You are on page 1of 42

OISD-RP-149

FOR RESTRICTED
CIRCULATION ONLY
No.

DESIGN ASPECTS FOR SAFETY


IN
ELECTRICAL SYSTEM

OISD - RECOMMENDED PRACTICES - 149


First Edition, February, 1996
Amended Edition, September 2001

Oil Industry Safety Directorate


Government of India
Ministry of Petroleum & Natural Gas
OISD - RP - 149
First Edition
February, 1996
Amended Edition, September
2001

FOR RESTRICTED
CIRCULATION ONLY

DESIGN ASPECTS FOR SAFETY


IN
ELECTRICAL SYSTEM

Prepared by:
COMMITTEE ON “DESIGN ASPECTS FOR ELECTRICAL SAFETY”

OIL INDUSTRY SAFETY DIRECTORATE


2ND FLOOR, “KAILASH”
26, KASTURBA GANDHI MARG
NEW DELHI - 110 001
NOTE
OISD publications are prepared for use in the oil and gas
industry under Ministry of Petroleum and Natural Gas. These are the
property of Ministry of Petroleum and Natural Gas and shall not be
reproduced or copied and loaned or exhibited to others without written
consent from OISD.

Though every effort has been made to assure the accuracy and
reliability of the data contained in these documents, OISD hereby
expressly disclaims any liability or responsibility for loss or damage
resulting from their use.

These documents are intended to supplement rather than


replace the prevailing statutory requirements.

Note 3 in superscript indicates the


modification/changes/addition based on the
amendments approved in the 19th Safety Council
meeting held in September, 2001July, 1999
FOREWORD

Oil Industry in India is nearly 100 years old. Due to various collaboration
agreements a variety of international codes, standards and practices are in vogue,
Standardisation in design philosophies, operating and maintenance practices at a
national level was hardly in existence. This lack of uniformity coupled with feedback from
some serious accidents that occurred in the recent past in India and abroad, emphasised
the need for the industry to review the existing state of art in designing, operating and
maintaining oil and gas installations.

With this in view, the Ministry of Petroleum and Natural Gas in 1986 constituted a
Safety Council assisted by the Oil Industry Safety Directorate (OISD) staffed from within
the industry in formulating and implementing a series of self-regulatory measures aimed
at removing obsolescence, standardising and upgrading the existing standards to ensure
safer operations. Accordingly OISD constituted a number of functional committees
comprising of experts nominated from the industry to draw up standards and guidelines
on various subjects.

The present document on “Design Aspects for Safety in Electrical System” was
prepared by the Functional committee on “Design Aspects for Electrical Safety”. This
document is based on the accumulated knowledge and experience of industry members
and the various national and international codes and practices.

It is hoped that provisions of this document if implemented objectively, may go a


long way to improve the safety to reduce accidents in Oil and Gas Industry. Users are
cautioned that no document can be a substitute for the judgement of responsible and
experienced engineer.

Suggestions are invited from the users after it is put into practice to improve the
document further. Suggestions for amendments, if any, to this standard should be
addressed to :

The Co-ordinator
Committee on “Design Aspects for Electrical Safety”
Oil Industry Safety Directorate
2nd Floor, “Kailash”
26, Kasturba Gandhi Marg
New Delhi - 110 001

This document in no way supersedes the statutory regulations of Chief Controller


of Explosives (CCE), Factory Inspectorate or any other statutory body which must be
followed as applicable.
COMMITTEE
ON
DESIGN ASPECTS FOR ELECTRICAL SAFETY
---------------------------------------------------------------------------------------------------------------------------------
NAME ORGANISATION
---------------------------------------------------------------------------------------------------------------------------------
LEADER

Shri V. P. Sharma Engineers India Limited

MEMBERS

Shri R. Sankaran Madras Refineries Limited

Shri U. P. Singh Indian Oil Corporation Limited

Shri Narendra Kumar Gas Authority of India Limited

Shri R. Raghupathy Engineers India Limited

MEMBER CO-ORDINATORS

Shri N. V. Mani Oil Industry Safety Directorate

Shri J. K. Jha Oil Industry Safety Directorate


---------------------------------------------------------------------------------------------------------------------------------
In addition to the above, several other experts from Industry contributed in the preparation,
review and finalisation of this document.
DESIGN ASPECTS FOR SAFETY IN ELECTRICAL SYSTEM

CONTENTS
-------------------------------------------------------------------------------------------------------
SECTION DESCRIPTION PAGE NO.
---------------------------------------------------------------------------------------------------------------------------------
1.0 INTRODUCTION

2.0 SCOPE

3.0 DEFINITIONS

4.0 POWER SYSTEM DESIGN

4.1 Capacity of Electrical Plant

4.2 Neutral Earthing

4.3 Short Circuit Capacities

4.4 Insulation Coordination

4.5 Protection and Metering

4.6 Emergency Power Supply

4.7 Critical Power Supply Systems

5.0 ELECTRICAL EQUIPMENT FOR CLASSIFIED


AREA

6.0 SUB-STATION LOCATION/LAYOUT

7.0 ELECTRICAL EQUIPMENT

7.1 Characteristics

7.2 Equipment Features

7.2.1 Transformers

7.2.2 H.V/M.V Switchboards

7.2.3 Motors (H.V & M.V)

7.2.4 Battery Charger and Distribution Board

7.2.5 Batteries and Battery Accessories

7.2.6 Equipment for Uninterrupted Power Supply


System

7.2.7 Capacitor Banks

7.2.8 Emergency Generator

---------------------------------------------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------------------
SECTION DESCRIPTION PAGE NO.
---------------------------------------------------------------------------------------------------------------------------------

7.2.9 Cables

7.2.10 Control Station

7.2.11 Convenience Receptacles

7.2.12 Actuators for Motor Operated Valves

8.0 PLANT CABLING

9.0 Plant Lighting

10.0 Plant Earthing

11.0 PLANT SAFETY AND SECURITY SYSTEMS

11.1 Plant Fire Detection and Alarm System

11.2 Communication System

11.2.1 Telephone System

11.2.2 Public Address System

11.2.3 Emergency Communication System


(Hot Line System)

11.2.4 Radio Communication System

a) Portable Walkie-Talkie System


b) VHF System

11.2.5 Telex System

12.0 MOBILE EQUIPMENT FOR HAZARDOUS


AREAS

12.1 Portable Hand Lamps

12.2 Diesel Engines

12.3 Storage Batteries

12.4 Testing Equipment

12.5 Miscellaneous Requirements

12.6 Vehicles

13.0 REFERENCES

=====================================================================
DESIGN ASPECTS FOR SAFETY IN ELECTRICAL SYSTEM

1.0 INTRODUCTION A connection to the general mass of


earth by means of an earth electrode. An
Safety in electrical system draws object is said to be ‘earthed’ when it is
maximum attention especially in the electrically connected to an earth
hydrocarbon industry, where classified electrode; and a conductor is said to be
hazardous atmosphere may be ‘solidly earthed’ when it is electrically
encountered and electricity may connected to earth electrode without a
constitute one of the sources of ignition fuse, switch, circuit-breaker, resistance or
for fire accidents and explosions. Besides impedance in the earth connection.
equipment damage and property loss,
electrical hazards may lead to injuries ii) Earth Continuity Conductor -
and fatalities to personnel due to electric
shock and burns. The electrical system The conductor, including any clamp,
designer, hence, faces a challenge to connecting to the earthing lead or to each
provide a safe and reliable electrical other of those parts of an installation
system. which are required to be earthed.

It is therefore imperative that safety iii) Earth Electrode -


aspects are built into the electrical
system right from the design and A metal plate, pipe or other conductor
engineering stage with the main objective embedded in the soil that makes a direct
of minimising equipment/system failure to contact to the general mass of the earth.
prevent injury to personnel and damage
to system components. iv) Earthing Lead -

Following the guidelines and adhering to The final conductor by which the
the safe practices given in this standard, connection to the earth electrode is made.
would ensure adequate levels of safety in
the electrical facilities of Oil Industry. v) Voltage, Low - (LV)

2.0 SCOPE The voltage which does not normally


exceed 250 volts.
This document recommends minimum
requirements in the design and vi) Voltage, Medium - (MV)
engineering of electrical installations in
the petroleum oil and gas sector. The voltage which normally exceeds 250
However, this standard does not cover volts but does not exceed 650 volts.
offshore installations. It also excludes
drilling rigs and well head installations. vii) Voltage High - (HV)
This standard is not intended for use as a
comprehensive design manual for The voltage which normally exceeds 650
electrical power system design. The volts but does not exceed 33 KV
standard in no way supersedes the
statutory regulations of the Chief viii) Voltage, Extra-High-(EHV)
Electrical Inspectorate, Factory
inspectorate, Chief Controller of The voltage which exceeds 33 KV under
Explosives, Director General Mines normal conditions.
Safety, Central Electricity Authority or ix) Impulse -
other Government bodies, which shall be
followed as applicable. Usually a periodic transient voltage or
current which rises rapidly to a peak value
and then falls, generally more slowly, to
zero.
3.0 DEFINITIONS
x) Earth Fault -]
I) Earth Connection -
Accidental connection of a conductor to A general term covering switching
earth. When the impedance is negligible, devices and their combinations with
the connection is called a dead earth-fault. associated control, measuring,
protective and regulating equipment;
xi) Earth Leakage Current - also assemblies of such devices and
equipment with associated inter-
The current following to earth on account connections, accessories, enclosures
of imperfect insulation. and supporting structures intended in
principle for use in connection with
xii) Insulation Fault - generation, transmission, distribution
and conversion of electrical energy.
An abnormal decrease in insulation Controlgear are switching devices
resistance. intended in principle for the control of
electrical energy consuming equipment.
xiii) Overload -
xx) Flame Arrestor -
Operating conditions in an electrically
undamaged circuit which cause an A device for releasing gas from an
overcurrent. enclosure in such a way that in case of
an internal explosion there is no
xiv) Short-Circuit - appreciable increase in internal pressure
and the released gas will not ignite the
The intentional or accidental connection of surrounding flammable atmosphere.
two points of a circuit. The term is often
applied to the group of phenomena which xxi) Nominal Voltage (of an Installation)
accompany a short circuit between points
at different potentials. Voltage for which an installation or part
of an installation is designated.
xv) Symmetrical breaking current
xxii) Highest System Voltage
The symmetrical breaking current, during
opening of a circuit breaker in the event of The highest R.M.S. phase to phase
a short circuit, is the r.m.s. value of the voltage, which occurs under normal
symmetrical short circuit current flowing operating conditions at any time and at
through the first phase to open at the any point in the system. It excludes
instant of contact separation. voltage transients (such as those due to
system switching) and temporary
xvi) Peak short circuit current voltage variation due to abnormal
system conditions (such as those due to
This is the highest instantaneous value of fault conditions on sudden disconnection
current after the occurrence of short of large loads).
circuit. It is given as a peak value. Its
magnitude depends on the instant of the xxiii) Lightning Protective System -
cycle at which the short circuit occurs.
The whole system of interconnected
xvii) Redundancy conductors used to protect a structure
from the effects of lightning.
Duplication of elements in a system or
installation, for the purpose of enhancing xxiv) Portable Equipment -
the reliability or continuity of operation of
the system or installation. Equipment which can be moved even
while in operation or which can easily
xviii) Electrical Equipment - be moved from one place to another
while connected to the electric supply.
The electrical machines, apparatus and
circuits forming part of an electrical xxv) Hand-Held Equipment -
installation or a power system.
Portable equipment intended to be
xix) Switchgear and Controlgear- held in the hand during normal use in
which the motor, if any, forms an a) Petroleum having flash point
integral part of the equipment. below 65°C or any flammable gas
or vapour in a concentration
xxvi) Stationary Equipment - capable of ignition is likely to be
present;
Either fixed equipment or equipment
not provided with a carrying handle b) Petroleum or any flammable liquid
and having such a mass that it cannot having flash point above 65°C is
easily be moved. likely to be refined, blended,
handled or stored at or above its
xxvii) Fixed Equipment - flash point.

Equipment fastened to a support or Zone 0 An area in which a flammable


otherwise secured in a specific atmosphere is present
location. continuously, or is present for long
periods.
xxviii) Self Powered Vehicle -
Zone 1 An area in which a flammable
A vehicle used for the conveyance of atmosphere is likely to be present
stationary equipment (e.g. periodically or occasionally during
compressors), personnel or goods in normal operation.
which petroleum or storage battery is
used to generate the motive power. Zone 2 An area in which a flammable
atmosphere is not likely to occur in
xxix) Flammable Material - normal operation and if it does
occur, it will exist for a short time
A flammable material is a gas, vapour, only.
liquid, and/or mist which can react
continuously with atmospheric oxygen xxxiv) Non-hazardous (Safe) Area -
and which may therefore, sustain a
fire or explosion when such reaction is An area, no part of which is within a
initiated by a suitable spark, flame or hazardous area.
hot surface.
xxxv) Electrical Apparatus for Hazardous
xxx) Flammable Mixture - Areas

A mixture of flammable gas, vapour, Electrical apparatus which will not


or mist with air under atmospheric ignite the surrounding flammable
conditions, in which after ignition, atmosphere in which it is used.
combustion spreads throughout the
unconsumed mixture. xxxvi) Intrinsic Safety (Ex-i) (Ref : IS : 5780)

xxxi) Hazard - A circuit or part of a circuit is


intrinsically safe when any spark or
The presence, or the risk of presence, thermal effect produced normally (that
of a flammable mixture. is, by breaking or closing the circuit) or
accidentally (for example by short-
xxxii) Hazardous (Flammable) Atmosphere - circuit or earth fault) is incapable,
under prescribed test conditions, of
In accordance with the Petroleum causing ignition of a prescribed gas or
Rules, an atmosphere containing any vapour.
flammable gas or vapour in a
concentration capable of ignition. An intrinsically safe apparatus is one
in which all electrical circuits are
xxxiii) Hazardous Area - intrinsically safe. It is placed in one of
the following categories:
In accordance with the petroleum
rules, an area shall be deemed to be a
hazardous area, where:
a) Category (Ex-ia) xxxx) Oil Immersed Apparatus - (Ex-o) (Ref :
IS : 7693) -
Apparatus in this category is
incapable of causing ignition in Electrical apparatus in which all parts
normal operation, or with a single on which are may occur in normal
fault, or with any combination of service are immersed in oil to a
two faults applied with a specified sufficient depth to prevent ignition of
safety factor for current and/or an explosive gas mixture that may be
voltage. present above the surface of the oil,
and all live parts on which areas do
b) Category (Ex-ib) not occur in normal service are either
immersed in oil or protected by some
Apparatus in this category is other recognised techniques.
incapable of causing ignition in
normal operation, or with any xxxxi) Non-sparking Apparatus (Ex-n) (Ref :
single fault applied, with a IS 8289) -
specified safety factor for current
and/or voltage. Apparatus which in normal operation
is not capable of igniting a surrounding
xxxvii) Flameproof Enclosure (Ex-d)-(Ref : IS explosive atmosphere, and in which a
: 2148) fault capable of causing ignition is not
likely to occur.
An enclosure for electrical apparatus
that will withstand, when the covers or xxxxii) Increased Safety (Ex-e) (Ref : IS :
other access doors are properly 6381)
secured, an internal explosion of the
flammable gas or vapour which may A method of protection in which
enter it or which may originate inside measures additional to those adopted
the enclosure, without suffering in ordinary industrial practice are
damage and without communicating applied, so as to give increased
the internal flammation to the external security against the possibility of
flammable gas or vapour for which it is excessive temperatures and the
designed, through any joints or occurrence of arcs or sparks in
structural openings in the enclosure. electrical apparatus which does not
produce arcs or sparks in normal
xxxviii) Pressurised Enclosure (Ex-p) (see IS : service.
7389 (part 1) -
xxxxiii) Special Protection ‘S’ -
An enclosure for electrical apparatus
in which the entry of flammable gas or A kind of protection which does not fall
vapour is prevented by maintaining into any of the recognised techniques,
the air (or other non-flammable gas) but which may be demonstrated to
within the enclosure at a pressure afford equivalent levels of protection to
above that of the external atmosphere. equipment intended for use in
classified hazardous areas. This is to
xxxix) Sand-filled apparatus (Ex-q) (Ref : IS : develop new ideas before standard
7724)- specifications are available.

Electrical apparatus which has all its The certificate will normally describe
live parts entirely embedded in a mass the techniques and conditions of use.
of powdery material, in such a way
that under the conditions of use for
which the apparatus has been 4.0 Power System Design
designed, no arc occurs within the
outer explosive atmosphere either by i) The design of electrical installation
the transmission of flame or by the shall ensure provision of a safe and
overheating of the walls of the reliable supply of electricity at all
enclosure. times. Safe conditions shall be
ensured under all operating conditions
including those associated with start-
up and shut down of plant, as well as - Normal loads
those arising out of failure of electrical (continuous/intermittent loads)
equipment. The isolation of a part of
system of electrical equipment due to - Essential loads (Emergency loads)
either maintenance or shutdown shall
not compromise safety. Power - Critical loads (e.g. computer, fire
distribution system shall constitute water pumps, communication,
sub-stations located near load centres instrumentation controls etc.)
as far as practical.
iii) Required redundancy (based on specific
ii) The design shall be broadly based process/operating needs) shall be built in
upon the following factors: the substation which feeds power supply
to the process units/important facilities so
- Safety to personnel and equipment that in case of tripping of one feeder, the
during operation and maintenance, unit/facility may not be adversely affected.

- Reliability of service, iv) The power system design shall ensure


system reliability. This assumes particular
- Ease of maintenance, significance where inplant generation
supplements the external power supply.
- Convenience of operation, For this, quick isolation of inplant system
from faulty grid, inplant load shedding etc.
- Maximum interchangeability of may need detailed consideration.
equipment,
v) Before carrying out system design, it is
- Elimination of fire risk, recommended that the following minimum
information/data be obtained, from the
- Facility for ready addition of future power supply authorities:
loads.
a) Incoming grid voltage and frequency,
- Suitability for applicable actual variation limits, guaranteed
environmental factors. power availability.

iii) Special attention is drawn to Chapter X b) Existing fault level of feeding bus and
of IE rules which includes requirements system expansion factor for fault level.
for design of electrical system as
applicable to oil mines. c) Location of feeding substation and
routing of supply lines/feeder and the
4.1 Capacity of Electrical Plant reliability of power supply.

d) Size of conductor and current carrying


i) All the components of the electrical capacity.
system shall be sized to suit the
maximum load, under the most severe e) Supply system neutral earthing.
operating conditions. The amount of
electrical power consumed by each f) Details of protection relays and their
process unit shall be calculated for its settings at sending end breaker side.
operation at the design capacity.
Accordingly, the maximum g) Required metering arrangements at
simultaneous consumption of power, receiving end.
required by continuously operating
loads shall be considered and vi) When capacitors are added to the system
additional margin shall be taken into for power factor improvement, necessary
account for intermittent service loads, if system study may be carried out to
any. decide measures for avoiding problems
due to hormonics, system resonance,
ii) While carrying out load analysis, loads oscillatory torques in rotating equipment,
shall be characterised under different in rush current, increase in voltage
heads as under: across capacitors due to use of series
reactor, harmonic loading of capacitor,
etc. The above assumes particular i) It is recommended that use of unearthed
significance where there is captive system may be avoided since arcing
generation. ground faults can result in severe over
voltages.
4.2 Neutral Earthing
ii) Where unavoidable (such as expansion
4.2.1 Earthed System projects where existing systems have
unearthed system) unearthed system shall
i) Power system neutral shall be earthed: have provision for detecting earth fault and
for isolation of faulty section through the
a) To limit the difference of electric potential use of core balance current transformers.
between all uninsulated conducting The current transformers (CTS) shall be
objects in a local area. sized in relation to the system capacitive
currents arising due to distributed
b) To provide for isolation of faulty equipment capacitance of the entire network. The
and circuits when a fault occurs. system shall also include alarm/tripping
provision using unbalance voltage sensing
c) To limit overvoltages appearing on the through open delta potential transformers
system under various conditions. (PTs) under earth fault conditions. Besides
it is recommended that provision of ‘on line
ii) The neutral earthing system employs one insulation monitoring facilities’ may be
of the following methods: considered.

a) Solid earthing for low, medium voltage 4.3 Short Circuit Capacities
system (upto 650V) and for high
voltage above 11 K.V. i) Each short-circuit interrupting device shall
have fault duty higher than the maximum
b) Resistance earthing for 3.3 KV to 11KV value of short circuit current calculated at
system. its location. The related switchgear and bus
ducts shall withstand the above maximum
iii) The values of neutral earthing resistors fault current (mechanical and thermal
normally applied in industrial power stresses) for a minimum duration of one
system are selected to meet the governing second.)
criteria for limiting transient over-voltages,
i.e. earth fault current should not be less ii) The sizing of high voltage cables shall be
than the system charging current. based on the short circuit withstand
Besides, the value of neutral earthing capacity for a minimum time period as
resistor selected shall limit the earth fault dictated by the protection system in
current to a value, which shall be sufficient addition to the maximum anticipated load
for selective and reliable operation of earth current carrying capacity.
fault protection system.
iii) It is to be noted that in the case of
However, where an earthing transformer is generators, whose excitation power is
used for obtaining the system neutral, the terminal dependent, short circuit in the
zero sequence reactance limit (i.e. RO > 2 system will result in drop of the terminal
X0) should also be considered. (R0 - zero voltage and consequently the over-current
sequence resistance of the circuit protective devices may not get adequate
including neutral resistor and X0 zero current for operation. To avoid such a
sequence inductive reactance of the situation, necessary excitation support shall
circuit). be provided unless & otherwise required.

iv) The neutral earthing resistor shall be able iv) While sizing, the system necessary
to carry at least 10% of its rated current consideration shall be given to restrict the
continuously, unless otherwise required, system voltage drop within permissible
and full rated current (100%) for a minimum limits during starting of large rated motor
duration of 10 seconds. or group of motors. At the same time, the
short circuit current shall be kept within
4.2.2 Unearthed System limits keeping in view of the market
availability of switchgears. Reduced
voltage starting (soft start feature) for
motors may be considered as per system
requirements. d. Bus differential shall be provided for all
H.T. switchgear having direct
4.4 Insulation coordination connection with the inplant generators
and other vital H.T. switchgear.
i) The insulation of electrical facilities shall
be designed considering the system iii) Longitudinal differential protection shall be
voltage, the system neutral earthing, and provided for important plant feeders in
the over-voltages resulting due to system general, and plant feeders connected to a
fault, switching or lightning surges. The captive power plant bus in particular.
insulation co-ordination between the Wherever the system is resistance
electrical equipment and the protective earthed, restricted earth fault protection
devices shall be done in line with IS: 3716 may be provided for transformer
and IS: 2165. secondary.

ii) Insulation coordination is a correlation of iv) Particular care should be taken in the
insulation of equipment and circuit with the selection of protective devices for
characteristic of protective devices such machines and equipment operating in
that the insulation is protected from over hazardous areas, so as to isolate the
voltages. faulty section in the shortest time possible.
For high voltage system, protective relays
iii) The rated insulation level of Switchgears shall be used. For medium voltage
shall refer to the power frequency systems, direct acting releases and/or
withstand voltage and impulse voltage protective relays may be employed.
withstand values which characterise the
insulation. In respect of systems with In general, quick acting relays (with time
nominal voltage of 132 KV and above, full delays if necessary) shall be used and all
insulation values shall be considered for fault tripping shall be done through high
non-effectively earthed system, and speed tripping relays.
reduced insulation values may be used for
effectively earthed system. v) The supply of Energy to every electrical
installation other than low voltage
4.5 Protection and Metering installations below 5 KW and those low
voltage installations which do not attract
i) The protective system shall be selected provisions of Section 30 of the Indian
and coordinated to ensure the following: Electricity Act, 1910, shall be controlled by
an earth leakage protective device so as
a. Protection of equipment against damage to disconnect the supply instantly on the
which can occur due to internal or occurrence of earth fault or leakage of
external short circuits, overloading, current (IE Rule 61A).
abnormal operating conditions,
switching, lightning surges, etc. Provided that the above shall not apply to
overhead supply lines having protective
b. The continuity of operation of those devices which are effectively bonded to
parts of the system not affected by the the neutral of supply transformers and
fault, is maintained. conforming to Rule 91 of I.E. Rules, 1956.

c. Personnel and plant safety. vi) Metering instruments shall be provided on


plant Main Switch Board to monitor the
ii) Accordingly, relays and protective devices power consumption and supervision of all
shall be suitably selected and coordinated. concerned parameters like current,
As a minimum, differential protection shall voltage, power, frequency, power factor
be provided for the following: etc. Ammeters in the field for monitoring
motor current may be provided as per
a. Transformers rated 5 MVA and above, process requirements. Metering and
protection current transformers shall be
b. Induction and synchronous motors preferably kept separate. In the case of
rated 1500 KW and above, contactor controlled feeders having long
length of control cables (more than 800
c. Generators rated 2 MVA and above. Mts. or so) due consideration shall be
given to the effect of capacitance on vii) Recommended relay protections for
ON/OFF operations of contactor. Transformers, motors and feeders which
are generally encountered in distributing
network are given below :
---------------------------------------------------------------------------------------------------------------------------------
RELAY TRANSFORMER MOTOR OUTGOING INCOMER
REF :ANSI/IEEE POWER DIST HV HV MVPCCC HV MVPCC
(IEEC 37.2)
--------------------------------------------------------------------------------------------------------------------------------
A. 51 IDMTL O.C. YES YES - YES YES YES YES
(4) (4)

B. 51(N) IDMTL E.F. YES NO - YES YES YES YES


(7) 4) (4)

C. 5IN BACK UP E.F. YES YES - NO NO NO NO


(SECONDARY SIDE
NEUTRAL)

D. MOTOR PROTECTION NO NO YES NO NO NO NO


RELAY WITH LOCKED
ROTOR FEATURE
(50, 51, 50N, 46, 49, 50L/R)

E. 50N INST REST EF YES NO - NO NO NO NO


(SECONDARY SIDE)

F. 50 INST.O.C YES YES - NO NO NO NO

G. 50N INST.EF (R) YES YES - NO NO NO NO


(6)

H. 87 DIFF.PROT. YES NO YES YES NO NO NO


(1) (2) (3)

I. 86 TRIPPING RELAY YES YES YES YES YES YES YES

J. 95 TRIP CKT SUP. YES YES YES YES NO YES NO

K. 63TX AUX RLYTRAFO YES YES - NO NO NO NO

L. 27,2 UNDERVOLTAGE - - YES - - YES YES


WITH TIMER (5) (5)
--------------------------------------------------------------------------------------------------------------------------------

(1) For transformers rated 5 MVA and above


(2) For motors rated 1500 KW and above
(3) For critical/long feeders.
(4) These relay functions can be substituted by inherent releases.
(5) Wherever Autotransfer feature is provided.
(6) Provide INST E/F 50N for transformers with primary delta.
(7) Provide IDMTL E/F 51N for transformer with primary star
viii) Medium Voltage Motor Protection: ii) Overall generator unit transformer
differential protection.
The minimum protection requirement shall
include fuses and thermal overload relay - In installations where generator is
suitably co-ordinated with contactor operating in parallel with the grid,
characteristics as per applicable Indian special protection such as out of
Standards (BIS). However M.V. Motors step relay may be required.
controlled by circuit breakers may have
either releases or relay for Motor - It is recommended that
Protection. synchorising check relay for bus
coupler may be provided on those
- Large MV Motors which are contactor switchboards having grid as well as
fed (90 KW and above) may have core in plant supply with manual transfer
balance earth fault protection in addition & momentary paralleling feature.
to bimetal and fuse combination or
composite motor protection relay. In addition to electrical protection
relays, rotating machines may also
- Bimetal relays shall be preferably with require tripping/alarm for excessive
inherent protection against single vibration, high winding temperature and
phasing. high bearing temperature.

ix) Generator Protection : x) Capacitor Protection

The Protecting generally used for The protective requirements of capacitors


generators are as under. However the provided for power factor correction will
actual protective requirements will vary vary depending upon the rating and the
from case to case, depending upon the system configuration.
rating, excitation system, operation, type
of prime mover etc. The recommended protections include:

- Differential protection (87 G) i) IDMTL over-current with high set


element for protection against short
- Stator earth fault (51 N) circuits.

- Rotor earth fault (61) ii) Instantaneous earth fault

- Voltage controlled overcurrent (51V) iii) Neutral phase displacement

- Reverse power (32) iv) Under voltage

- Field failure (40) v) Over voltage

- Unbalanced loading protection (46) vi) Each element of basic capacitor unit
may have its own built in fuse, which
(Negative sequence current protection) shall isolate the faulty capacitor.

- Stator winding temperature protection The capacitor bank feeders shall generally
(49 T) be tripped on bus under/over voltage
conditions and necessary interlock shall
- Under frequency protection (81) be provided for re-switching to take care of
capacitor residual voltage.
When generator with unit transformers
is employed besides individual M.V capacitors of smaller ratings may be
equipment protection, the following controlled with switch fuse units.
additional protections are
recommended: The continuous current rating of fuses and
switching devices for capacitors should be
i) Transformer over fluxing protection 30% higher than the normal full load
current.
i) These systems shall have inherent
4.6 Emergency Power Supply independent battery backup to maintain
continuity of supply to critical loads (e.g.
i) This is an independent back-up source of process control, communication, fire alarm
electric energy that upon failure or outage systems etc.) in the event of
of normal source, automatically provides normal/emergency supply failure.
reliable electric power within specified time
to critical devices and equipment whose 4.7.1 Un-interrupted Power Supply (UPS)
failure to operate satisfactorily may
jeopardise the health and safety of i) An un-interrupted power supply shall be
personnel or result in damage to property. provided, as required for meeting critical
loads that cannot withstand a momentary
ii) The emergency power supply system shall interruption/other A.C. mains disturbance
feed the following loads to enable in supply voltage. A separate battery shall
continuity of supply in the event of failure be provided for UPS system.
of MAIN SUPPLY.
ii) Following loads shall be connected to the
- Electrical loads essential for the UPS system:
safe shutdown of the plant.
- Critical instrumentation and process
- Emergency lighting, security control,
lighting, obstruction lights.
- Critical communication equipment,
- Process plant instruments as
required - Microprocessor based distributed
digital control system.
- Communication equipment, Fire
Alarm control panels. UPS system shall be fed from the
emergency system, wherever provided.
- D.C. Supply system, UPS system
iii) In case of total power failure, un-
- Auxiliaries of emergency set as interrupted power supply shall be available
applicable for at least 30 minutes or as determined
by the process considerations.
- Fire fighting equipment excluding
main fire water pumps iv) Each branch circuit of the UPS distribution
system shall have a fused disconnect
- Essential ventilation loads, and switch. The fuse shall be fast clearing type
and the fuse rating shall be coordinated
- Loads critical for process, plant and with the rating of the UPS system.
personnel safety.
4.7.2 DC Power Supply
iii) Emergency power supply shall be
available as per process/equipment i) Unless otherwise specified, independent
requirements, but within a period not DC power supply systems shall be
exceeding 30 seconds from the instant of provided for the following:
failure of normal supply.
- Plant shut-down system and DC
iv) Unless otherwise required, the emergency instrumentation.
generator in general may not run
continuously in parallel with the normal - Electrical switchgear controls and
power supply system. However, to critical (escape) lighting, critical
facilitate periodic testing and maintenance D.C. drives viz. LUBE OIL PUMPS
it is preferable to include synchronising etc.
facilities for short time parallel operation of
D.G. set unless objected to by electrical ii) Each DC power supply system shall
supply authorities. include charger-cum-rectifier, battery and
DC distribution board. DC link in the UPS
4.7 Critical Power Supply Systems system shall generally not be tapped for
DC instrumentation power supply except
in rare circumstances. ii) Following factors shall be considered for
proper selection of electrical apparatus
iii) Fire alarm system shall have a dedicated and equipment for areas where
24 V DC battery backup system. flammable gas or vapour risks may arise:

iv) It is recommended that D.C. supply for a) Area classification, i.e. Zone 0, 1 or 2
electrical controls, instrumentation, UPS
etc. shall have separate independent b) Gas group classification, i.e. the gas
battery banks. group.

4.7.3 Battery Sizing c) Temperature classification

i) Electrical Switchgear and Controls d) Environmental conditions in which


apparatus is to be installed.
Battery shall normally be sized for a load
cycle having a minimum duration of one Where practicable, electrical
hour. While deciding the load cycle, apparatus in general and switch and
consideration shall be given on specific control apparatus in particular shall
operating/safety requirements of plant & be installed in safe area. Substation
equipment e.g. lube oil pump of STG for and control room shall be located in
bearing oil flushing. The duration for safe area. While deciding the route of
battery sizing hence shall vary accordingly overhead power lines, necessary
as per specific operational requirements. considerations shall be given to avoid
overhead lines passing through
ii) DC Instrumentation Shutdown System hazardous areas.

This shall in general be sized for 30 Electrical equipment intended for


minutes, unless otherwise required. service in hazardous area shall be
selected in accordance with IS : 5571
iii) Fire Alarm System and these shall be approved by
recognised testing and certifying
The battery shall be sized for the authorities i.e. CCE or DGMS or
duration and load in line with the DGFASLI as applicable.
guidelines given in IS 2189.
For details on hazardous area
iv) EPABX (Telephone System) classification, enclosure protection
etc. OISD standard 113, NEC 1985,
This will have an independent battery IS 5571, 5572, IS 13408 Petroleum
back up system. Rules and Oil Mines Regulations
shall be referred.
4.7.4 Annunciation
iii) General guidelines for type of protection
Sensitive earth fault detectors shall be for electrical equipment in hazardous
provided in D.C. system to annunciate areas are enumerated in Table-I.
earth faults.
TABLE-I
5.0 Electrical Equipment for Classified TYPES OF PROTECTION
Areas -----------------------------------------------------------
Area Description Symbol
i) All the areas within the Battery limits shall Classif-
be classified for degree and extent of ication
hazard from flammable materials. The -----------------------------------------------------------
basis for hazardous area classification Zone 0
recognises the differing degrees of - Intrinsic safety category ‘ia’ ‘ia’
probability with which flammable
atmosphere may arise in the installation, Other electrical apparatus, ‘s’
in terms of the frequency of occurrence specifically designed for
and the probable duration of existence on Zone 0. (See Note 1)
each occasion.
Zone 1 Note 4 Oil-immersed apparatus may be used
- Any type of protection only in case its security will not be
adequate for Zone 0. impaired by tilting or vibration of the
apparatus.
- Flame proof enclosure ‘d’
Note 5 Name plate details of equipment
- Instrinsic safety category ‘ib ‘ib’ intended for use in hazardous area
shall include relevant marking of
- Pressurisation (See Table II) ‘p’ hazardous protection as per
applicable IS codes.
- Sand filling ‘q’
Note 6 Flameproof enclosures are covered
- Other electrical apparatus ‘s’ under compulsory certification.
specifically designed for Zone 1
TABLE-II
Zone 2 MINIMUM ACTIONS ON FAILURE
- Any type of protection ade- OF PROTECTIVE GAS FOR TYPE
quate for Zone 0 or Zone 1 OF PROTECTION ‘P’
-----------------------------------------------
- Increased safety (See Note 2) ‘e’ Area Classification Enclosure s Enclosure
does not contain
contain ignition-
- Non-sparking apparatus ignition- capable
(See Note 2) ‘n’ capable apparatus
apparatus
- Pressurisation (See table II) ‘p’ -----------------------------------------------------------
Zone 1 Alarm Alarm
- Oil Immersion (see note 4) ‘o’ and
switch off
Note 1 It may be noted that as per petroleum
rules the use of intrinsically safe Zone 2 No action Alarm
electricity apparatus in zone ‘0’ area is required
permitted only when the use of such -----------------------------------------------------------
apparatus cannot be completely 6.0 SUBSTATION LOCATION / LAYOUT
excluded, whereas the Oil Mines
regulations prohibit use of any The sub-station shall be located in a safe
electrical equipment in zone ‘0’ areas. area. Consideration shall be given to
cooling tower sprays, vapours
Note 2 The apparatus with type of protection contributing to insulation break down,
‘e’ and type of protection ‘n’ when vehicular traffic accessibility for
installed outdoors shall have installation of equipment or any other
enclosures providing at least the IS factor that might affect the safe
4691/2147. operation of the sub-station. (Refer
also OISD Standard 118 ‘Layout for
a. IP 55 where there are uninsulated Oil and Gas Installations’)
conducting parts internally, and
i) In large plants, the main sub-station floor
b. IP 44 for insulated parts. shall be raised above grade level and the
space below the sub-station floor shall be
Note 3 Presently there are apprehensions on utilised for installation of cable trays. The
the suitability of use of high voltage substation cellar shall have preferably a
Type ‘e’ and Type ‘n’ motors in Zone-2 clear height of 2 meters. The switchgear
areas. Since the research work is still rooms shall preferably be pressurised to
inconclusive, the existing standards prevent ingress of dust. Large substation
for Ex ‘e’ and Ex ‘n’ motors have not shall have three entries, one for
been revised. Advice of the concerned equipment entry, second for normal entry
statutory authority should be sought and the third emergency exit. Where as
while selecting Ex ‘e’ or Ex ‘n’ high required normal and equipment entries
voltage motors in Zone-2 areas. can be combined.
Pressurised sub station shall have station in a safe area to reduce noise level
necessary Airlock lobby for the normal in substation. If required DG set of smaller
entry. rating may be located in substation
building provided the substation is located
Small and medium size substations shall in a safe area. However in such cases, the
have one equipment cum normal entry foundation of such D.G. sets shall be
and the second for emergency exit. structurally delinked from the slab or floor
Emergency exit door in substation shall of the rest of the substation building.
open outwards. The main entry for Exhaust of Diesel Engine shall be kept
operating personnel shall be preferably away from Process/Hydrocarbon area.
provided with double door system.
Operator cabin may be separately located vii) Transformer yard/bay shall be provided
to avoid repeated opening of doors and with fencing and gate and shall have fire
dust entry to substation. Pressurised isolation walls for individual transformers.
substation building shall have fixed glazing Oil immersed equipment involving use of
with minimum number of openable large quantity of oil shall have oil soak pit
windows. All openings shall be kept and drain arrangement as per Indian
properly closed to maintain sufficient Electricity Rules and regulations. *Fire
pressure inside to prevent dust entry. fighting equipment, first-aid boxes, etc.
shall also be provided as required.
ii) Non pressurised remote switch (Further guidelines on this can be had
room/offsite substation shall have fixed from OISD standard 116 - ‘Fire Protection
glazing with suitable exhaust fans with facilities for Petroleum Refineries and
louvers to meet the ventilation Oil/Gas Processing Plants’ and OISD
requirements. Proper maintenance and standard 117 ‘Fire Protection Facilities for
care shall be taken to keep the room free Petroleum Depots and Terminals.)
from dust.
viii) The substation equipment layout and the
iii) The building shall sized to take care of clearances between different equipment
present/future needs and to maintain shall be planned to ensure ease of
adequate clearances between equipment, operation and maintenance and meet all
and equipment and wall for ease of requirements from the point of view of
operation and maintenance. Small sub- safety of the operating personnel.
stations shall suitably elevated by
compacting the soil so that the bottom of ix) Clearance between various equipment
the cable trench within substation is above shall also satisfy respective equipment
the surrounding grade level. manufacturer’s requirements and Indian
Electricity Rules. Where these are not
iv) Normally transformers, reactors, neutral specified the following minimum
earthing resistors etc. shall be installed clearances are recommended as general
outdoor. Equipment like UPS system and guidelines.
frequency stablisers shall be installed in a
separate air-conditioned room. The battery a) At the rear of H.V.
banks shall be located in a separate, Swbd : 1500mm
freely ventilated room in the sub-station
building alongwith the necessary exhaust b) At the front HV
system and water connection. Floor of the Swbd : 2000mm
battery room and the walls upto height of
one metre shall have acid resisting c) At the side of
material/coating/be painted with acid/alkali various boards
resistive paint or otherwise protected. from wall 1000mm

v) Necessary space to keep equipment d) At the front


under repair such as breakers, switch of various boards 1500mm
control gear items, spares/consumables between front to -2000 mm
like fuses etc. shall also be identified in front of two boards
building layout. (say DRAWOUT
MCCS) facing
vi) It may be preferable to locate DG sets in a each other.
separate house/shed away from Sub
e) At the rear of MV 1000mm and conditions on which the design of the
Switchboards electrical installation is based and shall in
requiring rear access particular, fulfil the requirements given in
Clause i) to vii) below.
f) Rear clearance in
other cases More than I) Voltage
750mm
otherwise Electrical equipment shall be suitable
less than with respect to the maximum steady
200mm. voltage (rms value for AC) likely to be
applied, as well as overvoltages likely to
g) Transformers with occur.
wall on one side As per IS
Tansformers with 100028 Note: For certain equipment, it may be
wall on three sides. necessary to take account of the lowest
voltage likely to occur.
h) Clear height of
busduct 2000mm Considerations shall also be given to the
from finished protective measures inherent in the
floor level systems and the method of neutral
earthing viz. earthed or unearthed
I) Clear space betw- system.
een Switch Board 1000mm
top and beam soffit ii) Current

(Note : The maximum length of switchgear All electrical equipment shall be selected
lineup may preferably be limited with respect to the maximum steady state
to 15-20 metres considering current (rms value for AC) which it has to
operation and maintenance carry in normal service, and with respect
requirements. to the currents (prospective, short circuit
currents) likely to be carried under
x) It is recommended that battery room, abnormal conditions and the period (for
UPS room, charger room, operator’s example, operating time of protective
room of large sub stations, located close devices, if any) during which it may be
to process units should have blast proof expected to flow.
walls. This is to protect vital control power
sources from any external damage, thus iii) Frequency
ensuring availability of control power for
safe shutdown in disastrous conditions Electrical equipment shall be suitable for
suitable for indoor use. continuous operation with respect to the
system rated frequency with variation
7.0 ELECTRICAL EQUIPMENT limits likely to occur.

Electrical equipment shall be selected, iv) Power


sized and installed so as to ensure
adequacy of performance, safety and All electrical equipment to be selected on
reliability. The equipment in general the basis of their power characteristics
shall conform to relevant Indian shall be suitable for the duty demanded
Standards and shall be suitable for from the equipment, taking into account
installation and satisfactory operation in the load factor and the service conditions.
the service conditions envisaged. Each equipment shall be able to deliver its
Specific attention is drawn to IS:9676 rated power for specified supply and site
for deciding the design ambient conditions with temperature rise remaining
temperature of electrical equipment. well within the design limits as per
applicable IS codes.
7.1 CHARACTERISTICS
v) System earthing
Every item of electrical equipment
selected shall have suitable All electrical equipment shall be selected
characteristics appropriate to the values considering the system neutral earthing
particularly in high voltage systems where
resistance earthing is commonly All unpainted steel parts shall be
employed. cadmium plated or suitably treated to
prevent rust corrosion.
vi) Conditions of Installation
If these parts are moving elements,
a) All the electrical equipment selected then these shall be greased.
shall have proper protection against
corrosive and solvent agents, water vii) Prevention of Harmful effects
ingress, thermal and mechanical
stresses as determined by the a) All electrical equipment shall be
environmental factors. If, however, an selected so that it will not cause
item of equipment does not have by harmful effects on other equipment or
design, the properties corresponding impair the supply during normal
to its location, it may be used on service including switchgear
condition that adequate additional operations. In this context, the factors
protection is provided as part of the which may have an influence include:
completed electrical installation. In
addition to the above, noise level and * Power factor
cooling/ventilation shall also be
considered. * Inrush current

PAINTING * Asymmentrical load

a) Rotating Machinery * Harmonics

Internal and external parts of the * transient voltage


casing and all metal parts likely to dips/overshoots.
come in contact with the surrounding
air shall be protected with anti- b) Energised parts shall be sufficiently
acid/anti alkali epoxy paint that will enclosed or isolated so as not to
resist corrosion under the particular expose personnel to explosion, fire,
atmospheric conditions. arcing, or shock hazards. Adequate
safety features shall be incorporated
b) Switchgear panels and in equipment design for the safety of
service boards operating personnel.

All metal surfaces shall be thoroughly 7.2 EQUIPMENTS FEATURES


cleaned and degreased to move mill
scale, rust, grease and dirt. Fabricated Certain essential safety features in
structures shall be pickled and then design to be considered in specifying
rinsed to remove any trace of acid. and sizing of commonly encountered
The under surface shall be prepared equipment such as Transformer,
by applying a coat of phosphate paint, Switchgear, Motors, Cables, Battery
and a coat of yellow zinc chromate charger Battery, and U.P.S. etc. are
promer. The under surface shall be enumerated below.
made free from all imperfections
before undertaking the finishing coat. 7.2.1 Transformers

After preparation of the under surface, i) The KVA rating shall depend upon the
the switchboard shall be spray painted maximum simultaneous continuous load
with two coats of final paint. Colour and probable system expansion loads. In
shade of final paint shall generally be general, the rating and the percentage
light admiralty grey shade No. 631 as impedance of each transformer shall be
per IS:5, unless otherwise required. selected to limit the continuous current
The finished panels shall be dried in rating and short circuit current to values
stovings ovens in dust-free within the ratings of available switchgear.
atmosphere. Panel finish shall be free The transformer impedances shall
from imperfections like pinholes, generally be as per Indian standards
orange peels, runoff paint, etc. unless otherwise required. The rating and
the percentage impedance of transformer
shall be compatible to permit start of v) The drawout carriage on the switchboard
highest rated motor while the transformer shall have three positions viz., ‘Service’,
is preloaded with maximum operating ‘Test’ and ‘drawn out’. Automatic safety
base load. shutters shall be provided to ensure the
inaccessibility of all live parts after the
ii) Transformers connected to Grid supply breaker is drawn out. It shall not be
may have ON LOAD TAP CHANGERS for possible to drawout the carriage or rack it
inplant control of secondary voltage. Plant in with circuit breaker closed. The
distribution transformers may have OFF breaker/contractor feeder trolley shall
CIRCUIT TAP changers. remain inside the cubicle even in the test
position. There shall be distinct overall
iii) In addition to standard accessories, the door for the breaker compartment and it
transformer shall be provided with should be lockable. All circuit breaker
auxiliary devices/protective devices such trucks of the same rating shall be
as Buchholz relay, oil level and oil temp. interchangeable.
indicator with alarm trip output contacts
and current transformers for the vi) Suitable interlocks shall be provided to
secondary side neutral for Protection. prevent faulty operation such as:
Transformers of rating above 2000 KVA
may be preferably have winding - ‘Pluging in’ or ‘drawing out’ of a closed
temperature indicators with Alarm/Trip breaker.
provisions.
- ‘Pluging in’ a breaker with earthing
7.2.2 High Voltage (H.V)/Medium Voltage isolator closed.
(M.V) Switchboards
- ‘Closing’ of earthing isolator with the
i) These shall be designed to ensure breaker ‘Plugged in’.
maximum safety during operation,
inspection, connection of cables and - Pulling out of auxiliary circuit plug with
maintenance with Switchboards breaker in service position.
energised.
- Pushing in breaker to service position
ii) The switchboard shall be totally enclosed, with auxiliary circuit plug not in
dust and vermin proof. position.

iii) Each unit of the switchgear shall have - Opening of compartment door with
necessary internal sheet metal barrier to isolating switch in ON position and
form separate compartments for buses vice-versa for Motor Control Centres.
instruments/relays/cable connections etc.
Compartment for cable connection shall The maximum height of operating
allow cable pulling, termination and handle/switches shall not exceed 1800
connection work with switchgear mm and the minimum height not
energised. Suitable arc propagation below 300 mm.
barriers shall also be provided.
Independent pressure release flaps shall - It shall not be possible to operate the
preferably be provided for each different circuit-breaker unless it is fully in
compartment of H.V. Switchboards. service or Test or isolated position.
Terminal strip for outgoing control cable
connections should be accessible to vii) Suitable eye bolts for lifting of panels
facilitate working and testing with breaker shall be provided. On removing the eye
in test/service condition and while the bolts, no holes offering access to panel
switchboard is energised. shall be permitted.

iv) Barriers shall be provided to permit viii) Different sections, viz. busbar,
personnel to work safely within an empty switchgear, cable, relays and meters etc.
compartment with the bus bars energised. shall be compartmentalised. Busbars and
The minimum clearance and creepage supports shall withstand specified short
distance of bus bars shall conform to IS circuit level without permanent
4237. deformation. Busbars shall be preferably
sleeved and joints shall be motors of rating above 160 kw shall be
taped/shrouded. Minimum clearances rated for high voltage. If required, the rating
between live parts, between live parts to of medium voltage motors may be
Earth and Neutral shall conform to extended upto and including 200 KW.
applicable IS code (IS 4237) Sleeve or anti friction type bearings shall be
Switchboards shall have additional safety used. Vertical motors shall have thrust
features such as falling tool shrouds for bearings suitable for the load imposed by
trapping of free fall of maintenance tools the driven machinery. Unless otherwise
on live parts. Busbar supports shall be of specified, all motors shall be designed for
synthetic material with high tracking ‘Direct ON line’ starting.
index. The switchboard shall have earth
busbar of adequate size. The switchgear iii) High voltage motors shall be suitable for
drawout trolley (in case of drawout starting under specified load conditions with
design) shall have suitable scraping earth 80% of the rated voltage at the terminals
connection. Feeder tag plates shall be and medium voltage motors shall be
provided at both front and rear side of suitable for starting under specified load
panels. Where required, busbar routing conditions with 75% of the rated voltage at
shall be clearly marked on the back side the terminals.
of the H.V. Switch board panels for easy
identification during maintenance. iv) The permissible noise level shall not
exceed the stipulations laid down in IEC
ix) All non-current carry metallic parts of 34-9.
mounted equipment/components shall be
bonded to the earth bus. v) Motor vibrations shall be within the limits of
IS-4729 unless otherwise specified for the
x) Surge absorbers to limit the switching driven equipment. Motors with sleeve
surges shall be provided as dictated by bearings may require proximity probes to
the type of arc quenching media and measure shaft vibration adjacent & relative
switching device. to the bearings.

xi) Starting of motors from substation shall i) Motors shall be required for continuous,
not be allowed and switch boards shall satisfactory operation at rated output under
not have close push button at the following conditions :
switchboard for motor starting.
a) The terminal voltage differing from its
xii) In specific cases, motors requiring rated value by not more than ± 6%.
frequent start/stop, (e.g. product, loading
pumps etc.) shall be controlled by b) The frequency differing from its rated
contractor feeder appropriate to its rating. value by not more than ± 3%

xiii) Switch Boards shall have anti c) Any combination of (a) and (b).
condensation heaters.
vii) Motor ratings and torque characteristics
7.2.3 MOTORS HIGH VOLTAGE (H.V.) shall be adequate to accelerate the load
& MEDIUM VOLTAGE (M.V) from zero to rated speed under starting
requirements as stipulated by process
7.2.3.1 General operating conditions. Normally, the
starting time shall be less than the hot
(1) Motors shall be totally enclosed, withstand time of the motor.
fan cooled type as far as
practicable. As a minimum, all viii) M.V. Motors in general and H.V. Motors
H.V. motors shall have anti where required shall be suitable for
condensation heaters. The restarting under full load after a
minimum degree of enclosure momentary loss of voltage with the
protection for motor shall be possibility of application of 100 percent of
preferably IP 44 for indoor use the rated voltage, when the residual
and IP 55 for outdoor duty motors. voltage has dropped down to 50 percent
and is in phase opposition to the applied
ii) Generally Motors upto and including 160 voltage.
KW shall be rated for medium voltage and
ix) Motor bearings shall be selected to give a and manufacturer shall provide detailed
minimum L-10 life rating of 5 years drawing showing insulation arrangement.
(40,000 hours) at rated operating condition
(the L-10 rating life is the number of hours vii) Motors shall be designed to withstand
at constant speed that 90% of a group of impulse voltage of at least (4Un+5) KV with
identical bearings will complete or exceed a wave front raise time of 1.2 microsecond
before the first evidence of failure). The and decay time of 50 microsecond to half
bearings shall be adequate to absorb axial the peak voltage.
thrust in either direction produced by the
motor itself or due to shaft expansion. On viii)The interturn insulation of H.V. motors shall
line greasing facility should be provided on be able to withstand a peak voltage of at
motor for all grease lubricated bearings least 0.5 (4Un+5) KV with a wave front rise
(anti friction bearings). Wherever time between 0.5 & 1.5 microsecond and a
spaceheaters are provided for motors, a decay time to half the peak voltage of
separate terminal box should be provided between 3 & 10 (microsecond).
for termination of spaceheater cables, as Un = rated line to line voltage.
far as practicable.
ix) Polarisation index
7.2.3.2 H. V. Motors
Polarisation index of H.V. stator winding
i) Winding insulation shall be class F and shall have a value of at least 2. If the
temperature rise limited to that specified in insulation value of the motor exceeds a
the applicable IS for class B insulation. value of 120 (Un+1) (where Un is rated line
- line voltage (KV) mega ohm, a minimum
ii) Motors shall be designed to allow minimum polarisation index of 1.5 is acceptable.
number of consecutive hot starts as
dictated by process operating 7.2.3.3 M. V. Motors
requirements. Number of uniformly spaced
startups in an hour shall be a minimum of i) Motors shall be designed to allow three
three. consecutive starts from cold condition, two
consecutive starts from hot condition and
iii) The main power Terminal Box shall be four uniformly distributed starts in one hour.
phase segregated and suitable to withstand
the specified fault level for a minimum ii) Motors shall be provided with minimum
duration of 0.2 sec. (Commensurate with class ‘B’ insulation or class ‘F’ insulation
instantaneous short circuit protection). may be considered for special applications
Winding ends shall be preferably brought and permissible temperature rise above the
out and star point made in a separate specified ambient temperature shall be
terminal box. Neutral terminal box shall limited to the values applicable for class ‘B’
have necessary space provision to mount insulation. The windings shall be
differential CTs for motors of rating 1500 tropicalised and adequately braced. The
KW & above. ends of the windings shall be brought out in
a terminal box with six terminals with
iv) Motors of rating above 1000 kw shall be suitable links to connect them in Delta.
provided with RTDs, BTDs. Separate However, motors rated upto 2.2 KW may
terminal boxes shall be provided for space be connected in star with three terminals.
heater and RTDs, BTDs.
iii) The terminal box of motor controlled by air
v) Induced voltage at the shaft of the motor circuit breaker shall be capable of
having uninsulated bearing system shall withstanding the full internal short circuit
not exceed 250 mV r.m.s. for roller and ball conditions, with the specified system fault
bearings and 400 mV r.m.s. for sleeve level for a minimum duration of 0.2 second
bearings with the motor running at no load. (Commensurate with instantaneous short
Alternatively, the non driving end bearing circuit protection). Where motor control is
shall be insulated from the motor frame to through contactor and MCCB, or back up
avoid circulating current. fuse, the terminal box shall be able to
withstand the let-through energy of
vi) The insulated bearing end shield or protective devices corresponding to
pedestal shall bear a prominent warning maximum system fault level.
iv) The terminal box shall be of sturdy ii) While sizing the battery following factors
construction and large enough to facilitate shall be taken in to consideration, in
easy connection of required number of addition to envisaged duty cycle :
cable runs and size. (specifically Aluminium
Conductor Cables). Additional trifurcating - Temperature correction factor.
boxes may be considered for motors - Ageing factor as applicable.
requiring termination of two or more parallel
runs of power cables. 7.2.6 Equipment for Uninterrupted
Power Supply System
7.2.4 Battery Charger and D.C.
Distribution Board i) This shall be of free-standing, floor
mounted, metal enclosed and vermin proof
Charger and D.B. shall be floor mounted, type having hinged door for front access
free standing, metal enclosed and vermin and suitable for indoor use.
proof type having front access hinged door
and suitable for indoor use. ii) Under normal conditions, the rectifier-cum-
charger shall feed the inverter and charge
This shall consist of battery the battery set. In case of mains failure, the
charger/rectifier, which shall feed the load battery shall supply the necessary power to
and keep the batteries under fully charged the inverter. The inverter in turn feeds the
condition. Provision shall also be made for load through the static switch. If the inverter
necessary boost charging/initial charging of malfunctions or is overloaded, the load
battery. shall be instantaneously transferred to the
by-pass line through the static switch.
7.2.5 Batteries and Battery Accessories Normally the inverter shall be operated in
synchronised mode with the by-pass line,
i) This shall be indoor stationary type (lead and manual forward transfer or manual
acid/Ni-Cd etc.) with adequate capacity to reverse transfer shall be effected without
meet the backup requirements as any break.
envisaged in the duty cycle. Accessories
shall generally be as follows : Automatic forward transfer, in case of
inverter malfunction, shall be effected with
- Battery stand made of treated first a break not exceeding 5 ms.
class teakwood assembled without the
use of any metal fastenings. 7.2.7 Capacitor Banks

- Intercell, inter ro and inter bank i) The capacitor shall conform to IS 2834
connectors and end take offs.
- specifications for shunt capacitor for power
- Porcelain cell insulators, stand system.
insulators.
ii) H. V. capacitor shall comprise appropriate
- Hydrometers suitable for specific nos. of basic single phase units (minimum
gravity readings. 4 nos. basic units in parallel per phase)
which shall be connected in star formation.
- Cell number plates and fixing pins as
required. iii) Capacitor banks shall be with necessary

- Thermometer with specific gravity 7.2.7 Capacitor Banks


correction scale Nos.
i) The capacitor shall conform to IS 2834 -
- Cell testing voltmeter (3V-0-3V) specifications for shunt capacitor for power
complete with leads 1 Metre. system.

- Rubber gloves ii) H. V. capacitor shall comprise appropriate


- Rubber aprons nos. of basic single phase units (minimum
- Spanner Set. 4 nos. basic units in parallel per phase)
which shall be connected in star formation.
iii) Capacitor banks shall be with necessary shall be adequate to make three attempts
discharge resistors to reduce the terminal with an interval of 5 to 10 seconds, if
voltage of each unit to a value equal to or required. In case the engine fails to start
less than 50V in 5 minutes. ‘FAIL TO START’ annunciation shall be
provided in substation or in control room.
iv) Steel rack assembly suitable for outdoor
installations (where outdoor location is v) The generator set shall be provided with
required) to accommodate the basic complete protection against overloads,
capacitor units with necessary post short circuits, ground faults, excitation
insulators. Panel assembly (where indoor failure, prime mover failure and shall
location is required) to accommodate the include other connected instrumentation
basic capacitor units, interconnecting interlocks.
busbars, insulators etc. The panel shall
have minimum IP-51 protection and shall vi) The load shall be switched on to the
be constructed with sheet steel of minimum generator only after the requisite voltage
thickness 2.0 mm. build-up.

v) Necessary series reactor to limit in rush vii) Diesel Engine installation, do not call for
current and suppress harmonics (where Area Classification, provided the D.G. room
required) is properly ventilated. Normally the
ventilation provided to remove heat from
vi) The impregnant in the capacitors shall be the radiator is adequate to take care of
non-toxic. hazard aspect.

7.2.8 Emergency Generator 7.2.9 Cables

i) The emergency generating sets shall form i) In order to avoid spread of fire due to
a complete package and shall be designed cables, it is recommended that the outer
to start automatically on power failure and PVC sheath of all cables used in industry
feed the selected loads. It shall be capable shall be flame retardant type conforming to
of taking care of the load variations (e.g. category AF as per IS: 10810. The cable
the starting of largest rated motors on a shall have a low smoke property. The
preloaded system). The unit shall be minimum Oxygen Index shall be 29 Note 3.
complete with necessary starting
equipment, associated control panel and ii) High voltage cables may be
shall be suitable for remote starting. Aluminium/Copper Conductor XLPE
insulated PVC sheathed, armored type.
ii) The regulation of generator voltage shall be
automatic and necessary instruments for The conductor screen, XLPE insulation
metering viz. Ammeter, Voltmeter, screen shall all be extruded in one
Frequency meter, KWH meter, Power operation by ‘Triple Extrusion’ process.
Factor, Hour run counter etc. shall be
included in control panel. iii) 1.1 K.V. grade cables may be
Aluminium/Copper Conductor PVC
iii) Warning of abnormal conditions shall be insulated, PVC sheathed, armored type.
incorporated prior to automatic trip to
prevent unnecessary shutdown. iv) All power and control cables shall
preferably have extruded inner and outer
All the six stator winding ends shall be sheaths.
brought out to an externally mounted
terminal box and shall be connected in star. v) Where single core cables are armored and
Necessary temperature detectors shall be are meant for use on A.C circuits,
provided for the stator winding. The armouring with non-magnetic material (e.g.
terminal box shall have sufficient space to Aluminium) shall be given.
receive the cables of specified size.
The communication cables shall conform to
iv) Emergency D.G. set shall have Auto ITD specification. For fire alarm systems,
starting arrangement but only with manual PVC insulated, armoured and overall PVC
switching off features. The rating (Ampere sheathed cable with 1.5 mm2 copper
Hours) of battery, for cranking the engine conductors may be used.
type of earth fault protection schemes.
vi) The power and control cables shall have (Guidelines on this can be had from IEC
the following minimum cross sectional 183).
areas :
x) When feeders comprising of parallel runs of
a) Medium voltage 4mm2 cables are envisaged, the size and type of
powercable Aluminium or individual cable shall be identical.
2.5 mm 2 Copper

b) Control cables 2.5 mm 2(Copper) 7.2.10 Control Station


(See Note 1 below)
i) Each Motor shall be provided with a control
c) Lighting 2.5 mm2 (Copper)/ station in the field. Motors installed at
4mm2 (Aluminium) elevated platforms (such as cooling tower
(See Note 2 below). fan, air fin cooler etc.) shall be provided
with one stop push button at ground level in
Note 1 In case of difficulty in connecting the addition to one near motor.
cables to instrument relay Annuciation
terminals, the minimum cross section ii) The control station enclosure shall have
may be reduced to 1.5 mm2 copper. suitable protection for site conditions such
as flameproof, weather-proof, dust-proof,
Note 2 For lighting inside the building copper corrosion resistant, etc.).
conductor cables shall be used.
Where conduit wiring is adopted, iii) The control station shall include the
minimum 1.5 mm2 copper conductor following equipment as per individual
PVC insulated wire may be used. requirements :

Note 3 Conductor size for wiring inside the - Start/stop push button/close,
panel for electronic neutral, Trip Switch
circuits/components shall be as per
manufacturer’s standard. - Ammeter,

vii) Cables shall be properly sized to carry - Local/Remote Selector Switch


without undue temperature rise the load
current under site derated conditions. The - Auto/Manual selector switch and
derating shall take into account ambient air cable glands.
temperature, ground/duct temperature,
grouping and proximity of cables with each iv) Stop push button shall generally have stay
other, thermal resistivity of soil etc. Cables put feature except in the case of critical
protected by fuses shall be able to drives such as lube oil pump etc.
withstand the maximum I2 t let through
energy of fuse. v) Control station shall have suitable locking
facility.
In other cases, cable shall be able to
withstand the fault current for a duration as 7.2.11 Convenience Receptacles
dictated by protective disconnecting device.
i) These shall have the necessary
viii) The type of cable selected and the mechanical interlocks and earthing
insulation shall be compatible with various facilities. The enclosure shall have
chemicals encountered in the plant and suitable protection for site conditions
other environment conditions such as specified such as flameproof, weather-
dampness highly corrosive atmosphere, proof, dust-proof, corrosion resistant, etc.
high/low temperature, radiation etc.,
bearing in mind that certain chemicals (e.g. ii) Welding receptacles shall be provided at
Benzene, Ethylene chloride) are known to suitable locations to ensure accessibility
be detrimental to PVC. with a 50 meters length of trailing cable to
any point in the process area. These shall
ix)The selection of voltage rating of H.V. be rated for 60 A suitable for 415 V, 3-
cables shall take into account the system phase system with a scraping earth
voltage, system earthing arrangements and connection.
iii) Adequate number of sockets for lamps b) flat formation with spacing as per
and portable tools shall be provided at requirement.
suitable locations to ensure accessibility
with a 15 meters length of cable to any - When cables are laid in a flat
point in the process area. These shall be formation, the individual cable fixing
rated for 15 A single phase supplied at clamps, and spacers shall be of non
240 V. Hand lamps and portable tools magnetic material.
shall be earthed through flexible cords.
The flexible cable shall have 3 cores of - As a general practice, the sheath of
multistrand copper conductor of minimum single core cables shall earthed to
size equivalent to 1.5 Sq mm, with PVC keep sheath at earth potential.
insulation and metal braiding. In However depending on the current
hazardous areas, handlamps shall be the cable has to carry, the feeder
rated for 24 Volts. Accordingly 240/24 V length and permissible sheath
transformers shall be provided either in potential, various methods of sheath
the plug or in separate flameproof bonding are employed, viz. single
enclosure. point bonding, bonding at middle,
sectionalised bonding etc., for which
7.2.12 Actuators for Motor Operated cable manufacturers
Valves recommendations shall be followed.

i) Valves with electrical actuators shall - It should be noted here that the
generally be provided with integral current rating of cables will vary
starters. depending upon laying formation,
method of sheath bonding etc.,
ii) The necessary local/remote selector apart from other derating factors
switch, start/stop control switches or push normally considered. (Ambient
button, torque limit switches etc. shall be temp., depth of laying etc.)
provided on actuator for local/remote
control depending on mode of selection. In iii) All trenches shall be sized depending upon
case of failure of torque limit switches, the the number of cables, and its voltage
mechanical design shall be adequate to grade. High voltage, medium voltage and
stall and trip the motor without damage. other control cables shall be separated
from each other by required spacing or
iii) The control circuits shall AC operated for running through independant pipes,
short distance or DC operated for trenches or cable trays as applicable.
extended distance. The actuator shall be Cable trenches inside substations shall be
provided with an anti condensation heater. filled with sand, pebbles or similar non-
flammable materials or covered with
8.0 Plant Cabling incombustible slabs. If a significant number
of cables are taken on racks/supports
i) Cables below ground may be laid in provided on the side wall of trench.
concrete trench/tunnel or directly buried.
Cables above ground shall be laid in cable iv) RCC covers of trenches shall be effectively
trays/cable racks. sealed to avoid ingress of chemicals and
oils.
However cabling for fire water system
shall as far as possible be taken in v) In unpaved areas, cables may be directly
exclusive route through underground buried in ground. Where underground
trench. cables cross roadways or pipe sleepers at
grade etc., they shall be protected by being
ii) While designing layout with single core drawn through sleeves/ducts to provide a
cable installations following factors shall permanent crossing. Sleeves/ducts ends
be considered : shall be effectively sealed thereafter.

a) Cables are laid as a general practice in vi) Concrete lined trenches shall have suitable
trefoil formation touching each other. drainage arrangement to avoid water
collection. Concrete lined cable trenches
or shall be sealed against ingress of liquid and
gases wherever the trenches leave a RCC slabs to prevent accumulation of
hazardous area or enter control room or flammable gas/vapour inside the trench.
substation. Pipes laid for mechanical
protection shall be sealed at both ends. xv)Cables shall be identified close to their
termination point by cable tag numbers as
vii) Above ground cables shall be well per cable schedule. Cable tag numbers
supported suitably at every 2 to 2.5 metres shall be punched on aluminium strap 2mm
interval and protected against mechanical thick flat or circular, securely fastened to
damage. Routing shall be decided to avoid the cable.
proximity to hot sources, place subject to
undue fire risk, gas, water, steam oil drains, xvi) Besides each underground cable shall
piping, air conditioning duct etc. Cable be provided with identify tags of lead
trays, racks and trenches shall sized to securely fastened at every 30 metres of
allow for 10 to 20% future cables reserve. underground length with at least one tag at
Each cable tray tier shall accommodate the each end before the cable enters the
cables preferably in single layer. ground.

Instrument and communication cables shall For further details, on installation practices
not be laid in the same trench/tray along and requirements refer OISD Standard 147
with electrical cables. The overall cable on ‘Inspection and Safe Practices during
layouts shall be designed for minimum Electrical Installations’.
interference between signal and power
cables. 9.0 Plant Lighting

viii) Cable cellars and important cable This can be broadly classified as under :
tunnels shall be provided with fire detection
and monitoring devices. i. Normal lighting

ix) Trailing cables for equipment such as ii. Emergency lighting


cranes and excavators shall have one
additional core for earthing and the cable iii. Critical lighting
shall be well protected against mechanical
damage. i) Normal and emergency lighting system
shall be on 415/240V AC supply, whereas
x) Cable straight through joints in power & critical lighting will be either on 220V or
control cables shall be avoided as far as 110V DC.
possible.
ii) Sufficient lighting shall be provided so as to
xi) Only type tested and approved make enable plant operators to move safely
termination kits shall be used. While within the accessible areas of plant and to
selecting the type of cable kit, necessary perform routine operations. In the event of
consideration may be given to the normal power failure, emergency lighting
additional safety measures needed for may be provided.
carrying out termination with kits of type
such as heat shrinkable type (particularly in iii) Lighting requirements provided during the
hazardous areas). failure of power supply for Normal lighting
are intended broadly,
xii) Cable route markers shall be installed at
every 30 metres intervals all along the a. to facilitate carrying out of specified
cable routes and also at cable joints and operations, for safe shutdown of the
locations where the direction of cable plant.
trench changes. Cable route markers shall
extend 600 mm above ground. b. to gain access and permit ready
identification of fire fighting facilities
xiii) Cable installations shall provide for such as fire water pumps, fire alarm
minimum cable bending redii as stations etc.
recommended by manufacturer.
c. Escape route for safe evacuation of
xiv) Cable trenches in hazardous area operating personnel.
shall be filled with sand and covered with
iv) The recommended areas for critical both emergency and normal lighting shall
lighting (D.C.) include : be fed by Normal power source. On failure
of normal supply, emergency lighting load
- Control rooms (Process & utility) will be transferred to emergency source
after the start of D.G. set within 15
- Main substations seconds. Critical lighting (D.C. supply
based) will be normally kept ‘ON’ and
- D. G. Shed during Normal/emergency power failure,
battery will provide power.
- Central Fire Station
viii) Besides, adequate number of self
- Fire water pump house (for startup contained portable hand lamps and Battery
of Diesel driven F.W. pump) emergency lighting units shall be provided
for immediate use in emergency at remote
- First Aid Centre stations and at other strategic places (safe
areas), wherever required, for personnel
- Emergency escape route safety.

v) The recommended areas for A.C. ix) HPMV/MLL lamps shall generally be used
emergency lighting includes : for outdoor plant lighting. Keeping in view
the restrike time lag and to avoid complete
- Control rooms (Process & utility) darkness in case of a voltage dip/brown out
conditions, necessary incandescent lamps
- Fire water pump house, Fire stations may be judiciously distributed throughout
the plant area. Incandescent lamps may be
- Main sub stations considered for emergency lighting to
achieve this objective, Fluorescent lamps
- Foot of stairs and ladder may be used for indoor lighting in non-
process buildings and control rooms. Safe
- Platforms with ladders changing area street lighting and yard lighting may
direction employ sodium vapour lamps. Low
pressure sodium vapour lamps shall not be
- Other changes of floor level, that installed in hazardous areas.
may constitute a hazard.
x) The illumination levels in different areas
- Strategic locations in Process, utility shall be as per good engineering practice.
areas where specific safety Depending on the nature of job activities to
operations are to be carried out be carried out the suggested minimum
such as : illumination levels for various areas are as
under :
* Areas near heat exchangers, --------------------------------------------------------
condensers Areas Illumination
in Lux
* Barring gears of steam turbine --------------------------------------------------------
- Main roads (along process 7 - 10
* Some portions of roads units, power houses,
interconnecting substations and workshops, etc.)
process plants.
- Secondary roads (along 3 - 5
vi) As a good engineering practice the A.C. storage tanks settling
emergency load is generally considered as basins etc.)
20-25% of Normal Lighting load. However
for small plants, where A.C. emergency - Tank farm 10
load is not substantial/where there is no
separate standby D.G. set, D.C. critical - Pump houses, sheds 100
lighting system may take care of entire
emergency lighting. - Main operation platforms 60
& access stairs
vii) The following operational philosophy is
recommended. Under normal operation, - Ordinary platforms 20
- Process areas, pipe 60 ii) Escape Lighting
racks, heat exchanger,
heater, separators, cooling a. Escape way (interior) - 5 Lux
tower, columns, pig
launching/receiving loading b. Areas at exit door and
area, flare etc. at points where it is nec-
essary to emphasise
- Switchgear bldg. 150-200 the position of potential
hazard if any. - 30 Lux
- Transformer bay 100
iii) Other notified general
- Battery room 150 outdoor areas - 1 Lux

- Control room bldg./laboratory 400 xii) The lighting fixtures on various circuits shall
be suitably interlaced so that failure of any
- Boiler house 150 one circuit do not result in complete
darkness.
- Charger/UPS rooms 150-200
xiii)Taller structures shall have aviation
- Cooling tower 60 obstruction lighting as per statutory
regulations (D.G.C.A.).
- Switchyard (i) operating area 100
xiv)Battery room shall have fixtures mounted
(ii) other areas 50 on wall in order to facilitate easy
replacement of fused lamps. Switches
- Warehouse 100 controlling the lighting fixtures and exhaust
fan shall be installed outside the battery
- Office 300 room.

- Compressor area 200 xv)Switches of lighting panels installed in


hazardous area, shall have a pole to break
- Watchroom 100 the neutral in addition to the poles for
phases.
- Stairs 50
When the means of isolation is located in a
- Corridors/lifts 70 non-hazardous area, the switch shall break
all poles including neutral or alternatively
- Tube well, gate & watchman may break only live poles, the neutral being
booth 100 isolated by a removable link.

- Fire house, garage 100-150 xvi)For details on installation practices refer


----------------------------------------------------------- OISD standard 147.

However, lighting levels in all areas shall 10.0 Plant Earthing


take into consideration the requirements
from point of view of safety, easy operation i) Earthing system in general, shall cover the
and maintenance. following :

xi) The illumination level requirements (during - Equipment earthing for personnel
normal lighting source failure) depends on safety,
the nature of activities to be carried out.
The suggested minimum illumination levels - System neutral earthing, and
are as below :
- Static and lighting protection.
I) Near to areas where Spot
specific safety operations lighting ii) The earthing system envisages an earthing
(visual tasks are to be to be network with designed number of earth
carried out (e.g. control provided electrodes attached to it. The following
room) shall be earthed :
sized PVC insulated aluminium conductor
- System neutral, cables, may be used for earthing
grid/connections.
- Current and potential transformer
secondary neutral vii) All utility, process pipelines and flanges
shall be earthed on entering or leaving the
- Metallic non-current carrying parts of all hazardous areas, except where conflicting
electrical apparatus such as with the requirements of cathodic
transformers, switchgears, motors, protection. In addition, steel pipe racks in
lighting/power panels, terminal boxes, the process units and offsite area shall be
control stations, lighting fixtures, earthed at every 25 meters.
receptacles etc.
viii) Equipment located remote from main
- Steel structures, Loading platform etc. earth network may be earthed by means of
individual earth conductors and earth
- Cable trays and racks, lighting mast and electrodes.
poles.
ix) Lighting protection shall be provided for the
- Storage tanks, spheres, vessels, columns equipment, structures and buildings which
and all other process equipments. are higher than 20 metres or as per the risk
index analysis worked out as per IS 2309.
- Electrical equipment fencing (e.g. Self-conducting structures do not require
transformer, yard etc.) lightning protection with aerial rod and
down conductors. They shall be connected
- Cable shields and armour to the earthing system at two points of the
base. An independent earthing network
- Flexible earth provision for Wagon, shall be provided for lighting protection and
Truck this shall be bonded with the main earthing
network below ground, minimum at two
iii) Plant earthing design shall generally be points.
carried out in accordance with the
requirements of Indian Electricity Rules and x) The resistance value of an earthing system
code of practice for earthing IS 3043. to the general mass of earth shall be as
follows :
- As far as possible, all earth
connections shall be visible for inspection. - For the electrical system and equipment,
a value that ensures the operation of
iv) All connections shall be carefully made and the protective device in the electrical
adequately locked against loosening. circuit but not in excess of 5 ohms.
Normally earthing system shall comprise of However, for generating stations
GI strip as main earth grid alongwith and large sub-stations this value
suitably located GI disconnecting plates to shall not be more than 1 ohm.
provide multiple earth connections between
earth grid and equipment and for - For lightning protection, the value of
connections between main earth grid and 5 ohms as earth resistance shall be
electrodes. Alternatively, mild steel strip desirable, but in no case it shall be
can also be used for earth grid after more than 10 ohms.
providing corrosion allowance.
xi) The main earthing network shall be used
v) Connections between GI earth electrode for earthing of equipment to protect against
and the disconnecting plates shall be done static electricity.
by GI strip. For highly corrosive areas, PVC
insulated A1 cond. cable (unarmoured) For further details on earthing installation
may be used. Connections between the practices refer OISD standard 147.
disconnecting plate and various equipment
shall be done by GI strip, GI wire or GI wire TABLE - III
rope, size as recommended in Table III. -----------------------------------------------------------
Type of Equipment Bare G.I. Strip/G.I.
vi) In corrosive areas, aluminium Bare Rope or
disconnecting plates alongwith suitably G.I. Wire
----------------------------------------------------------- 11.0 Plant Safety and Security systems
Motors upto 3.7 KW No. 8 SWG solid
wire This shall include the following systems:

Motors 5.5 KW to 10 mm (3/8") Wire 30 11.1 Plant Fire Detection and Alarm System
KW & welding
receptacles i) The purpose of a fire detection and alarm
system is to detect fire at the earliest and
Motors 37 KW and 16 mm (5/8") above to give an alarm so that appropriate
including HT Wire Rope action can be taken (e.g. evacuation of
Motors personnel summoning the fire fighting
organisation, triggering of extinguishing
Building Columns 40 X 5 Strip process etc.). An alarm system may be
activated by automatic detection devices
Storage Tank (Vertical 40 X 5 Strip viz. smoke detectors, heat detectors etc.
& Horizontal) or by manual operation of manual call
points i.e. break glass units.
Loading Racks 40 X 5 Strip
ii) Manned locations prone to fire hazard
Pipe racks, Vessels 10 mm (3/8") & shall have manual call points which on
Heat Exchanvers Wire Rope operation shall give audio-visual
indication at the control rooms and
Small Equipment & No. 8 SWG Solid actuate the sirens. If there are many
Instruments manual call point, these may be
conveniently grouped together to form
Lighting, Power & 10 mm (3/8") various zones and zone panels may be
Instrument Panels Wire Rope installed in convenient places other than
unit control rooms. Operation of each
Main Earth Bus/LT & As zone panel may be indicated by audio-
HT SW. Gear Intercon- Calculated visual indication in the main control panel
nections/Power Trans- in the unit control room as well as in the
former other zone panels with distinct colour
indicating the zone number.
EHV & HV Sub-Stations As Calculated
iii) A fire detection and alarm system shall:
Push Button Stations No. 8 SWG Solid
Wire a) operate quickly enough to fulfil its
intended functions;
Street Light Poles 10 mm (3/8")
Wire Rope b) reliably transmit the detection signal;

Lighting Transformer 16 mm (5/8") c) Translate this signal into a clear alarm


Wire Rope indication that will attract the attention of
----------------------------------------------------------- the user in an immediate and
Note : Lighting fixtures shall be earthed unmistakable way and indicate the
through the extra core provided in the location of fire and initiate operation of
lighting cable. ancillary service such as fire
extinguishing system, etc;
xii) Earth rods and conductors shall be
designed to cope with the conditions d) remain insensitive to phenomena other
imposed. The earth conductor shall be than those which its function is to detect;
adequately sized to carry the applicable and
maximum earth fault current without
undue temperature rise. All joints shall e) signal immediately and clearly any
be protected against corrosion. supervised fault that might jeopardies the
correct performance of the system. The
xiii) All the electrical equipment operating system shall also include a FIRE SIREN
above 250 volts shall have two separate of distinguished tone having a range of
and distinct connections to earth grid. about 8 kms. Audio/visual fire alarm may
be required at the following locations in a - Executive phone service shall include direct
large plant: unassisted (operator bypass)
communication to external lines for both
- Control room local and long distance telephone service.
- Fire station
- First aid centre iii) In areas with high ambient noise levels,
- Security office intensified bell signals may be provided to
- Fire water pump house produce an effective recognition noise level
of 6db above anticipated ambient noise
iv) Detailed design, selection and installation levels.
of fire detection and alarm system shall
be as per IS-2189. 11.2.2 Public Address System

11.2 Communication system i) A public address system shall be provided


for communication within the plant area and
The plant communication system shall it shall comprise master stations, central
include some or all of the following cabinet/exchange equipment (field station
facilities as per individual plant modules, amplifiers etc.), field stations,
requirements: paging loudspeakers etc. The public
address system shall provide, as a
- Telephone minimum, the following facilities:

- Public address system a) Paging within the plant area over


loudspeaker from the master station
- Emergency communication located in process control room.
system
b) Call back from any of the field stations to
- Radio communication system the master control station.

- Telex system. c) Communication or call from Master Control


Station to any of the field stations and
Certain requirements for each facility are communication between field stations at
given below as general recommendation. the discretion of Master Station.

11.2.1 Telephone System d) Communication between pre-designated


field stations as per process operating
i) A private automatic branch exchange requirements without interference of the
(PABX) system shall be provided. Trunk operator manning the master station.
lines connecting with the external
telephone network shall be provided and e) Operating an alarm call from master control
number of trunk lines shall be decided station over all the loud speakers during an
based on plant size and requirement. emergency.

ii) Selective telephone service control shall be ii) Paging speakers provided in areas having
arranged for all the extensions of the PABX high ambient noise levels shall produce a 6
to have one or more of the following service dB paging noise level above anticipated
functions: ambient level for effective recognition of
speaker’s voice signals.
- All phones shall have direct inter-
communication between all the extensions Also the field stations shall be capable of
of this exchange and all the extensions operating in areas of high noise levels
shall be able to accept any external calls without any interference.
handled by the exchange operators.
11.2.3 Emergency Communication System
- Non executive phones shall operate with
operator assistance for connection to i) The ‘Hot line system’ shall be designed to
external lines for both local and long provide a dependable communication link
distance telephone service. between predesignated points of operation.
This system shall be completely isolated
from the telephone system.
plant and pre-designated points outside the
ii) The emergency communication system plant. The system shall include necessary
shall include a ‘Direct phone to phone hot transmitter/receivers and associated
line (H.L.) system’ and a ‘Dedicated hot line antenna. The frequency of operation shall
(D.H.L.) system’. be decided in consultation with statutory
authorities (P&T).
iii) H. L. System
11.2.5 Telex System
By removing phone from cradle switch, the
corresponding phone at opposite end will One telex machine shall be installed in the
ring till answered or until the phone is administration building of the plant.
returned back to cradle disengaging the
circuit switch.

iv) D.H.L. System 12.0 MOBILE EQUIPMENT FOR


HAZARDOUS AREAS
A simplified selective dial scheme shall be
provided to give selective contact between 12.1 PORTABLE HAND LAMPS
all the extensions of this system. All the
telephones used for the emergency i) Hand lamps for use in hazardous area shall
communication system shall be red in be flameproof with an operating voltage of
colour and shall have ringing indication 24 V. The hand lamp shall be connected to
lights. the source of supply by a flexible 3x1.5 sq.
mm copper conductor PVC insulated metal
11.2.4. Radio Communication System braided cable.

Portable Walkie - Talkie system. This cable should be protected by


PVC/tough rubber sheath or similar
i) A walkie-talkie system shall be provided for covering. The metallic body or any other
radio communication within the plant area. exposed metal part of the hand lamp shall
The system shall operate in the simplex be connected to earthing system.
mode on U.H.F. and the exact frequency
shall be decided in consultation with P & T ii) The source of supply shall be located as
authorities. near as possible to the points to be
illuminated. Automatic protection employing
ii) The system shall consist of base station, earth leakage detection scheme (e.g. using
monitoring receivers, portable stations, ELCB with current sensitivity of 30 mA)
antennas and associated accessories. shall be provided to disconnect supply on
Adequate number of hand stations shall be occurrence of an earth fault. Hand lamps
provided. with self contained batteries shall have type
of protection appropriate to the applicable
iii) The system shall enable communication hazardous zone.
between portable station and the base
station or between any of the two portable 12.2 DIESEL ENGINES
stations. The system shall have a range of
approximately 6 km. i) The use of permanently installed diesel
engines in Zone-0 and zone-1 areas is
iv) The system shall provide excellent unacceptable and the use of permanently
penetration in all operating areas of the installed diesel engines in Zone-2 area
plant with no marginal locations and extend should be avoided wherever possible.
beyond the boundaries of the plant. The
system shall operate above the man-made ii) In the event of use of a permanently
noise spectrum to provide clear noise free installed diesel engine, being necessary in
communication in all areas of high electrical Zone-2 it is recommended that it should
noise. have the following minimum protection to
ensure safety :
11.2.4.1 VHF System
a) The starter shall be either of a flameproof
Radio communication (VHF band) may be electrical type (usually operated from the
provided for communication between the
mains supply or battery) or of the j) Alarms of automatic shutdown devices
following non-electric types : shall be provided, actioned by excessive
water temperature and low lube oil
i) Pneumatic pressure.
ii) Hydraulic
iii) Spring recoil k) A system using an alarm or trip device to
iv) Inertia, or protect the engine from excessive vibration
v) Hand start should be considered.

b) Any other electrical equipment associated l) An engine having a crank case volume of
with the engine shall be flameproof. over 0.5 m3 shall be provided with relief
Electrical equipment shall be effectively devices. Relief valves or breathers on
earthed and bonded. engines shall be fitted with flame traps or
discharge into the induction system
c) Cooling fan blades shall be made from non- downstream of the flame trap, if fitted and
metallic materials which do not accumulate upstream of the shut-off valve, if fitted.
electro-static charge. Dipsticks and/or filler caps should be
screwed or effectively secured by other
d) All belts shall be of anti-static, fire-resistant means.
type.
m) Intake and exhaust system design shall
e) In order to contain discharge of sparks or meet the following minimum requirements:
flames from the exhaust system, a gas
conditioner box and a flame trap shall be i) The length of the flame path through or
installed. Alternatively, the exhaust should across any joint shall be not less than 13
be designed to discharge to a location mm.
within a safe area.
ii) Suitable metal-clad or other acceptable
f) To prevent flashback through induction jointing material shall be interposed
system, wherever possible, air intakes for between all joint faces to ensure that
engines shall be located in safe area. leakage does not occur.
Alternatively a flame trap should be
installed. iii) Where valve spindles pass through the
walls of any component of the induction
g) The surface temperature of the engine and system, the diametrical clearance shall not
exhaust system shall not exceed 250°C exceed 0.13 mm, unless end caps are
when tested under full load conditions. In fitted.
some situations cooling of the exhaust
manifold and piping may be necessary, iv)No screw, stud or bolt-hole shall pass
using water jacketing or finned coolers through the wall of any component of the
and/or high temperature cut/outs or alarms system.
should be provided.
n) Decompression systems should not
h) However when either the free movement of normally be provided. However, if they are
air is restricted by thermal or acoustic essential, then the decompression parts
shielding or the ignition temperature of the should be provided with flame traps and
surrounding flammable atmosphere is ducted away to safe area.
below 200°C, no engine exposed surface
temperature shall exceed the minimum o) The fuel injection pump and governor
ignition temperature of the gases involved. where fitted should be so designed that
reverse running of the engine is not
i) To prevent overspeeding of the engine due possible.
to induction of flammable gases or vapours,
means shall be provided to stop the engine. 12.3 STORAGE BATTERIES
It can be either :
i) Storage batteries shall not be installed in
i) a valve to close the air intake, or Zone 1 locations, except those used in
ii) a system to inject carbon dioxide into portable lamps where the enclosure
the air intake. housing bulb, switch and battery shall be
flameproof type.
j) The cover of the battery case shall have
ii) As far as practicable use of storage special fastenings.
batteries in Zone 2 areas shall be avoided.
However where unavoidable, storage k) Exposed live parts of battery contained in a
batteries for use in Zone 2 areas shall be case shall be protected with rubber or
“Increased Safety” type. These shall meet equivalent insulated materials. However,
the following requirements : the openings for checking voltage may be
provided.
a) Celluloid and similar combustibles shall not
be used as constructional materials. Note : Charging of storage batteries shall be
conducted in non-hazardous
b) Battery containers as well as fittings and locations, while the cover of the
insulating parts outside the enclosed cells battery enclosure is kept open.
shall not consist of porous materials e.g.
wood or other flammable materials and 12.4 TESTING EQUIPMENT
shall be resistant to flame and the action of
electrolytes. a) All testing equipment such as meggers,
continuity tester etc. shall be intrinsically
c) Openings of cells necessary for the escape safe.
of the gases given off shall be so
constructed as to prevent splashing of the b) Terminal connections shall be made by
electrolyte. crimp type lugs.

d) The exterior of the cells shall be so c) Terminals shall be provided with rubber
constructed as to resist impact, and the cell covers.
cases shall be firmly fixed.
d) Enclosure and other constructional features
e) The cells shall be so built into the shall be suitable as per the area
containers that connection of the cells requirement.
getting loose in operation is improbable and
normally, the discharge voltage exceeding 12.5 MISCELLANEOUS
24 volts should not appear between
REQUIREMENTS
adjacent rows of cells.
a) The electrical equipment and the system as
f) The creepage distance between two poles
a part of mobile equipment shall be of
of adjacent cells shall not be less than 35
intrinsically safe/flame proof design, if
mm. Where the discharge voltage exceeds
required to be taken in classified hazardous
24 volts, the creepage distance shall be
areas.
correspondingly increased by 1mm per 2
volts.
b) The mobile apparatus shall be used for
temporary purpose only under competent
g) Where voltage of batteries is not less than
supervision.
50 volts, either the battery case shall be
subdivided by partitions or the batteries
c) No uninsulated current carrying part shall
shall be grouped into containers such that
be exposed.
in no grouping does a voltage exceeding 50
volts occur. In these cases, the partitions or
d) All components shall be accessible for
the containers shall have heights of at least
maintenance/repairs.
half that of the battery case.
e) All remote control or interlock circuits
h) The battery case shall be so constructed as
associated with restrained plug and socket
to ensure sufficient ventilation in order to
coupling should be intrinsically safe.
prevent accumulation of gases given off
from the battery, and the free space within
f) All electrical circuits shall be cut off
the case shall be as small as possible.
automatically in the event of :
i) The metallic cover of the battery case shall
i) The current in any circuit exceeding
be lined with materials resistant to
more than the rated value in any circuit.
electrolyte.
ii) A leakage current to earth/earth fault.
installations. Areas having flammable
12.6 VEHICLES gases and vapour

Commercial vehicles such as jeeps, trucks, * IS 5571 Guide for selection of


cars etc. shall not be allowed inside electrical equipment for hazardous areas.
hazardous area unless these are
specifically certified by competent authority * IS 13346 General requirements for
for use hazardous areas. electrical apparatus for explosive gas
atmosphere
13.0 REFERENCES
* IS 8239 Classification of maximum
The following codes, standards and surface temperature of electrical equipment
publications have either been referred to or for use in explosive atmospheres.
used in the preparation of this document
and the same shall be read in conjunction * IS 3043 Code of Practice for Earthing.
with this document :
* IS 3716 Insulation coordination
i) National Electrical Code of Bureau of application guide.
Indian Standards. (SP-30 : 1984)
* IS 732 Code of practice for electrical
ii) OISD Standards / Recommended Practices wiring installations.
such as :
* IS 6665 Code of practice for industrial
a) OISD - 147 “Inspection, and safe lighting.
practices during Electrical Installation”.
* IS 3646 Interior illumination : Part 1,
b) OISD - 116 - Fire Protection facilities Part 2 & Part 3.
for petroleum refineries and oil/gas
processing plants. * IS 1944 Code of practice for lighting of
public thoroughfares.
c) OISD - 117 - Fire Protection facilities
for petroleum depots and terminals. * IS 7689 Guide for control of
undesirable static electricity.
d) OISD - 118 Layout for Oil and Gas
Installations * IS 2309 Protection of buildings and
allied structures against lightning.
e) OISD - 113 ‘Electrical Area
Classification’. * IS 2189 Code of practice for selection,
installation and maintenance of Automatic
f) OISD - 137 “Inspection of Electrical Fire Detection and Alarm System.
Equipment”
* IS 3034 Code practice for fire safety of
iii) Indian Electricity Act & Rules 1956 (Ministry industrial buildings, electrical generating
of Irrigation & Power, Govt. of India) and distributing stations.

iv) The Petroleum Rules 1976 (Ministry of * IS 1646 Code of practice for fire safety
Industry, Government of India) of buildings (General) Electrical
Installations.
v) Oil Mines Regulations
* IS 10028 (Part 1, 2 & 3) code of
vi) C.B.I.P. (Central Board of Irrigation & practice for selection, installation and
Power) Technical Report No. 3 ‘Manual on maintenance of transformers.
Layout of Substations’.
* IS 2165 Part (1 & 2) Insulation
vii) BIS (Bureau of Indian Standards) Coordination.
Publications
* IS 2834 Specifications of shunt
* IS 5572 Classification of hazardous capacitor for power system.
areas (other than mines) for electrical
* IS 13408 Code of Practice for the
selection, installation and maintenance of
Electrical Apparatus for use in potentially
explosive atmospheres (other than mining
applications or explosives processing and
manufacture)

* IS 2148 Flameproof enclosures for


electrical apparatus

* IS 7389 Pressurised enclosures of


electrical equipment for use in hazardous
areas

* IS 7724 Sand filled protection of


electrical equipment for use in explosive
atmospheres

* IS 7693 Oil immersed electrical


apparatus for use in explosive gas
atmosphere

* IS 8289 Electrical equipment for type


of protection ‘n’

* IS 6381 Specification for construction


and testing of Electrical apparatus with type
of protection ‘e’

* IS 2147 Degrees of protection


provided by enclosures for low voltage
switchgear and control gear.

viii) IEC 34-9 Rotating

Electrical Machine - Part 9 (Noise Limit)

IEC 183 Guide to the selection of high


voltage cables

ANSI/ Standard Electrical Power


System

IEEE Device Standard Function


Numbers C37.2

You might also like