini, A., Bacco, D., Maccone, C., Castellazzi, S., &
Harrison, R. M. (2015). Spatial and indoor/outdoor gradients in urban
concentrations of ultrafine particles and PM 2.5 mass and chemical components.
Atmospheric Environment, 103, 307-320.
Schlesinger, R. B. (2007). The health impact of common inorganic components of fine
particulate matter (PM2. 5) in ambient air: A critical review. Inhalation
Toxicology, 19(10), 811-832.
Spengler, J. D., Samet, J. M., & McCarthy, J. F. (2001). Indoor air quality handbook (pp.
9-1). New York: McGraw-Hill.
Sundell, J. (2004). On the history of indoor air quality and health. Indoor Air, 14(s7), 51-
58.
Wallace LA, Emmerich SJ, Howard-Reed C. (2004). Source strengths of ultrafine and
fine particles due to cooking with a gas stove. Environmental Science Technology,
38, 2304–2311.
Wang, X. et al. (2006). Hospital indoor PM10/PM2.5 and associated trace elements in
Guangzhou, China. Sci. Total Environ, 366 (1), 124–135.
110
Williams, R., Creason, J., Zweidinger, R., Watts, R., Sheldon, L., & Shy, C. (2000).
Indoor, outdoor, and personal exposure monitoring of particulate air pollution:
The Baltimore elderly epidemiology-exposure pilot study. Atmospheric
Environment, 34(24), 4193-4204.
Williams, R., Suggs, J., Creason, J., Rodes, C., Lawless, P., Kwok, R., ... & Sheldon, L.
(2000). The 1998 Baltimore particulate matter epidemiology-exposure study: Part
2. personal exposure assessment associated with an elderly study population.
Journal of Exposure Science and Environmental Epidemiology, 10(6), 533.
Williams, R., Suggs, J., Zweidinger, R., Evans, G., Creason, J., Kwok, R., ... & Sheldon,
L. (2000). The 1998 Baltimore particulate matter epidemiology-exposure study:
Part 1. comparison of ambient, residential outdoor, indoor and apartment
particulate matter monitoring. Journal of Exposure Science and Environmental
Epidemiology, 10(6), 518.
Zhang, Q., Gangupomu, R. H., Ramirez, D., & Zhu, Y. (2010). Measurement of ultrafine
particles and other air pollutants emitted by cooking activities. International
Journal of Environmental Research and Public Health, 7(4), 1744-1759.
111
Appendix A
Facility Description
112
Table A.2: Activity Room Description
113
Table A.5: Dining Room Description
114
Table A.8: Community Space 1 Description
Facility 2
Primary use Watch TV or sleep
Flooring type Tile
Wall Construction Dry wall and 1 glass wall
Number of Windows 1
Evidence of water damage None
Number Supply 0
Number Returns 0
Floor Level 1
115