Professional Documents
Culture Documents
By
1. Introduction:
Earthquake results from the sudden movement of the tectonic plates in the earth’s
crust, figure 01. The movement takes place at the fault lines, and the energy released
is transmitted through the earth in the form of waves, figure 02, that cause ground
motion many miles from the epicentre, figure 03. Regions adjacent to active fault
lines are the most prone to experience earthquakes. As experienced by structures,
earthquakes consist of random horizontal and vertical movements of the earth’s
surface. As the ground moves, inertia tends to keep structures in place, figures 04,
resulting in the imposition of displacements and forces that can have catastrophic
results, figure 05. The purpose of seismic design is to proportion structures so that
they can withstand the displacements and the forces induced by the ground motion.
Historically, seismic design has emphasized the effects of horizontal ground motion,
because the horizontal components of an earthquake usually exceed the vertical
component and because structures are usually much stiffer and stronger in response to
vertical loads than they are in response to horizontal loads. Experience has shown that
the horizontal components are the most destructive.
For structural design, the intensity of an earthquake is usually described in terms of
the ground acceleration as a fraction of the acceleration of gravity, i.e., 0.1, 0.2, or
0.3g. Although peak acceleration is an important design parameter, the frequency
characteristics and duration of an earthquake are also important; the closer the
frequency of the earthquake motion is to the natural frequency of a structure and the
longer the duration of the earthquake, the greater the potential for damage.
Based on elastic behaviour, structures subjected to a major earthquake would be
required to undergo large displacements. However, recent design practices require
that structures be designed for only a fraction of the forces associated with those
displacements. The relatively low design forces are justified by the observations that
the buildings designed for low forces have behaved satisfactorily and that structures
dissipate significant energy as the material yield and behave in-elastically.
This nonlinear behaviour, however, usually translates into increased displacements,
which may result in major non-structural damage and require significant ductility.
Displacements may also be of such a magnitude that the strength of the structure is
affected by stability considerations.
Designers of structures that may be subjected to earthquakes, therefore, are faced with
a choice: (a) providing adequate stiffness and strength to limit the response of
structures to the elastic range or (b) providing lower-strength structures, with
presumably lower initial costs, that have the ability to withstand large inelastic
deformations while maintaining their load-carrying capability.
2. Structural Response:
The safety of a structure subjected to seismic loading rests on the designer’s
understanding of the response of the structure to ground motion. For many years, the
goal of earthquake design has been to construct buildings that will withstand
3
Storey Height
0
Displacement
(a) (b) (c)
Figure 07: Modal shapes for a three storey building (a) first mode; (b) second mode;
(c) third mode.
The first mode, figure 07a, usually provides the greatest contribution to lateral
displacement. The taller a structure, the more susceptible it is to the effects of
higher modes of vibration, which are generally additive to the effects of the lower
modes and tend to have the greatest influence on the upper stories. Under any
circumstances, the longer the duration of an earthquake, the greater the potential
of damage.
The configuration of a structure also has a major effect on its response to an
earthquake. Structures with a discontinuity in stiffness or geometry can be
subjected to undesirably high displacements or forces. For example, the
discontinuance of shear walls, infill walls or even cladding at a particular story
level, will have the result of concentrating the displacement in the open, or “soft,”
story, figure 08, 09. The high displacement will, in turn, require a large amount of
ductility if the structure is not to fail. Such a design is not recommended, and the
stiffening members should be continued to the foundation.
Figure 08: Upper storeys of open ground storey move together as single block.
Figure 09: Ground storey of reinforced concrete building left open to facilitate
parking.
such as masonry infill walls, are not considered in the design, unexpected and
often undesirable results can occur.
Finally, any discussion of structural considerations would be incomplete without
emphasizing the need to provide adequate separation between structures. Lateral
displacements can result in structures coming in contact during an earthquake,
resulting in major damage due to hammering, figure 13. Spacing requirements to
ensure that adjacent structures do not come into contact as a result of earthquake
induced motion are specified in relevant codes.
Figure 11: Buildings with one of their overall sizes much larger or much smaller
than the other two.
b. Member Considerations:
Members designed for seismic loading must perform in a ductile fashion and
dissipate energy in a manner that does not compromise the strength of the
structure. Both the overall design and the structural details must be considered to
meet this goal.
The principal method of ensuring ductility in members subject to shear and
bending is to provide confinement for the concrete. This is accomplished through
the use of closed hoops or spiral reinforcement, which enclose the core of the
beams and columns. When confinement is provided, beams and columns can
undergo nonlinear cyclic bending while maintaining their flexural strength and
MC1
M- M+
MC2
(a) (b)
Figure 14: Frame subjected to lateral loading (a) deflected shape; (b) Moments
acting on beam-column joint.
the total structure weight and then appropriates the base shear in accordance with
dynamic theory. The design seismic force can be determined based on the UBC-97
static lateral force procedure [sec. 1630.2, UBC-97 or Sec. 5.30.2, BCP 2007] and/or
the dynamic lateral force procedure [sec. 1631, UBC-97 or sec. 5.31, BCP-2007].
The static lateral force procedures (section 1630 of the UBC-97) may be used for the
following structures:
1. All structures, regular or irregular, in Seismic Zone 1 and in Occupancy
Categories 4 and 5 in Seismic Zone 2.
2. Regular structures under 240 feet (73152 mm) in height with lateral force
resistance provided by systems listed in Table 16-N, except where section
1629.8.4, Item 4, applies.
3. Irregular structures not more than five stories or 65 feet (19812 mm) in height.
4. Structures having a flexible upper portion supported on a rigid lower portion
where both portions of the structure considered separately can be classified as
being regular, the average story stiffness of the lower portion is at least 10 times
the average story stiffness of the upper portion and the period of the entire
structure is not greater than 1.1 times the period of the upper portion considered
as a separate structure fixed at the base.
The dynamic lateral force procedure of section 1631 shall be used for all other
structures including the following:
1. Structures 240 feet (73152 mm) or more in height, except as permitted by Section
1629.8.3, Item 1.
2. Structures having a stiffness, weight or geometric vertical irregularity of Type 1, 2
or 3, as defined in Table 16-L, or structures having irregular features not
described in Table 16-L or 16-M, except as permitted by Section 1630.4.2.
3. Structures over five stories or 65 feet (19812 mm) in height in Seismic Zones 3
and 4 not having the same structural system throughout their height except as
permitted by Section 1630.4.2.
4. Structures, regular or irregular, located on Soil Profile Type SF, which have a
period greater than 0.7 second. The analysis shall include the effects of the soils at
the site and shall conform to Section 1631.2, Item 4.
The total design base shear shall not be less than the following:
V = 0.11CaIW
In addition for seismic zone 4, the total base shear shall also not be less than the
following:
V = (0.8ZNνI/R) W
Nν = near source factor (Table 16-T of UBC-97 given below in Table 3)
Z = Seismic zone factor (Table 16-I of UBC-97 given below in Table 4)
Note: Table for soil profile type is given in appendix A of this document.
Structural period: The value of T shall be determined from one of the following
methods:
a. Method A: For all buildings, the value T may be approximated from the
following formula:
T = Ct (hn)3/4
Where,
Ct = 0.035 (0.0853) for steel moment-resisting frames.
Ct = 0.030 (0.0731) for reinforced concrete moment-resisting frames
and eccentrically braced frames.
Ct = 0.020 (0.0488) for all other buildings.
hn = Actual height (feet or meters) of the building above the base to the
nth level.
Alternatively, the value of Ct for structures with concrete or masonry shear
walls may be taken as 0.1/√Ac (For SI: 0.0743/√Ac for Ac in m2).
The value of Ac shall be determined from the following formula:
Ac = ∑Ae[0.2 + (De/hn)2]
The value of De/hn used in formula above shall not exceed 0.9.
Where,
Ac = the combined effective area, in square feet (m2), of the shear
walls in the first story of the structure.
Ae = the minimum cross-sectional area in any horizontal plane in the
first story, in square feet (m2) of a shear wall.
De = the length, in feet (m), of a shear wall in the first story in the
direction parallel to the applied forces.
Where,
wi = that portion of W located at or assigned to Level i.
δi = horizontal displacement at Level i relative to the base due to
applied lateral forces, f.
g = acceleration due to gravity.
fi = lateral force at Level i.
The values of fi represent any lateral force distributed approximately in
accordance with the principles of Formulas (30-13), (30-14) and (30-15) in
UBC-97 or any other rational distribution. The elastic deflections, δi, shall be
calculated using the applied lateral forces, fi.
Example: Calculate the base shear and storey forces of a five storey building
given in figure 16. The structure is constructed on stiff soil which comes under
soil type SD of table 16-J of UBC-97. The structure is located in zone 3.
w5 = 700 kip
w4 = 800 kip
w3 = 800 kip
w2 = 800 kip
60'-0"
w1 = 800 kip
12'-0"
Solution:
i) Base shear: According to static lateral force procedure the total design base
shear in a given direction can be determined from the following formula:
V = (CνI/RT) W
From table 16-R, Cν = 0.54
From table 16-K, I = 1.00, standard occupancy structures.
From table 16-N, R = 8.5, Concrete SMRF (will be discussed later).
T = Ct (hn)3/4 = 0.030 × (60)3/4 = 0.646 sec.
W = w1 + w2 + w3 + w4 + w5 = 4 × 800 + 700 = 3900 kip
Therefore,
V = {(0.54 × 1.00)/ (8.5 × 0.646)} × 3900 = 383 kip
The total design base need not exceed the following:
V = (2.5CaI/R) W
From table 16-Q, Ca = 0.36
Therefore,
V = (2.5CaI/R) W = {(2.5 × 0.36 × 1.00)/ (8.5)} × 3900 = 413 kip
The total design base shear shall not be less than the following:
V = 0.11CaIW
V = 0.11CaIW = 0.11 × 0.36 × 1.00 × 3900 = 154.44 kip
Therefore, V = 383 kip
ii) Vertical distribution of base shear to storey:
The joint force at a level x of the structure is given as:
Fx = (V – Ft)ωxhx/∑ωihi {i ranges from 1 to n, where n = number of stories}
Ft = Additional force that is applied to the top level (i.e., the roof) in addition to
the Fx force at that level.
Ft = 0.07TV {for T > 0.7 sec}
Ft = 0 {for T ≤ 0.7 sec}
∑ωihi = 800×12+800×24+800×36+800×48+700×60 = 138000 kip
Therefore for the case under consideration, Force for storey 1 is:
F1 = (383 – 0) × 800 × 12/ {(138000)} = 27 kip
Storey forces for other stories are given in table 6 below.
w5 = 700 kip
F5 = 117 kip
w4 = 800 kip
F4 = 107 kip
w3 = 800 kip
F3 = 80 kip
w2 = 800 kip
60'-0"
F2 = 53 kip
w1 = 800 kip
12'-0"
F1 = 27 kip
V = 383 kip
Figure 17: Base shear and storey forces.
Under gravity loads, tension in the beams is at the bottom surface of the beam in the
central location and is at the top surface at the ends. On the other hand, earthquake
loading causes tension on the beam and column faces at locations different from those
under gravity loading (figure 18c); the relative levels of this tension (in technical
terms, bending moment) generated in members are shown in figure 18d. The level of
bending moment due to earthquake loading depends on severity of shaking and can
exceed that due to gravity loading. Thus, under strong earthquake shaking, the beam
ends can develop tension on either of the top and bottom faces. Since concrete cannot
carry this tension, steel bars are required on both faces of beams to resist reversals of
bending moment. Similarly, steel bars are required on all faces of columns too.
Closed Hoops
Width of beam
3
4 depth of beam
Support (Column)
b. Flexural Reinforcement:
• Neither positive nor negative moment strength at any section in a member
may be less than one-fourth of the maximum moment strength at either end
of the member.
• The positive moment capacity at the face of columns must be at least one-
half of the negative moment strength at the same location, figure 22.
• Minimum two reinforcing bars top and bottom, throughout the member.
• ρmax ≤ 0.025.
c. Lap splices:
• Not within the joints.
• Not within twice the member depth “2h”, from the face of a joint or at other
locations where flexural yielding is expected.
• Lap splices must be enclosed by hoops or spirals with a maximum spacing
of one-fourth of the effective depth or 4″.
d. Transverse reinforcement:
Transverse reinforcement in the form of hoops, figure 24 must be used over a
length equal to twice the member depth measured from the face of the
supporting member toward mid span at both ends, as per calculation, but
fulfilling following conditions, figure 25.
(i) The first hoop must be located not more than 2 in from the face of the
supporting member.
(ii) Max spacing of the hoops over the length must not exceed:
a. ¼ of effective depth of beam,
b. 8 times dia of smallest longitudinal steel,
c. 24 dia of hoop bar
d. 12 in.
(iii) Elsewhere spacing not to exceed d/2.
d. Transverse reinforcement:
• ACI Code 21.4.4 specifies the use of minimum transverse reinforcement
over length lo from each joint face. The length lo may not be less than
(i) the depth “D” of the member at the joint face or at the section where
flexural yielding is likely to occur.
(ii) one-sixth of the clear span (hc)of the member; or
(iii) 18 in.
• Max spacing of ties within length lo.
(i) Least lateral dimension of column /4,
(ii) 6 times the diameter (db) of longitudinal reinforcement in column,
(iii) 4 + (14 – hx) /3; but not more than 6 inch and not less than 4 inch.
Where hx = maximum horizontal spacing (inches) of hoop or crosstie
legs on all faces of the column.
• Elsewhere spacing of ties is least of 6 db or 6 inch.
Figure 28: Beam column joints are critical parts of a building. Push pull forces on
joint cause (a) loss of grip on beam bars in joint region; (b) distortion of joints. These
result in irreparable damage in joints under strong seismic shaking.
Figure 29: Closed loop steel ties in beam-column joints. Such ties with 135o hook
resist the ill effects of distortion of joints.
Figure 30: Providing horizontal ties in the joint --- three stage procedure is required.
Figure 32: Anchorage of beam bars in interior joint. Diagram (a) and (b) show cross
sectional views in plan of a joint region.
Figure 33: Location and amount of longitudinal steel bars in beams. These resist tension
due to flexure.
Shear Wall is a wall designed to resist lateral forces parallel to the plane of the wall. It is
sometimes referred to as vertical diaphragm or structural wall. To ensure adequate
ductility, ACI 21.7.2 requires that structural walls have minimum shear reinforcement
ratios in both longitudinal and transverse directions ρν and ρn of 0.0025 and a maximum
reinforcement spacing of 18″. For details on shear walls, please refer to Seismic design of
reinforced concrete and masonry structures by Priestley, page 362.
6. Load combinations:
Broadly speaking, there are two types of codes in practice for design of structures.
The codes like UBC, IBC etc. provide guidelines on the overall performance of
structural systems, which also include procedures for determination of wind and
seismic demand on structures. Other codes such as ACI, AISC provide material
specific recommendations on the design of structures. Therefore designers use first
type of codes for evaluating seismic forces and second type for design and detailing
of earthquake resistant structures. Occasionally the two codes combined in this way
may not be compatible. To avoid any mismatch resulting from such merger, every
code explicitly mentions its counterpart code or codes. For example UBC 97 in its
chapter 19 on concrete reproduces the complete code of ACI 318-95, and wherein it
categorically states that UBC 97 shall be used in conjunction with ACI 318-95 for
design of all reinforced concrete structures. Similarly IBC 2000 is compatible with
ACI 318-02/05 and not with ACI 318-95/99 due to many reasons but mainly due to
difference in load amplification and strength reduction factors.
The chapter 7 of BCP SP-2007 can be used for earthquake resistant design of RC
structures using load combination and Strength Reduction Factors of chapter 5 of
BCP (UBC 97 load combinations).The chapter is compatible with ACI 318-05.
Table 8: UBC-97 Load combinations and strength reduction factors (section 1612.2.1)
Load Combinations Strength Reduction Factors
1.4D 0.9 (flexure)
1.2D + 1.6L 0.85 (Shear)
1.1 (1.2D + 0.5L ± 1.0E) 0.70 (Tied )
1.1 (0.9D ± 1.0E) 0.75 (Spiral)
The amalgamation of the codes shall be done carefully when softwares such as
SAP2000 or ETABS are used for analysis and design of structures. Though these
softwares allow the use of UBC 97 for calculation of earthquake forces and ACI for
design, when ACI 318-02/05 is selected for design, the software automatically loads
the combination of ACI against the recommendation of BCP which uses the
Design Pb: Design the structure given in figure 35 as SMRF. The structure is located in
seismic zone 4 of UBC-97. The seismic source in the locality is such that magnitude of
earthquake and slip rate may exceed 7.0 and 5.0 respectively. The closest distance of
structure to the known seismic source is greater than 15 km. The soil type is stiff. The
structure is 10′ high. Concrete compressive strength = 3 ksi, steel yield strength = 40 ksi
and Modulus of elasticity of concrete = 3000 ksi.
20'
R.C.C
Column
N
Slab Beam
15'
PLAN
B C F G
10' 7'
A D E H
15' 20'
ELEVATION
Data Given:
Material properties:
Concrete: fc′ = 3000 psi.
Reinforcement: fy = 40,000 psi.
Loads:
Live load = 30 psf
Superimposed dead load = 3″ mud layer.
Solution:
Step No 1: Sizes.
1. Columns:
As mentioned in section 5.2.2 of this document, the shortest dimension of column
shall not be less than 12″, therefore assume 12″ × 12″ column.
2. Beam:
Assuming beam cross-sectional dimensions = 12″ × 24″.
According to ACI 9.5.2.1, table 9.5 (a):
Minimum thickness of simply supported beam = hmin = l/16
l = clear span (ln) + depth of member (beam) [ACI 8.7]
l = 20 – (12/12) + (24/12) = 21′
Depth (h) = (21/16) × (0.4 + 40000/100000) × 12
= 12.6″ (this is minimum requirement by ACI 9.5.2.1).
Therefore, for h = 24″; d = h – 3 = 21″
Checks on limitation of section dimensions:
ln/d = 14 × 12/21 = 8 > 4 (ACI 21.3.1.2 satisfied)
Width/ depth = 12/24 = 0.5 > 0.3 (ACI 21.3.1.3 satisfied)
Width = 12″ > 10″, O.K.
Take 12″ × 24″ deep beams.
3. Slab:
lb/la = 20/15 = 1.33 < 2 “two way slab”
hmin = perimeter/180 = 2 × (20 + 15) × 12/180 = 4.66 in
Assume hf = 6″
Step No 2: Loading.
1. Gravity loads:
a. Slab:
Service dead load of/on slab = (6/12)×0.15+ (3/12)×0.12=0.105 ksf or 105 psf
Service Live load over slab = 30 psf = 0.03 ksf
b. Beam:
B1
RCC Column
B2 B2
RCC Beam
15'-0"
Tributary area of
slab on beam
45°
B1
20'-0"
Figure 36: Tributary area of slab on beam.
c. Column: All columns in the system are biaxial. The service loads on column
will come from analysis of the frame.
2. Earthquake Load:
Static Lateral force procedure: Also referred to as equivalent static lateral force
procedure.
The total design base shear is:
V = (CνI/RT) W
Where, for the case under consideration,
I = 1.00 {Standard occupancy structures, table 16-K of UBC-97}
R = 8.5 {for SMRF, table 16-N of UBC-97}
Cν = 0.64Nν {seismic zone 4/soil type SD, Table 16-Q of UBC-97}
Nν = 1.0 (For seismic source type A ≥ 15 km, Table 16-T of UBC-97)
Therefore, Cν = 0.64
T = Ct (hn)3/4
Where,
Ct = 0.030 (for reinforced concrete structures)
hn = total height of the structure = 10′
Therefore, T = 0.030 × (10)3/4 = 0.169 sec
Total seismic weight of the structure (W) is:
W = wslab + wbeams + wcolumns + wmud
= [(6/12)×15×20+(2×20+2×15)×(12/12)×(24/12)+4×(12/12)×(12/12)×10]×0.15
+(3/12) ×15×20×0.12 = 58.5 kip
Therefore,
V = (CνI/RT) W = {(0.64 x 1.00)/ (8.5 x 0.169)} x 58.5 = 26.06 kip
The total design base shear shall not be less than the following:
V = 0.11CaIW = 0.11 × 0.44 × 1.00 × 58.5 = 2.83 kip
In addition for seismic zone 4, the total base shear shall also not be less than the
following:
V = (0.8ZNνI/R) W = (0.8 × 0.4 × 1.00 × 1.00/8.5) × 58.5 = 2.20 kip
Therefore design base shear is V = 7.57 kip
The base shear shall be converted to storey forces in order to be used in the
analysis. As the structure is single storey, the storey forces assigned to storey level
in each direction will be as follows:
Figure 37: Base shear converted to storey forces in two mutually orthogonal
directions of structure.
Load Combinations:
Step No 3: Analysis.
Any structural analysis method may be used to analyze the frames shown above.
However, for the sake of clarity, only one of the frames will be analyzed manually
using moment distribution method while the rest of the frames will be analyzed by
finite element method based software (SAP2000).
Analysis for service dead load
Analysis is performed using Moment distribution method. Only analysis of N-S frame
(15 ft wide) is presented here.
These values are compared with FE method based software SAP2000, shown in
figure 38.
The remaining analysis (for service load) of N-S frame and E-W frame is done in
SAP2000 and complete analysis results are given in tables 10 and 11 respectively.
Table 10: Service values of load effects for N-S frame (15 ft) of the structure.
Moment (kip-in)
Member Axial (kip) Shear (kip)
Positive (mid) (supports) (supports)
AB 5.61 0.31 n/r 0 36
Dead BC 0.31 5.61 215 - 36 - 36
CD 5.61 0.31 n/r 36 0
Table 11: Service values of load effects for E-W frame (20 ft) of the structure.
Moment (kip-in)
Member Axial (kip) Shear (kip)
Positive (mid) (supports) (supports)
EF 6.9 0.62 n/r 0 75
Dead FG 0.62 6.9 339 -75 -75
GH 6.9 0.62 n/r 75 0
The factored values according to the calculated load combinations for all frame members
(beams and columns) are summarized in tables 12 through 15.
Table 12: Factored axial forces and shear forces in N-S frame (15 ft).
Table 14: Factored axial forces and shear forces in E-W frame (20 ft).
Step No 4: Design.
From the above analysis results, the beams and columns are designed for the
following demands.
Table 16: Maximum demand on members.
From above data, the moment demand of 566.96 corresponds to 0.76 in2, quite below
the Asmin mark of 1.26 in2. This means that all moment demands will give steel area
less than Asmin.
i) Design of Beams:
Table 17: Flexural design of beams
Flexural design
steel area from Design steel area # of bars
from analysis Asmax Bar
Beam 2
Positive Negative (in ) Positive Negative used
Positive Negative
steel steel steel steel
2 2 2 bars bars
(in ) (in ) (in ) (in2)
5
E-W
0.47 0.41 5.12 1.36 1.26 #5 5 (curtailing
Beam
3 bars)
5
N-S
0.76 0.50 5.12 1.26 1.26 #5 5 (curtailing
Beam
3 bars)
Note: Asmin = 1.26 in2
Lap splices:
• Not to be provided within the joints.
• Not to be provided within 2h = 2 × 24 = 48″, from the face of the joint or at other
locations where flexural yielding is expected.
• Maximum spacing of hoops on Lap splices is least of:
¾ d/4 = 21/4 = 5.25″
¾ 4″
Therefore, maximum spacing of hoops on Lap splice = 4″
• Lap splice length =(1.3 × 0.05 fy/ √fc′)×db = 30″
Transverse reinforcement:
• Transverse reinforcement shall be provided over a length of 2h = 2 × 24 = 48″,
measured from the face of the supporting member toward mid span at both ends.
• The first hoop shall be located at a distance of 2″ from the face of the supporting
member.
• Max spacing of the hoops over the length must not exceed least of:
a. ¼ × d = ¼ × 21 = 5.25″
b. 8db = 8 × 5/8 = 5″
c. 24dhoop bar = 24 × 3/8 = 9″
d. 12″
Therefore, maximum spacing of hoops over a region of 48″ from both ends of
beam ≤ 5″. Finally, using spacing of 5″.
• Elsewhere spacing shall not exceed d/2 = 21/2 = 10.5″.
Checklist for columns:
Flexural reinforcement:
• 0.01 ≤ ρg ≤ 0.06:
Therefore, for 8 #5 bars,
As/bh = 8 × 0.30/ (12 × 12) = 0.0166, O.K.
Lap splices:
• To be provided within the middle half of column height.
• Maximum spacing of ties on Lap splices is least of:
¾ d/4 = {12 – 1.5 – (3/8) – (5/8)/2}/4 = 2.45″
¾ 4″
Therefore, maximum spacing of ties on Lap splices = 2.45″ ≈ 3″
• Lap splice length =(1.3 × 0.05 fy/ √fc′)db = 30″
Transverse reinforcement:
• Length lo from each joint face is least of:
(i) Depth of member at joint face = 12″.
Beam-column joints:
• The transverse reinforcement used in columns shall be continued through the joint
in accordance with ACI 21.5.2.
• Column dimension parallel to beam longitudinal bar ≥ 20 × Beam long bar:
Column dimension parallel to beam longitudinal bar = 12″
20 × 5/8 = 12.5″ ≈ 12″, O.K.
• The development length of beam bars in columns with 90° hooks is not to be less
than largest of:
a. 8db = 8 × 5/8 = 5″
b. 6″
c. ldh = fydb/(65 √fc′) = 40000 × (5/8)/ {65 × √(3000)} = 7″
Therefore, development length = 7″
Step No 5: Drafting.
A B C
#3, 2 legged stirrups #3, 2 legged stirrups #3, 2 legged stirrups
#3 ties @ 5" c/c upto 2h = 4' @ 10.5" c/c @ 5" c/c upto 2h = 4'
@3" c/c
8 #5 bars
E E
Lap splice
3'-0"
D D
Development length
of column bars in
beam = 22" > 7"
2"
5 #5 bars #3 ties
@3" c/c
8 #5 8 #5
Bars Bars
12" 12"
1. FOOTING 3"
2. COLUMN 1-1/2"
3. SLAB 3/4"
4. BEAM 1-1/2"
3/8" 16 23
1/2" 21 30
5/8" 26 38
3/4" - 45
B/2
180° HOOK
BAR
A(in.) B(in.) C(in.)
DIA
A
B
3/8" 2.5 2.5 4.5
90° HOOK
5/8" 2.5 4.0 7.5
3/8" 18 6
1/2" 24 6
5/8" 30 8
3/4" 36 9
Prof. Dr. Qaisar Ali (http://www.eec.edu.pk) Page 55 of 56
Earthquake Engineering Center, N-W.F.P UET Peshawar A Monograph on Earthquake Resistant Design of R C Structures
References
¾ ACI 318-02/05