IEC 62056 1

IEC 62056
DLMS or Device Language Message Specification (originally Distribution Line Message Specification[1] ), is the
suite of standards developed and maintained by the DLMS User Association and has been co-opted by the IEC TC13
WG14 into the IEC 62056 series of standards. COSEM or Companion Specification for Energy Metering, includes a
set of specifications that defines the Transport and Application Layers of the DLMS protocol. The DLMS User
Association defines the protocols into a set of three specification documents namely Green Book, Yellow Book and
Blue Book.
The IEC TC13 WG 14 defines the DLMS specifications under the common heading: "Electricity metering - Data
exchange for meter reading, tariff and load control."
• IEC 62056-21: Direct local data exchange (3d edition of IEC 61107) describes how to use COSEM over a local
port (optical or current loop)
• IEC 62056-42: Physical layer services and procedures for connection-oriented asynchronous data exchange
• IEC 62056-46: Data link layer using HDLC protocol
• IEC 62056-47: COSEM transport layers for IPv4 networks
• IEC 62056-53: COSEM Application layer
• IEC 62056-61: Object identification system (OBIS)
• IEC 62056-62: Interface classes

Interface classes
In DLMS/COSEM, all the data in electronic meters and devices are represented by means of attribute values. Any
real world thing can be described by attributes; methods allow operations to be performed on the attributes.
Attributes and methods constitute an object. The first attribute in any object is the logical_name. It is one part of the
identification of the object. Objects that share common characteristics are generalized as an interface class with a
class_id. Instantiations of an interface class are called COSEM objects. IEC 62056-62 defines 19 interface classes
for COSEM object model.

IEC 62056-21
IEC 61107 or currently IEC 62056-21, was an international standard for a computer protocol to read utility meters.
It is designed to operate over any media, including the Internet. A meter sends ASCII (in modes A..D) or HDLC
(mode E) data to a nearby hand-held unit (HHU) using a serial port. The physical media are usually either modulated
light, sent with an LED and received with a photodiode, or a pair of wires, usually modulated by a 20mA current
loop. The protocol is usually half-duplex.
The following exchange usually takes a second or two, and occurs when a person from the utility company presses a
meter-reading gun against a transparent faceplate on the meter, or plugs into the metering bus at the mailbox of an
apartment building.
The general protocol consists of a "sign on" sequence, in which a handheld unit identifies itself to the metering unit.
During sign-on, the handheld unit addresses a particular meter by number. The meter and hand-held unit negotiate
various parameters such as the maximum frame length during transmission and reception,Whether multiple frames
can be sent without acknowledging individual frames(Windowing), the fastest communication rate that they can both
manage(only in case of mode E switching to HDLC) etc. Next the meter informs the hand held unit about the various
parameters that are available with it in various security settings viz. the 'no security logical group', ' the low security
logical groups' and ' the high security logical groups'.
If the parameter required is in no security group, just a get.request will provide the HHU with the desired response. If
the parameter required is in low security group, a password authentication of the HHU is required before information
IEC 62056 2

can be read.
In case of high security parameters,the meter challenges the hand held unit with a cryptographic password. The hand
held unit must return an encrypted password. If the password exchange is ok, the meter accepts the hand held unit- it
is "signed on."
After signing on, the hand held unit generally reads a meter description. This describes some registers that describe
the current count of metered units (i.e. kilowatt hours, megajoules, litres of gas or water) and the metering unit's
reliability (is it still operating ok?). Occasionally a manufacturer will invent a new quantity to measure, and in this
case, a new or different data type will appear in the meter definition. Most metering units have special modes for
calibration and resetting meter registers. These modes are usually protected by anti-tampering features such as
switches that sense if the meter enclosure has been opened.
The HHU may also be given limited rights to set or reset certain parameters in the meter.
The hand held unit then sends a sign-off message, and the meter automatically signs off after a previously negotiated
time interval after the last message, if no sign-off message is sent.

External links
• The DLMS User Association, which developed and supports the standard (excerpts of the standards are available)
[2]

• The official IEC standard [3]


• About DLMS/COSEM Standards and Specifications [4]
• Open Source solution for communicating with DLMS devices [5]
• DLMS Based Smart Meter [6]

References
[1] What is DLMS? http:/ / www. dlms. com/ faqanswers/ generalquestions/ whatisdlms. php
[2] http:/ / www. dlms. com
[3] http:/ / domino. iec. ch/ webstore/ webstore. nsf/ artnum/ 031526
[4] http:/ / kalkitech. com/ offerings/ solutions-dlms_solutions-about_dlmscosem/
[5] http:/ / www. gurux. org/ index. php?q=GXDLMSCOSEM
[6] http:/ / kalkitech. com/ documents/ DLMS%20smart%20meter_Presentation. pdf
Article Sources and Contributors 3

Article Sources and Contributors


IEC 62056  Source: http://en.wikipedia.org/w/index.php?oldid=408962632  Contributors: AFA, Anoopmgeorge, BillC, DavidDHaynes, Deville, Fahidka, Gp1973, Hamza Abusitta, Liuqun,
Markus Kuhn, MementoVivere, Mikko Kurunsaari, Ray Van De Walker, Rjwilmsi, Shcha, TheParanoidOne, Vaibhavgarg, Woohookitty, 19 anonymous edits

License
Creative Commons Attribution-Share Alike 3.0 Unported
http:/ / creativecommons. org/ licenses/ by-sa/ 3. 0/

You might also like