Advanced Features

ACE3600 System Tools


Suite (STS)
Version
0 12.50
AB
6802979C15-D

MOTOROLA and the Stylized M Logo are registered in the U.S.


Patent and Trademark Office. All other product or service names
are the property of their respective owners.

Copyright © Motorola 2008 All Rights Reserved


COMPUTER SOFTWARE COPYRIGHTS

The Motorola products described in this instruction manual may include copyrighted Motorola computer programs stored in
semiconductor memories or other media. Laws in the United States and other countries preserve for Motorola certain
exclusive rights for copyrighted computer programs including the exclusive right to copy or reproduce in any form the
copyrighted computer program. Accordingly, any copyrighted Motorola computer programs contained in the Motorola
products described in this manual may not be copied or reproduced in any manner without the express written permission of
Motorola. Furthermore, the purchase of Motorola products shall not be deemed to grant either directly or by implication,
estoppel, or otherwise, any license under the copyrights, patents or patent applications of Motorola, except for the normal
non-exclusive, royalty free license to use that arises by operation of law in the sale of a product.

Motorola, Inc.
1301 E. Algonquin Road,
Schaumburg, IL 60196 U.S.A.
Table of Contents
SCOPE ................................................................................................................................................................. 1
ACE3600 I/OS .................................................................................................................................................... 2
I/O Configuration .......................................................................................................................................... 2
I/Os and the Application ................................................................................................................................ 2
I/Os Hot Swap................................................................................................................................................ 3
I/O Module States .......................................................................................................................................... 3
Sleep Mode .................................................................................................................................................... 3
Hardware Tests.............................................................................................................................................. 4
Freeze Mode .................................................................................................................................................. 4
AUTOMATIC I/O RECOGNITION ........................................................................................................................... 5
POWER MANAGEMENT ....................................................................................................................................... 6
Configuration................................................................................................................................................. 6
Constraints..................................................................................................................................................... 7
SAFE FIRMWARE DOWNLOAD ............................................................................................................................. 8
FLASH FILE SYSTEM ........................................................................................................................................... 9
General .......................................................................................................................................................... 9
User Generated Flash Files......................................................................................................................... 10
Accessing Flash Files .................................................................................................................................. 10
Writing Flash Files ...................................................................................................................................... 11
Logging Flash Files..................................................................................................................................... 11
Flash File Headers ...................................................................................................................................... 11
Flash Files Diagnostics ............................................................................................................................... 12
ACCESSING DATABASE VARIABLES VIA COORDINATES .................................................................................... 13
Definitions ................................................................................................................................................... 14
EVENT DRIVEN SOFTWARE ............................................................................................................................... 16
Definitions ................................................................................................................................................... 16
Event Driven Mechanism............................................................................................................................. 17
Event Driven Tables .................................................................................................................................... 18
How to Use the Event Driven Software ....................................................................................................... 19
FAST EVENTS .................................................................................................................................................... 26
Events Triggers............................................................................................................................................ 26
Fast Event Definition and Configuration .................................................................................................... 26
Fast Event Scheduling ................................................................................................................................. 27
Enabling/Disabling Fast Events .................................................................................................................. 27
Monitoring of Fast Events ........................................................................................................................... 28
Fast Events Diagnostics .............................................................................................................................. 28
Testing Fast Events...................................................................................................................................... 28
Fast Events and Automatic Recognition ...................................................................................................... 29
NETWORK CONFIGURATION.............................................................................................................................. 31
Routing of Data Frames .............................................................................................................................. 31
Routing over Alternative Direct Link........................................................................................................... 32
Routing using Remote Failed Links Table ................................................................................................... 33
Using the Time To Live Counter.................................................................................................................. 34
MDLC OVER IP COMMUNICATION ................................................................................................................... 35
Overview...................................................................................................................................................... 35
Broadcast and Setcalls ................................................................................................................................ 36

i
New Features for MDLC over IP in ACE3600 ............................................................................................ 36
MDLC over IP/PPP Connections ................................................................................................................ 39
MDLC over IP/LAN Connections ................................................................................................................ 39
STS PC Communication Setup Options ....................................................................................................... 40
MDLC over IP Setup ................................................................................................................................... 40
MDLC over IP Site Paging.......................................................................................................................... 41
MDLC over LAN/Ethernet ........................................................................................................................... 42
MDLC over iDEN ........................................................................................................................................ 47
MDLC over Tetra ........................................................................................................................................ 60
MDLC over Standard Modem...................................................................................................................... 68
MDLC over GPRS ....................................................................................................................................... 71
MDLC over ASTRO IV&D .......................................................................................................................... 73
MDLC over Null Modem ............................................................................................................................. 81
Modem Configuration File .......................................................................................................................... 82
IP Conversion Tables .................................................................................................................................. 99
MDLC over IP Connection Verification .................................................................................................... 101
FIREWALL ....................................................................................................................................................... 103
Firewall Configuration.............................................................................................................................. 103
CLOCK FUNCTIONS AND SYNCHRONIZATION .................................................................................................. 104
RTU Clock ................................................................................................................................................. 104
Time Adjustment and Synchronization....................................................................................................... 104
Time Parameter Configuration.................................................................................................................. 106
Time Synchronization Diagnostics ............................................................................................................ 109
NTP Clock Synchronization....................................................................................................................... 109
Global Positioning System (GPS).............................................................................................................. 113
CORE DUMP .................................................................................................................................................... 117
MDLC ENCRYPTION....................................................................................................................................... 119
PROTOCOL ANALYZER .................................................................................................................................... 120
PID LOOP - PROPORTIONAL INTEGRAL DERIVATIVE ..................................................................................... 130
General ...................................................................................................................................................... 130
PID Function ............................................................................................................................................. 131
PID Table .................................................................................................................................................. 131
How to Use the PID................................................................................................................................... 133
PID Application Example .......................................................................................................................... 134
ENHANCED PID .............................................................................................................................................. 147
IRRIGATION ..................................................................................................................................................... 148
Irrigation Unit Types ................................................................................................................................. 148
STS Functions for Irrigation Units ............................................................................................................ 149
Tips on Using the STS for Irrigation.......................................................................................................... 150

APPENDIX A: RS232/RS485 ADAPTOR CABLES .......................................................................................... A-1


Connection to a Computer or Terminal..................................................................................................... A-1
Connection to a Modem............................................................................................................................. A-2
Connection to GPS Receiver...................................................................................................................... A-3
Connecting a User Port to a Printer.......................................................................................................... A-3
Connecting a User Port to an External Unit ............................................................................................. A-4
Connection to a Radio ............................................................................................................................... A-4
RTU-to-RTU Connection Using MDLC Protocol through RS232............................................................. A-5
RTU-to-RTU Synchronous Communication Using Plug-in Port ............................................................... A-5
ACE3600 RTU-to-ACE3600 RTU Connection Using MDLC Protocol through RS485 ............................ A-6

ii
ACE3600 RTU-to-MOSCAD RTU Connection Using MDLC Protocol through RS485 ........................... A-6
ACE3600 RTU-to-PC Ethernet Port Direct Connection without Hub ...................................................... A-7

APPENDIX B: REMOTE STS MODEM SETUP ................................................................................................. B-1


Hayes ACCURA 144 + FAX 144, V2.20E ................................................................................................. B-1
Hayes ACCURA 144 + FAX 144, V4.1...................................................................................................... B-4
Motorola OnlineSURFR 28.8 .................................................................................................................... B-5
Motorola OnlineSURFR 33.6 .................................................................................................................... B-8
Motorola OnlineSURFR 56K..................................................................................................................... B-9
UDS V.3225 ............................................................................................................................................. B-10
UDS V.3400 ............................................................................................................................................. B-12
USRobotics Sportster 14400 Fax............................................................................................................. B-14
USRobotics Sportster 28800 Fax............................................................................................................. B-17
USRobotics Sportster 56K Fax ................................................................................................................ B-20
Intel SatisFAXtion Modem/400e .............................................................................................................. B-21
Multitech Leased Line Modem................................................................................................................. B-24

iii
Scope

This reference manual provides useful background information on ACE3600 advanced system
features, communication features, and specialized utilities and features.

The system features include:

• I/Os
• Automatic I/O Recognition
• Power Management
• Safe Firmware Download
• Flash File System
• Accessing Database Variables via Coordinates
• Event Driven Software
• Fast Events
The communication features include:

• Network Configuration
• MDLC over IP Communications (Static LAN, Dynamic – DHCP Client, or PPP)
• Firewall
• Clock Functions and Synchronization
The utilities include:

• Core Dump Logger


• MDLC Encryption
• Protocol Analyzer
• PID Loop
• Enhanced PID
• Irrigation

1
ACE3600 I/Os

I/O Configuration
The ACE3600 RTU can include up to eight I/O modules in any combination, arranged in a
single frame (rack) and numbered 1-8.

The modules are configured in the ACE3600 STS I/O tab during site configuration (see figure
below.) The module types are selected from a drop-down list and include an FLN number
which is also printed on a label on the left side of the physical module. Two different DI/DO
FET modules (FLN3553, FLN3554) are available, with up to 16/32 user connections which
can be configured as either DI or DO, in groups of eight.

The I/O tab includes a field, ‘Enable auto I/O modules recognition at startup,’ which instructs
the unit to automatically recognize I/O modules when it is started up. This saves the user time
when configuring the site in the STS. If automatic recognition is enabled, no I/O modules can
be defined for the site and the I/O configuration must be uploaded from a unit. For more
information, see Automatic I/O Recognition.

Settings for I/O modules and individual I/Os can be set using the Advanced Configuration of
the specific I/O module. This includes defining values such as DO power source, AI/DI filters,
and AI differential. For details, see the Customizing the Configuration of a Site section of the
ACE3600 STS User Guide.

I/Os and the Application


The I/Os controlled by the RTU are represented by variables in the application database tables
and manipulated by the application process rungs. The process of linking the database
variables to the physical I/Os of the site is performed before compiling the application in the
2
Application Programmer. For more information, see Linking I/Os to the Database in the
ACE3600 STS User Guide.

If a ladder application is downloaded to the RTU and the I/O configuration associated with the
application does not match the I/O configuration in the unit, the application will not execute
and an error will be sent.

If a site configuration is downloaded to the unit with a working application, the unit will restart
and check the match between the I/O configuration associated with the application and the I/O
configuration in the unit. If the two do not match, the application will not execute and an error
will be sent.

If the system includes more than one site with the exact same I/O configuration, assigned to the
same application, the I/O Link information can be distributed from one site to the other sites.

During I/O link, the user can define input/output mask values to be used by the application if
the I/O module loses communication with the CPU.

I/Os Hot Swap


The ACE3600 RTU has a hot swap capability, which means that an I/O module can be
removed from its slots and reinserted (or replaced by another module of the same type) without
powering down the unit. The only exception to this rule is the main power supply module,
which cannot be removed during normal operation.

If an I/O module is replaced by another module of a different type, the I/O link association will
remain for any I/Os which are the same (e.g. DI in Frame 0 Module 1 linked to IN_1). For
those I/O whose types have changed, a popup will be displayed explaining that those links will
be erased (e.g. DI in Frame 0 Module 4 is now a DO).

I/O Module States


An I/O module can be in one of three states in the unit:

• Running: The I/O module in the slot matches the one in unit’s site configuration. (In this
case the application can run.)
• Failed: The I/O module is missing or the module in the slot does not match the one in
unit’s site configuration. (In this case the application cannot run.)
• Mode Selected: e.g. Freeze mode or Sleep mode. (Determined by user or application.)

Sleep Mode
Each I/O module can be switched by the user application program to Sleep Mode. In Sleep
Mode, the module does not function and the power consumption is minimized. During Sleep
mode, the user application program will get the predefined values (PDV) or keep the last value
(KLV) for each I/O. The PDV/KLV values are set in the I/O link table of the application
program. For more information, see the Application Programmer chapter of the ACE3600 STS
User Guide.

3
Hardware Tests
The RTU’s I/O modules can be tested using the STS Hardware Test utility. I/O module
parameters can be retrieved, the state of the I/Os can be scanned, and the application started
and stopped. The I/O module LEDs can be turned on and off. Information on the I/O module
power supply (DI/AI modules only) can also be retrieved. Individual I/Os can be tested.

During hardware tests, various values and settings can be changed by the user. These changes
will revert to their previous values/settings (saved by the system) under the following
circumstances:

• when the Hardware Test utility is closed,


• after ten minutes have elapsed,
• when the stopped application is run or the frozen module is unfrozen.
For more information, see the ACE3600 STS User Guide.

Freeze Mode
The STS Hardware Test utility enables the user to test inputs and outputs while the user
program is running. The I/O module can be set to Freeze mode. No actual values will be
read/written to the application until the module is unfrozen. The application will continue to
run; all unfrozen I/O modules will continue to interact normally with the application while the
frozen module will not be impacted by the application at all.

The user program will get the predefined value (PDV) or keep the last value (KLV) of each
input in the module instead of the actual inputs value. The DO values will keep the last value
they had at the time the module was frozen.

If the hardware test involves reading inputs only, the I/O module generally need not be frozen.
When testing outputs, the I/O module should be frozen to ensure proper execution of the
application.

If the user does not unfreeze the module, the STS will prompt to unfreeze it when closing the
Hardware Test utility or after ten minutes have elapsed.

For more information, see the Performing Hardware Tests section of the ACE3600 STS User
Guide.

4
Automatic I/O Recognition

The site configuration of an ACE3600 RTU includes the definition of all I/O modules in the
unit. In legacy MOSCAD systems, the user manually defined each module in each RTU using
the Site Configuration tool and then linked the physical I/Os to the definitions in the single-
and multiple-column tables using the Application Programmer tool.

With the Automatic Recognition feature, the ACE3600 RTU identifies the actual hardware (I/O
modules only) components in the unit when starting up and builds the initial site configuration
accordingly. This site configuration is based on the default site settings and the unique module
type ID number associated with each I/O module.

The Automatic Recognition feature saves time for the system definer who merely sets the
‘Enable auto I/O modules recognition at startup’ field (disabled by default) in the STS and
powers on the RTU. Once the initial I/O module configuration is determined, the site
configuration is uploaded using the Upload New Site command from the System menu. For
more information, see the Uploading a New Site to the STS section of the ACE3600 STS User
Guide. Further site configuration or advanced I/O configuration may be required. For more
information, see the Customizing the Configuration of a Site section of the ACE3600 STS User
Guide. Once all changes are made, the new site configuration can be downloaded to the unit.
For more information, see the Downloading to a Site section of the ACE3600 STS User Guide.

Note: In an RTU to which no site configuration has been downloaded, a default configuration
exists, with Automatic Recognition enabled. When uploading from an RTU to which no site
configuration has been downloaded, the Site Upload Form will list Default Site Configuration
instead of Site Configuration. The configuration of the inserted I/O modules and plug-in ports
PI1 and PI2 will be retrieved.

The RTU also identifies the module type automatically when an I/O module is inserted into a
slot (hot-swap) in a powered-up RTU which is configured for Automatic Recognition. If an
application is running, the application will ignore the newly inserted I/O module. When the
RTU is restarted, the application will relate to all I/O modules. After restart, the site’s I/O
configuration will also reflect the change in the I/O modules.

If a conflict arises between the I/O module configuration of an RTU associated with the
application and the actual I/O module configuration (as recognized by the Automatic
Recognition feature), an error will be sent to notify the user of incompatible definitions, and
the application will relate only to those modules which have no conflict.

When automatic recognition is set in the site configuration, the user cannot define I/O modules.
If the site configuration includes at least one I/O module, the user cannot enable automatic
recognition. In each case, the STS prompts the user to choose one option or the other.

5
Power Management

The ACE Power Management feature enables ACE3600 RTUs which run on batteries to
reduce the power consumption, and thus reduce the frequency of the RTU’s battery
maintenance. Power management is especially important for RTUs located in the field with
limited access, or RTUs integrated in systems with low levels of activities (i.e. RTUs are
frequently idle.)

Power management for an RTU is defined and implemented by the user using a ladder/‘C’
application program to control the power supplies in the system.

I/O modules and their power supplies are defined as new element types in the user tables. The
current state of the I/O module or power supply can be retrieved using a Scan(). A power
consuming element can be turned on/off as a result of an explicit user control.

IMPORTANT: It is the responsibility of the user when defining the application to


operate the RTU in accordance with its power management requirements. For
example, if the user tries to transmit data over a communication interface which has
been powered off, the transmit will fail (as it would in the case of a disconnected
cable.)

The following RTU components can be controlled using power management:

• I/O modules - Put an I/O module to sleep or wake up an I/O module according to the user
application request; retrieve an I/O module’s sleep mode.

• Power Supplies on the main power supply module, on the I/O modules, and on the CPU
board (i.e. belonging to the plug-in ports) - Turn power supplies on/off according to the user
application request; retrieve power supplies’ current state.

• LEDs – Disable LEDs after a pre-defined timeout.

The following system database tables control the power management: CPU Power Supply
[id:233], Main Power Supply 1 [id:234] and Main Power Supply 2 [id:235]. Also, DI and DO
tables can control the power management of DIs and DOs, respectively.

For details on ‘C’ functions used in power management, see the ACE3600 “C” Toolkit manual.

Configuration
A number of power management: configuration parameters are defined in the STS site
configuration, including LEDs operating mode, timeout for switching the LEDs off, and size of
the power manager’s message queue. For details, see Appendix A: Site Configuration
Parameters in the ACE3600 STS User Guide.

6
Constraints
Activities on the power supplies have latency (either because they are done through SPI
communication, or because it takes time for the power supplies’ hardware to stabilize.)
Therefore, a request to manipulate such a power supply is not immediately served. On the other
hand, we don’t want the process to wait for a response to the user’s request. Therefore, such a
request returns immediately and the user must check the hardware indications, (i.e. Get() the
hardware’s actual state) and act accordingly.

User requests are mutually exclusive. While the power manager processes a user request, it
disables rescheduling, preventing other requests from being simultaneously served.

7
Safe Firmware Download

A primary feature of the ACE3600 is the Safe Firmware Download. This feature ensures that
remote download of firmware to an RTU will not cause the RTU to become unreachable. This
feature is based on the concept that after new firmware is downloaded to an RTU and it is
restarted, the RTU should be able to communicate with the PC host which downloaded the
firmware. If it will not be able to communicate with the remote PC host, then RTU will roll
back to its previous firmware. This protects the RTU from a situation where a flawed firmware
image is downloaded and it becomes impossible to communicate with it remotely.

When an ACE3600 RTU is delivered from the factory, it contains the current firmware version
(primary image) in the Flash memory. It also contains a minimal bootstrap image in the Flash
memory, including the VxWorks operating system and a basic ACE application. The bootstrap
image enables you to start up the unit and download new firmware (in the unlikely event that
the unit cannot start up correctly with current loaded firmware, application and files.)

When the ACE3600 RTU is running, a new firmware version can be downloaded using the
ACE3600 STS Download feature from a remote/local host over the MDLC or IP network. In
the Download window, in the System File Settings, the ‘Evaluate request’ parameter (by
default enabled) instructs the unit to evaluate the newly downloaded image before making it
the primary image. Evaluation means the unit has received an evaluate request and then sends
an echo to the host STS within a period of five minutes after the new firmware download.
(The unit is rebooted 30 seconds after the end of the firmware download. The Evaluate request
is transmitted from the STS to the unit approximately every 30 seconds up to the five minute
limit).

If the downloaded firmware is evaluated and found to be problematic, the RTU will restart and
roll back to the earlier, robust, burned image, and a message will be displayed on the
Downloader screen. If the downloaded firmware is found to be sound, it will be burned to the
Flash memory and become the primary image.

It is recommended to always use the Safe Firmware Download.

A similar checks exists for site configuration files, where the system checks every new site
configuration that is downloaded. If there is a discrepancy between the I/O site configuration
in the ladder application and in the RTU, an error will be logged and the system will revert to
the previous configuration. See the Downloading to a Site section of the Operation chapter of
the ACE3600 STS User Guide.

Note that firmware files are large and may take a long time to download at low communication
speeds.

8
Flash File System

General
Information in the ACE300 RTU flash memory is organized and maintained as files in a flash
file system (Motorola Flash File System-MFFS). User flash files are created when the user
configures/administers the ACE3600 RTU using one of the STS utilities. In general, the user
will interact with these files via the STS GUI and the specific utility (e.g. Network Manager,
Phonebook, etc.) For those user files in flash which require handling outside the STS, high-
level file operations have been provided in the ACE3600 RTU ‘C’ Toolkit. These file
operations handle file pointers and low-level read/write operations and were designed to save
the user time and effort. For more information, see the ACE3600 RTU ‘C’ Toolkit User
Guide.

Note: System flash files cannot be accessed by the ‘C’ application. Burned system software
stored as a consecutive block instead of a flash file.

Associated with each user flash file type is a File ID, as shown in the table below.

File ID Description File ID Description


0 Ladder Application 33 X25 Address Table
1 Network Configuration 34 'C' Application Parameters without reset
2 PLC 1 35 Compressed Files
3 PLC 2 36 RDLAP Modem IDs Table
4 PLC 3 37 MAP27 Address Conversion Table
5 PLC To Master 1 38 NTP Configuration
6 PLC To Master 2 41 Feature File
7 PLC To Master 3 42 Modem Configuration PI1
8 Phone Book 43 Modem Configuration SI1
9 Sites Table 44 Modem Configuration SI2
10 'C' Application 45 Encryption File
11 Application Source 49 Modem Configuration PI2
13 TCP/IP Configuration 50 FPGA file for IO module
26 MOSCAD ACA Code 51 Predefined IO module values
27 MOSCAD ACA Data 53 Temporary Configuration File
29 'C' Application Parameters 56 Network Source File
30 Site Configuration 98 ACE Default Configuration
31 NetMon 'C' Application Parameters 100 Remote System File

9
File ID Description File ID Description
32 IP Conversion Table

In addition to user flash files, the user application can create log flash files (File ID #55)
during runtime.

User Generated Flash Files


Most of the files created and used by the STS are stored in the flash memory in a format which
is meaningful to the utility, and not to the user. The two files that are meaningful to the user
and should be accessible to the user application are the ‘C’ Application Parameters with Reset
files (File ID #29) and the ‘C’ Application Parameters without Reset files (File ID #34). These
files are created by the user offline (not during runtime) and are the responsibility of the user.

The File ID associated with ‘C’ application parameter files is determined by the choice of file
type in the STS Add-Ons Manager, as shown in the figure below. The file name extension or
suffix (e.g. .dat, .txt, etc.) is determined by the user. Most file types can have one instance in
the flash at any one time. ‘C’ Application Parameters files (with and without reset) can have
more than one instance (e.g. MyCfile.dat and MyCfile.txt).

Accessing Flash Files


The ACE3600 RTU ‘C’ Toolkit services enable the user application to access flash files by
either file ID (e.g. 29) or by filename (e.g. MyCfile.29). Where one instance of a file exists, it
can be accessed by file ID. Where more than one instance exists (e.g. MyCfile.dat and
10
MyCfile.txt) it should be accessed by filename. The ‘C’ application can also retrieve the size
of the flash file by filename.

Writing Flash Files


When the user downloads a file to the flash, all new data is saved as a temporary file
(fileID.tmp). The new file is validated by the system to ensure data integrity. If validation
succeeds, the temporary file is renamed (e.g. Myfile.<fileID>). If a file of that name already
exists in the flash memory, it will be erased and replaced with the new file.

Therefore, files of a file type which can have multiple instances in the flash (i.e. ‘C’ data
parameters) with different file name extensions (e.g. .dat, .txt, etc.) that are downloaded using
the *.* extension, should be given different filenames; otherwise the second instance of the file
will override the first instance which was just downloaded previously.

Note: There is no backup of old file versions.

In the event that a file download fails, the temporary file may remain in the flash memory, to
be overwritten the next time a file of that type is downloaded.

To clean up extraneous files from the flash, use one of the Erase Flash options in the ACE3600
STS Downloader utility.

Note: It is not recommended to create very large user files (greater than 1MB). Instead use
several smaller files.

Logging Flash Files


User logging flash files (e.g. database history files) are created and maintained by the user
application. The file ID of user logging flash files is 55. The format of the files is determined
by the user.

An advanced parameter which can be set in the STS site configuration determines the
Maximum size of Flash memory for user logging and the percentage of the flash to be used for
logging flash files.

The ACE3600 RTU ‘C’ Toolkit provides a number of specialized functions for performing
operations on user logging flash files, such as reading, writing, appending and removing
logging flash files. Information such as whether the logging flash file exists, the status of the
logging flash, the amount of free/used logging flash. For more information, see the ACE3600
RTU ‘C’ Toolkit User Guide.

Flash File Headers


All files in the flash memory include a 64 byte file header added automatically by the system
while the file is burned to the flash. The header includes information such as CRC, file name,
and the date and time the file was downloaded. When a flash file is read, the size of the file
which is returned includes the size of the header. To calculate the size of the actual contents of
a flash file (e.g. to copy the file contents to a buffer), you must subtract the size of the header.

11
Logging flash file headers are added automatically by the system. The logging flash services
provided by the ‘C’ Toolkit return the size of the file as well as the size of the file header.

Flash Files Diagnostics


Software diagnostics on the flash file system can be retrieved using the STS SW Diagnostics
and Loggers, Device MFFS. Level 0 provides information on the actual files in the flash file
system, and Level 3 provides information on the space available and in use in the flash file
system.

If after downloading a ladder application to the RTU, the site configuration information stored
in the RTU flash conflicts with that defined in the ladder application, the MFFS diagnostic will
list both files (although the ladder database and rungs will not be used.)

Under certain circumstances files are listed in the MFFS diagnostics but not used during
runtime due to integrity failures. For example: If the ladder was downloaded with the ‘Load
Only’ ladder application setting and the number of differentiators used in the rungs is different
than in the previously used ladder, then the new burned ladder will not be used.

Software diagnostics on the logging flash files can be retrieved using the SW Diagnostics,
Device LOGFLAS. Level 0 provides information about the logging flash status (current and
previous file and operations). Levels 1 and 2 provide information on the logging flash queue,
and Level 3 provides information on the buffers in use.

The list of application files in use that were loaded from Flash memory to RAM memory can
be retrieved using SW Diagnostics, Device FFILES Level 0.

12
Accessing Database Variables via
Coordinates

One of the most important features of the RTU is its database structure and concept (refer to
Appendix C: Database Tables and Types in the ACE3600 STS User Guide.) The RTU database
is divided into reserved and user-defined variables/constants, arranged according to various
data types (such as discrete inputs/outputs, value inputs/outputs, timers, parameters, etc.)

The application database is built as a set of tables, where each table defines a group of devices,
each row defines a separate device and each column contains a specific device data. The table
entries are assigned user-significant names, such as PUMP1.

Since database variables are assigned meaningful logical names, it is very easy to build,
understand and modify the database.

Two functions, FETCH and STORE, are available for accessing database variables also via
coordinates. Every database variable can be accessed by the following three coordinates:

• Z coordinate (Z=0,1,...,126) is the user table number in the RTU database

• Y coordinate (Y=0,1,...,249) is the row number in the user table that appears under the
index (Ind) column

• X coordinate (X=0,1,....,7) is the column number in the user table.

This way of accessing database variables may be useful for mapping the database of one RTU
into another RTU using user protocols (which use coordinates to access database variables
rather than logical names).

13
6BAccessing Database Variables via Coordinates

Definitions
Using the FETCH and STORE functions requires the definition of a single-column user table
of integer value type, with the following variables.

Note that the order of the variables in the table is mandatory. The variable names shown in the
table are recommended.

The first three values (Table#, Row# and Column#) represent the coordinates of the required
variable in the database. They must be set by the user before calling the FETCH or STORE
functions.

The FETCH/STORE call return code will be returned in the RetCod variable, as follows:

0 – OK
1 – spare
2 – invalid Z coordinate
3 – invalid Y coordinate
4 – invalid X coordinate

When calling the FETCH function, the required data will be put in Data0/ Data1 variables
according to the data type (specified by the ColTyp variable), as follows:

• If the data is of Bit type (ColTyp=1), the data will be put in Data0 variable according to the
following:

– If the data is 0, then Data0=0x0


– If the data is 1, then Data0=0xFFFF

• If the data is of Value type (ColTyp=2), the data will be put in Data0 variable.

• If the data is of Floating Point type (ColTyp=4), the data will be put in Data0 and Data1
variables.

Before calling the STORE function, the data to be stored in the database must be set as follows:

14
6BAccessing Database Variables via Coordinates

• If the data is of Bit type (ColTyp=1), the data must be put in Data0 variable according to the
following:

– If the data is 0, then Data0=0x0


– If the data is 1, then Data0=0xFFFF

• If the data is of Value type (ColTyp=2), the data must be put in Data0 variable.

• If the data is of Floating Point type (ColTyp=4), the data must be put in Data0 and Data1
variables.

For example, to store the value of fl1 (floating point variable) in the Z0,Y0,X0 coordinates, the
following rungs should be used:

Table#
( MOVE )
Z0

Row#
( MOVE )
Y0

Colmn#
( MOVE )
X0

C Data0
P fl1
Y #4

Store
( CALL )
Table #

#4 is a constant defined in a Constants table. Its value is 4 (4 bytes*8=32 bits).

15
Event Driven Software

Some applications, especially electrical ones and process control, have to deal with fast
changes caused by various events or follow these events with precise delay. The RTU provides
you with the necessary database types and special functions in order to deal with such events.

These functions allow you to get information on the change that has occurred (database
coordinates, data, and time stamp) and activate a specific process accordingly, rather than
polling the database. It also allows you to activate "fast" timers (shorter than Scan time) upon
events.

This chapter describes the event-driven Change-Of-State (COS).

The time stamp can also be retrieved without waiting for an event to take place and stored in
the Ladder Database.

Definitions

Data Type
The Event Driven concept is applicable only for Discrete Inputs of Time-Tagged DI (TgDI)
data type.

This data type is similar to the DI data type (see Appendix C: Database Tables and Data Types
in the ACE3600 STS User Guide.) Note that only the important inputs should be defined as
Time-Tagged DI, since this feature is CPU-time and space consuming. By calling the Time
function, a time stamp can also be retrieved and appended to an analog input called via the
SCAN function from the Ladder. This need not be related to a specific event.

I/O Link
The specification of a Time-Tagged DI as Event-Driven is done during I/O Link (accessed
from the Application Programmer). For details, refer to Application Programmer chapter of
the ACE3600 STS User Guide.

During I/O linking, each Time-Tagged DI may be defined in the Event Type column as one of
the following types:

16
7BEvent Driven Software

• TIMETAG – for time-tagged COS. Changes are stored in a time tag logger with the time of
occurrence in 1 msec resolution. For further details, refer to the ACE3600 STS User Guide.

• EVENT – for event-driven COS, described in this chapter.

• TAG+EVENT – for time-tagged and event-driven COS. A combination of the above two
types.

Event Driven Mechanism


When a COS occurs in one of the digital inputs defined as TgDI, the change is recorded in an
event queue, including the rack (frame) number, module number, and input number.

When calling the GtEvnt function, the event is transferred to the Event-Driven database table
(PRMEVENT table), while the rack (frame), module, and input numbers are translated into
X,Y and Z coordinates, (where: X=column no., Y=row no., Z=table no.). Simultaneously, the
corresponding table in the database is updated according to the change that has occurred.

The event's time (date and time) is written to the TmMost and TmLeas columns in the
PRMEVENT Table). These are two real type parameters, that represent the event's time as
follows:

TmMost TmLeas
Day Month Year Hour Minute Second mili-seco
1 byte 1 byte 1 byte byte 1 byte 1 byte 2 bytes
1-31 1-12 0-99 0-23 0-59 0-59 0-999

Since the tables can hold up to eight columns, all the time's parameters (day, hour etc.) are
arranged in two real type variables. In order to read specific information (e.g.: seconds), the
user should perform LSL (Logic Shift Left) or LSR (Logic Shift Right) for the relevant
variable, TmMost or TmLeas.

The number 0 in the YEAR byte (part of the TmMost) represents the year 1980, the number 1
represents the year 1981 etc. until the number 99 which represents the year 2079. (e.g.: 15
represents the year 1995).

17
7BEvent Driven Software

The system can simultaneously handle up to 150 events and timers. If there are more than 150
events/timers, the EvOvfl flag of the Reserved Flags table (one of the System Tables), will be
set to 1. In this case, it is recommended to clear the events queue (by calling the StEvnt
function), and performing ordinary scan.

The system can set timers for up to 10 seconds. If no event is read during this period of time,
the timer will be turned off, and the EvOvfl flag will be set to 1. It is the user's responsibility
to reset this flag to 0.

For operations that require delay, the RTU provides the SetTmr function. The end of the timer
is regarded as an event.

Event Driven Tables


The Event Driven software includes one System Table, named PRMEVENT. When you open
the PRMEVENT table, the following is displayed.

The PRMEVENT Table includes the following parameters:

• ___Typ – defines the type of event, as follows:

0 - there is no event in the queue (all other parameters are meaningless).

1 - there is an event in the queue (see other parameters).

2 - the event is caused by a delay timer (set by the SetTmr function).

3 - The RTU's time was set by the STS (using the STS Date & Time utility or Sync
command).

4 - The event is a power failure report.

5 - The existence of the time's parameters in the TmMost and TmLeas columns, is a result of
calling the Time function.

18
7BEvent Driven Software

• ___Tbl – the table number in the RTU database.

• ___Row – the row number in the table (___Tbl).

• ___Col – the column number in the table (___Tbl).

• ___Bit – the current status of the input.

• ___Val – the value for the timer (in x10 msec).

• ___TmMost – a four byte real number. Represents the following:


Day, Month, Year and Hour (1 byte each).

• ___TmLeas – a four byte real number. Represents the following:


Minutes, Seconds and milliseconds.

The two columns at the right of the PRMEVENT Table, show the time and date (TmMost and
TmLeas), in a readable format. The user may read these parameters on-line, by activating the
Monitor mode in the Application Programmer.

How to Use the Event Driven Software


The RTU provides you with three functions in order to implement the Event Driven concept, as
follows:

• GtEvnt – to retrieve an event from the event queue.

• StEvnt – to perform various functions, as follows:

♦ 0 – to clear the event queue (set value to 0).

♦ 1 – to disable the event-driven mechanism (set value to 1).

♦ 2 – to enable the event-driven mechanism (system default) (set value to 2).

• SetTmr – to start a timer after an event. The termination of the timer is also regarded as an
event (this timer does not depend on the Scan time). The value of the timer should be set in
the ___Val variable (in x10 msec).

The following rungs provide examples that cover all aspects of the Event Driven mechanism.

19
7BEvent Driven Software

Part of MAIN process

StEvnt
(1) ( CALL )
#2

GtEvnt
(2) ( CALL )

__Typ __Tbl
Procs1
(3) = ( JSP )

#0 #9

__Typ __Tbl
Procs2
(4) = ( JSP )

#0 #11

__Typ __Tbl
Procs3
(5) = ( JSP )

#0 #13

As part of the MAIN process, the above rungs check that an event has occurred, and fulfilling
certain conditions, activate appropriate subprocesses. The above rungs are described below:

Rung 1: The StEvnt function is called with a parameter of 2 to enable the Event Driven
mechanism. It is recommended to put this rung in the Init process.

Rung 2: The GtEvnt function is called; the system retrieves an event from the event queue
into the PRMEVENT table, including the event type, table number, column
number, row number, and data of COS.

Rungs 3-5: These rungs check the ___Typ variable and the affected table number; if ___Typ
is not 0 (meaning that there is an event in the queue), the system jumps to perform
a specific process according to the table number. For example, in rung 4 the
system jumps to the Procs2 subprocess since the table number is 11.

The rungs below describe the use of the timer function of the Event Driven mechanism.

20
7BEvent Driven Software

Part of Procs2 subprocess

I
(1) ( MOVE )
__Row

__Typ Inp1, I Inp2, I


Send2C
(2) / ( JSP )

#1
Inp1, I Inp2, I

__Typ Inp1, I Inp2, I


__Val
(3) ( MOVE )
#30
#1
Inp1, I Inp2, I
SetTmr
/ / ( CALL )

__Typ
Send2C
(4) ( JSP )

#2

(5) ( RET )

Rung 1: This rung stores the row number (___Row) in the I index.

Rung 2: If it is an event (not caused by a timer; ___Typ=1), and Inp1,I is not equal to
Inp2,I, then the system jumps to the Send2C subprocess to send specific bits to
the central.

Rung 3: If it is an event (not caused by a timer; ___Typ=1), and Inp1,I is equal to Inp2,I,
then the ___Val variable gets the value of 30 (thus, setting the timer to 300 msec),
and the SetTmr function is called to activate the timer. Note that the parameters of
the event are still kept in the PRMEVENT table.

Rung 4: If the event is caused by a timer (___Typ=2), the system jumps to the Send2C
subprocess to send the current status of Inp1,I and Inp2,I to the central.

Rung 5: Returns to the MAIN process.

In the MAIN process, you should add appropriate rungs to perform a loop, that checks if there
are additional events in the queue.

21
7BEvent Driven Software

Reading the TmMost and TmLeas Columns


The following rungs demonstrate how to read the time parameters from the PRMEVENT table.
The time parameter columns in the PRMEVENT table has two variables with seven parameters
each. When a specific parameter is required, the user should use the rotation functions LSL or
LSR (see Appendix B: Ladder Diagram Language in the ACE3600 STS User Guide) as
needed.

The following rung checks the analog value ANA1, and according to its value, activates the
Time function. This option allows the user to get the occurrence time of an analog event.

ANA1
Time
( CALL )
500+

To obtain the date and time, decode TmMost and TmLeast, as follows (provided that TmMost
and TmLeas are not zero and contain date/time information to be decoded):

Step 1. Define a set of user variables, as illustrated below. Variables 0 through 6 will get the
date and time components; variables 8 through 11 are auxiliary variables:

Data type: Integer Value (int)

Ind Name Value


0 Myear
1 Mmonth
2 Mday
3 Mhour
4 Mmin
5 Msec
6 Mmsec
7
8 Mv1
9 Mv2
10 Lv1
11 Lv2

Mv1, Mv2 (for TmMost) and Lv1, Lv2 (for TmLeas) must be consecutive.

Step 2. Define the following constants:

Data type: Int Constant

Ind Name Value


0 #4 4
3 #255 255
4 #8 8

22
7BEvent Driven Software

Step 3. Move the values as follows:

C Mv1

P TmMost

Y #4

C Lv1

P TmLeas

Y #4
Rung: r6

Mday
( MOVE )
Mv1

Mday
( LSR )
#8

A Mmonth

N Mv1

D #255

MYear
( MOVE )
Mv2

MYear
( LSR )
#8

A Mhour
N Mv2

D #255

Rung: r7

23
7BEvent Driven Software

Mmin
( MOVE )
Lv1

Mmin
( LSR )
#8

A Msec

N Lv1

D #255

Mmsec
( MOVE )
Lv2
Rung: r8

24
25
Fast Events

In order to execute the control program defined in the user application, the RTU performs all
functions written in the Ladder Diagram, one after the other. This is called a “scan”. After a
certain period of time, the RTU repeats this procedure. The period between two scans is called
“scan time.” During the scan, the RTU can respond to events or status changes in the devices
in the field, represented by database variables and values.

When an application requires a faster response to events than the scan time permits, fast event,
interrupt-driven triggers can be defined. Such a trigger activates a high priority fast process
which can react quickly to the physical change.

Events Triggers
The elements which can trigger fast events are:

• Digital Inputs

• Pushbutton PB2

• Delay Timers

Note: Analog inputs cannot be used to trigger fast events. If the application includes analog
inputs which require an immediate response, the user application itself should sample the
analog values frequently and activate the immediate process if needed.

Fast Event Definition and Configuration


Using the ACE3600 STS, the user can define the number of triggers, the number of fast
processes per trigger, and the size of the fast events queue.

The actual triggers and the high priority fast processes are defined using either the STS
Application Programmer (ladder diagram) or the ACE ‘C’ Toolkit (‘C’ code).
IMPORTANT: Fast events should not be operated both from a ladder diagram and ‘C’ code.

One event can trigger more than one fast process, and the same fast process can be activated by
more than one trigger.

The application can choose to activate the fast process(es) after a certain delay.

DI filtering (sampling to ignore spikes) and AI filtering (averaging of successive readings to


compensate for slight changes in analog readings) is generally defined in the advanced I/O
parameters during site configuration. In addition, APIs in the C toolkit enable the user to
change the filtering definitions during runtime.

26
8BFast Events

Fast Event Scheduling


An application which is constantly involved in fast scans and triggers, or a fast process which
is too time-consuming, may load the RTU to the point where it cannot function properly. The
proper balance between fast events and other runtime tasks should be found to ensure that the
system balance and scheduling are not impacted. In addition, the system keeps track of the
execution times of the fast processes and will produce an alert if they are too time-consuming.

The user is responsible for managing the fast events. If an error message is received that a fast
event process is consuming too many system resources, the user should act accordingly. The
system will not take any action other than reporting an error message.

Enabling/Disabling Fast Events


Triggers for fast events are enabled/disabled from ladder applications (using the TEN/TDS
operators) and from ‘C’ applications (using the MOSCAD_fastevent_enable_trigger,
MOSCAD_fastevent_disable_trigger services.)

T Proc T Proc
E Trig D Trig
N P1 S P1
where Proc is the process to be operated, Trig
is the trigger (PB pressed, DI change of state, or delay), and P1 is the trigger value (i.e. PB2,
DIx, # of delay seconds). See the application database Trigger States constants table for the list
of trigger definitions.

Notes:

• When enabling a trigger from the ladder application (using the TEN operator), make sure
to add a condition to the ladder rung.

• When enabling a pushbutton or DI trigger, the call to TEN should not be in a loop,
because once the trigger has been enabled, it is meaningless to enable it again.

• Generally, the ignition of a fast event trigger is preceded by the relevant logic in the
ladder. Ignition of a delay trigger does not necessarily include logic before triggering a
process.

• If there is a jump from the fast process to another rung, the compiler will produce a
warning, because this might lead to an infinite loop.

T Proc1
E FE_DI_COS
N DI,x
enables process Proc1 after DIx goes to state DI-COS.

T Proc1
E FE_PB_UP
N PushB2
enables process Proc1 after pushbutton PB2 is
pressed.

27
8BFast Events

T Proc1
E FE_DELAY
N #10
enables process Proc1 after delay of 10 seconds.

Monitoring of Fast Events


The user can monitor both the triggers and the fast processes, using either Process monitoring
in the STS Application Programmer (for ladder applications) or diagnostics APIs (for C
applications.)

When a fast process is monitored via the Application Programmer, the actual values of the
symbols received from the RTU during on-line operations are displayed. When a fast process
is monitored via a C application, system diagnostics (MOSCAD_get_sw_diag()) and user-
defined diagnostics (DCF6) can be used to keep track of the triggers, the time delays and the
processes’ execution (e.g. average/maximum runtime.)

Monitoring a rung with a call to the TEN (Trigger enable) operator will not provide any
meaningful information. Monitoring a fast process is not meaningful either, because the
monitor process has lower priority than the fast process. Therefore, software diagnostics are
the more useful way to follow the results of fast events.

Fast Events Diagnostics


Software diagnostics on fast events can be retrieved using the STS Software Diagnostics and
Loggers utility, Device F_EVNT.

Level 0 provides general information about the F_EVNT device configuration parameters and
overall execution (e.g. whether fast events are supported by the system software.)

Level 1 provides information about the last fast event, including errors that may have occurred.
At this level, you can verify that a delay trigger occurred (after the fact.) Errors that occurred
will also be reported to the error logger at the end of the fast process execution.

Levels 10, 11 provide information about DI triggers, and Levels 20, 21 provide information
about pushbutton triggers.

No diagnostics are provided for timer delay triggers.

Testing Fast Events


When programming an application with fast events, run several tests to determine the time
required by the application actually needs when running in the unit. Use the F_EVNT
diagnostics (e.g. ExecTm, Max ExecTm, and TmException) to verify that the fast process
executes without monopolizing system resources and choking the unit.

Note: If the application includes a jump from a fast process to another rung, the compiler will
produce a warning that this could lead to an infinite loop.
28
8BFast Events

In the event that a process monopolizes system resources and chokes the unit, a dump is made
to the error logger before the unit restarts. Once the unit has started up again, check the error
logger to identify the problem. Focus on the lines after “Reboot handler:” until
“prv_userrom_exec”. The figure below depicts such an Error Logger entry.

If, for some reason, the system is unable to initialize the fast event feature, the first line in the
F_EVNT level 0 diagnostic will indicate that ‘Fast event feature (F_EVNT software device)
disabled by system.’ Contact product support group.

Fast Events and Automatic Recognition


When the RTU is configured for ‘Auto I/O modules recognition at startup’, no I/O
configuration is defined for the site, because the unit identifies the I/O modules automatically.
Therefore, the ladder application will not include an I/O link table mapping the actual I/Os to
the application database. When programming a ladder application with DI fast events,
variables representing DI triggers are required as parameters to the TEN/TDS operators. If you
want to use DI fast events in a unit configured for Automatic Recognition, do the following:

1. In the site view, click on Upload.

2. In the Site Upload Form, select Site Configuration only and click on Upload.

3. In the popup Upload Notification dialog, click Yes to set the I/O Auto Recognition flag to
false in the site. This will enable the I/O configuration information to be saved.

4. Using the Application Manager, open the ladder application and define the database
variables required for the DI triggers.

5. In the application rungs, call the TEN/TDS operators with the trigger variables.

6. In the I/O link table, link the trigger variables to the actual DIs.

7. Compile and download the ladder application to the unit.

29
8BFast Events

For more information on Automatic Recognition, see Automatic I/O Recognition.

30
Network Configuration

The Network Configuration program is used for defining the communication nodes
(interconnection points between two or more links) in the network. The program defines the
network’s structure; there is no need to define all RTUs, only the nodes in the network. The
communication protocol uses these definitions for automatic routing of the packets through the
network.

In simple networks, such as one FIU connected to one communication link, it is not necessary
to use this program (see the Communication Network section in the ACE3600 STS User
Guide).

The RTU and FIU ports defined as Computer port, which serve as connection to the STS or
centrals, are not considered as links in the network but as local ports.

A network configuration is stored in a file. The network configuration can be loaded into the
RTU or FIU together with the application. During application loading, the user is asked to
provide the name of the network configuration file.

The same network configuration file is used for all the sites in the system and also may be used
in other networks that have the same structure. The network configuration must be loaded to
all sites in the system to enable each site to route the packets through the network.

When additional sites are to be added to the network, it is not necessary to change the network
configuration definitions since Network Configuration defines only the nodes in the network.
All you have to do is to define the main communication port of each site, via Site
Configuration, and to connect it to one of the network links, using the logical (symbolic) name
of the link.

The network table is generated automatically when using the STS to set up a system. The STS
Network Manager can be used to create additional network tables based on the specific
requirements of the system, and to associate those user-defined network files to the relevant
RTUs in the system.

Routing of Data Frames


The network configuration serves as an internal data bank which describes a path to each link
in the network. When data frames are to be relayed to another site, the node checks if it has a
direct link to the destination. If so, the data is transmitted. If there is no direct link, the unit
will use the network map to try to identify another path.

The STS SW Diagnostics device “NSTOCK” (Levels 2, 3) provides the full list of data links
(as defined in Network Configuration), and adds the status during runtime. The transmitting
node will search for a proper path (sequentially, starting with the first entry) until it is
successful. If some of the links are in “fail” state, the node will try the first link that is in
working order. If all possible links are in “fail” state, it will try the first path. If the
transmission fails, the frame is discarded, unless the “Remote Fail Link Awareness” feature is
enabled in the Site Configuration. (See Routing using Remote Failed Links Table below.)

31
9BNetwork Configuration

When a data link fails to acknowledge transmission, all network paths beginning with it are
marked as “fail” in the network data bank. The failed link can be restored to “OK” status if
another transmission happens to succeed. Another mechanism exists, whereby the network
performs periodic checks on failed links and restores them to “OK” status when an
acknowledgement is received. When this mechanism is disabled, the failed link is considered
to be restored after a specified period of time.

Routing over Alternative Direct Link


The Routing of Data Frames section above describes automatic routing between sites which are
not directly connected. The system will also perform automatic alternative routing between
nodes that are directly connected by more than one direct link (if one of them is failed). In
legacy systems, finding alternative communication routes across such systems was performed
by the user application.

All relevant links in the example below were defined in the Network Configuration and
downloaded to the units. This can be seen using the Software Diagnostics NSTOCK device
(Level 3). RTU100 will choose a link which is not failed for communication with RTUs 1-99
(as will be done in communication between RTU4 and RTU 88.) Thus if RTU100 is unable to
initiate communications with RTU2 over the radio link, due to a radio failure, it will
automatically attempt to communicate using the dial link. If no alternative links exist, or if all
fail, then the transmission will fail. In the case of a failed direct link (when an alternative
direct link exists), the recovery mechanism described above in Routing of Data Frames is
performed, according to the parameter settings in the site configuration.

RTU 1
RTU
101
RTU 2

L2
RTU RTU 3
PSTN
100

RTU 4

RTU 5

.
.
RTU 99

Routing over Direct Link is only possible with ACE3600 and the STS. If you upgrade old
legacy applications which try to transmit over alternate links, these should be modified to
prevent redundancy.

When RTU101 tries to transmit to one of the RTUs (1-99), the routing is actually performed by
RTU100. The behavior of the routing in the system, when one of the links to the designated
RTU is failed, is exactly as described in Routing over Alternative Direct Link above.

32
9BNetwork Configuration

Routing using Remote Failed Links Table


In early MOSCAD systems, if a communication disconnect occurred at a remote link (link
distance > 1) from the source (i.e. fail link), and the frame could not be transmitted, the frame
was discarded. The transmission could only be retried at the application layer (STS
communication, RTU-RTU, Burst.)

In current systems, when a system has a network structure which contains a loop, an alternate
routing scheme is feasible, i.e. the failed link can be bypassed and the frame can be transmitted
to the target unit. A node may also be enabled to choose an alternative path if the destination is
on one of its direct links. The routing is done using the data stored in the Remote Failed Links
Table. (The table can be viewed using the Software Diagnostics Level 5 device NSTOCK).
This data is collected by the transmitting unit if the Remote Failed Link Awareness option is
enabled.

A node that is not the originator of the frame that fails to forward an MDLC frame to the next
site, will return the frame to the originator (source) with additional information about the failed
link and site. A frame is returned only when no further routing is possible via all available
links. The site, the originator of the frame, and any site along the route all record the failed
links information in the Remote Failed Links Table. When a frame is to be routed by an RTU,
the failed links information from this table is used, as described in Routing of Data Frames
above.

If the ‘Do not route returned frame’ parameter in the site configuration is disabled, the returned
frame can be re-routed by the frame originator (before the application retry) using another path
from the network data bank, which does not include any failed links.

Failed link information is deleted from the Remote Failed Links Table upon link restoration
(when actual communication acknowledgement is received) as described above, or upon
timeout, as set by the ‘Remote Failed Links Table entry timeout’ advanced parameter in the
site configuration. When a communication to a failed link that is listed in the Remote Failed
Links Table is restored by actual communication, an additional transmission is generated to all
sites, notifying them to remove that entry from their table as well.

This feature can be enabled in the STS site configuration in the advanced parameters under
Network.

By default, routing using the Remote Failed Links information is disabled in the Site
Configuration making network behavior compatible with previous versions. To enable the
feature, the “Remote Failed Links Table size” must be greater than 0, and the “Time to Live
Preset Value” must be greater than 0. To enable the originating unit to resend the information
before the retry, the ‘Do not route returned frame’ parameter must be set to “NO”. (Avoid
using this unless necessary.)

If an RTU identifies more than one failed link during the same frame transmission, it updates
the Remote Failed Link Table with a general failure code, rather than specifying all the various
failed links. (The failed link entry will be marked with Link ID 255.) If any one of these links
is restored, the entry is removed from the Remote Failed Link Table and all failed links are
considered restored.

In order to prevent endless transitions between RTUs until a failed link is restored, set the
‘Remote Failed Links table entry timeout’ parameter in the site configuration to a value greater

33
9BNetwork Configuration

than the maximum of link retry timeouts (‘TX to failed RTU’ parameter) defined for all of the
RTU’s ports and the ports of neighboring RTUs.

The behavior of broadcast frames differs from that of other communications. A failed
broadcast frame does not cause the Remote Failed Link Table to be updated. A failed
broadcast to Site ID 0 does not seek an alternative path. A failed broadcast distribution to other
nodes where the ultimate destination is Site ID 0 does seek an alternative path.

This feature is intended to work in a simple looped shape network. Using it over a complex
multi-loop network may result in communication performance degradation, due to the heavy
communication required to maintain the Remote Failed Link Table information.

IMPORTANT: When setting this feature, all RTUs in the system must have a firmware
version that supports this feature.

Note: If the size of the Remote Failed Links table is increased substantially, you may need to
increase the ‘Stack size of application manager task’ parameter in the site configuration in the
Session category of the advanced parameters.

Using the Time To Live Counter


The Time To Live Counter feature prevents continuous transmissions in a loop shaped
network. Each frame is supplied with a counter set to the ‘Time To Live preset value’ by the
frame originator. The counter is decremented by one each time it passes a node. A node will
forward a frame as long as the counter is greater than zero. When the counter reaches zero, the
frame is discarded and the diagnostic information is stored. Use the Software Diagnostics
device NETWRK Level 11 in the Logger tool to view the information.

The Time To Live preset value is set in the STS site configuration. (See the ACE3600 STS
User Guide.) By default it is set to zero and the feature is disabled. This makes the network
compatible with previous versions. To enable the feature, set the value to be greater than twice
the longest path in the network (maximum numbers of nodes in the entire longest path).

The Time to Live feature is activated in the STS site configuration in the advanced parameters
under Network.

IMPORTANT: When setting this feature, all RTUs in the system must have a firmware
version that supports this feature.

34
MDLC over IP Communication

Overview
ACE3600 RTUs can use IP (Internet Protocol) technology to interface to advanced radio
infrastructure (e.g. TETRA or GPRS) and to standard private IP networks. Most benefits of the
MDLC protocol are preserved. MDLC and IP networks can be integrated in the same system,
as networking properties are preserved. MDLC applications need not be modified as the lower
layers of the protocol support IP.

MDLC packets to be transmitted are enveloped inside UDP/IP datagrams and sent between
remote RTUs or between an IP Gateway and an RTU over UDP port 2002. UDP Port number
is configurable for each port.

The ACE3600 RTU can have several MDLC over IP ports, each identified by its own link ID:
MDLC over RS232 PPP ports, and MDLC over LAN/Ethernet ports that can have static or
DHCP addressing modes. In some cases it is required that an MDLC over IP port have more
than one link ID.

Each MDLC over IP port has its own unique link ID. An IP address identifies each port, and is
set by the user in a static LAN port. For DHCP and PPP this address is learned automatically,
and the user does not need to define it.

A PC running STS can be connected to one of the RTU ports, to one of the serial ports of the
IP Gateway, FEP or to the Ethernet.

An MDLC over IP port can be used in one of four ways:

1. ACE3600 RTU port connected to a packet data radio/modem over PPP (Point to Point
Protocol). The RTU can act as a remote unit or as a front end serving a SCADA control
center (over PLC or user port).

2. ACE3600 RTU port connected to a LAN through one of its on-board or plug-in Ethernet
port. A direct LAN connection exists between the Ethernet port and the radio
infrastructure. The RTU can act as a remote unit or as a front-end serving a SCADA
center. This port can be configured as static LAN or as DHCP LAN.

3. ACE3600 FEP connected to LAN. An FEP serves as a front-end for a TCP/IP based
SCADA central and enables it to communicate with remote RTUs. The FEP can use
MODBUS over RS232 or any other propriety protocol over RS232 or LAN to
communicate with the SCADA. If a LAN is used, the ‘C’ Toolkit socket (user protocol
over IP) functions provide that functionality. The ACE36000 RTU can use a direct LAN
port connection with other RTUs over the radio infrastructure. It can also be connected
with a packet data modem/radio over PPP. For information on the ‘C’ Toolkit socket
functions, see the ACE3600 RTU ‘C’ Toolkit User Guide.

4. IP Gateway connected to LAN. An IP Gateway (IPGW) serves as a front-end for a TCP/IP-


based SCADA central and enables it communicate with remote RTUs. The IPGW uses a
direct LAN connection to the radio infrastructure. It cannot be connected with a packet
35
10BMDLC over IP Communication

data modem/radio over PPP. For this purpose an RTU (with packet data radio/modem) is
needed with RS232/RS485 to connect them.

Note: Although the ACE3600 RTU has Ethernet ports, it does not have the IP Gateway
functionality for connecting to a SCADA, nor can it be using with the EPIB Interface for that
purpose. If needed, use the IP Gateway instead.

Broadcast and Setcalls


Most wireless packet data networks do no support broadcast IP. When transmitting a group
call (Site 0), a separate frame is transmitted to each site specified in the IP Conversion Table
over UDP/IP. If broadcast IP exists, then this IP can be specified in the IP Conversion Table
under Site 0 with the proper link ID (port). Sending to Site 0 with that link ID will transmit a
single message, through that port, to all RTUs over UDP/IP using that address. Note that in
ASTRO IV&D, GPRS, TETRA and most wireless media, this is not supported, so a separate
message is transmitted to each site. It is preferable to transmit to each site separately, rather
than send this setcall, with a delay around 100-300 milliseconds between one transmission and
another.

New Features for MDLC over IP in ACE3600


The following features are available in ACE3600 that are not available in legacy MOSCAD
RTUs and IP Gateway. These features apply to Ethernet static, Ethernet DHCP, and RS232
PPP port types.

Multiple IP Ports
The user can specify more than one MDLC over IP port in ACE3600. This depends on the
media used, if Ethernet port can be set as Static LAN, or DHCP and if port is RS232 port can
be set as PPP. Each port is assigned its own Link ID. The IP Conversion Table includes a link
ID column which enables the same ACE3600 site ID to appear several times, with a different
link ID and appropriate IP address.

In some cases, it is necessary to have more than one link ID per MDLC over IP port. For
example, if RTU 1 has a single Ethernet MDLC over IP port, and communicates with another
RTU that has two (or more) MDLC over IP ports (Ethernet or PPP), LINE1 and LINE2. In this
case RTU 1 must have its MDLC over IP port with two link IDs: LINE1 and LINE2. This will
enable direct communication with RTU 2 LINE1 and RTU 2 LINE2 ports.

IP Conversion Table Enhancements


An IP conversion table can be assigned to each RTU/FEP. It maps each site ID+link ID (port)
to an IP address. The link ID column supports multiple MDLC over IP ports per RTU. Each
link ID uniquely identifies the port/IP connection of that RTU. The table enables the MDLC
over IP port to transmit MDLC packet to its destination based upon its site ID and link ID
(port).

36
10BMDLC over IP Communication

The enhanced IP conversion table also supports the user of a host name instead of a numeric
Ipv4 address (IP address). In order to use host names, the operator must support this in the
network DNS Server, and the user must specify them in the appropriate port configuration.

The IP conversion table is dynamic, which means its numeric addresses are automatically
learned/updated in runtime, for example when a new RTU is added, or an existing one changes
its addresses. In some cases, such as dynamic addresses of RTUs, there is no need to download
that table to FEP, simply because RTUs addresses are updated when they transmit to the FEP.
In this case, it is recommended that the user application perform these transmissions
periodically.

Note: The IP conversion table learns only a numeric IP address. Host names of other RTUs are
never learned.

Using Host Names


Sometime it is necessary to refer to an RTU or FEP using a host name rather than a numeric IP
addresses. Any MDLC over IP port (Ethernet or PPP) has that option, however it is the
responsibility of the user and network to make sure this is supported.

In the IP conversion table, set a host name instead of a numeric IP address for a specific site +
link ID. The link ID, for example LINE5, identifies the port/IP connection of that site.

To enable this, the port needs the list of DNS servers for that MDLC over IP port. This step
can be automatically learned. The list must be set only for an Ethernet port configured as Static
IP address mode. An Ethernet port configured as DHCP or an RS232 port configured as PPP
automatically learns this list from the network, and the user does not need to set them.

Note: Some PPP connected radios such as TETRA MTM700 and ASTRO IV&D radios do not
provide DNS information. These systems usually do not use host names either, but if
necessary, the user can set the list of DNS Servers in the port configuration.

The FQDN option for an Ethernet port configured as DHCP updates the DNS servers when a
new IP address is allocated to it by DHCP. The user need only set the full host name of that
port. A warning is logged if the router/DHCP server does not support this option,

Configuring NTP Servers


An Ethernet or PPP port can be configured for NTP protocol (NTP is UDP port number 123.)
In this case, the RTU will retrieve its time from a set of NTP servers specified by the user. The
clock offset between the RTU and these servers depends on network delays, and may be up to
100 milliseconds in some wireless media. The clock offset on LAN in the same Ethernet
network is approximately 1 millisecond.

Note: It is possible to define an NTP server with a full host name (e.g. www.mysite.com). To
do so, the user must set DNS servers for this port, either statically, or from a DHCP server or
PPP modem.

37
10BMDLC over IP Communication

User Protocol over IP


Both Ethernet and PPP ports provide an interface for a user application written in the ‘C’
Toolkit using MOSCAD_socket() functions, also known as “User protocol over IP”. An
MDLC over IP port can serve a user application at the same time as it serves MDLC which is
built in the socket API. MDLC takes one logical UDP port number (2002 by default); other
applications can use other TCP or UDP port numbers. For more information on the ‘C’ Toolkit
socket functions, see the ACE3600 RTU ‘C’ Toolkit User Guide.

Dynamic IP Address
Many wireless networks do not allocate a fixed IP address to a PPP modem such as the GPRS
modem. For the FEP to communicate with the RTU it must know its address or host name.
Since these networks do not provide a name for each modem, there is no option of setting them
in the FEP beforehand. In this case, the FEP should not be assigned an IP conversion table
with that link ID (port). The RTUs should be associated with a table which has the FEP’s IP
address. If the network operator assigns a host name to the FEP instead of a numeric address,
this can be set in the IP conversion table. When the RTU detects that its modem is connected,
it will notify this address, the FEP, of its new IP address, thus updating its table in runtime.
Since this process does not guarantee that the FEP will be updated, it is highly recommended
that user application periodically send a message to the FEP. For example, if the user
application expects an interrogation every two minutes from the FEP, and it has not received
that, it should send a message to the FEP. This will update the RTU address in the FEP.

MDLC over IP Port Routing


In the example mentioned in Dynamic IP Address above, for RTU-to-RTU (modem to modem)
communication, set ‘Enable routing of MDLC over IP port’ parameter in the FEP. Then assign
to the RTUs an IP conversion table which list the RTUs’ site IDs as having the FEP IP address.
When one RTU transmits to another, the transmission will go through the FEP which will route
it to its destination, without the need of a network configuration.

Note: This feature can also be used in an FEP connected to the CEN of ASTRO IV&D, where
it is required for one RTU connected to a radio to communicate with another RTU.

Downloading Modem Configuration Files


A modem configuration file (.stm) used for programming a modem can be downloaded to a
port configured for MDLC over IP/PPP or for dialup. The modem configuration files provided
with the system can be found in the [C|D]:\STS<version>\config directory. Before
downloading the modem configuration to an ACE3600 RTU, you must attach the file to the
port using the STS Add-Ons Manager. Specify the port (e.g. Modem Configuration PI1) in the
Add-Ons Manager. The modem configuration file will be stored under the
[C|D]:\STS<version>\System directory. Attach the file to all sites in the project which require
this modem configuration on that port.

For more information on attaching files using the STS Add-Ons Manager and downloading
files to the RTU, see the ACE3600 RTU User Guide.

Note: If you try to attach the same modem configuration to more than one port in the same
site, an error will be displayed. In this case, simply rename the file name.

38
10BMDLC over IP Communication

MDLC over IP/PPP Connections


The ACE3600 RTU can include up to four PPP ports - two on-board (SI1 and SI2) and two
plug-in RS232 ports (PI1 and PI2.) Each port may be PPP connected to a packet data
radio/modem over PPP and have its own link ID.

Several RS232 over PPP connections are supported:

• MDLC via IDEN modem (e.g. iM1000, iM1500)

• MDLC via Astro IV&D digital radio (e.g. XTL5000)

• MDLC via Standard modem (e.g. GPRS g18 data modem.) See MDLC over Standard
Modem Setup for configuration details. A modem configuration file must be attached to
the site and downloaded to the RTU when using this connection.

• MDLC via Tetra radio. This is similar to Standard modem. See MDLC over Tetra Setup
for configuration details. When using a Motorola radio (e.g.MTM700), no modem
configuration file needs to be downloaded.

• MDLC via Null modem. This is suitable for direct cable connections over PPP with
devices such as Terminal Servers, wireless modem, etc. Depending on the modem used
you may or may not need to download a modem configuration file.

• MDLC over ASTRO IV&D. See MDLC over ASTRO IV&D for configuration details.
When using the ASTRO IV&D (Integrated Voice & Data) connection, no modem
configuration file needs to be downloaded.

In order for a variety of modems to be used, a modem configuration file is downloaded to a


specific port configured for MDLC over IP. The modem/radio can also be diagnosed using AT
commands specified in that file. For MDLC over IP this feature is applicable to all
connections: Standard Modem, Null Modem, Tetra, iDEN, and ASTRO IV&D. Note: The
same modem configuration file can be used when configuring a port for MDLC over IP or
when configuring the port for dialup. For details, see Modem Configuration File below. Note
that for iDEN, Tetra and ASTRO IV&D the modem configuration is not required, since the
firmware already has these commands built in.

MDLC over IP/LAN Connections


The ACE3600 RTU can include one on-board 10/100 Ethernet BaseT port (ETH1) (not in
ACE3610) and up to two plug-in 10/100 BaseT ports (PI1 and PI2.) Each Ethernet port has its
own link ID and can be connected to the same or to a different network mask.

An Ethernet (LAN) port can be configured in one of the following modes:

• Static IP address mode. See MDLC over LAN/Ethernet for more information and Static IP
Address Configuration for configuration details.

• Dynamic (DHCP) mode. See MDLC over LAN/Ethernet for more information and
Dynamic Configuration over IP using DHCP for configuration details.

39
10BMDLC over IP Communication

STS PC Communication Setup Options


In order to communicate with RTUs and IP Gateways, the ACE3600 STS computer can be
connected in one of three ways. The Communication Setup utility is used to configure the
setup.

1. Serial port connection - The serial port of the PC is connected to the computer port of an
RTU or IP Gateway.

2. Ethernet port connection – The PC’s Ethernet connection is connected to a LAN via an
RTU or IP Gateway. In the Comm Setup utility, select Ethernet Port and set the Local IP
Address to that of the RTU or IP Gateway.

3. Peripheral Interface connection – The PC’s serial port is connected to a phone or a modem.
The STS can communicate with other RTUs/IP Gateways which are attached to
radio/modems. In the Comm Setup utility, select Ethernet Port and set the Local IP
Address to that of such an RTU. Note: The user must get access permission from the
provider to communicate with that RTU. A RAS connection such as Standard Modem
must be set up in the PC. Run the Phonebook Editor/Dialer and "dial" into the
modem/radio before running STS.

Note that it is possible to change the MDLC communication settings without stopping the
MDLC communication driver, by right-click on the MDLC communication driver icon in the
system tray, and selecting Change Settings.

For more information on using the STS Communication Setup and Phonebook Editor/Dialer,
see the ACE3600 STS User Guide.

MDLC over IP Setup


The general setup described below applies to all variations of MDLC over IP where the RTU is
connected to the IP via phone/modem or LAN. For the actual values to be assigned in the site
configuration (port type and parameters) refer to the appropriate setup section for variation.

1. Define the site configuration for either on-board serial or plug-in port, according to the
options below:

For IP connections via RS232/PPP, the port type will follow the form of:
RS232, Async, Connection Type, Connection Mode

where Connection Type is PPP and Connection Mode can be any of several
options, such as Tetra, iDEN, Standard Modem, etc.

For IP connections via LAN, the port type will follow the form of:
10/100 BT, Address Mode, Connection Type, Connected To:

where Address Mode is either DHCP Client or Static LAN, Connection Type is Ethernet
and Connected To is LAN.

Several advanced parameters will be set in accordance with the port configuration. The
parameters for MDLC over IP are described in detail under RTU Site Configuration for the
40
10BMDLC over IP Communication

MDLC over iDEN option below. For changes to these parameter settings for other
variations, see the specific setup section.

2. Define the IP conversion table using the IP Conversion Table Manager and attach it to the
site as an add-on file.

3. Where a modem configuration file is used, attach it to the port as an add-on file.

4. Download the site configuration and IP conversion table, the modem configuration file,
where relevant, the network configuration, and, if necessary, applications, etc. to the RTU.

5. Verify that the RTU can successfully communicate over IP via the radio/modem.

MDLC over IP Site Paging


A paging mechanism is available in each site (peer) to make MDLC over IP more reliable.
(This feature is the same as in Toolbox 9.54 and MOSCAD 9.25.) Paging a site before
transmitting MDLC data to it over IP, guarantees that the site is reachable. This is necessary
because MDLC over IP does not have a confirmed type of link in which the peer acknowledges
received packets (as opposed to other types of MDLC ports). It relies on the radio to have a
link layer that will guarantee a ‘best effort’ delivery, and thus avoids overloading the channel
with excessive traffic.

A site is paged by sending it a poll request and awaiting a poll reply. During this time, the
RTU can continue to transmit to other sites (and receive transmission from other sites). If the
site responds with a poll reply, or any other MDLC data, it is considered as reachable, and all
pending transmissions are sent to it immediately. Further transmissions will be sent to it as well
without paging until the site is declared as failed.

If an ‘ICMP Destination Unreachable’ message is received or if the site does not respond to
paging for a configurable poll interval, it will be polled again for a maximum number of polls.
If there is still no response, the site is considered to be failed, and the network layer is notified
so any pending transmissions can be redirected to an alternative route. If subsequent
transmissions are to be sent to the site through an MDLC over IP port, paging will be
performed again before actual transmission takes place.

The Site Paging mechanism can be enabled or disabled.

When using modem devices iDEN, Tetra, Standard and Null modem, all sites are reset to
unknown state when disconnecting and reconnecting the modem/cable to RTU. For ASTRO
IV&D because no DCD exists, the RTU detects the lack of signal from the port several seconds
(40 by default) after the data cable is disconnected, or the radio is powered off. As a result,
following this operation, paging will be performed before a transmission is sent.

With non-modem devices, such as MDLC via Ethernet, reconnecting cable will not cause
paging to be performed.

Three parameters (Check Alive timeout in seconds, Poll interval in seconds, and Maximum
number of polls) have been added to the Advanced Link layer for paging purposes and are
described in detail in the Advanced Link Layer section under MDLC via iDEN. For each
variation of MDLC over IP, the parameter setting may vary.

41
10BMDLC over IP Communication

MDLC over LAN/Ethernet


The ACE3600 RTU can communicate over Ethernet media, via the onboard Ethernet port
(where relevant) or 10/100BT plug-in ports.

The figure below illustrates an example of a SCADA system with IP Gateway and ACE3600
RTUs connected to Ethernet LAN:

SCADA
Central
STS
Ethernet 1

LINE 1
IP
RS-232 Gateway

STS
IP
Network

Ethernet 2
Ethernet 3

10BaseT 10BaseT
10BaseT

RTU-IP1 RTU-IP2 RTU-IP3


RS-232
STS on Ethernet on Ethernet
on-board Port Plug-in Port

With SCADA systems, the ACE3600 RTU can be connected to Ethernet/LAN as an FEP (FIU)
for a SCADA, and an RTU. It communicates with MDLC over IP between FEP/IP Gateway
and RTU. The IP Gateway’s unique functionality provides an API over TCP/IP API, for the
SCADA PC. It provides the SCADA with the current values of the RTU tables and with the
events (Bursts) that are associated with each entity. The ACE3600 does not have that
functionality built-in and requires an IP Gateway.

Unlike IP Gateway, the ACE3600 can be connected to several Ethernet connections. They can
reside on the same or on different network subnet masks, and are distinguished from one
another by a link name.

A number of connection methods are available when configuring an Ethernet-based RTU port:

1. Static IP address – The user sets the IP address within the configuration of the device in the
STS. To use this method, follow the instructions for configuring an RTU port in the
Operation chapter in the ACE3600 STS User Guide. All DHCP parameters will remain at
default values.
With static IP address mode, the user is required to set the link ID, IP address, subnet mask
and default gateway. If DNS or NTP servers are required, these must be defined as well.
DNS servers are only required if this port is to be accessed via a host name rather than a

42
10BMDLC over IP Communication

numeric IP address. In this case the operator assigns a host domain name to the FEP or
RTU. The IP conversion table must include the domain name well. If an NTP server is to
be used to obtain the time, the numeric IP address or domain name of the NTP server must
be defined.

2. DHCP-supplied reserved IP address – For every ACE3600 RTU Ethernet port, an IP


address will be reserved within the DHCP server. The link between the RTU and the
reservation will be based on unique ID. In the DHCP Server, set the unique ID. The
default unique ID is the MAC address.
In the DHCP server, define a reservation for a specific RTU based on its MAC address.

3. DHCP-supplied dynamic IP address – A dynamic IP address is distributed from the DHCP


server to the ACE3600 RTUs. The IP address of each ACE device is unpredictable. In this
case you will need a DNS server that will resolve the link between the IP address and the
RTU. You will have to supply a name for each RTU. This name will be updated within
the DNS server along with IP address of the RTU. Within IP conversion table of ACE3600
RTU you will use this DNS name instead of IP address.

In DHCP address mode, the user is only required to set the link ID for this port. If DNS
servers are required there is no need to set them, since they are learned from the network. If
NTP servers are required, the user must set them since they are not learned from the
network.

As an option, user can set a full host domain name for an Ethernet port that is configured as a
dynamic DHCP client. Each port should be set with a different name. This option allows the
network DNS servers to be updated when the DHCP server changes its IP address, keeping its
name up to date. This is called FQDN and is not always supported by the DHCP server (in this
case a warning is logged.)

In order to comply with IP networks standards, all configuration methods described in this
chapter are based on standard procedures used in IP networks.

Static IP Address Configuration


The user should configure the RTU Ethernet port in the site configuration as follows:
10/100 BT, Static LAN, Ethernet, LAN

Static IP Address Link Parameters


Self IP Address
Range: 000.000.000.001-255.255.255.254

IP address of the RTU Ethernet port. For information on this and other IP addresses in the
configuration, see your network administrator.
Default Routing IP Address
Range: 000.000.000.001-255.255.255.254

This serves as the router from the network address to the remote IP network. The IP network
mask of this address should be the same as the Self IP address. For example, if the IP network
mask is 255.255.255.0 and the Self IP address is 155.9.199.235, then 155.9.199.1 is a valid
default routing address. All IP datagrams transmitted to remote networks outside of
155.9.199.xxx will be directed to 155.9.199.1 router.
43
10BMDLC over IP Communication

This parameter is optional, in case IP Conversion Table has addresses beyond 155.9.199.xxx
for that port’s Link ID. If all RTUs, FEP and IP Gateway reside on 155.9.199.xxx it can be
0.0.0.0.
IP Network Mask
Range: 000.000.000.000-255.255.255.255

This parameter is required and determines the network mask along with Self IP address.

If a default router was specified, its network IP address (the logical AND of its IP address and
IP network mask) should be the same as the network Self IP address. For example, if the Self
IP address is 155.9.199.235 and network mask 255.255.255.0, the default router should be
155.9.199.xxx (for example 155.9.199.1).

Other Link Parameters


Links: Range: LINE 1-LINE 29.

Default: LINE 1

User can assign more than one link name. ACE3600


supports several link names on the same MDLC over IP
port. This feature enables RTU #1 that has one MDLC over
IP port, for example ETH1, to communicate directly with
RTU #2 that has two MDLC over IP ports, LINE1 and
LINE2. In this case, assign LINE1 and LINE2 to the RTU
#1 MDLC over IP ETH1 port.

DNS Servers As an option the user may enter up to three DNS servers.
This step is only necessary if using host names for this
specific link in the IP conversion table.

NTP Server As an option user may specify up to three NTP Servers. If


defined, they will be polled for the time of day every 2
seconds-17 minutes. Expect a clock offset of 1 millisecond
if connected to the same network, and a tenth of a
millisecond if connected to different networks. The NTP
server can be an Internet server or an ACE3600 FEP. If it is
an FEP, it is up to the user to set its clock. Note that in
ACE3600, a 1 millisecond drift occurs every 2 minutes, if
not connected to external sync source such as NTP or GPS.

Dynamic Configuration over IP using DHCP


10/100 BT, DHCP Client, Ethernet, LAN

Ethernet ports of the ACE3600 RTU can be configured dynamically using DHCP. Each one of
these ports can be configured as a DHCP client.

44
10BMDLC over IP Communication

When such a port is configured as a DHCP client, it will receive several vital IP parameters
from the DHCP server such as IP address, Subnet mask, Default router, etc.

MDLC over DHCP Link Parameters


The following parameters must be configured for each IP port in the ACE3600 RTU. The
values chosen for the parameters will define the method in which the ACE3600 fits into the
network.

Links: Range: LINE 1-LINE 29.


Default: LINE 1
User can assign more than one link name. ACE3600
supports several Link names on the same MDLC over IP
port. This feature enable RTU #1 that has one MDLC over
IP port, for example ETH1, to communicate directly with
RTU #2 that has two MDLC over IP ports, LINE1 and
LINE2. In this case, assign LINE1 and LINE2 to RTU #1
MDLC over IP ETH1 port.

Host Full Name Range: free text format.


Default: empty string.
If user specifies a string, this should be the full name of the
port as provided by the DNS Server. The DHCP Server will
update the DNS Server when allocating or changing the IP
address of that host, keeping it up to date with the recent
address of port. This is called FQDN. If a DHCP
Server/router does not support this option, a warning will be
logged.

DNS Servers A user may enter three DNS servers, though this step is not
necessary since it is learned from DHCP Server. Note also
this is only required when using host names for this
specified link name in the IP conversion table.

NTP Server As an option the user may specify up to three NTP Servers.
If defined, they will be polled for the time of day every 2
seconds-17 minutes. Expect a clock offset of 1 millisecond
if connected to the same network, and a tenth of a
millisecond if connected to different networks.
The NTP server can be an internet server, or an ACE3600
FEP. If it is an FEP it is up to the user to set its clock. Note
that in ACE3600 a 1 millisecond drift exists every 2
minutes, if not connected to external sync source such as
NTP or GPS.

MDLC over DHCP and Static LAN Advanced Link Parameters


The following parameters must be configured for each IP port in the ACE3600 RTU. The
values chosen for the parameters will define the method in which the ACE3600 fits into the
network.

45
10BMDLC over IP Communication

The following parameters are common to all Link names configured for this LAN port. They
are the same for DHCP client and for Static LAN.

MDLC over IP port Range: 1-65535


number Default: 2002
This number is common to all RTUs and IP Gateways
connected to this link. This number identifies the MDLC.
This is a UDP port number and the provider should be
consulted.
It is important that this number not be in use as specified
by the TCP/IP standard RFC0960.
Enable Sync Range: Disable/Enable
Default: Disable
If this parameter is Enabled, this port can send an MDLC
Sync to other RTUs, and receive an MDLC sync.
If this parameter is Disabled, this port does not send an
MDLC Sync, and ignores received sync frames. It can
however forward sync words that were initiated from
other Link IDs, or from the STS.
It is recommended to use the NTP protocol instead for
time settings.
Notify IP Address Range: Disable/Enable
when connected Default: Enable
When enabled, if an RTU’s IP address is changed or
obtained from a modem, the RTU will send a message to
update its IP Address in all sites.
Note: These messages are sent one after the other, and it
is not guaranteed they will be delivered and accepted.
Enable routing on Range: Disable/Enable
MDLC over IP port Default: Disable
When enabled, an RTU or FEP can route back MDLC
over IP packets received that were destined for a different
site ID. When disabled, an RTU or FEP ignores packets
received which are destined for other sites.
This parameter allows two RTUs to communicate via this
RTU, and is useful if they have dynamic IP addresses.
Note also that the RTUs need to transmit periodically in
order for their IP address to be updated in its IP
conversion table.
A paging mechanism to each site (peer) in IP conversion table makes MDLC over IP more
reliable. The following parameters have been added to Link layer and are optional. For more
information refer to MDLC over IP Site Paging.

46
10BMDLC over IP Communication

Check Alive timeout in Range: 0-65535 sec


seconds Default: 35
Specify timeout in seconds from the last reception from a
peer. If nothing has been received from the peer during
that timeout, it will be paged before the next transmission
(see below). This behavior guarantees that a peer will be
reachable over IP. If it does not respond, route
transmissions to it through alternate routes.
Check alive timeout is measured independently for each
site in the IP conversion table.
If this parameter is 0, a peer will always be considered as
reachable, once a single reception has been received from
it.
This parameter is considered to be 0 regardless of its
value if ‘Maximum number of polls’ is 0.
Poll interval in Range: 0-65535 sec
seconds Default: 10
Specify interval in seconds between polls of peer. When a
peer is being paged, a poll request is sent. If no answer is
received after that period of time, another poll request
will be sent until the Maximum number of polls was sent
(next parameter).
Poll interval is measured independently for each site in
the IP conversion table.
If this parameter is 0, a single poll (or no polls) will be
sent to the peer according to Maximum number of polls
(0 or not.)
Maximum number of Range 0-255
polls Default: 3
Specify the number of poll requests to send in order to
check if the peer is alive. When paging a peer, if no
response is received, it is polled again. If the peer has
been polled for the Maximum number of polls without
answering, it is considered as failed, and all transmission
are routed through an alternate path.

MDLC over iDEN


With SCADA systems, ACE3600 RTUs can be connected to iDEN iM1000/iM1500 modems
(OEM version >=35.01.00) to communicate using PPP over iDEN infrastructure to the IP
network. Since iDEN infrastructure connects to Local Area Networks (LAN) as well, a LAN-
connected IP Gateway or FEP can communicate directly with these RTUs over iDEN
infrastructure.

The iM1000/iM1500 is configured to operate works in various modes, including:

47
10BMDLC over IP Communication

• Packet Data (PD)


• Circuit Data (CD)
• Packet Data over Circuit Data (PD over CD)

MDLC over iDEN, which uses IP technology, deals only with the first mode (PD). The other
two can only be used with an external dialup port in the RTU, and do not support direct
communication with another RTU/IP Gateway having an MDLC over IP port. Therefore they
are not relevant to this topic.

In the figure below, the SCADA central and IP Gateway are connected via LAN to iDEN
infrastructure. Each RTU has an iM1000/iM1500 modem connected to its MDLC over IP Port.
A unique IP address is assigned to each RTU according to its modem’s identifier. All
communication between RTUs and the IP Gateway involves sending datagrams in packets over
the internet (IP). A PC running ACE3600 STS can be connected directly to an RTU or operate
remotely over IP.

SCADA
Central
Ethernet
IP
LINE 1 Routing
Net
IP
RS-232 Gateway
STS

Home
iDEN Agent
infrastructure Interface
Router
Mobile
Base Data
Station Gateway

LINE 1

iDEN iM1000 iDEN iM1000


Packet Data Packet Data
modem modem

RS-232 RTU-A RTU-B


STS

48
10BMDLC over IP Communication

IP Gateway/FEP to RTU Communication


A datagram transmitted from the IP Gateway is received by the Home Agent (HA) which
encapsulates the frame and transmits it through the Interface Router (IR) to the Mobile Data
Gateway (MDG). In IP terms, encapsulating a datagram and directing another entity to de-
encapsulate it, is called tunneling. The MDG de-encapsulates it and extracts its destination IP
Address from the IP Header. The MDG then consults a table which maps each IP Address to its
correlated iM1000 modem. Using the LAPi protocol, the MDG encapsulates the datagram in a
LAPi frame, and transmits it to the appropriate iM1000 modem. The modem may need to be
paged before the actual transmission. (See IDEN Modem Session State/Paging below.)

RTU to IP Gateway/FEP Communication


When an RTU configured for MDLC over iDEN transmits a datagram towards the IP Gateway,
the modem requests a packet channel. When an available packet channel is found, the modem
encapsulates the frame in LAPi and transmits it over the air and base station to the MDG. The
MDG then extracts the RTU’s datagram from the LAPi frame and passes it to the Interface
Router (IR) on the LAN. The IR routes the packet to the IP Gateway using conventional IP
routing. Depending upon the LAN topology, datagrams may or may not pass through the HA
(which acts as a default Internet router in this case).

RTU to RTU Communication


When an RTU transmits a datagram to another RTU’s IP Address, the transmission to the
MDG is handled the same way as when transmitting to an IP Gateway. The MDG forwards the
datagram to the IR on the LAN. The IR functions as an internet router, routing the datagram to
the Home Agent (HA). The HA tunnels it to the MDG (through the IR). which de-encapsulates
the original datagram and identifies the iM1000 modem address for the destination IP address.
The MDG then encapsulates the datagram in LAPi protocol and transmits it to that iM1000
modem as described above. (See IDEN Modem Session State/Paging below.)

iDEN does not support group calls (RTU-to-RTU broadcasts). To send a frame to a group of
sites, the application should send to each site individually, leaving a short wait time between
each transmission (about 300 milliseconds).

IDEN Modem Session State/Paging


In order to lengthen battery life and also to allow voice and data operations in a modem at the
same time, the concept of session state was defined for iDEN equipment. A modem is dormant
or idle when it has not received/transmitted data for some time. Because less communication is
required in dormant/idle state, the battery drain is reduced. In this state, it is able to receive
both voice dispatch calls/alerts, and paging.

Paging is a “wake up call” which causes a dormant/idle modem to wake up and allocate
appropriate RF resources needed to communicate over a packet data network. Once the packet
channel has been accessed, the paged modem will become active for a limited amount of time.
While in active state, the modem can only handle packet data, and cannot get any voice
dispatch calls. It is important to note that the iM1000 modem only handles data and no
voice/dispatch calls.

Note: Because of the overhead involved in paging and accessing a channel, there will be a
certain delay before the modem becomes active and can receive data. The length of the delay
49
10BMDLC over IP Communication

depends on the topology and state of the network. This may be relevant for some applications
involving data sent from one RTU to another.

MDLC over iDEN Setup


The general steps of the MDLC over iDEN Setup are identical to the MDLC over IP Setup.

Note that a paging mechanism in the MDLC protocol makes MDLC over IP more reliable.
Setting these parameters in the Advanced Link layer is explained above in MDLC over IP Site
Paging above.

RTU Site Configuration


In the Site Configuration tool, set up either PI1/PI2 or SI1/SI2 as RS232, Async, PPP, iDEN.
RS232, Async, PPP, IDEN

Currently the iDEN modem can be physically connected to PI1/PI2 or SI1/SI2. Only one
iDEN modem can be used per RTU because its internal IP address is the same.

The Advanced parameters should be set as defined below.

Link Parameters for PI1/PI2 or SI1/SI2


Links Range: LINE 1-LINE 29.
Default: LINE 1
The user can assign more than one link name. ACE3600
supports several link names on the same MDLC over IP
port. This feature enables RTU #1 that has one MDLC
over IP port, for example ETH1, to communicate directly
with RTU #2 that has two MDLC over IP ports, LINE1
and LINE2. In this case, assign LINE1 and LINE2 to
RTU #1 MDLC over IP ETH1 port.
Data Speed Range: 1200 - 115200
Default: 19200
DNS Servers The user may enter three DNS servers, however this step
is not necessary since they are learned from the modem.
NTP Server The user may specify up to three NTP Servers. If defined,
they will be polled for the time of day every 2 seconds-17
minutes. Expect a clock offset of around 100
milliseconds. The NTP server can be an Internet server,
or an ACE3600 FEP. If it is an FEP it is up to the user to
set its clock. Note that in ACE3600 a 1 millisecond drift
exists every 2 minutes, if not connected to an external
sync source such as NTP or GPS. Note that NTP servers
are never learned from the modem.

50
10BMDLC over IP Communication

Advanced Physical Layer


The values of these parameters are identical to other variations of MDLC over IP as described
above.

Format The valid values are:


7 bits Even Parity 2 stop bit
7 bits Odd Parity 2 stop bit
7 bits Even Parity 1 stop bit
7 bits Odd Parity 1 stop bit
8 bits No Parity 2 stop bit
8 bits Even Parity 1 stop bit
8 bits Odd Parity 1 stop bit
Default: 8 bits No Parity 1 stop bit
Port Mode Default: DTR/CTS Support
Hardware flow control of the port includes DTR and CTS
signals.
Optional AT command This additional AT string can be used to enhance the
string modem just before the modem is returned to online mode
after configuration. For more details, see Modem
Configuration below.
RTS Always On The RTS of the RTU is connected to the modem’s DTR.
It is controlled by software, and is On. By default, it is
On.
Number of Default: 2.
configuration attempts Range: 0 to 255.
to reset radio/modem
If the RTU fails to configure or register an iDEN modem,
it restarts the iM1000/iM5000 modem using AT
commands. This parameter determines how many failed
attempts to connect modem are required before restarting
it.
If a modem configuration file was downloaded, the
n_failstoreset variable in file overrides this setting.
Wait time after Reset Default: 7 seconds.
radio [sec] Range: 0 to 255 seconds.
Specify how long to wait after restarting the radio/
modem as above before attempting to configure and
register it.
If a modem configuration file was downloaded, the
SetRtsTimeout variable overrides this setting.

51
10BMDLC over IP Communication

PPP echo send max Default: 0


retries Range: 0 to 255.
If not 0 it determines the number of retries to poll the
modem if it does not reply. If retried with no response for
max retries, the data cable to the modem is regarded as
disconnected.
For iDEN leave it 0.
This parameter is intended to be used when no DCD input
signal is provided by the modem.
If a modem configuration file was downloaded, the
pppechosendmaxretry variable overrides this setting.

If a PPP connection type is used, the following optional parameters exist as well but for iDEN
they should be left unchanged. They are intended to support more modems/radios.

PPP echo send Default: 0


interval [sec] Range: 0 to 255.
If not set to 0, it determines the time interval to poll the
modem over PPP. If no reply is received within PPP
echo send max retries, it will declare the cable as
disconnected, and start to reconnect with the modem.
For iDEN leave it as 0.
This parameter is intended to be used when no DCD input
signal is provided by the modem.
If a modem configuration file was downloaded, the
pppechosendinterval variable overrides this setting.
PPP protocol Default: Enable
compression Range: Disable/Enable
If enabled, this configures PPP to use protocol field
compression as defined in RFC1661.
For iDEN leave it enabled.
If a modem configuration file was downloaded, the
pppprocomp variable overrides this setting.
PPP address Default: Enable
compression Range: Disable/Enable
If enabled, this configures PPP to use address field
compression as defined in RFC1661.
For iDEN leave it enabled.
If a modem configuration file was downloaded, the
pppaddrcomp variable overrides this setting.
User name Set the appropriate user name for connecting to the
modem when performing PPP authentication.
If a modem configuration file was downloaded, the
username variable in the file overrides this setting.

52
10BMDLC over IP Communication

Password Set the appropriate password for connecting to the


modem when performing PPP authentication.
If a modem configuration file was downloaded, the
password variable in the file overrides this setting.

Advanced Link Layer


ACE3600 supports several link names on the same port. This feature enables RTU #1 that has
one MDLC over IP port, for example ETH1, to communicate directly with RTU #2 that has
two MDLC over IP ports, LINE1 and LINE2. In this case, assign LINE1 and LINE2 to RTU
#1 MDLC over IP ETH1 port.

The following parameters are specific for each link name:

TX to failed RTU every Range: 0-30


<O: DISABLE 0-30> Default: 0 (also disables)
Min
It specifies a period of time in seconds, after which a
failed link will be considered as being back in order,
provided the value of the Periodic check of failed RTU
parameter is set to Disable.
If the Periodic check of failed RTU parameter is enabled,
it specifies the period of time in seconds after which the
Network layer issues a control frame to check the failed
link.
Periodic check of Default: Disable
failed RTU The network sends a control frame to check whether the
link is still in "failed" status. The frame is issued if the
link has been in "failed" status for the period of time
specified in the TX to failed RTU every <O:DISABLE 0-
30> Min parameter.
Default group IP Range: 000.000.000.000-255.255.255.255
address Identifies Site ID 0 which is used for Group Call on
specific link ID.
Get host by name Default: Enable.
using DNS This parameter enables host name within IP Conversion
Table for the specified link name. If set to Disable, host
names cannot be used within that link name in IP
Conversion Table.

The following parameters are common to all Link names configured for this port.

53
10BMDLC over IP Communication

MDLC over IP port Range: 1-65535


number Default: 2002
This number is common to all RTUs and IP Gateways
connected to this link. This number identifies the MDLC.
This is a UDP port number and the provider should be
consulted.
It is important that this number not be in use as specified
by the TCP/IP standard RFC0960.
Enable Sync Range: Disable/Enable
Default: Disable
If this parameter is Enabled, this port can send an MDLC
Sync to other RTUs, and receive an MDLC sync.
If this parameter is Disabled, this port does not send an
MDLC Sync, and ignores received sync frames. It can
however forward sync words that were initiated from
other link IDs, or from the STS.
It is recommended to use the NTP protocol instead for
time settings.
Notify IP Address Range: Disable/Enable
when connected Default: Enable
When enabled, if an RTU’s IP address is changed or
obtained from a modem, the RTU will send a message to
update its IP Address in all sites.
Note: These messages are sent one after the other, and it
is not guaranteed they will be delivered and accepted.
Enable routing on Range: Disable/Enable
MDLC over IP port Default: Disable
When enabled, an RTU or FEP can route back MDLC
over IP packets received that destined to a different site
ID. When disable, an RTU or FEP ignore packets
received which are destined to other sites.
This parameter allows two RTUs to communicate via this
RTU, is useful if they have dynamic IP address. Note also
they need to transmit periodically for their IP address to
be updated in its IP Conversion Table.

54
10BMDLC over IP Communication

Modem configuration Range: 40-255 sec


timeout (Sec) Default: 40
The period of time the network will wait for successful
configuration of the modem upon power up of modem or
RTU. If within this period, the modem configuration
does not complete, RTU marks the port as Failed, though
configuration continues. If configuration fails, the
modem may not be properly configured. Configuration
status can be checked using the Error Logger and
Software Diagnostics (LIN1L Level 0, 101.
For more details, see Modem Configuration below.
Enable RALP Default: Yes
Radio Application Layer Protocol. Enables periodic
sampling of the modem to get messages about its status
(whether the modem is registered in the network and can
send/receive packet data over the infrastructure). Modem
diagnostics can also be checked using the Software
Diagnostics utility. The valid values are:
Yes
No
Like RCP, RALP uses a separate socket from the data
socket and works in parallel to MDLC over the air using a
PPP connection.
Get modem status Range: 0-255 sec
sample time (Sec) Default: 10
Relevant only if Enable RALP is YES.
The period of time to wait between checking the status of
the modem (if it is registered with the network and able
and to send/receive packet data over the infrastructure.)
Modem diagnose reply Range: 10-255 sec
timeout (Sec) Default: 10
Relevant only if Enable RALP is YES.
The period of time for the Software Diagnostics to wait a
reply from the modem before returning an error. (e.g.
LIN1L levels, 102, 103.)
Restart modem when Range: 10-255 sec
deregistered Default: Yes
Relevant only if Enable RALP is YES.
If Yes, then restart the modem each time it is detected that
the modem has been de-registered by the system. This
will make the modem more reliable, however MDLC data
may be lost when restarting the modem (until it initiates
itself.)

55
10BMDLC over IP Communication

Disconnect on idle Range: 1- 65535


timeout sec Default: 0
When specifying a timeout in seconds, the RTU monitors
the delay from the last time anything was received from
the modem (during PPP mode). If this time expires, this
means there is a problem with the modem connection.
The RTU will disconnect and reconnect to the modem.
If 0, this parameter ignored.
Registration life time Range: 0 to 65535 seconds
Default: 7200
If not 0, this sets an interval in which a connected
radio/modem is deregistered and reregistered for packet
data.
The RTU adds an offset to this number, which is derived
from its site ID, so not all radios are restarted and context
activated at the same time.
If a file was downloaded, this parameter can be
overridden using the regLifeTimeout variable.
A paging mechanism to each site (peer) in IP conversion table makes MDLC over IP more
reliable. The following parameters have been added to Link layer and are optional. For more
information refer to MDLC over IP Site Paging.

Check Alive timeout in Range: 0-65535 sec


seconds Default: 35
Specify timeout in seconds from the last reception from a
peer. If nothing has been received from the peer during
that timeout, it will be paged before the next transmission
(see below). This behavior guarantees that a peer will be
reachable over IP. If it does not respond, route
transmissions to it through alternate routes.
Check alive timeout is measured independently for each
site in the IP conversion table.
If this parameter is 0, a peer will always be considered as
reachable, once a single reception has been received from
it.
This parameter is considered to be 0 regardless of its
value if ‘Maximum number of polls’ is 0.

56
10BMDLC over IP Communication

Poll interval in Range: 0-65535 sec


seconds Default: 10
Specify interval in seconds between polls of peer. When a
peer is being paged, a poll request is sent. If no answer is
received after that period of time, another poll request
will be sent until the Maximum number of polls was sent
(next parameter).
Poll interval is measured independently for each site in
the IP conversion table.
If this parameter is 0, a single poll (or no polls) will be
sent to the peer according to Maximum number of polls
(0 or not.)
Maximum number of Range 0-255
polls Default: 5
Specify the number of poll requests to send in order to
check if the peer is alive. When paging a peer, if no
response is received, it is polled again. If the peer has
been polled for the Maximum number of polls without
answering, it is considered as failed, and all transmission
are routed through an alternate path.

MDLC Session Logical Channels Advanced Parameters


Application layer

Stack size of Range: 1000-4000


application manager Default: 1300
task

Modem Configuration Sequence


The parameters described above for the iDEN modem are configured through in the site
configuration when the modem or RTU is powered up. The RTU sends AT commands to the
modem to change its mode to offline, program the necessary settings, and return it to online
mode. This is transparent to the user, but during this time the RTU cannot transmit MDLC via
this port. Any data sent is queued until the modem returns to online mode. If the configuration
fails, queued data is returned to the network for retransmission via an alternative route. If the
configuration fails, it is possible that the modem was not properly configured. The Error
Logger and Software Diagnostics should be checked to identify the problem (IPLINK LIN1L
Level 0, 101).

Other parameters are set by the iDEN infrastructure over the air when the modem is powered
up. If the configuration fails, this may be due to a problem with the iDEN infrastructure. In
this case, users should consult with the iDEN network operator.

If one of the modem’s internal settings (i.e. the service key used for fraud prevention/
authentication, number assignment module, network ID, or passcode) needs to be modified,
this can be done locally, using the Applet IX1000 software. The Master Reset operation may
also be required to change the modem identification number and enable the iDEN
57
10BMDLC over IP Communication

infrastructure to reset parameters in the modem. These changes should only be performed in
coordination with the technical support group.

• Disconnect the modem from the RTU.


• Connect the modem to a PC running the Applet software.
• Open the Modem Configurations window.
• Modify the settings as instructed by the technical support group.
• Power/cycle the modem.
• Reconnect the modem to the RTU.

Special AT Commands for the iDEN Modem


The following default AT commands are sent by the RTU when configuring the iDEN modem.
These commands can be overridden/added by specifying the Optional AT command string in
the Advanced Physical Layer parameters in the Site Configuration utility. This string will be
sent last to the modem prior to setting it to “online mode” and may override previous settings.

Note: The set of AT commands listed below is suitable for iM1000 modem. For that purpose,
an appropriate modem configuration file can be downloaded to RTU. (For details, see Modem
Configuration File below.) For a complete description of the AT commands, refer to Applet
user manual.

ATZ2 – Load profile 2 (packet data) into the modem.

AT&D0 – Instruct the modem to ignore DTR, since the RTU does not support it.

AT&C1 – Instruct the modem to activate CD in online mode.

AT+WV300=1 – Instruct the modem to use its own mobile IP stack.

AT+WV302=7200 – Set the modem registration lifetime to two hours.

AT+WV175=10 – Set the modem’s session timeout to 10 seconds, i.e. after 10 seconds from
the last communication over the air, the modem becomes idle and needs to be paged in order to
receive data. Setting it to 0 makes the session state permanent.

AT+WS46=24 – Set the modem to packet data mode.

AT+WS45=4 – The modem will initiate PPP when going online.

AT+WS182=3 – Communication over the air will not be compressed. Setting this parameter to
1 will compress data over the air.

Note: If needed, before the modem is set to online mode, it is reregistered using the commands
AT+WPDEREG and AT+WPREG. This occurs only when the RTU powers up, and after the
modem has been deregistered from the system.

AT+wvreset – Reset modem via AT command.

The modem is restarted using this AT command after several unsuccessful attempts to
configure or register it (refer to Number of configuration attempts to reset radio/modem). This
command is also issued by the RTU when connecting to the modem for the first time.

58
10BMDLC over IP Communication

AT+WS53? – Checks the signal quality on a normalized scale (from 0 to 100), where 100 is
the best signal, and <75 means it is poor quality.

The firmware checks the signal quality before attempting to register the modem. If signal
quality is below 75, the RTU will keep issuing this command until getting a better value. If
reasonable quality is not reached within Modem configuration timeout (by default it is 40
seconds), the RTU declares the modem configuration as failed. It will retry to configure the
modem immediately afterwards. If failed for more than Number of configuration attempts to
reset radio/modem times successively, it will restart the modem using the above AT command.

AT+IPR= –Sets the modem data speed.


By default, the data speed of the iDEN iM1000/iM1500 modem is set to 19200 to match the
default data speed of the RTU. The firmware automatically sets the modem data speed to the
rate specified by the user for the port.

If the data speed of the RTU port is changed, firmware will change the modem speed
accordingly.

It is recommended that all RTUs operate their modems on the same data speed.

59
10BMDLC over IP Communication

MDLC over Tetra


With SCADA systems, ACE3600 RTUs can be connected to a Tetra radio. Tetra
infrastructure and radio should support packet data.

The connection to Tetra can be made via LAN or via radio. An IP Gateway or an RTU with an
Ethernet plug-in or on-board port can be connected to a LAN. In Tetra terms, an RTU that is
connected through LAN is called a LAN RTU. An RTU that is connected to a radio is called a
PEI (Peripheral Interface) RTU. A PEI RTU is connected to a radio through RS232 using
standard PPP (Point to Point Protocol).

In the figure below, the SCADA central and IP Gateway are connected via LAN to Tetra
infrastructure. Each RTU has an MTM700 radio connected to its MDLC over IP Port using
PPP. A unique IP address is assigned to each RTU according to its radio’s identifier (SSI). All
communication between RTUs and the IP Gateway involve sending datagrams in packets over
the Internet (IP). A PC running ACE3600 STS can be connected directly to an RTU or operate
remotely over IP.

SCADA
Central
Ethernet
IP
LINE 1 Routing
Net
IP
RS-232 Gateway
STS

Tetra
Infrastructure
SW MI

LINE 1

Tetra Tetra
MTP700 MTP700
radio radio

RS-232 RTU-A RTU-B


STS

The STS can communicate with remote RTUs over IP using the Tetra infrastructure. The PC
running the STS is connected to the Tetra radio (e.g. MTH500 radio) or to the RTU. For this

60
10BMDLC over IP Communication

purpose, the PC should have a Tetra PD installation (as specified in the CPS user manual).
After setting up the connection, the user should run the STS Communication Setup utility,
select Ethernet port and specify in a focal point RTU/IP Gateway IP Address under ‘Local Site
IP Address’.

It is important to note that RTU to RTU communication is routed through the infrastructure
LAN system and not directly.

Note that a paging mechanism to each site (peer) in IP conversion table makes MDLC over IP
more reliable. For details, see MDLC over IP Site Paging.

Tetra does not support group calls (RTU-to-RTU broadcasts). To send a frame to a group of
sites, the application should send to each site individually, leaving a short wait time between
each transmission (about 300 milliseconds).

MDLC over Tetra Setup


The general steps of the MDLC over Tetra Setup are similar to the MDLC over IP Setup. For
MTM700, MTM800, a modem configuration file is not required. If a different radio used, a
modem configuration file is required. Refer to Downloading Modem Configuration Files
above.

RTU Site Configuration


In the Site Configuration tool, set up either PI1/PI2 or SI1/SI2 as RS232, Async, PPP. Select
Tetra:
RS232, Async, PPP, Tetra

Use the FTN6359A connector (RS232-E+). This will enable the RTU to control DTR of the
radio. Refer to Appendix A of this manual for details on the FTN6359A (RS232-E+)
connector.

The Advanced parameters are the same as described above for general MDLC over IP with the
following exceptions:

Link Parameters for PI1/PI2 or SI1/SI2


Links: Range: LINE 1-LINE 29.
Default: LINE 1
User can assign more than one link name in the same
physical port. ACE3600 supports several Link names on
the same MDLC over IP port. This feature enable RTU
#1 that has one MDLC over IP port, for example ETH1,
to communicate directly with RTU #2 that has two
MDLC over IP ports, LINE1 and LINE2. In this case,
assign LINE1 and LINE2 to RTU #1 MDLC over IP
ETH1 port.
Data Speed Range: 1200 – 115200
Default: 9600

61
10BMDLC over IP Communication

DNS Servers The user may enter three DNS servers. Note that TETRA
MTM700 and MTM800 radios do not learn the server
information from the modem, so if host names are used in
the Customer Enterprise Network (CEN)/LAN, the user
should enter this information. On the other hand, most
applications do not have host names in the CEN of
TETRA.
NTP Server The user may specify up to three NTP Servers. If defined,
they will be polled for the time of day every 2 seconds-17
minutes. Expect a clock offset of around 100
milliseconds. The NTP Server can be the FEP on CEN or
any PC acting as an NTP server that the user set up in the
CEN.
If an FEP is used, and it is not connected to GPS, it is up
to the user to set its clock. Note that NTP servers are
never learned from the modem.

Advanced Physical Layer


The values of these parameters are identical to other variations of MDLC over IP as described
above.

Format The valid values are:


7 bits Even Parity 2 stop bit
7 bits Odd Parity 2 stop bit
7 bits Even Parity 1 stop bit
7 bits Odd Parity 1 stop bit
8 bits No Parity 2 stop bit
8 bits Even Parity 1 stop bit
8 bits Odd Parity 1 stop bit
Default: 8 bits No Parity 1 stop bit
Port Mode Default: DTR/CTS Support
Hardware flow control of the port includes DTR and CTS
signals.
Optional AT command This additional AT string can be used to enhance the
string modem just before the modem is returned to online mode
after configuration. For more details, see Special AT
Commands for the Tetra Radio below.
RTS Always On The RTS of the RTU is connected to the modem’s DTR.
It is controlled by software, and is On. By default, it is
On.

62
10BMDLC over IP Communication

Number of Default: 2.
configuration attempts Range: 0 to 255.
to reset radio/modem
If the RTU fails to configure or register a modem, and the
modem supports this feature, it can restart the modem
using AT commands. This parameter determines how
many failed attempts to connect to the modem are
required before restarting it.
If a modem configuration file was downloaded, the
n_failstoreset variable in file overrides this setting.
Wait time after Reset Default: 7 seconds.
radio [sec] Range: 0 to 255 seconds.
Specify how long to wait after restarting the radio as
above before attempting to configure and register it.
If a modem configuration file was downloaded, the
SetRtsTimeout variable overrides this setting.

If a PPP connection type is used, the following optional parameters exist as well, but for iDEN
they should be left unchanged. They are intended to support more modems/radios.

PPP echo send max Default: 0


retries Range: 0 to 255.
If not 0 it determines the number of retries to poll the
modem if it does not reply. If retried with no response for
max retries, the data cable to the modem is regarded as
disconnected.
For iDEN leave it 0.
This parameter is intended to be used when no DCD input
signal is provided by the modem.
If a modem configuration file was downloaded, the
pppechosendmaxretry variable overrides this setting.
PPP echo send Default: 0
interval [sec] Range: 0 to 255.
If not set to 0, it determines the time interval to poll the
modem over PPP. If no reply is received within PPP
echo send max retries, it will declare the cable as
disconnected, and start to reconnect with the modem.
For iDEN leave it as 0.
This parameter is intended to be used when no DCD input
signal is provided by the modem.
If a modem configuration file was downloaded, the
pppechosendinterval variable overrides this setting.

63
10BMDLC over IP Communication

PPP protocol Default: Enable


compression Range: Disable/Enable
If enabled, this configures PPP to use protocol field
compression as defined in RFC1661.
For iDEN leave it enabled.
If a modem configuration file was downloaded, the
pppprocomp variable overrides this setting.
PPP address Default: Enable
compression Range: Disable/Enable
If enabled, this configures PPP to use address field
compression as defined in RFC1661.
For iDEN leave it enabled.
If a modem configuration file was downloaded, the
pppaddrcomp variable overrides this setting.
User name Set appropriate user name for connecting to the modem
when performing PPP authentication.
If a modem configuration file was downloaded, the
username variable in the file overrides this setting.
Password Set appropriate password for connecting to modem when
performing PPP authentication.
If a modem configuration file was downloaded, the
password variable in the file overrides this setting.

Advanced Link Layer


ACE3600 supports several link names on the same port. This feature enables RTU #1 that has
one MDLC over IP port, for example ETH1, to communicate directly with RTU #2 that has
two MDLC over IP ports, LINE1 and LINE2. In this case, assign LINE1 and LINE2 to RTU
#1 MDLC over IP ETH1 port.

The following parameters are specific for each link name:

TX to failed RTU every Range: 0-30


<O: DISABLE 0-30> Default: 0 (also disables)
Min
It specifies a period of time in seconds, after which a
failed link will be considered as being back in order,
provided the value of the Periodic check of failed RTU
parameter is set to Disable.
If the Periodic check of failed RTU parameter is enabled,
it specifies the period of time in seconds after which the
Network layer issues a control frame to check the failed
link.

64
10BMDLC over IP Communication

Periodic check of Default: Disable


failed RTU The network sends a control frame to check whether the
link is still in "failed" status. The frame is issued if the
link has been in "failed" status for the period of time
specified in the TX to failed RTU every <O:DISABLE 0-
30> Min parameter.
Default group IP Range: 000.000.000.000-255.255.255.255
address Identifies Site ID 0 which is used for Group Call on
specific link ID.
Get host by name Default: Enable.
using DNS This parameter enables host name within IP Conversion
Table for the specified link name. If set to Disable, host
names cannot be used within that link name in IP
Conversion Table.
The following parameters are common to all Link names configured for this port.

MDLC over IP port Range: 1-65535


number Default: 2002
This number is common to all RTUs and IP Gateways
connected to this link. This number identifies the MDLC.
This is a UDP port number and the provider should be
consulted.
It is important that this number not be in use as specified
by the TCP/IP standard RFC0960.
Enable Sync Range: Disable/Enable
Default: Disable
If this parameter is Enabled, this port can send an MDLC
Sync to other RTUs, and receive an MDLC sync.
If this parameter is Disabled, this port does not send an
MDLC Sync, and ignores received sync frames. It can
however forward sync words that were initiated from
other Link Ids, or from Toolbox.
It is recommended to use the NTP protocol instead for
time settings.
Notify IP Address Range: Disable/Enable
when connected Default: Enable
When enabled, if an RTU’s IP address is changed or
obtained from a modem, the RTU will send a message to
update its IP Address in all sites.
Note: these messages are sent one after the other, and it
is not guaranteed they will be delivered and accepted.

65
10BMDLC over IP Communication

Enable routing on Range: Disable/Enable


MDLC over IP port Default: Disable
When enabled, an RTU or FEP can route back MDLC
over IP packets received that destined to a different site
ID. When disable, an RTU or FEP ignore packets
received which are destined to other sites.
This parameter allows two RTUs to communicate via this
RTU, is useful if they have dynamic IP address. Note also
they need to transmit periodically for their IP address to
be updated in its IP Conversion Table.

Modem configuration Range: 40-255 sec


timeout (Sec) Default: 40
The period of time the network will wait for successful
configuration of the modem upon power up of modem or
RTU. If within this period, the modem configuration
does not complete, RTU marks the port as Failed, though
configuration continues. If configuration fails, the
modem may not be properly configured. Configuration
status can be checked using the Error Logger and
Software Diagnostics (LIN1L Level 0, 101.
For more details, see Modem Configuration below.

Disconnect on Range: Disable/Enable


icmp:netunreach Default: Disable
If set to Enable, connection to the modem/radio will be
terminated by force when getting an icmp:netunreach.
This message specifies that the peer site was unreachable
because of network problems. Sometimes these problems
can be resolved by reconnecting to the modem.
For Tetra, it is recommended to leave it set to Disable.
Disconnect on idle Range: 1- 65535
timeout sec Default: 0
When specifying a timeout in seconds, the RTU monitors
the delay from the last time anything was received from
the modem (during PPP mode). If this time expires, this
means there is a problem with the modem connection.
The RTU will disconnect and reconnect to the modem.
If 0, this parameter ignored.

66
10BMDLC over IP Communication

Does modem support Range: YES/NO


abort sequence Default: NO
With Tetra radios such as MTM700, no abort sequence is
supported. Abort sequence is a +++ string sent with a 1
second delay before and after, causing the modem to
move into command mode.
Specifying this parameter as NO will expedite connection
to Tetra radio.
Ignore CD Range: Never, Always, When connect
Default: Never.
When connecting to the modem, its CD is constantly
being polled, and if inactive, the RTU will reconnect to it.
This parameter enables the user to bypass the polling by
ignoring CD. Setting this parameter to Always will cause
RTU not to check CD at all. Setting it into When connect
will ignore CD during the PPP connection phase. When
PPP is connected, CD will be polled.
Setting this parameter to Never will always check CD.
Registration life time Range: 0 to 65535 seconds
Default: 7200
If not 0, this sets an interval in which a connected
radio/modem is deregistered and reregistered for packet
data.
The RTU adds an offset to this number, which is derived
from its site ID, so not all radios are restarted and context
activated at the same time.
If a file was downloaded, this parameter can be
overridden using the regLifeTimeout variable.

With Tetra, a paging mechanism to each site (peer) in the IP conversion table has been added
to make MDLC over IP more reliable. If the parameters below are not visible, they will have
the default values as specified. The parameters are the same as in other variations of MDLC
over IP, but their default values were changed to suit Tetra infrastructure. For more
information, refer to MDLC over IP Site Paging.

Check Alive timeout in Range: 0-65535 sec


seconds Default: 35 sec
Poll interval in Range: 0-65535 sec
seconds Default: 9 sec
Maximum number of Range 0-255
polls Default: 3

67
10BMDLC over IP Communication

Special AT Commands for the Tetra Radio


The following AT commands are sent by the RTU when configuring the Tetra radio. They can
be overridden/added by specifying the Optional AT command string in the Advanced Physical
Layer parameters in the Site Configuration utility.

It is recommended to override these defaults by downloading a modem configuration file


adopted for the radio, such as MTM700.stm for MTM700. For details, see Modem
Configuration File below.

AT+IFC=2,2 – Instruct the radio to use hardware flow control.

AT+WS45=4 – Instruct the radio to initiate PPP with the RTU when getting the ATD
command.

MDLC over Standard Modem


To avoid system setup for each modem/radio which supports packet data, a general concept has
been introduced for, whereby IP can connect to any modem or radio supporting packet data. A
standard modem supporting packet data is a modem which requires an AT command set to
configure and PPP to initiate. It can connect to a PC using Microsoft Standard Modem and
RAS setup.

A modem configuration file can be downloaded into the RTU specifying the exact command
set needed by the modem/radio. A default AT command set is used in case this file is not
downloaded. The same concept is used for circuit data modem over dial port.

The following modems/radios may be configured using a modem configuration file. Files for
this purpose are provided in the C:\STS<version>\config directory.

• GPRS G18 modem (G18.stm file)

• Other standard PPP radios

For information of downloading modem configuration files, see Downloading Modem


Configuration Files above.

Connection to Standard modem is made using PPP over the operator infrastructure. Since the
operator infrastructure connects to LAN as well, a LAN-connected RTU can communicate
directly with these RTUs over that infrastructure, if enabled by the operator.

Some modem vendors such as Siemens MC75 have an internal IP address for PPP connection.
This address should be unique per RTU. If so, only one modem of the same vendor can be
connected to RTU, since they all have the same IP address. Other vendors’ modems such as
Motorola g18 do not have an internal IP address; in this case several MDLC over IP ports can
be configured to connect with them.

To verify if more than one modem can be used, try to connect two modems and see if you get
an error message: IP Address in use by other ports.

68
10BMDLC over IP Communication

MDLC over Standard Modem Setup


The general steps of the MDLC over Standard modem Setup are identical to the MDLC over IP
Setup. If a modem configuration file is used, this too must be downloaded to the RTU port.

RTU Site Configuration


In the Site Configuration tool, set up either PI1/PI2 or SI1/SI2 as RS232, Async, and select
PPP for Standard Modem:
RS232, Async, PPP, Standard Modem

As with Tetra, the FTN6359A connector (RS232-E+) should be used. Refer to Appendix A for
details on the FTN6359A (RS232-E+) connector.

The Advanced parameters are the same as described above for general MDLC over IP and
MDLC over Tetra. Some of their defaults have been changed.

Link Parameters for PI1/PI2 or SI1/SI2


Data Speed Range: 1200 – 115200
Default: 9600

Advanced Physical Layer


The values of these parameters are identical to other variations of MDLC over IP as described
above.

Advanced Link Layer


The values of these parameters are identical to other variations of MDLC over IP as described
above.

Check Alive timeout in Range: 0-65535 sec


seconds Default: 300 sec
Poll interval in Range: 0-65535 sec
seconds Default: 9 sec
Maximum number of Range 0-255
polls Default: 3

Special AT Commands for Standard Modem


The following AT commands are sent by the RTU when configuring the Standard modem.
They can be overridden/added by specifying the Optional AT command string in the Advanced
Physical Layer parameters in the Site Configuration utility.

It is recommended to override these defaults by downloading a modem configuration file


adopted for the radio, such as G18.stm for GPRS. For details, see Modem Configuration File
below.

69
10BMDLC over IP Communication

AT+IFC=2,2 – Instruct the radio/modem to use hardware flow control.

AT&C1 – Instruct the radio/modem to activate CD in online mode.

AT&D1 – Instruct the radio/modem to check if DTR is active. When the RTU deactivates
DTR, the radio/modem will reset its port, and the PPP connection will terminate.

AT+WS45=4 – Instruct the radio/modem to initiate PPP with the RTU when getting the ATD
command.

70
10BMDLC over IP Communication

MDLC over GPRS


An RTU can be connected to GPRS through a LAN or through a radio. An IP Gateway or an
RTU with an Ethernet port can be connected to the LAN. An RTU which is connected to a
radio through RS232 using standard PPP (Point to Point Protocol).

In the figure below, the SCADA central and IP Gateway are connected via LAN to the GPRS
infrastructure. Each RTU has a G18 GPRS/GSM modem connected to its MDLC over IP Port
using PPP. A unique IP address is assigned to each RTU according to its modem identifier
(IMSI). All communication between the RTUs and the IP Gateway involves sending
datagrams in packets over the Internet (IP). The GPRS infrastructure routes those packets
directly between two RTUs, or between IP Gateway and an RTU. A PC running STS can be
connected directly to an RTU or operate remotely over IP.

SCADA
Central

Ethernet

IP RTU
Gateway RSlink1 g18 GPRS
Packet Data
modem

GPRS
infrastructure

LINE 1

g18 GPRS g18 GPRS


Packet Data Packet Data
modem modem

RS-232 RTU-A RTU-B


STS

A single GPRS modem can be connected to an RTU. Other ports can be connected to other
GSM modems using dialup ports.

GPRS does not support group calls (RTU-to-RTU broadcasts). To send a frame to a group of
sites, the application should send to each site individually, leaving a short wait time between
each transmission (about 300 milliseconds).

71
10BMDLC over IP Communication

It is recommended that the operator provide an APN (Access Point Name) for a fixed IP
address and enable one modem to communicate with another over UDP port 2002. If this is
not possible, the following should be done:

1. The assigned FEP must have a fixed IP or host name. Make sure the operator supports
UDP port 2002 from modem to FEP and vice versa.

2. Assign an IP Conversion table to the RTUs with that FEP IP address or host name.

3. In the application, each RTU should transmit periodically to the FEP, so it learns the recent
address (e.g. every 2 minutes.) Or else wait for a timeout and if nothing is received from
the FEP, send it a message.

Since there are no fixed IP addresses, one modem cannot communicate with another. If this is
required, the FEP can be used to route information between modems as follows:

1. Assign an IP Conversion table to the RTUs with the FEP Site ID + Link ID and IP address,
along with all other relevant sites which need to communicate over that GPRS Link ID.

2. In the FEP, enable the ‘Enable routing on MDLC over IP port’ parameter in the Advanced
link parameters for that Link ID.

MDLC over GPRS Setup


Configuring an RTU to operate over GPRS is the same as configuring MDLC over IP for the
Standard modem connection. If a modem configuration file is used (e.g. G18.stm), this too
must be downloaded to the appropriate RTU port.

Note that before downloading the modem configuration file for GPRS, you need to change its
APN according to your operator instructions. The APN (Access Point Name) is an address such
as intranet.motorola.co.il in the following string under [ConfigurePD] section:

<AT+CGDCONT=1,"IP","intranet.motorola.co.il","0.0.0.0",0,0><OK><4>

The APN defines the security and capabilities set by your provider for your SIM cards.

For MDLC over IP to work it must have a fixed IP Address. Most GPRS APNs change IP
addresses each time the RTU reconnects PPP. Reconnecting PPP is a valid operation and can
be done more than once. In order for other sites to communicate with an RTU using MDLC
over IP, it is mandatory that the RTU receive the same IP Address each time it reconnects PPP.
Therefore, you must request APN having a fixed IP address allocation from your operator.

Note: Each SIM Card has unique identifiers for a GPRS/GSM modem. Placing a given SIM
card on different modems causes the same settings to be retrieved from infrastructure (phone
number, IP Address etc.) regardless of the modem.

Use the STS Add-Ons Manager and Downloader to select the modem configuration file for the
specified port and download the G18.stm file.

RTU Configuration
In the Site Configuration tool, set up either PI1/PI2 or SI1/SI2 as RS232, Async, PPP. Select
Standard Modem:

72
10BMDLC over IP Communication

RS232, Async, PPP, Standard Modem

The Advanced parameters are the same as described above for MDLC over Standard Modem.

MDLC over ASTRO IV&D


With SCADA systems, ACE3600 RTUs can be connected to an ASTRO IV&D radio. The
ASTRO infrastructure (6.4 or higher) and radio must support integrated voice and data (named
IV&D). This is relevant to Motorola subscriber data radios such as the XTL5000 mobile.

The connection to ASTRO IV&D can be made via LAN or via radio. The LAN is called a CEN
(Customer Enterprise Network). An IP Gateway or RTU with an Ethernet port can be
connected to the CEN. On the other end, an RTU can be connected to an ASTRO IV&D radio
via an RS232 data cable. Note that a specific codeplug which supports the data option must be
used when programming them.

Note also that mobile radios such as XTL5000 can work in Analog mode on Trunk II with a
DPSK modem. This has nothing to do with MDLC over IP; both the radio and the RTU are
configured differently.

In the figure below, the SCADA central and IP Gateway are connected via LAN to a Customer
Enterprise Network (CEN). The CEN is connected via a border router gateway to the ASTRO
IV&D infrastructure. An RTU, running MDLC over IP protocol over PPP, is connected via
XTL5000 radio using an RS232 data cable. A unique IP address is assigned by the GPRS
Gateway Support Node (GGSN) to each RTU according to its radio individual unit ID (UID),
such that when a frame is transmitted from the CEN to that IP address, the Packet Data Router
(PDR) and Radio Network Gateway (RNG) transmit it to the appropriate radio.

Unlike other infrastructures such as iDEN and TETRA, this IP address and radio unit ID
cannot be retrieved for diagnostics from the radio. Instead a dummy IP Address is provided by
the radio as configured in its CPS.

73
10BMDLC over IP Communication

SCADA
Central
Ethernet
Customer
LINE 1 Enterprise
Network
IP
RS-232 Gateway

STS

ASTRO IV&D GGSN


infrastructure
PDR

Base RNG
Station

LINE 1

XTL5000 Radio XTL5000 Radio

RS-232 RTU-A RTU-B


STS

74
10BMDLC over IP Communication

A PC running STS can be connected directly to an RTU, directly to a radio, or it can operate
remotely over the CEN.

For an RTU or PC to communicate over the air using an ASTRO IV&D radio, the radio must
be context activated, or registered for data, in addition to the PPP connection over RS232
interface. The RTU uses SNMP protocol and sets a value in a MIB variable defined for this
radio. When this succeeds, the radio configuration is completed, and the radio (using the IP
address provided periodically by the GGSN in the infrastructure) is able to receive and transmit
data. If the context activation fails or is deactivated, the RTU causes the radio to restart (power
itself off and on.) Once the radio has been context activated, an RTU (or PC) can transmit IP
frames over the air to the PDR which routes them to the GGSN and CEN.

Certain configuration steps are performed on the radio itself using the CPS and in the
infrastructure using the UCM tool. See the relevant radio documentation for more information.

There are two types of hardware interface between the RTU and the radio: For a mobile radio
such as the XTL5000, the interface is comprised of a radio data cable over RS232.
Note: A PC needs a tool called Data Link Manager (DLM) in order to communicate over the
air.

ASTRO IV&D does not support group calls (RTU-to-RTU broadcasts). To send a
frame to a group of sites, the application should send to each site individually, leaving
a short wait time between each transmission (300-1000 milliseconds depending upon
the communication used.)

Sending frames from one RTU to another when both are connected to radios may not
be reliable, because of the ASTRO IV&D's limited resources. It is recommended to
have an RTU connected to LAN (CEN) that will route the information between them.

RTU Site Configuration


In the Site Configuration tool, set up either PI1/PI2 or SI1/SI2 as:
RS232, Async, PPP, ASTRO IV&D

The Advanced parameters are the same as described above for general MDLC over IP and
MDLC over Tetra. Some of their defaults have been changed.

As an option, the user can override some of these settings by downloading a modem
configuration file such as XTL5000.stm to the RTU port to which the radio is connected.

Link Parameters for PI1/PI2 or SI1/SI2


Link name: Range: LINE 1-LINE 29.
Default: LINE 1
All RTUs and IP Gateways use the same line.

75
10BMDLC over IP Communication

Data Speed Range: 1200 - 57600


Default: 19200

If the RTU needs to log into the infrastructure/radio using a user name via PPP connection,
specify the following parameters.

User name Set the appropriate user name for connecting to the
modem when performing PPP authentication.
By default it should be left empty.
If a modem configuration file was downloaded, the
username variable overrides this setting.
Password Set the appropriate password for connecting to the
modem when performing PPP authentication.
By default it should be left empty.
If a modem configuration file was downloaded, the
password variable overrides this setting.
SNMP agent port Range: 0-65535
number Default: 161.
This number determines the UDP port number for setting
the SNMP context activate MIB variable in the radio.
Relevant only if Context activate radio is set to Enable in
the Advanced Link Layer.
SNMP trap port Range: 0-65535
number Default: 162.
This number determines the UDP port number for getting
traps from the radio via SNMP during context activation.
Relevant only if Context activate radio is set to Enable in
the Advanced Link Layer.
Packet data status Default: .1.3.6.1.4.1.161.3.6.30.2.1.1.1.
name This is a string identifying the MIB name for context
activating the radio. It is called packet data status (PDS)
MIB. Relevant only if Context activate radio is set to
Enable in the Advanced Link Layer.
Default routing IP The default gateway of the RTU.
address This value should remain 000.000.000.000.
IP network mask The subnet mask assigned by to the radio.
This value should remain 000.000.000.000.

76
10BMDLC over IP Communication

MDLC over IP port Range: 1-65535


number Default: 2002
This number is common to all RTUs and IP Gateways
connected to the link. This number identifies the MDLC.
This is a UDP port number and the provider should be
consulted.
It is important that this number not be in use as specified
by the TCP/IP standard RFC0960.

Advanced Physical Layer


The values of these parameters are identical to other variations of MDLC over IP as described
above.

Optional AT command This additional AT string can be used to enhance the


string modem just before the modem is returned to online mode
after configuration.
RTS Always On The RTU powers the radio off by unsetting this signal.
By default, it is On.
Number of Default: 3.
configuration attempts Range: 0 to 255.
to reset radio/modem
If the RTU fails to context active the radio, it restarts it
using AT commands.
This parameter determines how many failed attempts to
connect (context activate) the radio must occur before
restarting the radio.
If a modem configuration file was downloaded, the
n_failstoreset variable overrides this setting.
Wait time after Reset Default: 7 seconds.
radio [sec] Range: 0 to 255 seconds.
Specify how long to wait after restarting radio as above
before attempting to configure and register it.
If a modem configuration file was downloaded, the
SetRtsTimeout variable overrides this setting.

77
10BMDLC over IP Communication

PPP echo send Default: 10


interval [sec] Range: 0 to 255.
If not 0 it determines the time interval to poll the radio
over PPP. If no reply is received within max retries, it
will declare the cable as disconnected, and start to
connect with the radio again.
This parameter is needed because ASTRO IV&D radios
do not have DCD.
If a modem configuration file was downloaded, the
pppechosendinterval variable overrides this setting.
PPP echo send max Default: 3
retries. Range: 0 to 255.
If not 0 it determines the number of retries to poll the
radio if no reply is received. If no response is received
after max retries, the data cable to the radio is regarded as
disconnected.
This parameter is needed because ASTRO IV&D radios
do not have DCD.
If a modem configuration file was downloaded, the
pppechosendmaxretry variable overrides this setting.
PPP protocol Default: Enable
compression Range: Disable/Enable
If enabled this configures PPP to use protocol field
compression as defined in RFC1661.
For ASTRO IV&D, leave it disabled.
If a modem configuration file was downloaded, the
pppprocomp variable overrides this setting.
PPP address Default: Disable
compression Range: Disable/Enable
If enabled this configures PPP to use address field
compression as defined in RFC1661.
For ASTRO IV&D, leave it enabled.
If a modem configuration file was downloaded, the
pppaddrcomp variable overrides this setting.

78
10BMDLC over IP Communication

Advanced Link Layer


Disconnect on Range: Disable/Enable
icmp:netunreach Default: Disable
If set to Enable, the connection to the radio will be
terminated by force when getting an icmp:netunreach.
This message specifies that the peer site was unreachable
because of network problems. Sometimes these problems
can be resolved by reconnecting to the modem.
For ASTRO IV&D it is recommended to leave it set to
Disable.
If a modem configuration file was downloaded, the
DisconctIcmpNet variable overrides this setting.
Does modem support Range: YES/NO
abort sequence Default: YES
Specify YES if the modem supports an abort sequence, a
+++ string sent with a 1 second delay before and after,
causing the modem to move into command mode.
For ASTRO IV&D radios, this parameter should be set to
YES.
If a modem configuration file was downloaded, the
AbortSeqExist variable overrides this setting.
Disconnect on idle Range: 1- 65535
timeout sec Default: 0
When specifying a timeout in seconds, the RTU monitors
the delay from the last time anything was received from
the modem (during PPP mode). If this time expires, there
is a problem with the radio context activation. The RTU
will disconnect and context activate the radio.
If a modem configuration file was downloaded, the
DisconctRxIdleTime variable overrides this setting.
Ignore CD Range: Never, Always, When connect
Default: Always.
ASTRO IV&D radios do not provide DCD signal when
connected, therefore this parameter should Always ignore
CD.
If a modem configuration file was downloaded, the
IgnoreCD variable overrides this setting.

79
10BMDLC over IP Communication

Registration life time Range: 0 – 65535


Default: 0
This parameter is useful with infrastructure that requires
periodic restart of radio.
If 0, periodic restart of radio is disabled (but can be done
via application). If not 0, it specifies how long the RTU
keeps the radio context activated before restarting, and
then context activates it again.
The RTU adds an offset to this number, which is derived
from its site ID, so not all radios are restarted and context
activated at the same time.
If a file was downloaded, this parameter can be
overridden using the regLifeTimeout variable.
Notify IP Address Range: Disable/Enable
when connected Default: Enable
When enabled, once a radio get context activated, the
RTU send a message to update its IP Address in all sites.
Note: these messages are sent one after the other, and it
is not guaranteed they will be delivered and accepted.

The RTU connected to the radio uses the MDLC paging mechanism as with Tetra and iDEN.
An MDLC paging mechanism to each site (peer) in IP conversion table makes MDLC over IP
more reliable. For the IP Gateway and IP Interface connected on the CEN, if these parameters
are not visible, they take their default values as 0, and issue no MDLC paging from the CEN.
For more information, refer to MDLC over IP Site Paging.

Check Alive timeout in Range: 0-65535 sec


seconds Default: 300 sec
Poll interval in Range: 0-65535 sec
seconds Default: 9 sec
Maximum number of Range 0-255
polls Default: 3

The following parameters affect the way the RTU context activates the radio and monitors it
via SNMP protocol. The ASTRO IV&D setup requires an SNMP component to be configured
in order for the radio to context activate (register for data). This is configured in the radio using
the CPS tool and in the RTU using STS.

Context activate radio Range: Disable/Enable


Default: Enable
When enabled, context activate the radio via SNMP, and
monitor it according to the below parameters.

80
10BMDLC over IP Communication

Radio context Range: 0-255 sec


activation timeout Default: 30 sec
This parameter is relevant if Context activate radio is set
to Enable.
It determines how long to wait for a radio to be context
activated. If the timeout expires, the RTU will
reconfigure the radio, and restart it if needed.
Get radio status Range 0-255 sec
sample time Default: 10 sec
This parameter is relevant if Context activate radio is set
to Enable.
Once the radio is context activated, the RTU will monitor
it periodically to see that it is still context activated. This
parameter determines how frequently to do check this.
SNMP socket timeout Range: 0-255 sec.
Default: 10 sec.
This parameter is relevant if Context activate radio is set
to Enable.
The RTU sets a radio’s context activate variable and
monitors it via an SNMP socket. This parameter
determines how long to wait for a response from the
radio, before declaring it as failed. If failed, RTU will
reconfigure the radio, and restart it if needed.

Special AT Commands for ASTRO IV&D


The following AT commands are sent by the RTU when configuring the ASTRO IV&D radio.
They can be overridden/added by specifying the Optional AT command string in the Advanced
Physical Layer parameters in the Site Configuration utility.

A modem configuration file such as XTL5000.stm for mobile XTL5000 radio can be
downloaded to override these defaults.

AT#RESET – Instruct the radio to restart.

AT – Check that the radio is connected and can be configured.

ATH – Disconnect the radio from PPP mode after issuing an abort sequence (+++).

ATE0V1 – Set no echo and AT command verbose return codes.

AT&K3 – Instruct the radio to use hardware flow control.

ATD – Connect the radio in PPP mode.

MDLC over Null Modem


The RTU can connect to any device using direct cable over PPP. This is supported for MDLC
over IP and can connect, for example, to a Terminal Server over PPP.

81
10BMDLC over IP Communication

This connection is made using PPP and is basically the same as MDLC over Standard modem.

When the RTU is powered up, it sends a client string and expects a clientserver response. Only
when it gets that response will it initiate PPP and poll for CD. CD is constantly being polled,
and if it drops, PPP is disconnected. The user can opt to ignore CD using Advanced Link Layer
parameters in the site configuration. In this case, PPP is initiated upon power up. When
connected, CD is polled in order to stay connected. If it drops, then PPP is reconnected.

By default, the RTU acts as a Windows Null modem connection. It sends a client string and
expects a clientserver response before initiating PPP. The user can override this behavior by
downloading a modem configuration file.

MDLC over Null Modem Setup


The general steps of the MDLC over Null modem Setup are identical to the MDLC over IP
Setup. Although no real modem exists, a modem configuration file can be attached to a port
and downloaded to override the default settings of the port.

RTU Site Configuration


In the Site Configuration tool, set up either PI1/PI2 or SI1/SI2 as RS232, Async, and select
PPP for Null Modem:
RS232, Async, PPP, Null Modem

The Advanced parameters are the same as described above for general MDLC over IP and
MDLC over Standard modem and are therefore not repeated here.

Modem Configuration File


For ACE3600 RTUs, a modem configuration file can be downloaded to the following PPP
ports (packet data modems):
RS232, Async, PPP, iDEN
RS232, Async, PPP, Tetra
RS232, Async, PPP, Standard Modem
RS232, Async, PPP, Null Modem
RS232, Async, PPP, ASTRO6 IV&D

For ACE3600 RTUs, a modem configuration file can be downloaded to the following dialup
(circuit data) port:
RS232, Async, External dialup

(Note for dialup: You must use the RS232E+ adaptor.)

The modem configuration file (also called standard modem configuration file) is an ASCII file
with sections in which exact AT commands can be specified for connecting to a modem. Some
“environment variables” can be set as well to define the exact behavior of the port control
function (dealing with connecting the modem and checking that it remains connected.) This file

82
10BMDLC over IP Communication

also contains special sections for diagnosing the modem using AT commands via STS SW
Diagnostics.

Since several circuit data modems can be connected to RTU, the user should specify for which
port the file is being downloaded: i.e. port PI1, PI2, SI1 or SI2. This is done in the
Downloader utility. Note that for now, only a single packet data modem/radio can be connected
to an RTU.

The same configuration file can be used with different sections for circuit data programming
and packet data programming. Since dialup port (circuit data) and PPP ports (packet data)
configure the modem differently, separate sections have been set for each type: The
ConfigureCD section configures a dialup port, and ConfigurePD configures a PPP port.

For dialup ports only, a dedicated section called ChkVld is used to check that the modem is
operational and able to receive calls.

To enable the user diagnose the modem status, Diag0 to Diag7 sections have been allocated.
These sections are invoked when using the SW Diagnostics level 223 or above. Level 223 is
set for running Diag0, level 224 for Diag1, etc. This diagnostic disconnects the modem
temporarily while diagnosing the modem. For that reason, the dialup port will refuse to
perform this operation while in the middle of a call and returns an error. MDLC Over IP
enables this feature by disconnecting PPP temporarily and turning it back on once the
diagnostics are complete.

Modem Configuration File Example


The following is an example of a modem configuration file for the G18 modem (G18.stm):
[Initialize]
$FileVersion= 1.10 ; Version of file 1.x must stay the same.
; Advised to increase revision on each
update.
$WaitForOk= 2000 ; Wait time for OK in milliseconds
$WaitForDial= 30000 ; wait time for Dialup in milliseconds
$WaitForDiag= 15000 ; Wait for diag timeout in milliseconds
$DTEIPAddr= 0.0.0.0 ; IP Address of DTE (MOSCAD).
; Set to 0 in order to obtain from radio.
$GtwyIPAddr= 0.0.0.0 ; IP Address default gateway.
; Set to 0 in order to obtain from radio.
$DTESubnetMask= 0.0.0.0 ; Subnet Mask
; Set to 0 in order to obtain from radio.
$Username= ; PPP user name if authentication is
needed.
$Password= ; PPP password if authentication is
needed.
$AbortSeqExist= 1 ; 1 - Modem support abort Sequence
$IgnoreCD= 2 ; 0 - Never / 1 - Always / 2 - Ignore CD
when connecting
$DisconctIcmpNet= 0 ; 1 - Disconnect modem when getting
ICMP:Net Unreach
$DisconctRxIdleTime= 900 ; Disconnect on idle timeout in seconds
(15 min)
; 0 - never disconnect if inactive,
$UnsetRtsTimeout= 2000 ; Wait time before restart the modem
(unset RTS).
$SetRtsTimeout= 4000 ; Wait time after restart the modem
(setting RTS).
$ModemAddress= 0 ; Modem/radio address (string)
$ModemVersion= 0 ; Modem/radio version (string)
83
10BMDLC over IP Communication

$ModemName= Motorola GSM g18 ; Modem/radio type for diagnotic purposes


$ModemRSSI= -- ; Modem/radio RSSI
$ToggleRtsCommand= 0 ; 1 - Toggle RTS (modem's DTR) at
SetCommandMode
$pppechosendinterval= 0 ; PPP Echo send interval in milliseconds.
$pppechosendmaxretry= 0 ; PPP Echo send max retries.
$pppprocomp= 1 ; 1- Enable PPP protocol compression
$pppaddrcomp= 1 ; 1- Enable PPP address compression
$pppmaxmtu= 1500 ; PPP Max MTU frame size
$pppauthpro= 0 ; PPP Authentication Protocol
0xc023/0xc223
$pppasynctl= 0 ; PPP Async Control Char Map
$n_failstoreset= 2 ; Number of configuration failures to reset
modem
$max_failedtime= 120000 ; If failed to configure for 120 seconds
errorlog
; Applicable for IP and not for dialup modems
$WaitAfterDial= 2000 ; 2 seconds to wait after dialup to another
modem
; Relevant for dialup only.
$RetryModemConfig= 0 ; Set to 1 if need to retry modem
configuration
; Relevant for dialup only.
$RegLifeTime= 7200 ; Registration timeout in seconds

[Prereset]
; Does nothing except for unsetting RTS
; (powers modem's plastic box off)

[Postreset]
; Does nothing except for setting RTS
; (powers modem's plastic box on)
[SetCommandMode]
<><><1> ; Wait 1 second.
<+++><><1> ; Wait 1 second.

[HangupCD] ; **For MDLC over Dialup**


<ATH0x0D><> ; Send ATH\r. Expect no reply.
<ATH><NO CARRIER><4> ; Send ATH\r; Expect NO CARRIER reply
; within 4 seconds.
<AT><OK><2> ; Send AT\r; Expect OK reply within
; 2 seconds.

[HangupPD] ; **For MDLC over IP**


<0x7e0xff0x030xc00x210x050x020x000x040x590x280x7e><><2> ; Send LCP
; Terminate Request
<ATH0x0D><> ; Send ATH\r. Expect no reply.
<ATH0x0D><> ; Send ATH\r; Expect no reply.
<AT><OK><2> ; Send AT\r; Expect OK reply within
; 2 seconds.
[VerifyParms]
<ATI3><$ModemVersion> ; Send ATI3\r; store reply in $ModemVersion
<AT+CIMI><$ModemAddress>; Send AT+CIMI\r; store reply in $ModemAddress
<AT+CSQ><$ModemRSSi> ; Send AT+CSQ\r; store reply in $ModemRSSi
[ConfigureCD] ; **For MDLC over Dialup**
<><><5> ; Wait 5 seconds after modem recovers.
<AT&F0><OK> ; Restore to factory configuration.
<ATE0V1Q0X4&C1S0=2><OK> ; Configuration string
<AT+CMGF=10x0D><><2> ; Set modem in SMS text mode.
<AT&W0><OK> ; Save in profile 0.
<AT&Y0><OK> ; After powerup, load profile 0

84
10BMDLC over IP Communication

[ConfigurePD] ; **For MDLC over IP**


<AT><OK><2> ; Send AT\r; expect OK reply within 2
; seconds.
<AT&F0&D0&C2&K3E0V1W1S95=47><OK><2> ; Configuration within 2 seconds.
<AT+CMGF=10x0D><><2> ; Set modem in SMS text mode
<AT+CGATT=1><OK><5> ; Attach to GPRS; expect OK reply within 5
; seconds.
<AT+CGPRS?><+CGPRS: 1><2> ; Check GPRS coverage.
; Expect +CGPRS: 1 reply.
<AT+CGDCONT=1,"IP","intranet.motorola.co.il","0.0.0.0",0,0><OK><4>
; Define APN - PDP contact (profile)

[DialPD] ; **For MDLC over IP**


<ATD*99#><CONNECT><40> ; Set Modem in PPP mode by dialing ATD*99##
[GoOnLine] ; **For MDLC over Dialup**
<ATO><CONNECT> ; Go online from command mode (circuit data).
[ChkVld] ; **For MDLC over Dialup**
<AT><OK> ; Send AT\r; expect OK.
<AT+CREG?><+CREG:000 001> ; Send AT+CREG?\r; expect +CREG:000 001
; reply.

[Diag0] ; This is level 223.


<ATI3><$Diag> ; Modem version :
<AT+CIMI><$Diag> ; Modem IMSI :
<AT+CPIN?><$Diag> : Modem pin number:
<AT+CGMR><$Diag> : Hardware Version:
<AT+CGMI><$Diag> : Manufacturer :
[Diag1] ; This is level 224.
<AT+CSQ><$Diag> ; Signal quality :
<AT+CREG?><$Diag> ; Registration :
<AT+CGATT?><$Diag> ; Is GPRS Attached:
<AT+CGPRS?><$Diag> ; Is GPRS Covered :
<AT+CMGF?><$Diag> ; Is in Text mode :

[Diag2] ; This is level 225.


<ATE1><OK>
<AT&V><$Diag><2>

Modem Configuration File Sections


Several modem configuration files are included as part of the STS installation. The structure of
the modem configuration file is comprised of the following sections.

Section Name PPP port Dialup Invoked when


Initialize Starting to configure Starting to configure Starting to configure
modem or when a new file modem or when a new file modem.
was downloaded. was downloaded.
SetCommandMode Hanging up PPP. Hanging up call.
HangupCD Hanging up call. Dialup only.
HangupPD Hanging up PPP. PPP only.
Hanging up PPP is invoked
when need to diagnose
modem, or when start to
configure it.

85
10BMDLC over IP Communication

Section Name PPP port Dialup Invoked when


VerifyParms Configure modem in PPP PPP only.
Step [1]. Modem is configured when
it is detected that PPP is
not connected or when
RTU is restarted or when a
new file is downloaded.
ConfigureCD Configuring modem made Dialup Only.
at power restart or when
check validity fails. Step [1]
of 3.
ConfigurePD Configure modem in PPP PPP only.
Step [2]. Modem is configured when
it is detected that PPP is
not connected.
VerifyIPParms Optional step before PPP only.
DialPD. If need to read modem IP
Address via AT commands
such as iM1000.
DialPD Configure modem in PPP PPP only.
Step [3]. Modem is configured when
it is detected that PPP is
not connected.
ChkVld Checking modem able to Dialup only.
receive calls. Made when If fails, modem is
modem was idle for reconfigured.
specified number of
seconds.
Diag0 SW Diagnostics of LIN1L SW Diagnostics of LIN1D LIN1L and LIN1D is the
level 223. level 223. name of the port with
LINE1 link ID.
This section is optional.
Diag1 SW Diagnostics of LIN1L SW Diagnostics of LIN1D This section is optional.
level 224. level 224.
Diag2 SW Diagnostics of LIN1L SW Diagnostics of LIN1D This section is optional.
level 225. level 225.
Diag3 SW Diagnostics of LIN1L SW Diagnostics of LIN1D This section is optional.
level 226. level 226.
Diag4 SW Diagnostics of LIN1L SW Diagnostics of LIN1D This section is optional.
level 227. level 227.
Diag5 SW Diagnostics of LIN1L SW Diagnostics of LIN1D This section is optional.
level 228. level 228.
Diag6 SW Diagnostics of LIN1L SW Diagnostics of LIN1D This section is optional.
level 229. level 229.
Diag7 SW Diagnostics of LIN1L SW Diagnostics of LIN1D This section is optional.
level 230. level 230.

Section Name PPP port Dialup Invoked when

86
10BMDLC over IP Communication

Section Name PPP port Dialup Invoked when


Prereset Issue reset AT command to Issue reset AT command to First time configuring
radio/modem when radio/modem when modem, or after failed to
applicable. Some modems applicable. Some modems configure several times
can be powered off and on can be powered off and on consecutively.
this way. this way.
Postreset Check if modem connected Check if modem connected After restarting modem
after restarted. after restarted. and waiting for it to
recover.

MDLC over IP Modem Configuration


The MDLC over IP port runs certain sections of the modem configuration file to configure the
modem and set it in PPP. This is done using a packet data modem connection such as Standard
Modem or Tetra. During this time, the port is not considered eligible for transmission, and any
transmissions are held pending for a predetermined time in a queue. This time is determined in
the site configuration in the Advanced Link Layer Modem Configuration Timeout parameter.

Modem restart

1. Prereset section.

2. Toggle RTS.
3. Postreset section.

This section is issued when first configuring the modem, or after failing to configure the
modem several times consecutively. The [Prereset] section is intended to restart power via an
AT command. If the modem does not support this feature, leave this section empty.

Depending upon the hardware setup with the modem, the RTU RS232 signals may be used to
power it off and on. For example with G18, the RTU toggle its RTS and powers off and on the
modem. A new board FCN6070 provides that feature for some portable radios such as ASTRO
IV&D XTS2500.

Finally, the RTU waits for the modem to power up, and then checks if it is alive by running the
[Postreset] section.

The RTU will not continue configuring modem until the modem restart succeeds. Leave those
sections empty if they are not supported by your modem.

Modem disconnection:

4. SetCommandMode section.

5. HangupPD section.

This puts the modem into command mode and makes sure the modem is connected to the port
prior to configuring it.

87
10BMDLC over IP Communication

In some modems such as G18, an LCP Terminate Request must be sent. This binary string,
which is part of the PPP protocol, makes sure that the modem disconnects PPP, if it was on.
Therefore this is the first string sent in the HangupPD section.

Note for SetCommandMode: Some modems do not support an abort sequence (a 1 second idle
line, followed by +++ string and another 1 second of idle line.) When a modem is connected
this sequence sets it in command mode, where it can be programmed using AT commands.
However, for modems that do not support this feature, leave section [SetCommandMode]
empty, and set the following variable ToggleRtsCommand=1. This will force the RTU to
toggle its RTS output when setting command mode. Using a proper RS232E+ adaptor/cable
(FTN6359A) will connect that signal to the modem’s DTR input, causing it to disconnect. For
that to work, the modem must have been configured previously with AT&D1.

Modem configuration:

6. VerifyParms section. Verifies modem identity. This is not a mandatory section.

7. ConfigurePD section.

8. DialPD dialup modem and place it in PPP mode. This cause modem to register within
infrastructure.

Once modem has been configured it is now monitored to maintain that connection. Its PPP
connection is monitored as well as its DCD signal, which shows that it is active. This indicates
that the modem is indeed registered and able to receive and transmit IP over the air. Some
modems do not have DCD. A variable named IgnoreCD can be set to 2 (IgnoreAlways) so the
DCD will not be polled. It is recommended to consult with technical support before using such
a modem/radio.

PPP based modems initiate PPP once you dial into it. Connecting PPP involves actually
registering the modem within the infrastructure. This may take several seconds or up to a
minute. During this time, the port is not considered eligible for transmission and any
transmissions are still held pending in queue. Once PPP is connected, the frames can be
transmitted.

The modem is configured in the following situations:

1. When it is detected that the modem is not PPP connected, or its DCD has dropped;

2. When the RTU experiences a power restart (with or without battery);

3. When the RTU restarts because of a new configuration;

4. When downloading a new configuration file;

5. When diagnosing the modem using modem configuration file; levels 223 and above are
used for that purpose.

In the last three cases, the modem is disconnected and is not configured immediately. When
diagnosing using a modem configuration file, the modem is interrogated using AT commands,
and its responses are queued within the MDLC over IP port. Once all responses received,
MDLC over IP port reconfigures the modem as specified above.

Note that if it is done remotely, e.g. over a GPRS network, the diagnostic response may take 30
seconds or more. The user should set the modem configuration timeout to be long enough so
88
10BMDLC over IP Communication

that the response does not get lost. A 30 seconds timeout is a typical delay but it may need to
be extended to 60 seconds.

MDLC over Dialup Modem Configuration


The user can configure the modem from the RTU using the MDLC over Dialup port. In
previous systems, the user had to configure the modem externally (e.g. PC terminal) and then
save those parameters in the modem. A config modem string can be defined in the Physical
Layer to configure the modem. The modem configuration file enables the user includes the
config modem string and other AT commands. If no modem configuration file exists, the
config modem string will be used. If both exist, the modem configuration file will be used.

MDLC over Dialup is different than MDLC over IP in the way it configures modem and
connects it. It is important to note that the same modem can work in both modes, but the user
must decide when configuring the port, what method to use. With MDLC over Dialup, the
modem is placed in circuit data mode, meaning it establishes phone call conversations with
remote sites upon transmitting to them. It accepts calls when another site transmits an MDLC
frame to it. Most of the time the modem is idle, meaning it is in command mode. It only
moves into data mode, when it needs to transmit or is called from another site. After a
predetermined idle time, the modem disconnects the call. With MDLC over IP, the modem is
ALWAYS in a “call”. The “call” is actually PPP mode. This enables it to receive MDLC over
IP frames from remote sites, as well as sending them. This “call” does not consume any air
resources since it begins with the RTU and ends in the modem itself.

MDLC over Dialup configures the modem by running the following sections of the modem
configuration file:

Modem disconnection:

1. SetCommandMode section.

2. HangupCD section.

This puts the modem into command mode and makes sure the modem is connected to the port
prior to configuring it.

Modem configuration:

3. VerifyParms section. Verifies modem identity. This is not a mandatory section.

4. ConfigureCD section.

Once the above is accomplished, the modem is not connected. It simply waits for calls, and if
frames need to be transmitted, the RTU initiates a call to a remote site.

To make it more reliable when using wireless modems such as G18 GSM modem in dial mode,
the modem is monitored periodically to check if it is registered. This is done by running the
chkvld section every few seconds. This section is optional, and if empty, no action is taken.
In the G18.stm file, this section is not empty; if it fails to get an appropriate response from the
modem, it reconfigures modem as specified above.

89
10BMDLC over IP Communication

How to Test a Modem for Dialup


Prior to using an external modem, emulate an external terminal using a PC and any standard
communication program, and set its parameters as follows:

• 9600 bps (for example)


• 8 bits
• no parity
• 1 stop bit

Enter the modem telephone numbers into the site phonebook.

If you are using an external modem, set its configuration according to the following list.

Action Command

Disable off-line echoing ATE0


Enable audio messages ATV1
Disable quiet mode (The status codes are sent to the ATQ0
terminal.)
Enable all codes ATX4
Enable carrier detect when a connection is AT&C1
established.

You may enter the commands in one string, ATE0V1Q0X4&CI&W, where &W implies
saving the above parameters for the next power-up.

It is also possible to configure the modem from the RTU over a dialup port. A modem
configuration file is used to send the appropriate AT commands to the modem. For more
information, see the MDLC over Dialup Modem Configuration.

When several RTUs are connected to the PSTN (Public Switching Telephone Network), as
illustrated below, several configurations are viable as described in the examples that follow.

RTU 2
MODEM AT
PORT SI2

MODEM AT
PORT SI1 MODEM AT
RTU 1 PSTN PORT SI2
RTU 3

MODEM AT
MODEM AT PORT SI2
PORT SI1 MODEM AT
MODEM AT
PORT SI2 PORT SI1

RTU 4 RTU 5

90
10BMDLC over IP Communication

Note that in the illustrated configurations, as in all the connections over the PSTN, there is only
one link ID. It is the responsibility of the software to decide which line to dial. When two
lines are available, the Port SI1 line has priority.

1. To communicate between RTU 1 and RTU 2:

• Configure RTU 1 port as external modem.

• Update the RTU 2 telephone number.

• Any transmission from RTU 1 to RTU 2 will cause automatic dialing. As the
connection is established, information will be transferred from one modem to
the other. When no information is transferred for a period longer than the
“Hanging up an unused line by INITIATOR after...” Advanced Physical Layer
parameter, the line will be disconnected.

2. To communicate between RTU 1 and RTU 4:

• Configure RTU 1 port as external modem.

• Update the two RTU 4 telephone numbers.

• Any transmission from RTU 1 to RTU 4 will cause automatic dialing to the
first number in the phone book. If the first number is busy, or there is no
answer, the second number is automatically dialed. As the connection is
established, information will be transferred from one modem to the other.
When no information is transferred for a period longer than the “Hanging up an
unused line by INITIATOR after...” Advanced Physical Layer parameter, the
line will be disconnected.

3. To communicate between RTU 4, RTU 5, and RTU 3 simultaneously:

• Configure RTU 4 Port SI1 and SI2 as external modem.

• Update the two RTU 5 telephone numbers and the RTU 3 telephone number.

• Any transmission from RTU 4 to RTU 5 will cause automatic dialing from the
first available port (when both ports are available, Port SI1 is chosen) to the
first number on the list. If the first number is busy, or there is no answer, the
second number is automatically dialed. As the connection is established,
information will be transferred from one modem to the other. When no
information is transferred for a period longer than the “Hanging up an unused
line by INITIATOR after...” Advanced Physical Layer parameter, the line will
be disconnected.

• Any transmission from RTU 4 to RTU 3 while RTU 4 and RTU 5 are
connected, will cause automatic dialing from Port SI2. If RTU 4 and RTU 5
are disconnected, then Port SI1 will be selected for dialing.

91
10BMDLC over IP Communication

Diagnosing the Modem over the MDLC over Dialup Port


MDLC over Dialup can also diagnose a modem using its modem configuration file. This is
done by connecting the STS and running the SW Diagnostics on Device LIN1D Level 223 or
above. If the appropriate DiagX section (e.g. Diag0 for 223, Diag1 for 224) does not exist in
the modem configuration file, no action is taken. If it exists, the modem is interrogated and its
responses are displayed in SW Diagnostics.

Note that for MDLC over Dialup, if a phone call is held, this operation is not executed and an
error is displayed. This means, that unlike MDLC over IP, diagnosing the modem using its
configuration file cannot be done remotely over dialup. (It can be done either locally from
another port or remotely from another link.)

Modem Configuration File Variables


The variables listed below control the way modem is configured by the RTU.

The modem configuration file serves both types of ports: MDLC over IP port connected to a
packet data modem over PPP and MDLC over dialup port connected to a circuit data modem.
For MDLC over IP some of these variables also appear in the Site Configuration and are
marked accordingly. Some of these variables are relevant only for PPP (packet data), and some
are relevant for dialup as well.

The variables are initialized in the modem configuration file in the [Initialize] section
each time modem is to be configured. If a variable exists in the file, that value overrides default
settings in the site configuration.

There are three types of variables:

• INT – Four byte integer variables representing time or Boolean (true or false) values.
Boolean values are 0 for false and 1 for true.

• IP Address – Four digit IP addresses in the form of xxx.xxx.xxx.xxx where xxx ranges
from 0 to 255.

• String – Any character string up to 30 characters.

Usually a variable is set manually in the [initialize] section as explained above. For
example:
$WaitForOk= 2000
sets the WaitForOK variable to 2000.

A variable can also be set/overridden from the modem. For example:


<AT+CIMI><$ModemAddress>
sends the AT+CIMI command to the modem and sets the ModemAddress variable to the
modem address in the response.

All variable values can be viewed using the SW Diagnostics level 221 for LIN1L (or LIN1D in
dialup port). LIN1 stands for link ID LINE1. If a different link ID is used, such as LINE7 the
device would be LIN7L or LIN7D.

92
10BMDLC over IP Communication

The FileVersion variable is used to identify the modem configuration file version.
FileVersion=xx.yy, where xx is the file version and yy is the file revision. When the file
is downloaded, the RTU verifies that it supports its version.

The file version (xx) should not be changed unless stated. The revision number (yy) is used to
keep track of your changes to the file. It has no meaning to the modem but it is recommended
that it be increased each time the file is changed. For the first release of this feature, the file
version should be set to 1.0.

Variable name Meaning Type Comment


FileVersion File version and revision: STRING Used for both PPP and
version.rev (e.g. 1.0) dialup.

The following variables are used when programming the modem. Some of them are PPP-
specific. Some are common to both MDLC Over IP and MDLC Over Dialup.

Variable name Meaning Type Comment


WaitForOk Default timeout in millisecs INT Common to both
to wait for modem reply MDLC Over IP and
MDLC Over Dialup

WaitForDial Default timeout in millisecs INT MDLC over Dialup


to wait for connection to only
succeed when dialing

WaitForDiag Timeout in millisecs used INT Common to both


when diagnosing modem; has
no meaning for now

DTEIpAddr IP Address of RTU IP Address MDLC Over IP only

DCEIpAddr IP Address of modem IP Address MDLC Over IP only

GTWYIpAddr IP Address of gateway IP Address MDLC Over IP only

DTESubnetMask Subnet mask of modem IP Address MDLC Over IP only

DTEPrefixlen Number of 1s (most INT MDLC Over IP only


significant bits) in subnet (iDEN especially)
mask, e.g. 16: 255.255.0.0

UserName Username to be used when STRING MDLC Over IP only


authenticating PPP using Also found in Site
PAP or CHAP configuration user
section.
Password Password to be used when STRING MDLC Over IP only
authenticating PPP using Also found in Site
PAP or CHAP configuration user
section.

93
10BMDLC over IP Communication

Variable name Meaning Type Comment


AbortSeqExist 1 if modem supports abort INT Common for both
sequence. Abort sequence is
+++ string sent to modem in For MDLC over IP,
order to change it from data also found in Site
to command mode. configuration
Advanced Link.

IgnoreCD Whether or not to ignore CD. INT Common to both


0 – never ignore, 1 – ignore
always, 2 – ignore during For MDLC over IP,
dial. also found in Site
configuration
Advanced Link.

DisconctIcmpNet Disconnect modem when INT MDLC Over IP only


getting ICMP:Destunreach Also found in Site
configuration
Advanced Link.

DisconctRxIdleTime Disconnect modem when not INT MDLC Over IP only


getting anything for Also found in Site
RxIdleTime in seconds. 0 configuration
means it will never be Advanced Link.
disconnected.

SetRTSTimeout Time to wait after setting INT Common to both


RTS in milliseconds and
powering on the modem
where applicable (e.g. G18
and XTS2500 ASTRO
IV&D radio)

UnsetRTSTimeout Time to wait after unsetting INT Common to both


RTS in milliseconds and
powering on the modem
where applicable (e.g. G18
and XTS2500 ASTRO
IV&D radio)

ToggleRTSCommand 1 if need to toggle RTS when INT Common to both


setting modem in command
mode.
0 RTS will not be toggled
when setting modem in
command mode.

The following variables are for diagnostics only.

Variable name Meaning Type Comment

94
10BMDLC over IP Communication

Variable name Meaning Type Comment


ModemName Name of modem STRING Common to both

ModemAddress Address of modem such as STRING Common to both


MAC address

ModemVersion Version of modem STRING Common to both

ModemRSSI RSSI of modem STRING Common to both

The following additional PPP variables are available in the STS configuration. If these
variables were set in a file, their value set in that file overrides those settings.

Variable name Meaning Type Comment


Pppechosendinterval PPP Echo send interval in INT MDLC over IP only.
milliseconds. By default it is
0. To support modems that
do not provide DCD input to
RTU, RTU will poll modem
using PPP in order to check
if it is connected.
Pppechosendmaxretry PPP Echo send max retries. INT MDLC over IP only
If modem does not reply
within that limit, it is
detected as disconnected.
RTU will try to reconnect it
via PPP.
Pppprocomp PPP protocol compression. INT MDLC over IP
This parameter can be 0 or 1.
By default it is 1 which
specifies that the RTU use
this option. For those CDMA
modems which do not
support that feature, it should
be set to 0.
Pppaddrcomp PPP address compression. INT MDLC over IP
This parameter can be 0 or 1.
By default it is 1 which
specifies that the RTU use
this option. For those CDMA
modems which do not
support that feature, it should
be set to 0.
PPPmaxmtu PPP maximal frame in bytes. INT MDLC over IP
1500 is standard.

95
10BMDLC over IP Communication

Pppauthpro PPP authentication protocol. INT MDLC over IP


If 0, it will be negotiated with
the modem via PPP protocol.
Two other authentication
protocol supported are
0xc023 (PAP), and 0xc223
(CHAP). The user can force
the RTU to ask for another
protocol, but as a PPP client
this is usually 0.
PPPasynctl PPP Async Control Character INT MDLC over IP
Map. Usually set to 0.

96
10BMDLC over IP Communication

The following variables are not PPP related:

Variable name Meaning Type Comment


N_failstoreset Number of configuration INT MDLC over IP
failures to reset modem. This
MDLC over Dialup
parameter is interpreted
differently in MDLC over IP
than in dialup.
In MDLC over IP, when
failing to connect to the
modem several times, it
determines after how many
failures to restart the modem.
If 0, it will never be restarted.
In dialup, the modem is
restarted immediately after
detecting it has failed. If this
parameter is 0, it will not be
restarted.
Max_failedtime This parameter is in INT MDLC over IP
milliseconds.
If the RTU failed to connect
with modem for 120 seconds,
it will notify the error logger.
WaitAfterDial Time to wait in milliseconds INT MDLC over Dialup
after dialing to another
modem and getting
connected. This is to enable
the other modem enough
time to connect. By default
this parameter is set to 2000
(2 seconds).
RetryModemConfig If set to 1, instruct the RTU INT MDLC over Dialup
to keep retrying to configure only
modem in case it was
disconnected and failed
configuration.
By default it is 0: The RTU
will try to configure modem
only once, and if it fails will
not retry.

The following variable is for the [DiagX] section such as Diag0. It instructs the RTU to route
the modem response into the SW Diagnostics.

Variable name Meaning Type Comment


Diag Last modem response when STRING
executing Diag section.

97
10BMDLC over IP Communication

Modem Configuration File Command Syntax


The format of the AT commands in the modem configuration file is as follows:

<AT command><Expected response><Timeout in seconds>

If no <AT command> is specified, no command will be issued. Note that empty brackets <>
must be used if no command is to be issued.

If no <Expected response> is specified, the RTU will wait the specified timeout and ignore any
response. Note that empty brackets <> must be used if no response is expected. ‘0x0D’ should
be appended to the AT command with in this case.

If no <Timeout in seconds> is specified, the RTU will wait $WaitForOkTimeout seconds for
the modem to respond.

If the received response does not match the <Expected response>, the RTU will keep waiting
for specified timeout (500 milliseconds). If the desired response is still not received, it will
restart modem configuration again.

Each AT command is automatically appended with \r (0x0D Hex), unless <Expected


Response> is empty. In that case, ‘0x0D’ should be appended explicitly in the command.

Each AT command response is automatically prefixed and appended with \n\r (0x0A and
0x0D) by the modem. When specifying the <Expected response>, there is no need to specify
them.

<Expected response> can also be an environment variable. For example:


<AT+CIMI><$ModemAddress>
will issue the AT+CIMI Command and put its response in ModemAddress variable.

Multiple responses can be expected by specifying them inside the braces (of expected
response). For example:
<ATH><(OK)(NO CARRIER)>
will expect either OK or NO CARRIER response.
<AT+CREG?><+CREG:00(0)(1) 001>
will expect +CREG:000 0001 or +CREG:0001 001 as an output.

The \ delimiter can be used as an escape character if ‘$’ or ‘>’ is within an AT command or a
response, as follows:
<AT\$command><OK>
will issue AT$command and expect an OK response.

One can also send binary bytes instead of ASCII by prefixing each byte with ‘0x’ as follows:
<0x7e0xff0x030xc00x210x050x020x000x040x590x280x7e><><2> ; LCP
Terminate Request
This string is a binary string comprised of the bytes 7e in hex, ff in hex, 03 in hex etc. It is used
for terminating a PPP session.

98
10BMDLC over IP Communication

IP Conversion Tables
The IP conversion table is created in the ACE3600 STS using the IP Conversion Table
Manager. Note that unlike the network configuration, there is no default, and any IP
conversion tables must be created manually. The IP conversion table maps sites in the system
(site ID+link ID) to IP addresses or host names. Each site ID/link ID pair can have one unique
entry in the table, though an IP address can appear in more than one row. A site ID of 0 is
reserved for a group call.

In RS232 PPP and Ethernet DHCP, the IP address is read from the network once it is
connected to the RTU. In Astro IV&D, this is not the real IP address set by the infrastructure;
rather, it is a dummy address configured in the radio via the CPS Mobile Computer IP address
which is (by default 192.168.128.2). In the IP conversion table do not specify this address, but
the actual IP address assigned by the infrastructure operator. Note: The IP address displayed
by the SW Diagnostics LIN1L level 0 is the dummy address and should not be used in the IP
conversion table.

The ACE3600 IP conversion table format includes a link ID column which allows more than
one port in the same site to be connected to LAN or to PPP. Any legacy MOSCAD RTU or IP
Gateway in the network must defined using its own Toolbox IP Conversion Table utility.

Control
Center

CEN LAN
FEP 100
LINE 1 FEP 10.5.1.xx

LINE 2

Packet Data
Network

192.5.1.xx

Subscriber Radio Subscriber Radio


1 2

LINE 1 PPP/RS-232 LINE 1 PPP/RS-232


PEI PEI
RTU-A RTU-B
LINE 2
LINE 2
LAN
155.9.1.xx

In the example above, two sets of IP conversion tables should be created and the FEP’s Table
should be assigned to the RTUs:

FEPs Table:

Site ID Link ID IP Address or Host name

99
10BMDLC over IP Communication

100 LINE1 10.5.1.160

100 LINE2 155.9.1.17

The RTUs Table should be assigned to the FEP:

Site ID Link ID IP Address or Host name

1 LINE1 192.5.1.161

1 LINE2 155.9.1.18

2 LINE1 192.5.1.162

2 LINE2 155.9.1.19

As another example the IP conversion table can be set with names rather than numeric Ipv4
addresses. In this case make sure these names are the full host names set by your network
administrator. Make sure the DNS Server are either learned (DHCP and PPP) or set them
manually in port configuration (Static LAN). You can check DNS servers in the STS SW
Diagnostics device DNS_CLI level 1. For example:
DNS servers list
----------------

*ETH1 10.5.34.2

PI2 10.6.34.2

PI1 www.mysite.com 155.9.16.102 155.9.16.103 155.9.193.240 * marks the


recently used DNS server

The list above is sorted by ports – each port has its own DNS servers. The same DNS server
can appear in more than one port. Note: The www.mysite.com is the zone domain name
obtained from DHCP server.

In this example assume the operator has assigned two names for FEP: FEP1.moto.com for port
LINE1 and FEP2.moto.com for port LINE2. The FEPs Table should look as follows:

FEPs Table:

Site ID Link ID IP Address or Host name

100 LINE1 FEP1.moto.com

100 LINE2 FEP2.moto.com

100
10BMDLC over IP Communication

In this example, LINE2 is Static LAN so the user needs to set the DNS servers of LINE2
network in the LINE2 port configuration of RTU #1 and RTU #2. LINE1 is PPP, so there is no
need to set these servers – they are learned from the network automatically.

In principle it is recommended to create two sets of IP conversion tables – one that will be
assigned to an FEP/IP Gateway on the LAN, and one to all other RTUs which are connected
with the ASTRO IV&D radios. The first will include the above information concerning each
RTU, and the second will have only the FEP/IP Gateway.

For MDLC over iDEN, MDLC over Tetra, and MDLC over Standard or Null Modem, consult
the system provider for the infrastructure relating to the IP addresses.

You can also check the IP Address yourself. After the RTU is configured in the STS, connect
the modem to the RTU, and invoke the SW Diagnostics tool in the Software Diagnostics &
Loggers utility. For a port link ID named LINE1, first run device LIN1L level 101 and see if
the state of the configuration task is “Connected and registered”. Then run level 0, and see the
RTU IP Address as obtained from the modem.

MDLC over IP Connection Verification


Once the setup for the desired MDLC over IP variation is completed and the necessary files
(site configuration and IP Conversion table and perhaps modem configuration file) have been
downloaded to the RTU, the connection should be verified.

1. Check that the radio/modem is powered up. This can generally be done by checking
the radio display. For Astro radios, the RTU powers it off and on every few seconds, if
it is unable to context activate it. If the radio has no display (e.g. Astro model type I),
check that the LED on top is turned on when the PTT button is pressed.

2. Check the connection status using the Software Diagnostics tool. In device LINxL,
level 101, verify that the State of configuration task is set to Connected and Registered.
(This means that the radio is context activated.) In device LINxL level 0, check that
the IP Address was set by the radio/modem/infrastructure (no longer 000.000.000.000).
Next, check that the Port is in Fail diagnostic is set to No.

3. If the above diagnostics indicate a configuration failure, repeat the steps described in
the MDLC over IP setup for the desired variation and check the physical connection
between the RTU and the radio. Certain Astro IV&D and GPRS radios/modems that
are not context activated will be restarted by the RTU. You can recheck the State of
Configuration Task and the Cause for configuration failure diagnostics and check the
error logger after two minutes. Verify that the Site ID appears in the IP Conversion
table, check the IP addresses, etc. For Astro IV&D radios that were configured using a
CPS, verify that the radio was programmed correctly.

4. Once the radio has been successfully context activated by the RTU, check the
communication over the air. For example, try to read the error logger from a remote
RTU using the STS. The local RTU should be able to communicate with the remote
RTU over the radio/modem.

5. If using host names, check with SW Diagnostics, device DNS_CLI level 1 that a DNS
server is OK. Each port may have its own set of DNS servers.

101
10BMDLC over IP Communication

102
Firewall

The ACE3600 Firewall package enables the user to define a variety of firewall protections.
The package is based on Windriver™’s firewall package, version 1.0.

Firewall Configuration
The firewall is configured and activated in the ACE3600 STS site configuration per site, for all
IP ports in the site. The user can specify the list of IP addresses to accept, i.e. the list of IP
addresses allowed to pass through this firewall. If no IP addresses are defined, then all
addresses are allowed.

The following attributes are defined for the firewall.

Activate firewall? <Disable/Enable> [Disable]:


Whether the site’s firewall should be activated.

Max size of ICMP packet <0-65535> [100]:


The MAX size of ICMP Echo (ping) allowed. A ping packet with a bigger size will be ignored,
no response will be sent back.

Address List
The list of IP addresses allowed to pass through this firewall. If no IP address is defined, then
all address are allowed. To add or remove addresses from the list, click on Address List. To
append a line, click on Append Line. To remove a line, click on Remove Line.
To save the list, click on OK.

If the firewall is active, all UDP/ TCP ports will be blocked (e.g. telnet, http) except for the
following:

• DHCP port

• DNS port

• MDLC port (UDP 2002)

• NTP port

103
Clock Functions and Synchronization

RTU Clock
The ACE3600 RTU has one time source, an internal system clock which is in microsecond
resolution. This time source is updated using a backup source of the RTC hardware
component - Real Time Clock (seconds accuracy).

In addition, external clocks, such as GPS and NTP servers can be used as a time source.
See NTP Clock Synchronization and Global Positioning System (GPS) below.

The time resolution of the system clock is hour, minute, second, millisecond, microsecond.
The date resolution is day, month, year. Leap year support is automatic.

When the RTU first starts up, the system clock is set according to the RTC, which always
retains its time in seconds (even when the RTU is powered down.) The RTU time can then
be set using a number of mechanisms.

The RTU clock controls the date and time of the ACE3600 unit. Date and time information
is used for timestamps on events such as time tagging changes to time tagged discrete
inputs, etc. Note these time tags are in millisecond resolution.

The ACE3600 includes configurable time zone support, where RTUs in one time zone can
adjust messages received from another time zone. The time zone is commonly used in
conjunction with NTP servers and a GPS receiver. These servers operate in UTC
(Universal Time Clock) which is in the (Greenwich Mean Time) GMT time zone. Setting
the time zone in a unit will adjust it to the local time.

The ACE3600 also supports daylight savings time. Daylight savings time is used only in
conjunction with a time zone. The start and end dates for daylight savings time (month,
day, hour) can be defined in the Daylight Saving Dates table. (The current year is
assumed.) The RTU will check these dates and adjust the time by one hour when
appropriate. The time zone is set in the STS site configuration and the daylight savings
time is set in the application system table.

Time Adjustment and Synchronization


MDLC time synchronization of the RTU clock can be performed locally or remotely, using
MDLC protocol over a variety of communication media, including conventional radio,
RS485, and RS232. Synchronization is accurate to 1 millisecond+0.5 (very low delay.
With IP media, this feature can be enabled, but because its accuracy/delay is unpredictable
it is not recommended. NTP, the recommended method of obtaining the time over IP
media (PPP or Ethernet), allows accuracy of 1 to 100 milliseconds depending on the media.

In ACE3600 RTUs, a new MLDC extended time synchronization can be enabled which
includes the synchronizing RTU’s password. In this case, all RTUs in the system must use
the same password. This extended time synchronization also enables synchronizing two

104
RTUs in different time zones, and better accuracy than the MOSCAD MDLC legacy
synchronization. Note that by default, the ACE3600 uses MOSCAD MDLC legacy
synchronization (to support IP Gateway and MOSCAD RTUs) which does not include the
time zone and password features.

Note: An extended time synchronization of two RTUs, where only one is configured for
time zone, will proceed as if both RTUs are in the same time zone.

The RTU clock can be synchronized during runtime using a number of methods. Before
synchronizing the clock, make sure that the appropriate parameters have been configured
properly. (See Time Parameter Configuration below.)

User Time Control Actions

• STS Date & Time utility – From the STS, the user sets the RTU date/time to the PC’s
date/time (which is limited to seconds accuracy.) For information on using the
Date & Time utility, see the Operation chapter of the ACE3600 STS User
Guide.

• STS Sync utility – From the STS, the user instructs the local RTU to synchronize (in
milliseconds accuracy) the date/time of other RTUs attached to one or all links.
It is recommended to synchronize all links, so that the entire system has the
same date/time. For information on using the Sync utility, see the Operation
chapter of the ACE3600 STS User Guide. Note that MDLC dialup links do not
support synchronization.

• User Application –
- The user application (ladder or ‘C’) can synchronize RTUs on one or all links
using the Sync function. It is recommended that an RTU with a reliable clock
source synchronize all RTUs in the system once per day to correct clock drift.
The requirement for legacy MOSCAD RTUs to synchronize RTUs at least once
every 48 days is not relevant to ACE3600 RTUs. However, ACE3600 has a drift
of 30 ppm which is 2.6 seconds per day if not connected to an NTP server and/or
GPS receiver. The worst case is a drift of 1.8 milliseconds per minute, or 18
milliseconds per 10 minutes. Typical tests shows better results at 1 millisecond
per 2 minutes, or 5 millisecond per 10 minutes. The interval of sending a time
sync, is proportional to that clock offset/accuracy – sending a sync every 2
minutes assures a 1 millisecond offset typically.)
For information on the Sync function, see Appendix B: Ladder Diagram
Language in the ACE3600 STS User Guide. For information on the
MOSCAD_sync(), MOSCAD_datetime_syncall() ‘C’ services, see the ‘C’
Toolkit for ACE3600 RTUs User Guide.

- When the user application (ladder or ‘C’) updates the Time & Date database
system table, it also changes the RTU time and date. For more information on
the Time & Date database system table, see Appendix C: Database Tables and
Data Types in the ACE3600 STS User Guide.

- The user can update the same Time & Date database system table
(HH:MM:SS) using the Application Programmer database monitor function. In
this case, synchronization is direct (no time zone aspect.) For information on

105
monitoring a database table, see the Application Programmer chapter of the
ACE3600 STS User Guide.

System Time Control Actions

• GPS Connection – An RTU which is connected to a GPS receiver continuously polls


the GPS time and synchronizes itself. Because the clock source is reliable, this
RTU can be used to synchronize the rest of the system. See the Global
Positioning System (GPS) section below.

• NTP Connection – An RTU which is connected to an NTP server continuously polls


the NTP server(s). Because the clock source is reliable, this RTU can be used to
synchronize the rest of the system. The accuracy of NTP time depends on the
link to the NTP server. It can be 1 millisecond in a LAN where the NTP server
reside on the same network, and up to 100 milliseconds if using wireless media
such as GPRS or TETRA. See the NTP Clock Synchronization section below.

Notes:

1. When obtaining the time from system time control actions (GPS receiver
and/or NTP server) and the time is valid, the ClockValid system flag in the
Reserved flags system table is set to 1. When this flag is set, all user time
control actions (e.g. Date & Time command, Sync command) are ignored.

2. An RTU or FEP connected to a GPS receiver and/or NTP server, can


synchronize other RTUs either from the ladder application Sync command,
or using STS Sync operation. Note that for IP media this is disabled by
default, and is not recommended, but for non-IP media such as radio or
RS485 it is valid.

3. PC hosts, NTP servers, and GPS receivers operate on UTC time (GMT
time zone). If it is necessary to us the local time– set this time zone in the
‘Timezone offset in minutes’ advanced parameter in the STS site
configuration.

If the synchronizing RTU is in a different time zone than the RTU being synchronized and
uses extended time sync,, the system will adjust the time accordingly; the receiving RTU
will add the time zone of the sender to the global time (GMT) and use this. If only one of
the two RTUs involved is configured for time zone support, the synchronization will
proceed as if both sites are in the same time zone.
Note: A legacy MOSCAD RTUs is treated as an RTU which is not configured for time
zone support.

Time Parameter Configuration


Configuration of the RTU’s clock and time characteristics and functions is done during
system initialization. Compatibility issues may arise in hybrid systems which include
ACE3600 RTUs and legacy MOSCAD RTUs. The behavior of the RTU is such situations
is determined by the settings in the relevant STS site configuration parameters.

106
Time Synchronization
The following Time Synchronization parameters are found in the Advanced tab of the STS
site configuration.

Time sync method <Extended Sync/Legacy Sync> [Legacy Sync]:


This parameter defines the method to be used when sending time synchronization. In a
system with legacy RTUs, the sync method should be Legacy Sync.

Extended Sync – RTU sends sync protocol frames containing time zone and
password, with nanosecond resolution. (1 millisecond accuracy
over synchronous media (radio) and over asynchronous RTU to
RTU media.)

Legacy Sync – For synchronizing legacy MOSCAD RTUs. No time zone or


password, with milliseconds resolution. Assumes sending RTU is
in the same time zone. (5 millisecond accuracy) This is the default
in ACE3600.

Password check in case of long sync<Check/Ignore Password> [Check Password]:


This parameter determines the behavior of the RTU when it receives a password in an
extended sync frame. Note this parameter has no meaning when receiving a legacy MDLC
sync. The valid values are:

Check Password – RTU will check password in extended sync frames and
authenticate sync message before updating the clock. If it does
not match it will be rejected. See SW Diagnostics Device
TIMESYN level 10 for statistics of received/ignored sync
frames. This is the default in ACE3600, but is relevant for
extended sync only.

Ignore Password – RTU will ignore password in extended sync frame and update the
clock for any extended sync frame. This is useful in case you
have RTUs with different passwords. RTUs with default
configuration have the default of Ignore Password.

What to do with received short sync messages? [Don’t Ignore SHORT sync messages]:
This parameter determines the behavior of the RTU when it receives a short (legacy) sync
frame. It has no meaning when receiving an extended MDLC sync. The valid values are:

Ignore SHORT sync messages – Do not update the clock when legacy sync
messages are received.

Don’t Ignore SHORT sync messages – Update the clock when legacy sync messages
are received. This is the default, so ACE3600 can
be synced from a MOSCAD or from another
ACE3600.

Time Zone
The following Time Zone parameters are found in the Advanced tab of the STS site
configuration.

107
Time zone learning mode <No time zone/User Configured> [No time zone]:
This parameter determines how the time zone of the unit is set.

No time zone - RTU will have no time zone. The next parameter ‘Time zone offset
in minutes’ will be ignored. If an extended time sync frame is
received, it will sync with the same time zone as the sending RTU. If
using a system control time such as GPS receiver or NTP server is
used, its time will be GMT time. The Daylight Savings database
table is ignored.

User Configured – The user can set the local time zone in the ‘Time zone offset in
minutes’ parameter. The daylight savings database table is read to
determine daylight saving time. When receiving an extended time
sync from another RTU or when receiving Set Date & Time from
the STS, the difference in time zone is taken into account, so they
can operate in different time zones.
In this mode, daylight savings time start/end dates can be specified
in the Daylight Savings database table. When the unit moves from
no daylight savings to daylight savings, the time tag logger is
notified that the time has changed.

Note: If a user-configured RTU powers up when daylight savings time is in effect, and
errors occur during startup, those errors will be logged with no daylight savings time.

Time zone offset in minutes <(-720)-720> [0]:


The time zone offset from GMT, counting east. This parameter is relevant if the ‘Time zone
learning mode’ parameter is set to “User Configured.”

Port Advanced Link Parameters


The following parameter is found in the Advanced Link parameters for MDLC over IP
(PPP or Ethernet) ports (serial onboard or plug-in) in the Ports tab of the STS site
configuration.

Enable sync <Disable/Enable> [Disable]:


For PPP and 10/100 BT connections. This parameter enables or disables synchronization
over IP. It must be enabled in both the sending and receiving unit in order to synchronize.
Note: Because the delay is unpredictable, enabling this parameter is not recommended.
Use NTP instead where possible.

Daylight Saving Dates Table


The Daylight Saving Dates table is used to define the start and end dates for daylight
savings time.

MonthStart: This variable represents the month (1..12) during which daylight savings
begins.

DayStart: This variable represents the day (1..31) on which daylight savings begins.

108
HourStart: This variable represents the hour (0..23) at which daylight savings begins.

MonthEnd: This variable represents the month (1..12) during which daylight savings ends.

DayEnd: This variable represents the day (1..31) on which daylight savings ends.

HourEnd: This variable represents the hour (0..23) at which daylight savings ends.

Time Synchronization Diagnostics


Synchronization diagnostics can be retrieved from the ACE3600 RTU using the STS SW
Diagnostics & Logger device TIMESYN. Level 0 provides MDLC time synchronization
parameters. Level 10, 11 provide MDLC time synchronization statistics. For details, see
the TIMESYN device in the ACE3600 Software Diagnostic Output and Error Messages
manual.

Use device NTP level 3 to view the local time with all its aspects, even when no NTP
servers are configured. This level will show the local time of RTU, if the unit is time zone
aware, the time zone in minutes (offset from GMT), and whether daylight savings time is in
effect.

NTP Clock Synchronization


The Network Time Protocol (NTP) can be used as an external clock source to synchronize
the ACE3600 RTU over IP with one or more NTP servers.

In the MOSCAD system, the NTP works in client/server mode, in which a client RTU polls
another server and gets a reply. The server can be another RTU operating NTP, or a host
(PC, Unix, Linux). NTP poll the server RTU every 2 seconds, every 4 seconds, 8 and so on,
up to a poll every 17 minutes. NTP provides client accuracies typically within a
millisecond on LANs and up to 100 milliseconds on WANs (Internet, GPRS). Any RTU
(usually FEP) can act as a server. This enable setting its time via MDLC time sync, for
example, and having other RTUs specify it as an NTP server and obtain their time from it.

NTP synchronizes clock both in time and frequency. In time means it make its clock offset
as close as possible to the server. In frequency means it learns the server drift (time
between “ticks”) in order to avoid polling it every few seconds. An example, not related to
NTP, is ACE3600 send MDLC Sync over radio to another ACE3600. The clock offset
guaranteed to be less than 1 millisecond. However a 30ppm clock drift after 1 minute offset
will be 1.8 milliseconds. NTP prevents that by learning the drift frequency of the server.

User can set a single NTP server, or several ones. NTP operates under the assumption that
each server's time should be viewed with a certain amount of distrust. NTP really prefers to
have access to several sources of lower stratum time (at least three) since it can then apply
an agreement algorithm to detect insanity on the part of any one of these. Normally, when
all servers are in agreement, NTP will choose the best of these, where "best" is defined in
terms of lowest stratum, closest (in terms of network delay) and claimed precision, along
with several other considerations.

109
As the below figure shows, at the top of any NTP hierarchy are one or more stratum 0
reference clocks. These are electronic clocks such as GPS signals, radio signals, or
extremely accurate frequency control. Reference clocks are assumed to be accurate. In
ACE3600 a GPS port can be configured, it will serve as a reference clock for that RTU. In
this case RTU will operate on stratum 1 with an accuracy of 200 microseconds.

Figure 1 NTP architecture


As the above figure shows, time is distributed from an NTP subnet of servers. Each server
comprises a stratum, which designate its location in terms of hops to the UTC source. The
stratum 1 is the most accurate server of which all servers should be synchronized to. Up to
15 stratum levels may exist. Stratum 16 means server unreachable.

The accuracy of other clocks is judged according to how “close” a clock is to a reference
clock (the stratum of the clock, the network latency to the clock, and the claimed accuracy
of the clock. The accuracy of NTP thus depends on the network environment. Because NTP
uses UDP packets, traffic congestion could temporarily prevent synchronization, but the
client can still self-adjust, based on its historic drift. Under good conditions on a LAN
without too many routers or other sources of network delay, synchronization to within a
few milliseconds is normal. Anything that adds latency, such as hubs, switches, routers, or
network traffic, will reduce this accuracy. The synchronization accuracy on a WAN is
typically within the range of 10-100 ms. For the Internet/GPRS synchronization accuracy is
unpredictable, so special attention is needed when configuring a client to use public NTP
servers. Testing with the ACE3600 connected with the Internet gains accuracy of 20-30ms,
but theoretically it may be even 100ms.

NTP uses UTC time base (Coordinated Universal Time). UTC evolved from Greenwich
Mean Time (GMT). GMT is based on the earth’s rotation, which is not constant enough to
be used for detailed time measurements. UTC is based on a standard second length
determined by the quantum phenomena. There is a difference of a few seconds between the
two (14seconds in 2006), so every several years add one more second (called leap second)
to UTC. This is built in NTP protocol.

To translate the UTC time into local time, user can configure Time zones and Daylight
Savings in RTU. Note however, that if setting NTP server to another stand alone
ACE3600, which has no time zone, both will operate with the same local time if no time
110
zone set. If that ACE3600 is connected to a GPS or to another NTP server then there is a
need to set a time zone.

NTP Setup
1. In MDLC over IP port (either RS232 PPP or 10/100 BaseT) select up to three NTP
servers. In some systems, where NTP servers are not available, specify another
RTU/FEP ACE3600. The IP address of NTP server can be either numeric such as
10.17.1.161 or host name such as www.ntp.comm.mot.com . The later format can be
used only if DNS servers were set or learned from the network. If you have several
MDLC over IP port, you can set-up several NTP servers, but make sure the above tree
structure is preserved.

2. Connect this server to a GPS or to another NTP server(s). Another option is not to
configure it with any GPS and NTP servers.

3. Set time zone. In the above first two cases you also need to set time zone in advanced
parameters, so it operates in local time. In the last case, where using a stand alone
ACE3600 as a server (no GPS and no NTP configured) there is no need to set a time
zone.

4. Make sure all servers are in sync. If you configure your primary sever as connected to
GPS, make sure it is able to receive satellites. Check GPS level 1 and NTP level 1 to
see it is synchronized, otherwise it will not be regarded as a valid server. If your
primary server is not configured for GPS and to any other NTP server, it is OK, but
make sure you have only one like that or sync it periodically to avoid clock drift from
other servers (for example by time sync it every few minutes).

The NTP advanced parameters explained in ACE3600 STS User Guide, Appendix A Site
configuration parameters. The most important parameters are shown below:

Max sync offset in msec <0-500> [0]:

The maximum permitted offset of the RTU clock from its NTP server(s). If the offset
exceeds this amount, the NTP servers will be polled frequently to correct the offset,
possibly causing a heavy communication load. When set to 0, the offset is not checked. It is
recommended to leave this parameter set to 0.

Minimal poll interval in sec <1-64> [4]:

The minimal interval in seconds between polling the NTP server(s). NTP works by polling
its servers. This is the minimal time in seconds that is polled. After a poll and sync, the
interval to the next poll is multiplied until reaching the ‘Maximal poll interval in seconds’.
(See the next parameter.)

Note: When contact with the server is lost, the minimal poll interval is used to resync as
fast as possible.

Maximal poll interval in seconds <1-1311072> [1000]:

The maximal interval in seconds between polling the NTP server(s). See ‘Minimal poll
interval in sec’ above. 1000 seconds is ~17 minutes.

111
Transmit BURST when poll <Yes/No> [Yes]:

If this parameter is set to YES (default) when polling 8 messages are sent instead of one
every 2 seconds apart in order to sync as fast as possible. If NO only a single poll message
is sent.

Time sync lost before declare ‘no sync’ in sec [120]:

The number of seconds to wait before declaring ‘no sync’ state after being in sync. When
no reply is received from the NTP server(s), or when getting invalid replies ‘no sync’ is
declared, and the ClockValid in the Reserved Flags database system table is set to 0. 120 by
default means it takes 2 minutes to indicate that.

Notify error logger when losing sync <Yes/No> [Yes]:

Whether notification should be sent to the error logger when declaring ‘no sync’. By
default this parameter is "YES", meaning a message is logged into error logger when
getting into "no sync" state after being in sync. If ‘no sync’ again, no message is logged
until the user retrieves SW diagnostics device NTP level 10.

NTP Diagnostics and Verification


To verify that NTP is functioning properly, use the STS SW Diagnostics, the Error Logger and
the ladder application database:

1. Check STS SW Diagnostic device NTP level 1. If it is operative, it will shows “clock
synchronized” and the current clock offset.

2. An error is logged if synchronization is lost from all NTP servers.

3. Check the application database system table Reserved flags field ClockValid. If it is 0,
this means NTP is not functioning properly.

Note: When NTP is OK (synced) the ClockValid flag is set to 1 in database system
Reserved flags table. In this case, the ACE3600 will inhibit any user attempt to
change the clock, either from the database monitor, STS Site Date & Time, or
when getting an MDLC Time Sync message. It could however, send an MDLC
Time Sync to other RTUs as initiated from a local connected STS, or from user
application.

To check the NTP servers status:

1. Check STS SW Diagnostic device NTP level 2. It shows the list of NTP servers.

112
Sun Oct 29 10:33:07 2006 SITE: 2 LINK: LINE 2 DEVICE: NTP LEVEL: 2

Fail Prev Next

Peer address port assoc Strat test Flags poll poll delay offset disper. maxrxtime

------------ ---- ----- ----- ---- ---- ---- ----- ------ ------- ------- ---------

10.5.1.160 ETH1 30780 16 0000H 0301H 617 409 0.000 0.000 0.000 0.000

*10.5.1.161 ETH1 30781 10 0000H 0341H 505 518 1.125 -0.729 0.071 3.396

The first column shows the status of the NTP server. 10.5.1.160 is unreachable because it
has no symbol, and 10.5.1.161 is reachable ‘*’ marks it as a system peer. Both are polled
via ETH1. The stratum of the system peer is 10 meaning this is an ACE3600 which is not
connected to any NTP server or GPS receiver, otherwise it would have much smaller
stratum. The Prev and Next Poll designate in seconds when last time polled and when will
next poll occur. The delay is in milliseconds says 1.125 milliseconds delay to server. The
offset is also in milliseconds –0.729 milliseconds. The dispersion says how stable is the
clock, the less it is the better the clock. maxrxtime is for internal use.

Another method of testing NTP is using ntpq <ACE3600 IP address>. This utility is
provided in the STS installation and is a standard way of testing NTP. Refer to
http://www.eecis.udel.edu/~mills/ntp/html/ntpq.html for information on how to use this
utility. The most common commands are rv and pe to show clock status and NTP servers.

Global Positioning System (GPS)


The ACE3600 system can use a GPS receiver precise time measurement application for
synchronization purposes, to synchronize the RTU with other SCADA systems.

The ACE3600 RTUs use GPS timing receivers equipped with a 1 Pulse per Second (PPS)
output. The receivers are connected to an RTU port. In case of a satellite failure, the time
is manufactured internally and the receiver indicates its inability to trace the satellite.

The recommended GPS receiver is the Synergy Systems SynPaQ/E GPS Sensor with M12+
Timing Receiver which must be purchased from a Synergy vendor. Along with the timing
receiver, a data/power cable and antenna should be purchased. For details on connecting to
the GPS receiver, see Appendix A: RS232/RS485 Adaptor Cables in this manual.

113
RTU Site Configuration
Open the STS site configuration and configure any one of the serial or plug-in ports to
RS_232, Async, GPS receiver. Only ONE per RTU can be configured as GPS receiver.
The other parameters are automatically set as shown below.

The default parameters values are set for the Oncore M12+T receiver, but may be changed,
as necessary.

Link Parameters for PI1/PI2 or SI1/SI2


Time period to get data from GPS (sec) <8-60> [10]:
This field defines the interval between two time updates from the GPS receiver. . Note that
a drift of 30 ppm per day in ACE3600 RTU is 1.78 milliseconds per minute. Setting the
clock every 10 seconds will prevent this drift.

The GPS advanced parameters explained in ACE3600 STS User Guide, Appendix A Site
configuration parameters. The most important parameters are shown below:

Advanced Link Layer


Offset in milliseconds Default: 0

Range: 0- 86400000

The field defines the time offset to add for


GPS time in the Universal Time Coordinate
(UTC). The range is 0-86400000 msec.
This parameter is for testing purpose and
should be left as 0. For adding local time
offset set it in time zone section of advanced
parameters.

Powerup with factory defaults Default: Disable

Range: Disable/Enable

If Enabled the GPS receiver will power up


with defaults from factory, taking it longer
to obtain time.

114
Set GPS in position Hold (Timing only) Default: Enable

Range: Disable/Enable

This parameter should be enabled for


M12+T timing receiver and disabled for
non- timing receivers.
If enabled, in order to perform precise
timing, the GPS receiver position is
determined and then the receiver is put into
Position-Hold mode where the receiver no
longer solves for position. With the position
known, time is the only remaining unknown.
When in this mode, the GPS receiver only
requires one satellite to accurately determine
time. If multiple satellites are tracked, then
the time solution is based on an average of
the satellite measurements.

Advanced Physical Layer


RTS Always ON Default: No

Range: Yes/No.

This parameter should be left as NO since


RTS has no meaning in GPS.

Polarity of PPS Input signal Default: Active LOW

Range: Active LOW/Active HIGH

This parameter determines the PPS (Pulse


per second) polarity in DCD input. For
M12+T it is set as LOW.

After setting the GPS parameters and downloading the configuration to the RTU, the unit
starts updating its time accordingly. You may use the Get Site Time & Date utility to
verify the RTU time.

GPS Diagnostics and Verification


The system flag, ClockValid, is included in the Reserved Flags (system) table. A value of
‘1’ indicates that a GPS receiver is connected to the RTU and the receiver is updated from
the satellite. When ClockValid=1 the RTU updates its time from the GPS, and ignores any
synchronization words received from other systems, from the Site Time & Date utility, or
through the ladder diagram language. ClockValid=0 indicates that the GPS receiver is not
connected to the RTU, or that the GPS is connected and a satellite connection failure has
occurred. Following system power-on, it takes up to 15 minutes for the GPS receiver to
start reading the satellite time.

115
The ladder controlled GpsOfs value is included in the Reserved Values (system) table.
This value enables the user to update the MOSCAD unit to Daylight Savings Time.

The GpsOfs default value is ‘0’, and it may be either positive or negative according to the
specific time changes (measured in hours). This value is added to the local offset from
universal time ‘Offset in milliseconds’ value, defined in the port Advanced Properties
window.

When the GpsOfs is set, the RTU time is updated starting from the next GPS report, except
following a “cold restart”, which may last up to one minute.

Verify the GPS time using STS SW Diagnostics, device GPS level 1. or using device NTP
level 1 to see that time is synchronized, and level 3 to see the local time.

NTP Advanced Parameters for GPS


The NTP advanced parameters affect the GPS. In ACE3600 the GPS is regarded as an
NTP clock source over RS232. The defaults are suitable for GPS, yet the following
parameters enable warning messages when losing time synchronization (when ClockValid
is 0.):

Time sync lost before declare ‘no sync’ in Default: 120


sec The number of seconds to wait before
declaring ‘no sync’, when no reply is
received from the NTP server after a poll.
During this wait period, polling is increased.
If ‘no sync’ is declared, the ClockValid flag
in the Reserved Flags database system table
is set to Nr (see the next parameter.) If GPS
is configured, ‘no sync’ occurs when no
valid satellite status is received for this
period of time.

Notify error logger when losing sync Default: Yes


Range: Yes/No
Whether notification should be sent to the
Error Logger when declaring ‘no sync’. By
default this parameter is "Yes", meaning a
message is logged into error logger when
getting into "no sync" state after being in
sync. If ‘no sync’ occurs again, no message
is logged until the user retrieves SW
Diagnostics device NTP level 10.

116
Core Dump

The main purpose of the Core Dump software component is to help the ACE developers to
identify the source and the reason of unexpected reboots. Core Dump is a diagnostic tool and
does not intervene in the application or software flow. In all of functionality modes described
below, the Core Dump software component becomes active only after the processor or the
VxWorks operating system notifies about an unrecoverable error (crash). When this happens,
the Core Dump saves some information before the RTU restarts. This information can be
uploaded later and analyzed off-line.

One example of a situation where the RTU will crash is when trying to divide by zero. (Some
applications cannot tolerate an undefined result of dividing by zero.) Another example is when
the software inadvertently tries to access illegal memory addresses. These scenarios are
common in user ‘C’ applications.

When an RTU resets in the field, the indications of possible reasons for the failure are lost.
The Core Dump feature, when enabled, can save a “frozen” image of the full system memory
in use (including tasks, semaphore messages, variables, memory allocations, communication
buffers, etc.) before the reset. This provides the ACE developer with the full status of the
system at the time the memory image was taken and helps to pinpoint the cause of the failure.
The "frozen" image is actually a file which is analogous to "core dump" file of UNIX OS. The
"frozen" image file can be uploaded later for off-line analysis.

In order to save the image of the memory, the RTU freezes all tasks for approximately one
minute. During this time, the RTU will not monitor or control any devices. All LEDs except
for the ETH port will be frozen. If stopping all tasks for this period is not acceptable, (e.g. a
pump might continue operating unmonitored) the Core Dump can be set to Reduced
functionality (see below).

The Core Dump can also be configured to save partial information only (Reduced
functionality.) The partial information may contain descriptive messages, register values,
function callback traces of the failure from the system memory, the task that caused the failure,
etc. To save partial information, the RTU freezes all tasks for much less time, several
milliseconds, before it resets the RTU. After the restart, the ACE becomes active again.

In both Reduced and Full Functionality modes, the partial information is logged to the Error
Logger. In Reduced Functionality there is no “core dump”.

The Core Dump feature is configured in the ACE3600 STS site configuration using the SMA
Online advanced parameter in the Core Dump category. Reduced functionality is the default
setting. See Appendix A: Site Configuration Parameters in the ACE3600 STS User Guide.

IMPORTANT: Do not set SMA Online to Disable.

Uploading the Core Dump and its associated files can be done using the Core Dump Upload in
the STS. The Core Dump file, though saved in compressed format, may be very large (several
megabytes, depending on available physical RAM and its percentage of usage). An IP
connection or other fast media is recommended for the upload. For more information, see
Uploading the Core Dump Files in the Operation chapter of the ACE3600 STS User Guide.

117
Core Dump

118
MDLC Encryption

The MDLC Encryption add-on feature enables wireless communication over a distributed
system.

SCADA system components communicate using the MDLC protocol, based on the seven
layers of the OSI (Open Systems Interconnection) model published by ISO, and adapted for
SCADA communications. To secure the information being sent, the communication is
encrypted before being sent.

A time-based authentication system with clock synchronization incorporated into the user
application further enhances the security of the encrypted data.

For information on the MDLC Encryption feature, see the MDLC Encryption Feature User
Guide (Motorola publication number 6802971C35).

119
Protocol Analyzer

The Protocol Analyzer is a diagnostic tool which enables the user to monitor and analyze
MDLC communication over various channels in two different ways:

• By means of an additional RTU defined as an adaptor that collects data for the Protocol
Analyzer. This adaptor monitors one port and transfers the received data through a
second port to the Protocol Analyzer program.

• By monitoring the communication between two RTUs through RS-link, between a


computer and RTU through a computer Port, or between an RTU and an external
modem. This way of monitoring requires two 8 pin-to-25 pin female adaptors and two
serial ports on the STS computer.

a) Monitoring a Radio Link

The additional RTU should include a CPU module, radio and power supply. Using the STS
site configuration program, configure a CPU Port (e.g. port SI1) as RS232, Async, Protocol
Analyzer Port.

The CPU receives through a radio port all the frames (without address checking)
transmitted in the radio link, and transfers them through the Protocol Analyzer port to the
STS computer for evaluating, storing and displaying.

The radio port (e.g. PI2) should be defined according to the type of radio being used. A
third port (port SI2) can be defined as Computer Port to enable reconfiguration of the CPU
(back to normal mode of operation).

After configuring the CPU as a Protocol Analyzer, the following connections should be
performed as depicted below:

120
Protocol Analyzer

RTU

FIU
FIU

CENTRAL

RTU

PROTOCOL ANALYZER

PORT
PI1

PORT
SI1

PORT
SI2

PORT RADIO
STS PI2

CPU MODULE

b) Monitoring a Multi-Drop Link

To monitor the communication on a multi-drop link, connect Port PI2 through a 2-wire
multi-drop adaptor to the channel – see the figure below. Port PI2 should be defined
according to the type of modem and the data speed in use.

RTU RTU
RTU RTU
RTU

2-WIRE MULTI-DROP
CENTRAL

PROTOCOL ANALYZER

PORT
PI1
PORT
SI1

PORT
SI2

PORT 2-WIRE
PI2 MULTI-DROP
STS ADAPTER

CPU MODULE

121
Protocol Analyzer

c) Monitoring an RS-232 Link

The communication on an RS-232 link (such as RS-link or Computer Port) is full-duplex.


Usually, there is no need to monitor this type of communication. Nevertheless, if you have
to monitor this type of communication, perform the following connections – see the
following figure:
STANDARD
MOSCAD ADAPTER
(MALE or FEMALE)

FULL-DUPLEX TO
ACE3600 MDLC PROTOCOL
COMPUTER
RTU OR
MONITORED ACE3600 SITE
RS-232
8-pin
T-connector

TO PORT SI1

TO PORT SI2

25-PIN
FEMALE
ADAPTER

STS
PROTOCOL ANALYZER

Since the communication is full-duplex, two ports of the STS are used. You should use two
standard 8-pin T-connectors and two 25-pin female adaptors: one monitors the Tx Data and
the second the Rx Data of the communication – refer to the following table.
Adaptor for RTU Tx Monitoring Adaptor for RTU Rx Monitoring

8-pin 25-pin Function 8-pin 25-pin Function


female female

1 3 STS Rx Data 2 3 STS Rx Data


4 7 GND 4 7 GND
7 (+12V) 6 DSR 7 (+12V) 6 DSR

Protocol Analyzer Program


The Protocol Analyzer program monitors the data transmitted in the communication
channels and displays the analyzed data. The Protocol Analyzer may analyze any link in
the system.

The Protocol Analyzer is run from the Windows Start->Programs->STS<version>-


>Protocol Analyzer command. When you start up the Protocol Analyzer utility, the
following screen is displayed:

122
Protocol Analyzer

Icons
The icons at the top of the Protocol Analyzer include Local Communication, Remote
Communication, Stop Monitoring, Pause Monitoring, Analyze, Print and Print Preview.

Menus
The menus in the menu bar include File, Monitor, and Help.

Setting Communication Monitoring Parameters


1. To specify the parameters for monitoring communication on a local link, select the
Local Communication command from the Monitor menu.
Result: The Set Local Communication Parameters dialog box is opened, as shown
below.

123
Protocol Analyzer

To specify the parameters for monitoring communication on a remote link, select


the Remote Communication command from the Monitor menu.
Result: The Set Remote Communication Parameters dialog box is opened, as
shown below.

124
Protocol Analyzer

2. Enter the names (e.g. COM1) of the ports of the RTU to which the protocol
analyzer is connected. The order is irrelevant. For a remote link, only one port is
defined.

3. Enter the data speed of the link being monitored.

4. Enter the system address of the link being monitored.

5. Enter the name of the log file in which the monitored data should be collected (the
default is monc.dat.)
You can click on the browse icon to select the name of the desired .dat file. The
Open dialog box defaults to the log sub-directory of the STS directory where STS
stores log files by default.
The raw log file include the source site, the number of bytes that were collected
(size of the frame) and the frame contents.

6. Click on the desired format to be used (MDLC frames or Free Format).

MDLC Frames The data being monitored should be collected in the log file in a
format which will enable MDLC based analysis. If MDLC
Frames is selected, analyzed data can be viewed as in Analyzing a
Log File below.

Free Format The data being monitored should be collected in the log file in a
format which will not enable MDLC based analysis. The log file
will show the raw data going over the link. Non-MDLC analysis,
where the data is divided into frames based on delimiters specified
by the user, can be performed on the log file. See the Non-MDLC
Frame Delimiters field in the Set MDLC Layers to Analyze dialog.

7. Once the parameters are set, you are ready to start monitoring.

Monitoring the Communication on a Link


1. Once the parameters are set, click the Start button to start monitoring.
Result: The screen will clear, the new log file name will appear at the top of the
window and data sent over the link will begin to appear in the window.

2. To temporarily stop the monitoring of the link, select the Pause Monitoring
command from the Monitor menu, or click on the Pause Monitoring icon.

3. To stop the monitoring of the link, select the Stop Monitoring command from the
Monitor menu, or click on the Stop Monitoring icon.

Opening a Log
1. To open and view an existing log file of raw data collected from a communication
link, select the Open Log command from the File menu.
Result: A dialog box is opened from which the user can select the desired .dat file.
The Open dialog box defaults to the log sub-directory of the STS directory where
STS stores log files by default.

125
Protocol Analyzer

The raw log file include the source site, the number of bytes that were collected
(size of the frame) and the frame contents.

2. Select the log file from the drop-down list and click OK to open it.
Note that the designation of the site (Site 0) simply means that the first monitored
data was transmitted from that site. When monitoring a multi-drop link (remote),
all logged monitored data will seem to originate from Site 0. When monitoring an
RS232 link, the data will either be marked Site 0 (first to transmit) or Site 1
(second to transmit).

Opening an Analyzed File


1. To open and view an existing file of analyzed information, select the Open
Analyzed File command from the File menu.
Result: A dialog box is opened from which the user can select the desired .mon
file. The Open dialog box defaults to the log sub-directory of the STS directory
where STS stores log files by default.
The raw log file include the source site, the number of bytes that were collected
(size of the frame) and the frame contents.

2. Select the log file from the drop-down list and click OK to open it.
The analyzed file lists all the monitoring options which were selected under
Analyze Log file (which MDLC layers were monitored, source/destination address
ranges) and the actual analyzed data. This data is displayed by layer with each
frame described in detail (date sent, sending site, frame content) as shown below.

Because all seven layers of the MDLC protocol were selected to be analyzed (using the
Analyze Log File command) the 18 bytes which were sent over the link are shown (seven
in the Link layer, one in the Network layer, etc.) If not all the layers were analyzed, the
number of bytes displayed would be less than 18.

Note that the designation of the site (Site I/Site II) is used to differentiate between the two
transmitting sites, but the actual Destination and Source Site IDs are shown in the data
frame content. When monitoring a multi-drop link (remote), all logged monitored data will
seem to originate from Site I. When monitoring an RS232 link, the data will either be
marked Site I (first to transmit) or Site II (second to transmit).

126
Protocol Analyzer

Analyzing a Log File


1. To perform analysis on the current log file of raw data from the communication
link, select the Analyze Log File command from the File menu.
Result: The Set MDLC Layers to Analyze dialog box opens, as shown below.

127
Protocol Analyzer

2. Under Analyzer options, specify which MDLC layers are to be considered during
the data analyze. Click on whichever layers of the MDLC protocol you want to be
considered during the data analyze. Click the Bytes layer when you want to see the
data in a stream of hexadecimal bytes.

3. Under Source Address Ranges, specify the address range of the transmitting site.
Enter the starting and ending (decimal) addresses of sites (Site ID) whose data is to
be analyzed when transmitting data over the link. (RTU address= Site ID + System
address)
Under Destination Address Ranges, specify the address range of the receiving site.
Enter the starting and ending (decimal) addresses of sites (Site ID) whose data is to
be analyzed when receiving data over the link. (RTU address= Site ID + System
address)

4. For Free Format data, under Non-MDLC Frame Delimiters specify frame
delimiters for dividing the data stream as decimal values of hexadecimal Start/End
frame delimiters. The default Start and End values are –1, which cause the data to
be displayed in a stream of up to 200 hexadecimal bytes with no delimiters. If
other Start/End values are entered, the displayed data stream will be divided based
on the specified delimiters.

128
Protocol Analyzer

5. Once the preferences have been defined, click OK to begin the data analysis.

Previewing a File before Printing


To see how the current file will look when printed, select the Print Preview command from
the File menu. This command functions like the standard Windows Print Preview
command.

Printing a File
To send the current file to be printed, select the Print command from the File menu. This
command functions like the standard Windows Print command.

Exiting the Protocol Analyzer tool


To exit the Protocol Analyzer tool, select the Exit command from the File menu.

129
PID LOOP - Proportional Integral
Derivative

General
The following figure describes the PID Loop performed by the ACE3600 RTU.

The measured process value is converted by the transducer into voltage or current, which in
turn is converted by the A-to-D converter into a scaled analog input - a real (32-bit floating
point) value designated by the symbol pidIN which represents the current value of the
measured process.

The PID block is driven by the error signal (E) calculated as the difference between the
setpoint - pidSP (the desired value) and pidIN (the actual value).

The PID block transfer function is defined by its parameters. Its output, pidOUT, is a real
(32-bit floating point) value, driving the D-to-A converter.

The output of the D-to-A converter, voltage or current, is used as the controlling drive for
the process.

The purpose of the loop is to minimize the error E(t) by driving the process to follow the
setpoint value.

If E(t) = SP(t) - IN(t), then the transfer function of the PID block is defined as follows:

OUT (t ) = I 0 + KKi ∫0 E (t )dt + KE (t ) + KKd dE ( t )


t

dt

where:

130
PID LOOP - Proportional Integral Derivative

IN(t) - the PID input that represents the measured process value in "Input
Engineering Units" [IEU].

SP(t) - the setpoint value in [IEU].

E(t) - the error signal.

OUT(t) - the output of the PID loop in "Output Engineering Units" [OEU].

K- the gain of the loop in [OEU/IEU].

Ki - integration factor in "repetitions per second" [l/sec].

Kd - derivative factor in seconds.

I0 the initial value of the integral (when t=0) in [OEU].

In the PID table, all the abovementioned variables have the prefix pid, i.e. IN becomes
pidIN, SP becomes pidSP, etc.

PID Function
The PID function performs the following three calculations:

• The proportional calculation, whose contribution to the output signal is directly


proportional to the error signal.

• The integration, whose contribution to the output signal is proportional to the integral of
the error between 0 to t plus I0, which serves as the initial value of the integral (for t=0).

The integral drives the process of the setpoint value with a zero position error.

• The derivation, whose contribution to the output signal is proportional to the rate of
change of the error signal.

PID Table
To access the PID table, open an application using the Application Manager in the STS, the
Application Manager command in the STS GUI or the Application Programmer utility in
STS Start Menu program list. In the Database tab, click on User Tables to open the list of
database user tables, as shown below.

131
PID LOOP - Proportional Integral Derivative

• If no PID Table appears in the list of user table names, it must be created. Right-click on
the User Tables and select Append Table -> PID Table from the context menu.

• If PID Table appears in the list of user table names, double-click its name in the table
name list.

The following is displayed:

The PID table includes the following parameters. For more details on each parameter, see
the example project:

• pidIN - the scaled analog input (32-bit floating point value) that represents the
controlled process.

The value in this column is updated when the SCAN function using this column name
is called.

132
PID LOOP - Proportional Integral Derivative

• pidSP - this variable represents the setpoint, the desired state of the controlled process.
This is a real parameter variable that has an initial value for each row (each loop).

You may modify the value of this variable in the rungs when a change in the controlled
process is needed.

• pidK - this real parameter variable represents the gain of the loop. Its initial value
usually remains the same. The value of this variable may be modified in the rungs.

• pidKd - derivative factor in seconds that controls the output correction rate at which the
output responds to the change of error. A value of zero will disable the derivative
action. The value of this variable may be modified in the rungs. Default: 0.0

• pidKi - integration factor in "repetitions per second”. A value of zero will disable the
derivative action. The value of this variable may be modified in the rungs. Default: 0.0

• pidInt - this is the integral section in the equation above, i.e.

This real parameter value starts with an initial value which represents I0. It is
continuously modified to represent the value of the above equation. The value may be
changed in the rungs to any desired value.

• pidDb - this variable defines the PID output dead band. It prevents frequent changes of
the pidOUT variable when the absolute value of the difference between the new
calculated value and the current value is smaller than the pidDb value. When pidDb=
pidOUT, the pidOUT variable is always updated by the PID. Default: 0.0

The value of this variable may be modified in the rungs.

• pidOUT - the scaled analog output (32-bit floating point value) that drives the process.

Note that the PID table, like all other User tables in the database, can be edited, deleted,
searched, or converted to a printable file. Rows can be added, as can a table description.

How to Use the PID


In order to use the PID, the PID table and other User database tables are built in the
Application Programmer, with variables corresponding to physical elements. Process rungs
are programmed in the Ladder Diagram language which define the behavior of outputs as a
function of the states and their inputs and time. An analog input is scanned, the PID
function is called to perform the PID loop and then the analog output of the PID loop is
scanned.

The example below shows a PID application for an ACE3600 RTU. While the specific
application controls water flow, the concept of the PID control is universal and the example
described herein can be used for other applications.

133
PID LOOP - Proportional Integral Derivative

PID Application Example

General
This application is used to control water flow by changing the position of a regulating
valve. The flow is measured by an Analog Input (range: 0-15000 liter/hour). The valve
position is controlled by an Analog Output (range: 0-100%).

The database used in this example is described below. Each table in the database is shown
as it appears in the application. Each variable used in the tables is described. Finally the
application process rungs are described as they have been implemented in the sample
project.

Glossary
CV - Controlled Value: The measured or calculated process input
SP - Process SetPoint value
Err - Process error = SP - CV
AO - Process Analog Output: Sets the position of the controlled element

PID control function


A PID control function is used to set an analog output as a function of a process setpoint
and a feedback analog signal of the controlled value. The function include three
adjustments, each of which is represented in the PID table by a variable:

• Proportional (pidK variable)


• Integral (pidKi variable)
• Derivative (pidKd variable)

The application includes additional features, such as:

• Operation Mode – Manual (set by operator) or Automatic (PID) mode.


• Validity Check - The process variables are to be within a predefined valid range.
• Cycle time - Time interval between consecutive calculations of PID function

The impact of the three adjustments of the PID is as follows:

1. The proportional part of the PID function contributes to its output the result of

(PidK) * (Err). That means that AO increases when Err increases, and AO decreases when
Err decreases, by the proportional gain PidK.

The PID function does not put a limit to the proportional part. In certain cases, when Err is
large, it may cause the AO to be changed by large steps and to reach its limits. This may
cause fluctuations in analog output and unstable condition of the controlled process. In
order to prevent this problem, the application reduces the PidK when Err is large. Thus the
Integral action is dominant when Err is large, and the Proportional action is more dominant
when Err is small.

134
PID LOOP - Proportional Integral Derivative

Note: Setting the PID function parameters requires some knowledge about tuning PID
loops. The current version of PID function and the application example described below,
does not include 'self tuning' feature. The user has to set them manually, write additional
application or use external PC based software for this purpose.

2. The integral part of the PID contributes to its output the result of

[(PidK*PidKi) * Integral of (Err)], where the summation is performed every time the PID
calculation is performed. That means that AO increases as long as Err is positive, and AO
decreases as long as Err is negative. The summation result is stored in the PidInt variable,
where it can be set by the application too.

The PID function does not put a limit to the integral part. In certain cases, this may cause
the AO to reach its low or high limits. The application, as explained later, has to deal with
such situations.

3. The derivative part of the PID contributes to its output the result of

(PidK*PidKd) * (Err rate of change). That means that AO increases as long as Err rate of
change is positive, and AO decreases as long as Err rate of change is negative. If Err is
constant the derivative portion of the PID function equals to zero.

In the described example the derivative factor was set to zero, since its action is not
required for flow control.

Operation Mode
A PID loop can be either in Auto mode or in Manual mode. In Auto mode, the operator
can set the required flow and the PID function sets the AO according to process conditions.
In Manual mode, the operator can set the position of the regulating valve directly, and the
PID function results are ignored.

The ACE3600 application handles the transition from one operation mode to the other.

Validity Check
The controlled value of a loop is usually an analog input. The application in the following
example also supports the validity check of the CV, in order to prevent loop malfunction.

The PID setpoint is also checked to be within predefined limits. If it exceeds these limits, it
is operates according to the minimum or maximum setpoint range accordingly.

Moreover, the resulting AO of the PID function is also checked for validity before updating
the physical analog output.

The PID application, described in this section, uses the built in PID table, with additional
User tables and process, to control the CV (e.g. pipe flow) by setting the position of the AO
(e.g. regulating valve). The inputs of the function are the required flow (SP) and the
measured flow (CV).

Database Tables
The database tables are shown below. Each variable used in the tables is described.

135
PID LOOP - Proportional Integral Derivative

Operator Interface Table


This table contains the variables that can be set by the operator who controls the process via
an HMI station:

Table name: Operator Interface COS name:


Table symbol: Last index (Ind): 0
Last index name: LstPid
Ind CV_Set AO_Set ModSet
(int) (int) (iprm)

0 0

CV_Set - Controlled Value setting for PID loop in Auto mode


AO_Set - Analog Output setting for PID loop in Manual mode
ModSet - Setting of PID loop Operation mode (1 = Auto, 0 = Manual)

PID Table
Table name: PID Table COS name:
Table symbol: Last index (Ind): 0
Last index name: I_PID

Ind pidIN pidSP pidK pidKd pidKi pidInt PidDb PidOUT


(sAI) (rprm) (rprm) (rprm) (rprm) (rprm) (rprm) (sAO)

0 0.0 3.0-4 0.0 10.0 0.0 0.0

Ind pidIN EGU Zero (%) EGU EGU High


Zero 100%=Full Scale

0 0% 0.0 1.0

Ind PidOUT EGU Zero (%) EGU Zero EGU High


100%=Full Scale

0 0% 0.0 1.0

The PID function runs according to the following variables:

pidIN - PID controlled value input. - Represents the controlled value (CV). This value is
not linked directly to the analog input and is updated by application. The scaling of the
input can be defined in this column, by setting the EGU Zero and EGU High accordingly.

136
PID LOOP - Proportional Integral Derivative

pidSP - Represents the process setpoint (SP)

pidK - Proportional gain factor. A default value is defined in the table. Application changes
the value according to Err value, as explained later.

pidKd - Differential factor. Equals zero. Not used for flow control process.
pidKi - Integral factor. A default value for the integral part mutiplier is defined in the table.
However, application changes this value when the relevant pidK is changed, as explained
later
pidInt - Accumulated (calculated) integral part.

pidDb - PID Process output deadband sets the minimum step of change in the PID function
output. In the application example it is set to zero. For fast response process this value
should be kept to a minimum.

pidOUT - PID function output. This value is not linked directly to the analog output. The
scaling of the output can be defined in this column, by setting the EGU Zero and EGU
High accordingly. For the process in this example the output range is defined as 0 - 100
(%). Its value is checked to be in a certain range before updating the analog output variable.

PID I/O Table


This table is used to link the process CV analog input and AO analog output. The values
are scaled to 0 - 100 percent.

Table name: PID I/O COS name:


Table symbol: Last index (Ind): 0
Last index name:

Ind Pid_AI Pid_AO


(sAI) (sAO)

Ind Pid_AI EGU Zero (%) EGU Zero EGU High


100%=Full Scale

0 20%=Live Zero 0.0 100.0

Ind Pid_AO EGU Zero (%) EGU Zero EGU High


100%=Full Scale

0 20%=Live Zero 0.0 100.0

Pid_AI - PID loop controlled value analog input (linked to an AI module)


Pid_AO - PID loop analog output (linked to an AO module)
EGU Zero–used to define the scaling of the PID controlled value input pidIN

137
PID LOOP - Proportional Integral Derivative

EGU High –used to define the scaling of the PID controlled value input pidIN

PID P & I Parameters Table


These parameters are used to define the basic proportional and integral factors.

Table name: PID P & I Parameters COS name:


Table symbol: Last index (Ind): 0
Last index name:

Ind PID_P PID_I


(rprm) (rprm)

0 3.0-4 10.0

PID_P - Proportional factor (also multiplies the Integral part)


PID_I - Integration factor

PID Parameters Table


This table includes user definable parameters that are used to check validity of input (CV)
or output (AO) of the PID function.

Table name: PID Parameters COS name:


Table symbol: Last index (Ind): 0
Last index name:

Ind AlrDB AlrTim CV_Min CV_Max AO_Min AO_Max


(rprm) Mn:Sc (rprm) (rprm) (rprm) (rprm)

0 5.0 05:00 0.0 15000.0 0.0 100.0

AlrDB - PID alarm dead band (percent of full scale)


AlrTim - Time delay to set the PID alarm flag. This alarm indicates that the PID process
value did not reach the setpoint within the AlrDB range within this time delay.
CV_Min - Minimum value of CV (controlled value)
CV_Max - Maximum value of CV (controlled value)
AO_Min - Minimum value of AO (analog output)
AO_Max - Maximum value of AO (analog output)

138
PID LOOP - Proportional Integral Derivative

PID Flags Table


The variables of this table are used for checking the existing error (SP-CV) of the PID loop.

Table name: PID Flags COS name:


Table symbol: Last index (Ind): 0
Last index name:

Ind PidDif DifTmp RTemp O_Max O_Min PidAlr


(real) (real) (real) (bit) (bit) (bit)

PidDif - Difference (Err) between setpoint (SP) and process controlled value(CV)
DifTmp – Process error in CV engineering units
RTemp - Process error in percents of CV full scale
O_Max - Temporary bit. Indicates that output has reached its maximum position
(AO_Max)
O_Min - Temporary bit. Indicates that output has reached its minimum position (AO_Min)
PidAlr - Pid loop alarm flag. This alarm indicates that the PID process value did not reach
its setpoint (including the AlrDB deadband) within the predefined time (AlrTim)

Second Timers Table


Table name: Second Timers COS name:
Table symbol: Last index (Ind): 0
Data type: Timers Second (Sc:Ms)

Ind Name Value

0 TPID 01:00

TPID - PID calculation time interval (multiplied by 10 ms). The timer preset value is set by
PtPID.

User Flags Table


Table name: User Flags COS name:
Table symbol: Last index (Ind): 0
Data type: Discrete (bit)

Ind Name Value

0 BTemp

Btemp - Temporary flag

139
PID LOOP - Proportional Integral Derivative

User Parameters Table


Table name: User Parameters COS name:
Table symbol: Last index (Ind): 0
Data type: Integer Parameter (iprm)

Ind Name Value

0 PtPID 100

PtPID - A parameter to set PID calculation time interval (10msec resolution). The
minimum setting for running 8 PID loops is 100 (1 second).

Constants
The application uses the following constants:

Integer Constants - Manual = 0, Auto = 1


Real Constants - R0 = 0.0, R100 = 100,0

Programming Process Rungs


The chart below lists the rungs which have been programmed for application.

Rung Description
P05 Scan PID AI
P10 Reset Index p
PL10 Local Setpoints
PL12 Local Setpoints
P18 Manual mode limits
P20 Manual Mode
P21 Jmp P50 if no TPID
P25 Auto Mode
P30 Check Input range
P50 Increment Index p
P60 Check Index p
P90 Run PID Calc
M91 Jmp P200 if no TPID
P100 Reset Index p
P110 Check Output range
P112 Calc PID loop error
P113 Set PI factors

140
PID LOOP - Proportional Integral Derivative

P114 Set O_Max flag


P115 Set O_Min flag
P130 Increment Index p
P140 Check Index p
P200 Scan analog output
P210 Run PID Timer

The following are the actual rungs of the application.

Rung P05: Scan the analog input (CV) of the PID loop.

Pid_AI
P05 (SCAN)

Rung P10: The number of PID loops which are controlled by the application is set by the
number of rows in the PID Table. The same application with an index 'p' handles all loops.
This rung resets 'p' index to run the first PID loop.

p
P10 ( RST )

Rung PL12: In Auto mode, the Pid_AO is always copied to AO_Set. This enables smooth
transition to Manual mode without a step change in the loop SP.
ModSet,p AO_Set,p
PL12 = (MOVE)
Auto Pid_AO,p

Rung P18: In Manual mode, the AO_Set value is checked to be within a predefined range
(AO_Min and AO_Max). If it exceeds these limits, the output is set to the relevant limit.

ModSet,p AO_Set,p Pid_AO,p


P18 = > (MOVE)
Manual AO_Max AO_Max,p

AO_Set,p Pid_AO,p
< (MOVE)
AO_Min AO_Min,p

Rung P20: In Manual mode, the Pid_AI is checked to be within a predefined range
(CV_Min and CV_Max) and copied to CV_Set. This enables smooth transition to Auto
mode without a step change in the loop PidSp.

141
PID LOOP - Proportional Integral Derivative

In addition, the AO_Set value is checked to be within a predefined range (AO_Min and
AO_Max) and is copied to Pid_AO, and PidInt. Updating the latter variable is also
important to keep the AO in the last position when loop mode is changed to Auto, while
there is no change in the setpoint.

ModSet,p Pid_AI,p Pid_AI,p pidSP,p


P20 = > > (MOVE)
Manual CV_Min,p CV_Max,p Pid_AI,p

Pid_AI,p Pid_AI,p
= =
CV_Min,p CV_Max,p CV_Set,p
(MOVE)
pidSP,p
AO_Set,p AO_Set,p Pid_AO,p
> < (MOVE)
AO_Min AO_Max AO_Set,p
AO_Set,p AO_Set,p
= =
AO_Min AO_Max pidInt,p
(MOVE)
Pid_AO,p

Rung P21: Skips the next two rungs when PID loop is not calculated.

TPID P50
P21 / ( JMP )

Rung P25: In Auto mode, the CV_Set (set by the operator) is checked to be within a
predefined range (CV_Min and CV_Max) and copied to PidSp. In addition the AO_Set
value is updated by the Pid_AO.

ModSet,p CV_Set,p CV_Set,p pidSP,p


P25 = > < (MOVE)
Auto CV_Min,p CV_Max,p CV_Set,p

CV_Set,p CV_Set,p
= =
CV_Min,p CV_Max,p AO_Set,p
(MOVE)
Pid_AO,p

142
PID LOOP - Proportional Integral Derivative

Rung P30: In Auto mode, the Pid_AI is checked to be within a predefined range (CV_Min
and CV_Max) and copied to PidIn accordingly.

ModSet,p Pid_AI,p Pid_AI,p pidIN,p


P30 = > < (MOVE)
Auto CV_Min,p CV_Max,p Pid_AI,p

Pid_AI,p Pid_AI,p
= =
CV_Min,p CV_Max,p
Pid_AI,p pidIN,p
> (MOVE)
CV_Max,p CV_Max,p

Pid_AI,p pidIN,p
< (MOVE)
CV_Min,p CV_Min,p

Rung P50: Counts up (increments) the index counter (to execute the next loop).

p
P50 ( CTU )

Rung P60: Checks the index counter.

p PL10
P60 < (JMP)
I_PID

p
=
I_PID

Rung P90: Runs the PID calculation on all loops every TPID interval.

TPID P.I.D.
P90 ( CALL )

Rung M91: Skips the next rungs, which check the PID function results, if PID function was
not performed.

TPID P200
M91 / ( JMP )

143
PID LOOP - Proportional Integral Derivative

Rung P100: Resets a new index.

p
P100 ( RST )

Rung P110: Checks the PidOut (PID function output) to be within a predefined range
(AO_Min and AO_Max), and copies it to Pid_AO accordingly.

ModSet,p pidOUT,p Pid_AO,p


P110 = < (MOVE)
Auto AO_Min,p AO_Min,p

pidOUT,p Pid_AO,p
> (MOVE)
AO_Max,p AO_Max,p

pidOUT,p pidOUT,p Pid_AO,p


> < (MOVE)
AO_Min,p AO_Max,p pidOUT,p

pidOUT,p pidOUT,p
= =
AO_Min,p AO_Max,p

Rung P112: PID loop performance is checked. If the output fails to be within a predefined
range (PidSp +/- AlrDB) for longer than AlrTim, an alarm flag (PidAlr) is set.

ModSet,p PidDif,p
P112 = - pidSP,p
Auto Pid_AI,p
DifTmp,p
(MOVE)
PidDif,p
DifTmp,p DifTmp,p
< - R0
R0 DifTmp,p

RTemp,p
(CALC)
RTemp,p
AlrTim,p
>
(DON)
AlrDB,p
AlrTim,p PidAlr,p
( )

RTemp,p = DifTmp,p/(CV_Max,p - CV_Min,p) * (R100)

144
PID LOOP - Proportional Integral Derivative

Rung P113: In order to prevent large fluctuations in output when Rtemp (process error in
percents) is greater than AlrDb (user defined parameter), the application divides the PidK
by a constant 100. In order to keep the integral factor unchanged, it is multiplied by the
same constant. Thus, the Integral action is dominant when process error is large, and the
Proportional action is more dominant when process error is small.

ModSet,p RTemp,p pidK,p


P113 = > / PID_P,p
Auto AlrDB,p R100
RTemp,p pidKi,p
= x PID_I,p
AlrDB,p R100
RTemp,p pidK,p
< (MOVE)
AlrDB,p PID_P,p
pidKi,p
(MOVE)
PID_I,p

Note: The constant is used for the example only. For a practical PID loop, the proper
constant (or other type of handling these factors) must be implemented.

Rung P114: In Auto mode, when PidOut exceeds AO_Max, it is kept at that level. The first
time the process error becomes negative, the AO_Max is copied to PidInt. This operation
eliminates the effect of positive accumulated value of the Integral portion when AO is in its
maximum position.

ModSet,p pidOUT,p O_Max,p


P114 = > ( L )
Auto AO_Max,p

O_Max,p PidDif,p pidInt,p


< (MOVE)
R0 AO_Max,p
O_Max,p
(U )

145
PID LOOP - Proportional Integral Derivative

Rung P115: In Auto mode, when PidOut exceeds AO_Min, it is kept at that level. The first
time the process error becomes positive, the AO_Min is copied to PidInt. This operation
eliminates the effect of negative accumulated value of Integral portion when AO is in its
minimum position.

ModSet,p pidOUT,p O_Min,p


P115 = < ( L )
Auto AO_Min,p

O_Min,p PidDif,p pidInt,p


> (MOVE)
R0 AO_Min,p
O_Min,p
(U )

Rung P130: Counts up (increments) the index counter (to execute the next loop).

p
P130 ( CTU )

Rung P140: Checks the index counter.


p P110
P140 < ( JUMP )
I_PID
p
=
I_PID

Rung P200: Writes the resulting analog output to Pid_AO by Scan operation.

Pid_AO
P200 ( SCAN )

Rung P210: Sets and runs the TPID timer.

TPID TPID
P210 (MOVE)
PtPID

TPID TPID
/ (DON)

146
Enhanced PID

The ACE3600 Enhanced PID Application enables the ACE3600 to control up to 32


independent PID loops (independent processes), each with five PID modes: one manual
and four types of auto modes. The PID calculation algorithm depends on the chosen mode.

The ACE3600 Enhanced PID Application includes a powerful tool for graphically
monitoring the control process, which also enables interactive PID coefficient tuning.

If a legacy PID loop application exists in the RTU, an Enhanced PID application can also
be defined for the RTU.

The Enhanced PID Application is installed as a separate add-on option to the STS.

For more information, see the ACE3600 Enhanced PID Application User Guide, provided
with the RTU.

147
Irrigation

The ACE3600 STS can be used to build, configure and maintain sophisticated distributed
SCADA-based (Supervisory Control and Data Acquisition) irrigation systems. The
elements and handling of irrigation systems differ slightly from other SCADA systems.

An irrigation system consists of an IRRInet Control Center (ICC), field units (RTUs) and
portable device for on-site programming of field units.

For detailed information on planning and setting up an irrigation system, see the IRRInet-
M System Planner.

Irrigation Unit Types


The STS supports the following irrigation system three field unit types: IRRInet-ACE,
IRRInet-M (as Master) and IRRInet-M (as Slave). For detailed information on the field
units and irrigation functions, see the IRRInet-M System Planner. For detailed information
on using the STS to configure and deploy units, see the ACE3600 STS User Guide.
References to ACE3600 in the ACE3600 STS User Guide apply to IRRInet-ACE RTUs as
well, except where noted otherwise.

The STS does not support legacy Irrigation units: IRRIcom, IRRInet-XL or IRRInet-XM.
However, the STS can be used with certain legacy units, as described in Legacy Irrigation
RTUs below.

IRRInet-ACE
The IRRInet-ACE unit is an ACE3600 RTU running the Irrigation (Master) application.
Its hardware and system software is identical to that of the ACE3600 RTU.

The IRRInet-ACE supports two modes of operations:

• RTU – Performing all irrigation functions, reporting to the IRRInet Control Center
(ICC).
• Stand Alone – Performing all irrigation functions as a stand-alone unit when the system
is installed without an ICC.
With DIOS (Distributed I/O System) connectivity, the IRRInet-ACE can activate Piccolo-
XR units with its PIU (Piccolo Interface Unit) functionality.

The IRRInet-ACE RTU can be programmed on site, using an IRRinet Terminal for Pocket
PC.

The IRRInet-ACE may be installed in a totally new irrigation system, or in a legacy system
in addition to/instead of a legacy IRRInet-XL or IRRInet-XM unit.

148
Irrigation

IRRInet-M Master/Slave
There are two types of IRRInet-M:

• IRRInet-M AC (for AC solenoids)


• IRRInet-M DC (for DC solenoids)
The IRRInet-M RTU supports three modes of operations:

• RTU – Performing all irrigation functions, reporting to the ICC via MDLC network.
(loaded with the IRRIV Master application)
• Stand Alone – Performing all irrigation functions as a stand-alone unit when the system
is installed without an ICC. (loaded with the IRRIV Master application)
• Remote I/O – Serving as a distributed I/O for another “master” unit that performs all
irrigation functions (when loaded with the IRRIV Slave software).
This is applicable when multi-site control synchronization is needed.
With PIU connectivity, the IRRInet-M can activate Piccolo-XR units.

The IRRInet-M RTU can be programmed on site, using an IRRinet Terminal for Pocket
PC.

The IRRInet-M (master mode) may be installed in a totally new irrigation system, ICC V14
or higher. The IRRInet-M (slave mode) may be installed in a legacy system in addition
to/instead of a legacy Scorpio unit.

Important: Although the IRRInet-M looks like the IRRIcom and MOSCAD-M on the
outside, it is a different unit, with different connectors, hardware, and software. These
units are NOT interchangeable.

STS Functions for Irrigation Units


The ACE3600 STS can be used to perform the following functions on IRRInet-M units,
either via local connection or via the communication network.

• Designing the system (areas, sites, communication links) in a graphical desktop, with a
system-wide (multiple sites/areas) approach
• Configuring the RTU sites (unit ID, ports, I/Os, advanced parameters)
• Real-time monitoring of application tables in the RTU
• Downloading/uploading files
• Updating the RTU date and time
• Testing hardware elements and plug-in communication ports
• Retrieving errors and software diagnostics logged in the RTUs
For detailed information on using the STS to configure and deploy units, see the ACE3600
STS User Guide.

149
Irrigation

Tips on Using the STS for Irrigation

Toolbox for Irrigation


For legacy irrigation systems, MOSCAD Programming ToolBox 9.54 should be installed
on the PC along with the ACE3600 STS software.

Defining and Configuring an IRRInet-M RTU


When defining an IRRInet-M unit, follow the instructions in the Operation chapter of the
ACE3600 STS User Guide. Differences between handling an IRRInet-M unit and an
ACE3600/IRRInet-ACE unit are specified in the individual procedures.

Note: When an IRRInet_M is connected to a PIU (via RS232), the port’s advanced physical
parameter ‘RTS Always On’ must be set to Yes.

Network Configuration in Irrigation Systems


The figure below illustrates an irrigation system, with an RTU (FIU) connected to the STS
PC via RSlink19 and a set of RTUs (IRRInet-ACE or IRRInet-M) which communicate with
the FIU via radio link, and with PIU/Scorpio units via RSlink1 or RSlink2.

IRRInet-ACE/ IRRInet-M Legacy Units


IRRInet-M Masters Slaves/Routers
Radio1 PIU
RSlink1
RTU 1 Radio
RTU 101 (Intrac) Scorpio
RSlink2

STS Radio1
PIU
PC RSlink1
Radio
RTU 2
RTU 102 (Intrac) Scorpio
RSlink19
RSlink2

RTU 100 Radio1


PIU
FIU RSlink1
Radio
RTU 3 (Intrac)
RTU 103 Scorpio
RSlink2
Radio1 .
. PIU
RSlink1
Radio
RTU 99
(Intrac)
RTU 199 Scorpio
RSlink2

Irrigation systems such as the one depicted above should not use the generic network
configuration table produced automatically by the STS. Instead, a customized network
table should be created and maintained, as follows:

1. After defining two connected sites (RTU 100 and RTU 1) with their links (RSlink19
and Radio1 for RTU 100, and Radio1, RSlink1, RSlink2 for RTU 1), save the generic
network configuration table produced by the STS as a private network table. (See the
Managing the Network and Editing a Network Table sections in the Operation chapter

150
Irrigation

of the ACE3600 STS User Guide.) Initially, the network table should have two entries
in it.

2. Delete the second entry (for RTU 1), leaving one entry with a Site ID and two (or more)
Link IDs.

3. Continue defining the rest of the RTUs in the system, using the following convention:
Only links from the RTU to PIU units should be named RSlink1.
Only links from the RTU to IRRInet-M Router (for connection to Scorpio, Impact, and
IRRIcom legacy units) should be named RSlink2.

4. Edit the customized network table to show only those communication nodes which are
not connected to PIU and legacy units.

5. To simplify the viewing the system in the GUI’s Diagram view, it is recommended to
hide the RSlink1 and RSlink2 links in the display. To do so, click on the Links button
in the System view.

Legacy Irrigation RTUs


The STS does not support legacy irrigation units. However, the STS can be used with
IRRInet-XM and IRRInet-XL legacy units, as follows:

To define an IRRInet-XM module, drag the Legacy->MOSCAD entry in the inventory. To


define an IRRInet-XL module, use the Legacy->MOSCAD-L entry in the inventory.
Although the RTUs that are created will be marked as MOSCAD/MOSCAD-L in the STS
GUI, you can download relevant Irrigation files to the RTUs and retrieve errors and
diagnostics from them.

As with legacy MOSCAD RTUs, the site configuration of legacy irrigation units must be
imported. See the instructions on importing a site configuration in the Operation chapter of
the ACE3600 STS User Guide.

The table below lists the Add-on files which should be imported from the Toolbox project
directories [C|D]:\Tbox954\... and downloaded together with the site configuration and
network configuration to the units. See the instructions on using Add-on files and
downloading in the Operation chapter of the ACE3600 STS User Guide.

File Type File


Extension
Ladder .b, .s
Application
PLC 1, 2, 3 .fls
PLC to Master .fls
1, 2, 3
‘C’ Application .fls
IP .ipp
Configuration

151
Irrigation

File Type File


Extension
‘C’ Application *.*
Parameters
IP Conversion .ipc
Table

Important: Because the irrigation system works with ICC V14, all legacy irrigation RTUs
must be upgraded to V570 of the project files.

152