You are on page 1of 6

Project Number:

Project Name:

Location:
Date: Monday, January 31, 2011
Prepared By:

Floor Plan: Main Floor


Circuit Information:

Manifold 1 Total Length: 671 m - Barrier PEX 16mm


(36.7 °C)

Circuit Length Manifold Tube Type


Room 2
29.3 W/m²
22.9 °C
Supplemental: 3.1 W/m²
A-1 96 Manifold 1 16mm
Heated Area:6.5 m²

Room 3
29.4 W/m²
A-2 95 Manifold 1 16mm
22.9 °C
Supplemental: 0.0 W/m²
Heated Area:6.4 m²
Room 1
32.0 W/m²
21.2 °C
Supplemental: 0.0 W/m²
Circuit A-2
95 m @ 203 mm
Flow: 0.10 L/s
A-3 97 Manifold 1 16mm
Heated Area:16.3 m²
T: 3 °C

Circuit A-8
97 m @ 203 mm A-4 96 Manifold 1 16mm
Flow: 0.03 L/s
T: 8 °C

A-5 94 Manifold 1 16mm


A-6 95 Manifold 1 16mm
Room 9
21.2 W/m²
22.2 °C
Supplemental: 0.0 W/m²
Heated Area:15.0 m²
A-8 97 Manifold 1 16mm
Room 12
33.3 W/m²
23.3 °C
Supplemental: 0.0 W/m²
Heated Area:49.7 m²
Circuit A-5
94 m @ 203 mm
Flow: 0.07 L/s
T: 4 °C

Circuit A-3
97 m @ 203 mm
Flow: 0.01 L/s
T: 14 °C

Circuit A-1
96 m @ 100 mm
Flow: 0.08 L/s
T: 4 °C
Room 5
36.4 W/m²
21.6 °C Room 4
Supplemental: 1.0 W/m² 31.7 W/m²
Heated Area:15.5 m² 23.2 °C
Supplemental: 0.0 W/m²
Heated Area:10.1 m²

Circuit A-6
Circuit A-4 95 m @ 203 mm
Room 7 96 m @ 203 mm Flow: 0.07 L/s
35.5 W/m²
23.5 °C
Flow: 0.07 L/s T: 4 °C
Supplemental: 0.0 W/m² T: 4 °C
Heated Area:3.4 m²

Note: Details of the tubing bend radius have been simplified for clarity. Consult tubing Project Number:
manufacturer for specific bend radius recommendations.
Floorplan: Main Floor (Fit To Page)
Heat Loss Summary
ASHRAE (Residential) Load Calculation

February 7, 2011

Project Information
Project #: Notes:
Name:
Location:

Load Calculation Summary


Design Location: WELLINGTON INTL, Building Heat Loss: 3893 W
Load Calculation Method: ASHRAE (Residential) Infiltration/Ventilation: 960 W
Outdoor Temperature: 1.9 °C
Floorplans / Levels: Radiant Heating: 3857 W
Main Floor 132.6 m² Radiant Back Losses: 3731 W
Total Area: 132.6 m² Baseboard: 0 W
Forced Air: 0 W
Other: 36 W
Total Heating Load: 7623 W

Load Calculation Results


Total Project
Room Area Heating Type Room Temp Walls Windows Doors Skylights Floor Ceiling Infiltration Additional Recovered Design Load Unit Loss
Panel Loss
Total For Project 132.6 RH,OTH 962 920 192 0 3742 847 960 0 0 7623 61.7

Length = m Area = m² Temperature = °C Heat Loss = W Unit Heat Loss = W/m² Rv = m²·K/W Created using LoopCAD 2010
RH = Radiant Floor Heating BB = Baseboard FA = Forced Air O = Other Heating SM = Snowmelt N = Not Heated Version:2.3.0190 (Trial)

See end of report for important Notes and Disclaimers. Page 1 of 2


Name: Heat Loss Summary
Project #: February 7, 2011

Main Floor
Suspended Construction
Room Area Heating Type Room Temp Walls Windows Doors Skylights Floor Ceiling Infiltration Additional Recovered Design Load Unit Loss
Panel Loss
Room 1 17.6 RH 18.0 187 104 0 0 472 103 127 0 0 993 61.0
Room 2 7.1 RH,OTH 20.0 45 46 0 0 194 47 52 0 0 384 59.3
Room 3 7.0 RH 20.0 44 46 0 0 191 46 51 0 0 379 59.5
Room 4 11.1 RH 20.0 55 116 0 0 313 73 80 0 0 638 62.3
Room 5 16.8 RH,OTH 18.0 159 185 0 0 475 98 122 0 0 1039 66.9
Room 7 3.9 RH 20.0 39 29 0 0 111 26 28 0 0 233 67.9
Room 9 16.9 RH 20.0 23 0 64 0 421 111 122 0 0 741 47.5
Room 12 52.2 RH 20.0 410 393 128 0 1565 343 378 0 0 3217 64.7
Sub Total 132.6 RH,OTH Multiple 962 920 192 0 3742 847 960 0 0 7623 61.7

Disclaimers
With the permission of ASHRAE, portions of the 2005 ASHRAE Handbook – Fundamentals are reproduced in this software, including the Climatic Design Conditions data. The program and data are provided "as is" without warranty
of any kind either expressed or implied. The entire risk as the quality and performance of the program and data is with you. In no event will ASHRAE be liable to you for any damages, including without limitation any lost profits, lost
savings, or other incidental or consequential damages arising out of the use or inability to use this program or the data . © 2005 ASHRAE, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

The calculated values shown in this report are based on the data input by the user of the software. Inaccurate or erroneous data input will result in inaccurate or erroneous results. You are strongly advised to review all input data
carefully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability for your application.
IN NO EVENT WILL AVENIR SOFTWARE INC. (“AVENIR”) OR ITS AFFILIATES BE LIABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY CONSEQUENTIAL, INCIDENTAL, INDIRECT OR
SPECIAL OR PUNITIVE DAMAGES WHATSOEVER (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA AND THE LIKE), EVEN IF SUCH PARTY
HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. AVENIR’S CUMULATIVE LIABILITY FROM ANY CAUSE RELATED TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED
TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT.

Length = m Area = m² Temperature = °C Heat Loss = W Unit Heat Loss = W/m² Rv = m²·K/W Created using LoopCAD 2010
RH = Radiant Floor Heating BB = Baseboard FA = Forced Air O = Other Heating SM = Snowmelt N = Not Heated Version:2.3.0190 (Trial)

See end of report for important Notes and Disclaimers. Page 2 of 2


Heating System Summary

February 7, 2011

Project Information
Project #: Notes:
Name:
Location:

Project Summary
Load Calculation Method: ASHRAE (Residential) Total Tubing Lengths: Building Heat Loss: 3893 W
Design Location: WELLINGTON INTL, Barrier PEX 16mm 671 m Infiltration/Ventilation: 960 W
Outdoor Temperature: 1.9 °C
Floorplans / Levels: Total RH Circuits: 7 Radiant Heating: 3857 W
Main Floor 132.6 m² Total Manifolds: 1 Radiant Back Losses: 3731 W
Total Area: 132.6 m² Total Zones: 3 Baseboard: 0 W
Forced Air: 0 W
Other: 36 W
Total Heating Load: 7623 W

Zone Heating Summary

Zone # Area Construction Heating Types RH Total Manifolds Flowrate Head Loss RH Load BB Load Other Load Total Load
Circuits Tubing
101 0.0 N/A 0 0 0 0.00 0 0 0 0 0
201 132.6 Heat Transfer Plates Below Sub-floor RH,OTH 7 671 1 0.44 48 7610 0 36 7623
202 0.0 N/A 0 0 0 0.00 0 0 0 0 0
Total 132.6 Heat Transfer Plates Below Sub-floor RH,OTH 7 671 1 0.44 48 7610 0 36 7623

Room Heating Summary (By Construction Type)


Heat Transfer Plates Below Sub-floor
Zone # Room Name Heating Area Heated Manifold Tube RH Tube Total Floor Required Unit RH RH Load Other Load Total Load
Type Area # Size Circuits Spacing Tubing Cover RV Temp. Load
201 Room 4 RH 11.1 10.1 Manifold 1 16mm 1 203 96 0.1 40 62.3 638 0 638
201 Room 5 RH,OTH 16.8 15.5 Manifold 1 16mm 1 100 97 0.1 40 65.9 1023 16 1039
201 Room 9 RH 16.9 15.0 Manifold 1 16mm 1 203 94 0.1 35 47.5 741 0 741

Length = m Area = m² Temperature = °C Heat Loss = W Unit Heat Loss = W/m² Rv = m²·K/W Created using LoopCAD 2010
RH = Radiant Floor Heating BB = Baseboard FA = Forced Air O = Other Heating SM = Snowmelt N = Not Heated Version:2.3.0190 (Trial)

See end of report for important Notes and Disclaimers. Page 1 of 2


Name: Heating System Summary
Project #: February 7, 2011

201 Room 1 RH 17.6 16.3 Manifold 1 16mm 1 203 98 0.1 38 61.0 993 0 993
201 Room 7 RH 3.9 3.4 Manifold 1 16mm 1 203 96 0.1 40 67.9 233 0 233
201 Room 12 RH 52.2 49.7 Manifold 1 16mm 3 203 289 0.1 41 64.7 3217 0 3217
201 Room 3 RH 7.0 6.4 0 198 0 0.1 38 59.5 379 0 379
201 Room 2 RH,OTH 7.1 6.5 0 192 0 0.1 38 56.2 364 20 384

RH Manifold Summary

Manifold Name # Zones # Circuits Flowrate Head Loss Required Supplied Temp. Max Temp. Manifold Type Control Type # Actuators
Temp. Drop
Manifold 1 1 7 0.44 48 41 37 14 Stainless Steel Manifold 0
Total 1 7 0.44 48 41 - - - - 0

Disclaimers
With the permission of ASHRAE, portions of the 2005 ASHRAE Handbook – Fundamentals are reproduced in this software, including the Climatic Design Conditions data. The program and data are provided "as is" without warranty
of any kind either expressed or implied. The entire risk as the quality and performance of the program and data is with you. In no event will ASHRAE be liable to you for any damages, including without limitation any lost profits, lost
savings, or other incidental or consequential damages arising out of the use or inability to use this program or the data . © 2005 ASHRAE, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

The calculated values shown in this report are based on the data input by the user of the software. Inaccurate or erroneous data input will result in inaccurate or erroneous results. You are strongly advised to review all input data
carefully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability for your application.
IN NO EVENT WILL AVENIR SOFTWARE INC. (“AVENIR”) OR ITS AFFILIATES BE LIABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY CONSEQUENTIAL, INCIDENTAL, INDIRECT OR
SPECIAL OR PUNITIVE DAMAGES WHATSOEVER (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA AND THE LIKE), EVEN IF SUCH PARTY
HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. AVENIR’S CUMULATIVE LIABILITY FROM ANY CAUSE RELATED TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED
TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT.

Length = m Area = m² Temperature = °C Heat Loss = W Unit Heat Loss = W/m² Rv = m²·K/W Created using LoopCAD 2010
RH = Radiant Floor Heating BB = Baseboard FA = Forced Air O = Other Heating SM = Snowmelt N = Not Heated Version:2.3.0190 (Trial)

See end of report for important Notes and Disclaimers. Page 2 of 2


Radiant Panel Schedule

February 7, 2011

Project Information
Project #: Notes:
Name:
Location:

Design Conditions and Summary


Load Calculation Method: ASHRAE (Residential) Building Heat Loss: 3893 W
Design Location: WELLINGTON INTL, Infiltration/Ventilation: 960 W
Outdoor Temperature: 1.9 °C
Floorplans / Levels: Radiant Heating: 3857 W
Main Floor 132.6 m² Radiant Back Losses: 3731 W
Total Area: 132.6 m² Baseboard: 0 W
Forced Air: 0 W
Other: 36 W
Total Heating Load: 7623 W

Radiant Panel Details


Panel Type #1 - Heat Transfer Plates Below Sub-floor
Plate Type: Aluminum sheet
Plate Thickness: 0.508 mm
Plate Length: 305 mm
Sub-Floor Thickness: 19.050 mm
Sub-Floor Rv: 0.2 m²·K/W
Joist Construction: Joist 2"x10" pine, 16" OC
Joist Spacing: 406 mm
Joist Insulation Rv: 0.9 m²·K/W
Spacing: 100 mm, 305 mm
Floorplans:
Main Floor 123.6 m²

Created using LoopCAD 2010


Version:2.3.0190 (Trial)

See end of report for important Notes and Disclaimers. Page 1 of 2