INSTRUMENT SYMBOL LETTER IDENTIFICATION TABLE

MISCELLANEOUS SYMBOLS: VALVE ACTUATORS: FIRST LETTER SUCCEEDING LETTERS


MEASURING ELEMENTS: SYMBOL MEASURED OR READOUT OR
OUTPUT
INITIATING MODIFIER PASSIVE MODIFIER
FUNCTION
DIAPHRAGM OPERATED BACK PRESSURE VARIABLE FUNCTION
FLOW ORIFICE REGULATOR (SELF CONTAINED)
DIAPHRAGM SEAL VIDEO CAMERA
A ANALYSIS ALARM
DIAPHRAGM OPERATED C CONDUCTIVITY CONTROL
LEVEL GAGE GLASS, FLOAT, PRESSURE REDUCING
VORTEX METER WITH HANDWHEEL
MAGNETIC, DISPLACEMENT OR LEVEL ELEMENT / LEAK DETECTION REGULATOR (SELF CONTAINED)
DIFFERENTIAL-PRESSURE TYPE ELEMENT D DENSITY DIFFERENTIAL
LEVEL INSTRUMENTS CCTV CAMERA HAND OPERATED OR E VOLTAGE ELEMENT
XX XX - INDICATES THE TYPE HANDWHEEL PRESSURE REDUCING
RUPTURE DISK (PRESSURE RELIEF) REGULATOR WITH F FLOW
EXTERNAL PRESSURE TAP
MAGNETIC FLOW METER G GLASS
PNEUMATIC PISTON
VARIABLE AREA FLOW METER (ROTAMETER)
BELL (ALARM) (SINGLE ACTING) BACK PRESSURE REDUCING HAND (MANUALLY
REGULATOR WITH H HIGH
INITIATED)
PRESSURE OR VACUUM EXTERNAL PRESSURE TAP
FLOW INDICATOR VALVED I CURRENT INDICATE
(ROTAMETER WITH ATTACHED VALVE) RELIEF (ANGLE PATTERN) PNEUMATIC PISTON
TEMPERATURE SENSING
ELEMENT WITH HANDWHEEL J POWER

K TIME
TEMPERATURE ELEMENT (WITH WELL) INLINE PRESSURE OR
RADIATION SENSING ELEMENT L LEVEL LIGHT LOW
VACUUM RELIEF PNEUMATIC PISTON
IA DIAPHRAGM OPERATED
(DOUBLE ACTING) W/ POSITIONER M MOISTURE
INLINE RADIATION ELEMENT
INLINE FLOW INSTRUMENT
ORIFICE,
XX - METER TYPE O
XX 3-VALVE INSTRUMENT RESTRICTION

ALARM HORN MANIFOLD MOTOR OPERATED PRESSURE,


P
VACUUM
PNEUMATIC PISTON
PITOT OR PITOT- VENTURI TUBE
FLOW METER IA (SINGLE ACTING) W/ Q STATUS TOTALIZE
AIRSET POSITIONER
MOTOR OPERATED VALVE R RADIATION RECORDER
W/ MANUAL OVER-RIDE
I ORF O (R) CONVENTIONAL
S SPEED SAFETY SWITCH
AVERAGING PITOT TUBE FLOW METER
RADAR LEVEL SENSOR RELIEF VALVE SPECIFIC
WITH DETAILS: SG
AIR OPERATED GRAVITY
I INLET SIZE
T TEMPERATURE TRANSMIT
ORF ORFICE SIZE
TURBINE OR PROPELLER FLOW METER
O OUTLET SIZE U MULTIVARIABLE
SOLENOID
(R) RELIEF CONDITION
DIRECT CONNECTED NOMENCLATURE: V VIBRATION VALVE
PRESSURE SENSOR GENERIC FLOW METER F = FIRE
B = BLOCKED OUTLET WEIGHT OR
3-WAY SOLENOID W WELL
FORCE (STRAIN)
C = CONTROL FAILURE
CORIOLIS FLOW METER P = PROCESS WF WEIGHT FACTOR
M = MECHANICAL FAILURE
T = THERMAL EXPANSION 4-WAY SOLENOID X TROUBLE FAILURE FAILURE
FLOW NOZZLE R = REVERSE FLOW RELAY,
EVENT, STATE COMPUTE,
Y
PRESSURE SENSOR PILOT OPERATED RELIEF OR PRESENCE CONVERT
WITH DIAPHRAGM SEAL, PIPED ULTRASONIC FLOW METER VALVE
4-WAY DUAL
SOLENOID Z POSITION ACTUATOR

INSTRUMENT SYMBOLS: DETAIL 1A: ON / OFF PNEUMATIC ACTUATED, DETAIL 1B: THREE - WAY PNEUMATIC ACTUATED, DETAIL 1C: MODULATING DETAIL 1D: ON/OFF PNEUMATIC ACTUATED
PRIMARY ELEMENT OR
LOCALLY MOUNTED INSTRUMENT
COMPUTER INPUT / OUTPUT DCS / PLC CONTROL NOTE 6 DCS / PLC CONTROL NOTE 6 PNEUMATIC ACTUATED, DCS / PLC CONTROL WITH POSITION
NOTE 2
(WHERE
OPEN
CLOSE
NOTE 2
(WHERE
OPEN DCS / PLC CONTROL TRANSMITTER AND SAFETY SOLENOID
CLOSE
ANNUNCIATOR CABINET OR APPLICABLE) TRAVEL APPLICABLE) NOTE 6 NOTE 6
TRAVEL SAFETY
PANEL MOUNTED INSTRUMENT FAULT OPEN
STATUS LIGHT, BEACON FAULT INTERLOCK
W = WHITE, R = RED, G = GREEN CLOSE
INSTRUMENT MOUNTED TRAVEL
NOTE 1 NOTE 1 FAULT
ON BACK OF PANEL
(INACCESSIBLE)
SOFTWARE INTERLOCK
INSTRUMENT MOUNTED AT
AN AUXILIARY LOCATION NOTE 2
(WHERE
CONTROLLER (YYC FOR DCS
PLC FOR PLC) APPLICABLE)
RELAY
NOTE 1 NOTES 1, 3, 5
DCS SHARED DISPLAY IA NOTE 1
NOT NORMALLY ACCESSIBLE IA NOTE 4
VENT
POWER RELAY
VENT
NOTE 1, 3 NOTE 1, 3
DCS MONITORING FUNCTION VENT
NOTE 1, 3
ACCESSIBLE IN AUXILLARY IA
HARDWARE INTERLOCK LOCATION (PANEL HMI) IA
XX
VALVE FAIL ACTION
DCS CONTROL OR MONITORING VALVE FAIL ACTION AS PER P&ID AS PER P&ID
FUNCTION ACCESSIBLE TO THE VALVE FAIL ACTION
WHERE X = PROCESS VARIABLE AS PER P&ID
OPERATOR VALVE FAIL ACTION AS PER P&ID (F = FLOW, P = PRESSURE, ETC.)

DETAIL 1E: ON/OFF PNEUMATIC ACTUATED DCS / PLC


CONTROL WITH POSITION TRANSMITTER FOR SAFETY INTERLOCK TAG DESCRIPTION I / O TYPE VALVE FAIL POSITIONS

NOTE 6 ZSO OPEN LIMIT SWITCH DI SYMBOL DESCRIPTION


SAFETY OPEN
ZSC CLOSE LIMIT SWITCH DI FO FAIL OPEN
INTERLOCK CLOSE
NOTES: TRAVEL ZIO
ZIC
LIMIT SWITCH INDICATION OPEN
LIMIT SWITCH INDICATION CLOSE
SDI
SDI
FC
FL
FAIL CLOSED
FAIL LAST
FAULT
1. LOOP NUMBERS FOR TAGS ARE TAKEN FROM THE VALVE TAG, AS SHOWN ON EACH P&ID THAT
ZA VALVE STATUS SOFT
REFERENCES THIS DETAIL.
2. INTERLOCK NUMBER AND PROPER SYMBOL (DCS OR PLC) WILL BE SHOWN ON PROCESS P&ID. HIS VALVE SWITCH SOFT
3. FOR VALVES LOCATED IN PITS WITH EXTENDED VALVE STEMS / ACTUATORS, LIMIT SWITCH AND XY SOLENOID VALVE/POSITIONER DO/AO
POSITIONER WILL BE LOCATED OUTSIDE THE PITS. NOTE 2
(WHERE
ZT POSITION TRANSMITTER AI (SAFETY) IN-PROGRESS TO SUPPORT
4. SAFETY SOLENOID VALVE (SY) IS TO TRIP THE VALVE TO ITS FAILURE POSITION. ZI POSITION INDICATION SOFT
5. REMOTELY MAINTAINABLE MODULATING CONTROL VALVES WILL UTILIZE A PNEUMATIC PISTON APPLICABLE)
XV ON-OFF VALVE N/A
60% DESIGN REVIEW
ACTUATOR.
6. ACTUATOR TYPE (SINGLE ACTING, DOUBLE ACTING, ETC.) AND SOLENOID TYPE (3-WAY, 4-WAY, NOTE 1, 3 SY
ZY
SAFETY SOLENOID (AS REQUIRED)
POSITION INDICATION (AS REQUIRED)
DO (SAFETY)
AI
NOT FOR CONSTRUCTION
ETC.) WILL BE SPECIFIED ON THE INDIVIDUAL VALVE DATASHEETS.
7. FOR COMPLETE CONTROLS AND STATUS INDICATIONS OF MOTORS, CONTROL STATIONS, AND
VFDS, SEE I/O LIST DOCUMENT 31269-19-LST-0002. IA
8. EVERY SAFETY PLC ANALOG INPUT SIGNAL IS ALSO WIRED VIA A SIGNAL SPLITTER TO AN
ANALOG INPUT IN THE DCS FOR MONITORING AND DIAGNOSTICS.
VALVE FAIL ACTION
AS PER P&ID