You are on page 1of 9

IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO.

1, MARCH 2008 119

Large Offshore DFIG-Based Wind Farm With


Line-Commutated HVDC Connection to the Main
Grid: Engineering Studies
Serhiy Bozhko, Member, IEEE, Greg Asher, Fellow, IEEE, Risheng Li,
Jon Clare, Senior Member, IEEE, and Liangzhong Yao

Abstract—The paper considers a solution for integration of large fully proved while LCC HVdc technology has been operated
offshore doubly fed induction generator-based wind farms with a with high reliability for more than 30 years. However, the LCC
common collection bus controlled by a STATCOM into the main requires a commutation voltage supplied by a synchronous com-
onshore grid using line-commutated high-voltage dc connection. A
design procedure is described and the controlled system is validated pensator [3]. Alternatively, a STATCOM can be used [4], [6] that
using PSCAD/EMTDC simulations confirming high performance can typically provide much faster control than a synchronous
of the proposed control strategy in both normal operation condi- compensator and with lower losses.
tions and faults. Engineering issues related to STATCOM capacitor For reasons of energy capture and reduced drive train stresses,
sizing and reduction of STATCOM rating are considered and their variable speed turbines are becoming the norm for new wind
effectiveness is confirmed.
farm installations. The direct-drive synchronous generator (op-
Index Terms—Controller design, doubly fed induction generator tionally with permanent magnet excitation) and doubly fed in-
(DFIG), frequency, high-voltage dc (HVdc) transmission, stability, duction generator (DFIG) have become the two generator alter-
STATCOM, voltage, wind energy.
natives. The former has the disadvantages of cost and a power
converter rated for the full power. Although requiring a gearbox,
I. INTRODUCTION the DFIG requires a converter of only 25% of the generator rating
T IS PREDICTED [1] that by 2020, up to 12% of the world’s for an operating speed range of 0.75 to 1.25 per unit (p.u.) and is
I electricity will be supplied from wind power. The majority
of wind farms are planned to be offshore where wind conditions
considered a lower cost, proven technology solution. The ratings
of commercial DFIG-based wind turbines now reach 5 MW [7].
are generally better while planning restrictions are reduced. For The converter-controlled DFIG, STATCOM, and LCC HVdc
example, several wind farms with registered capacities around have all been well studied as separate components. In [4]
1000 MW are planned off the north-west coast of Great Britain and [6], the overall power system concept and possible control
with distances over 100 km to the nearest grid connection point. paradigms have been described, but these studies have not
To transmit such bulk power over such distances creates chal- included system analysis or a formal procedure of control
lenges for both system operators and wind farm developers. system design. A detailed mathematical study of the system
Currently, two alternative connection methods are available for that resulted in the plant model appropriate for a formal control
connection of remote wind farms to the grid: high-voltage dc design had been represented by the authors in [8]. The present
(HVdc) and high-voltage ac (HVac). It is proven [2]–[4] that the paper is a logical continuation of our previous study [8]: the
HVdc transmission offers many technical, economic, and envi- proposed control algorithm is applied to the more realistic
ronmental advantages for large wind farm with long distances power system configuration, the model for simulation studies
to the main grid. includes lumped DFIG model under converter control [9] to
The HVdc transmission can be based on two alternative tech- represent 1000 MW wind farm, the mechanical dynamics is
nologies: voltage source converter (VSC) using IGBTs and taken into account, the HVdc is modelled according to the First
line-commutated converter (LCC) using thyristors. The VSC Benchmark Model for HDdc studies [10], and includes detailed
technology has the advantage of forced commutation so that switching models for both rectifier and inverter together with
an external voltage source is not required, but it has higher their harmonic filters, and the impedances of all offshore cables
overall losses than thyristor-based LCC HVdc. Moreover, the and transformers are considered as well. The performance of
present power rating for a single VSC is limited at the 330 MW the power system during normal operation and faults is studied,
level [5], and the reliability of VSCs in service has yet to be and engineering issue of STATCOM rating is discussed.

Manuscript received January 21, 2007; revised March 30, 2007. Paper no.
TEC-00012-2007. II. POWER SYSTEM STUDIED
S. Bozhko, G. Asher, R. Li, and J. Clare are with the Department of Electrical
and Electronic Engineering, Nottingham University, Nottingham NG7 2RD, The power system studied is shown in Fig. 1. It comprises
U.K. (e-mail: serhiy.bozhko@inottingham.ac.uk; greg.asher@nottingham. an DFIG-based offshore wind farm, an island platform for
ac.uk; eexrl@gwmail.nottingham.ac.uk; jon.clare@nottingham.ac.uk). HVdc rectifier station and auxiliary equipment, ac filters, and a
L. Yao is with the AREVA T&D Technology Centre, Stafford ST17 4LX,
U.K. (e-mail: liangzhong.yao@areva-td.com). STATCOM unit. Whereas, capacitive ac filters can compensate
Digital Object Identifier 10.1109/TEC.2007.914155 for the HVdc converter reactive absorption in lumped amounts,

0885-8969/$25.00 © 2008 IEEE

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.
120 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO. 1, MARCH 2008

Fig. 2. Simplified diagram of the system studied.

Fig. 1. Power system studied.

the STATCOM provides fine reactive power control. In addition,


the STATCOM being a voltage source can provide the commu-
tation voltage required by the HVdc link and dynamic reactive
power compensation for the network during disturbances and
fault conditions. Commutation voltage and reactive power con-
trol can also be sourced from DFIGs, but high reactive power
compensation by the DFIGs will add to losses in the wind farm
connection cables. The offshore platform is linked to the main Fig. 3. Block diagram of the proposed control structure.
onshore inverter station via submarine HVdc cable.
If the offshore ac grid voltage is kept constant by STATCOM
control, then the output active and reactive power of DFIGs
can be set for particular rotor (wind) speed to effect a standard can be to or from the bus. The parameters Ro and Lo repre-
variable speed energy capture [9], [11]. This determines the sent the HVdc dc-link cable connection and the cable capac-
references for the DFIG d- and q-axes current controllers. In itance being neglected for control design. The HVdc inverter
steady-state operation, the total active power delivered by all is in voltage-control mode, and under normal conditions has
DFIGs must balance the power transferred to the HVdc link, little effect on the offshore grid control regimes. It is replaced
consumed by local loads and dissipated as losses. Any imbalance by an equivalent dc voltage source Eo . The ac harmonic fil-
will cause the STATCOM dc-link voltage to vary, turning the ters are designed to suppress 11th, 13th, and higher harmonics
STATCOM capacitor voltage into an indicator of active power and have natural frequencies above the designed control system
imbalance. Therefore, as suggested in [4], [6], and [8], it can be bandwidths. For control purposes, the filters are represented by
used for fast adjustment of HVdc dc-link current reference. In their dominant low-frequency capacitor Cf . Power losses in the
this paper, the DFIGs are under vector control as given in [9], STATCOM and HVdc converters are ignored.
and the HVdc is in accordance with the CIGRE benchmark The d-axis of a rotating dq frame is affixed to offshore ac grid
model [10]. The main control objective is an optimal tracking voltage vector VG so that the aim of the control is to control
of generated wind power and its transfer into the main onshore the magnitude and rotational speed of VG subject to disturbance
grid through the HVdc link while controlling the voltage and currents IG and IC . The dq-axis STATCOM Isd and Isq currents
frequency at the offshore ac bus. are tightly controlled with the PI current controllers outputting

The parameters of power system studied in this paper are the STATCOM voltage demands Vsd and Vsq∗ . Similarly, the
given in Appendix I. The rated voltage of the offshore ac bus HVdc Link current I0 is also controlled with a controller out-
is 132 kV, rated HVdc power is 1000 MW (500 kV/2 kA) and putting the HVdc rectifier firing angle α. The control structure
STATCOM energy storage is 9 MJ (20000 µF/30 kV). is shown in Fig. 3.
In Fig. 3, the HVdc-link current demand I0∗ is derived from
the dc-link STATCOM voltage controller while the STATCOM
III. SYSTEM CONTROL
dq-axis current demands are derived from the grid voltage vector
The control design procedure has been considered in detail controllers. The controlled plant of Fig. 3 is derived in [8] and is
by the authors in [8] and is only summarized here. The aim of shown to be a third-order system linearized about the operating
the control system is to regulate the voltage and frequency of the HVdc rectifier firing angle α0 , and decoupled through the use of
offshore ac bus while regulating the power flow via control of appropriate feedforward terms. The natural frequencies of the
the HVdc Link. The control elements and their interconnectivity converter current loops and the system control loops of Fig. 3 are
are shown in Fig. 2. given in Appendix I and reflect the sampling rates appropriate
The wind farm supplies a current IG to the local ac bus, while to the STATCOM rating. It was shown in [8] that the simulated
the current IC flows to the HVdc link. Passive RL elements rep- system transients (i.e., changes in generated wind farm power
resent the transformers and cable parameters. The STATCOM represented through transient changes in IG ) have dynamics
current IS direction depends on the operational demands, and corresponding to the designed controller natural frequencies.

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.
BOZHKO et al.: LARGE OFFSHORE DFIG-BASED WIND FARM WITH LINE-COMMUTATED HVDC CONNECTION TO THE MAIN GRID 121

B. Control System Performance


The control system should maintain the collector grid volt-
age and frequency under the continuously changing wind farm
power. The simulation results of Fig. 5(a) show the response to
a series of steps in wind farm real power demand (1 p.u. → 0.8
p.u. → 0.6 p.u. → 0.5 p.u. → 0.9 p.u. → 0.8 p.u. → 1 p.u.) to
represent a worst-case transients. Fig. 5(a) shows the excellent
regulation of the voltage and frequency of the offshore ac grid
and the power balancing performance via control of the STAT-
Fig. 4. Power system for simulations.
COM dc-link voltage. Since the ac filters in the model are tuned
for the rated HVdc power, the fine reactive power balancing is
clearly provided by the STATCOM under the regulatory action
of the voltage control loops.
IV. SYSTEM MODELING Fig. 5(b) shows the control performance under a solid bal-
A. Development of PSCAD System Model anced onshore mains fault of 160 ms duration (8 cycles at
50 Hz). Fault occurs at t = 0.1 s. The power to HVdc drops,
A study of the designed control system has been performed and the STATCOM starts to absorb the excess of active power
through PSCAD/EMTDC simulations of the system shown in in the local ac bus resulting in dc-link overvoltage up to 67 kV
Fig. 4. The designed PI controllers with the corresponding (91.4%). With a delay for fault detection and communication
closed-loop natural frequencies are given in the Appendix II. (10 ms as assumed), the demand for wind farm output power
The PSCAD/EMTDC model includes a wind farm simulated drops to zero resulting in the fall of output power with the
as a lumped DFIG of appropriate rating [8]. The windfarm is dynamics of power control loop. Both the grid voltage and fre-
connected via a 10-km-long 33 kV submarine ac cable via a quency are well controlled during a fault, and therefore, the
transformer TG to the local offshore 132 kV ac bus where the wind farm can stay connected. When the fault is cleared at t =
HVdc rectifier and ac filters are installed. The voltage at this 0.26 s, the HVdc dc-link voltage recovers, the power transmis-
bus is controlled by the STATCOM according to controls de- sion resumes, and after some transient the STATCOM dc-link
scribed earlier. The aggregate DFIG back–back converters and voltage returns to its rated value.
the STATCOM are simulated using detailed nonswitching con- Simulation results in Fig. 5 confirm high performance of the
verter model while both the HVdc rectifier and the inverter proposed system in both normal conditions and during a severe
are line commutated 12-pulse thyristor converters (switching fault. In the mean time, the results raise engineering concerns
models [12]). The inverter operates under extinction angle con- regarding STATCOM rating: during a fault, the STATCOM re-
trol [3]. The HVdc dc-link cable is represented by its T-circuit active power demand in peak reaches 1.3 p.u. at the HVdc base,
equivalent to represent a transmission distance of 100 km. The and some measures should be considered to lower it. The sim-
main onshore grid connection (230 kV) is assumed to be quite ulation results also show that the STATCOM dc-link capacitor
weak with short-circuit ratio SCR = 2.5. is a subject of significant overvoltage during faults. Both these
The DFIG control is according to [9] with a dq-frame aligned points are related to the STATCOM sizing problem and are
to the stator flux. The rotor-side converter current components considered in the following section.
ir q and ir d are controlled by fast current loops with a natural
frequency of 500 Hz. The rotor current demands Ir∗q and i∗r d are
derived from DFIG P, Q controllers, respectively, with natural
frequencies of 5 Hz. The DFIG front-end converter is oriented
onto the stator voltage and its current components ig q and ig d V. ENGINEERING STUDIES IN STATCOM SIZING
are controlled at the same frequency. The d-axis component i∗g d The STATCOM should be capable of handling the power
is derived from a DFIG converter dc-link controller of natural system operation in both normal conditions and faults. As one
frequency 20 Hz, while the q-axis component i∗g q is set to zero. can see from simulation results Fig. 5(a), both active and reactive
In this study, it is assumed that the wind is sufficient to supply power flows to/from the STATCOM in normal mode are very
an arbitrary active power demand Pˆ* set by the user (although low. Active power just covers the losses within the STATCOM,
in practice, the i∗r q would be fed from a real wind signal via a and reactive power demand is within the difference between
maximum power point tracker) while reactive power demand neighbor steps of switchable ac filters. For the studied case
Q∗ is set to a small nominal value to supply the reactive power with nonswitchable ac filters tuned at rated HVdc power, the
demanded by the local transformer. The magnetizing reactive maximum reactive power demand did not exceed 0.12 p.u. when
power of the DFIG is thus supplied from the rotor converter. It is wind farm output varies from 0.5 to 1 p.u. In the mean time, in
noted that in this study, the reactive power required by the HVdc order to handle the fault, both STATCOM active and reactive
rectifier is supplied by the harmonic filters and the STATCOM power demands are significantly increased. In this section, we
under both operational and fault conditions. It can of course be are analyzing the engineering issues related to the STATCOM
supplied from the DFIG although losses in the ac cables would behavior under the fault conditions and consider measures to
count against this under normal operational conditions. reduce its rating.

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.
122 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO. 1, MARCH 2008

Fig. 5. System performance. (a) Under normal operation (left). (b) During a solid three-phase fault in the onshore grid (right).

A. Effect of Faults on STATCOM DC-Link Capacitor Sizing Consider three right-hand side terms in details. The wind farm
receives fault detection signal with a communication delay τd ,
The STATCOM active power flow is related to the problem
of overvoltage across its dc-link capacitor. Analysis of power and then, the output power reduces according to the dynamics
flow during fault allows one to derive criteria for the capacitor of DFIG current (or power) loop that can be approximated as
first-order lag τG . Therefore, the first term in (9) can be derived
sizing. The energy e, passed into this capacitor is
as follows:
 t
 t
e(t) = e0 + (PG − PC − Pl ) dt (1)  −
t −τ d 

t0 PG dt =PG 0 τd + PG 0 τG 1 − e τ G . (4)
0
where e0 is its prefault value, and PG , PC , and P1 are windfarm
power, HVdc power, and losses correspondingly. This energy Losses assumed are constant (P10 = const), therefore
defines the voltage across the STACOM capacitor CS :  t
Pl dt = Pl0 t. (5)
CS ES2 dc (t) 0
e(t) = . (2)
2 The HVdc power starts to drop without communication delay,
Introducing overvoltage factor kv = ES dc m ax /ES dc0 , the fol- and the transient is assumed according the first-order lag with
lowing expression can be derived using (1) and (2): time constant τC :
 t  t  t  t
CS ES2 dc0  2   − t 
kV − 1 = PG dt− PC dt− Pl dt. (3) PC dt = PC 0 τC 1 − e τ C . (6)
2 t0 t0 t0 0

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.
BOZHKO et al.: LARGE OFFSHORE DFIG-BASED WIND FARM WITH LINE-COMMUTATED HVDC CONNECTION TO THE MAIN GRID 123

when fault is detected. The voltage-dependant current limitation


(VDCL) [3] can reduce the I0 demand during the fault. However,
the VDCL is primarily intended to improve inverter recovery
during ac-system faults [3]. Since VDCL operation is based on
rectifier output voltage that does not necessarily drops to zero
during a fault and does not drop immediately, the reduction of
reactive power demand in offshore grid is not as substantial as
desired.
During a fault, the HVdc current controller in the original
control structure (see Fig. 3) is under influence of two different
trends. Due to the drop of inverter-side dc-link voltage, the HVdc
Fig. 6. Selection of STATCOM dc-link capacitor. current increases sharply and the controller has to increase α in
order to decrease rectifier-side dc voltage and dc-link current I0 .
Simultaneously, the output of STATCOM dc-link voltage con-
Simultaneous solution of (3)–(6) with respect to capacitor
troller pushes the HVdc current demand up in order to reduce
value results in a criterion for the STATCOM capacitor sizing in
STATCOM capacitor overvoltage. Therefore, significant reduc-
order to guarantee that the capacitor overvoltage during a fault
tion of the reactive power demand can be expected if STATCOM
will not exceed some acceptable level kV ES dc0 :
dc-link voltage control is suppressed during a fault. This can be
CS m in implemented if fault detection scheme will zero the demand for
   −
t −τ d   − t   I0 when fault occurs. In this case, the rectifier ac current IC de-
2 PG 0 τd +PG 0 τG 1−e τ G −PC 0 τC 1−e τ C −Pl0 t cays quickly, and subsequently, the STATCOM reactive power
=  2  . demand would be significantly reduced. On the other hand, fast
ES dc0 kV − 1
2
reduction of I0 to zero in presence of ac filters in offshore grid
(7) (they are necessary for harmonic compensation and reactive

Using this expression, one can derive plots for particular stud- power support during normal operation) means that STATCOM
ied cases. Thus, for the power system studied with kV = 1.3 had to compensate for full reactive power generated by these ac
(i.e., 30% acceptable overvoltage), τG = 3 ms, and τC = 2 ms, filters when IC drops to zero. It works against the reduction of
and for maximum fault duration equal to 0.16 s (8 cycles at the STATCOM reactive power demand. This can be relieved if
50 Hz), the curve (7) for CS m in selection has been calculated us- dc-link current demand at faults is not zeroed, but set to some
ing MATLAB and is shown in the Fig. 6. The curve is produced value I0fin in order for rectifier to absorb the reactive power
as an upper envelop for a family of different curves, correspond- generated by ac filters. In our study, this value has been set at a
ing to different values of fault duration up to 0.16 s (shown in value 0.25 p.u.
Fig. 6 by thin lines, in number of cycles n, n = 1, . . . , 8). In the mean time, fast reduction of HVdc-link current means
Therefore, the minimal value of the STATCOM dc-link capaci- fast decay of active power transferred to the HVdc. Since the
tor should be chosen above the given curve for particular value windfarm output power is controlled via relatively slow power
of communication delay. In this case, it is guaranteed that the control loops, it means that STATCOM has to absorb the fast
overvoltage at the end of the fault with specified duration would developing excess of active power in the offshore grid. There-
not exceed the value kV ES dc0 . fore, decrease of STATCOM reactive power demand as earlier is
The derived criterion (7) put additional constrains for ca- compromising on its active power demand and additional over-
pacitor selection by STATCOM manufacturers and should be voltage to the STATCOM dc-link capacitor. It leads to the need
considered together with conventional sizing criteria, such as for extra costs for either the overvoltage-withstanding capacitor
maximum voltage ripple during single- and three-phase local or larger capacitor. To some extent, this can be relieved if after
grid faults. In any case, additional criteria should always be fault detection, the wind farm output is controlled not via power
considered in the context of the designed purpose of the STAT- control loops but via fast DFIG current control loops, putting
COM, which is to provide voltage and reactive power regulation zero demand for generator q-axis current. But due to the dis-
for the adequate operation of the HVdc-link in steady state and tant location of wind turbines from the technological platform
during faults in the onshore grid. (see Fig. 1), there is a communication delay τd before DFIGs
receive a fault detection signal. During this delay, the wind farm
still delivers full output power to the offshore grid. Therefore,
B. Reduction of the STATCOM Rating for Handling Fault the STATCOM rating in order to handle the fault scenario in-
Conditions evitably depends on the value of τd . Consider this effect in
For the case studied, the peak reactive power demand nearly details.
reaches 1.3 p.u. (at HVdc base). This is due to the fact that
the HVdc rectifier ac current become mainly reactive when the
C. STATCOM Rating and Communication Delay
rectifier’s firing angle moves toward 90◦ in attempt to reduce dc-
link current. Therefore, the first natural step to reduce reactive Under normal operation, before the fault occurs, both ac-
power demand during faults is to reduce HVdc dc-link current tive and reactive current components of HVdc rectifier in the

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.
124 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO. 1, MARCH 2008

offshore grid are given as follows [8]:


2 2
IC d = kI0 cos α; IC q = − kI0 sin α (8)
3 3
where k depends on rectifier type and transformer turns ratio.
According to the aforementioned considered measures, imme-
diately as fault occurs (no communication delay within a tech-
nological island), the HVdc dc-link current starts to reduce from
its prefault value I0ini to its final fault value I0fin under controller
action according to ideal loop response:
Fig. 7. Phasors to illustrate STATCOM current demand during fault
I0 (t) = (I0ini − I0fin )e−t/τ C L + I0fin (9) development.

where τC L is an equivalent time constant of closed HVdc dc-


link current control loop. It results in the following voltage at STATCOM current is negligible due to tiny difference between
rectifier dc-side terminals: these two currents (the proportions in Fig. 7 are not kept for
dI0 (t) illustrative purposes). When fault occurs, rectifier current IC
V0 (t) = R0 I0 (t) + L0 is decaying according to (6) and possible phasor trajectory
dt
is shown by dashed line. Due to Kirchhoff, the STATCOM
= (I0ini −I0fin )(R0 −L0 /τC L ) e−t/τ C L +R0 I0fin . (10) phasor should follow the same loci (1–2–3–· · ·–7 as shown in
On the other hand, this voltage is defined by offshore grid voltage Fig. 7), and its final position obviously coincides with the phasor
and rectifier firing angle, namely: IG (but in opposite direction) unless the DFIGs start to reduce
IG . Therefore, if communication delay exceeds some value, the
V0 (t) = kVG d cos α. (11) STATCOM apparent power demand during fault development
may reach the value of apparent power delivered by the wind
Assuming offshore ac grid voltage is under tight control, i.e.,
farm.
VG d ≈ const, one can derive the firing angle as follows:
 
(I0ini −I0fin )(R0 −L0 /τC L ) e−t/τ C L +R0 I0fin D. Further Analysis on STATCOM Rating Reduction
α = arccos .
kr kT VG d After the communication delay τd expires, the STATCOM
(12)
apparent power is still rising, but with lower rate since the wind
Substitution of (12) into (8) results in general expressions for
farm begins to reduce the output. While the development of
HVdc rectifier d- and q-axes current components. For simplified
STATCOM power demand between t = 0 and t = τd is out of
case when I0fin = 0, these expressions are given as
one’s control, it is possible to make this demand having superior
2
2 I0ini (R0 − L0 /τC L ) −2t/τ C L maximum in the vicinity of t = τd and decreasing after this
IC d = e
3 VG d point. This is due to the fact that after this time, one can utilize
reactive power capabilities of the DFIGs front-end converters.
2
2 I0ini (R0 − L0 /τC L ) −2t/τ C L
IC q = − e The reactive current reference for this converter(s) can be set
3 VG d during fault as a function of measured reactive current demand

kr2 kT2 VG2 d e2t/τ C L of the HVdc rectifier together with the ac filters. In other words,
× − 1. (13) front-end DFIGs converters support the STATCOM in reactive
I0ini (R0 − L0 /τC L )2
2
power demand during fault handling. Note that this resource may
These expressions demonstrate some quite important phenom- be limited by wind farm power factor operational constrains.
ena for STATCOM rating studies: the dynamics of HVdc rec- The STATCOM active current component, i.e., its active
tifier ac currents is twice as faster than the dynamics of HVdc power demand can be reduced after t = τd as well. This can
current loop. Indeed, the exponential terms in (13) have now an be achieved if STATCOM is supported in active power balanc-
equivalent time constant as little as τC L /2. It means that when ing by DFIGs through rotor q-current controls. If it was assumed
fault occurs, the STATCOM currents develop twice as faster earlier that q-axis current demand is zeroed during a fault (after
than the HVdc dc-link current decays. Therefore, the communi- communication delay), then in this case, it can be set by mea-
cation delay τd has a crucial role when considering STATCOM sured active current component at the HVdc terminals. Note that
rating. For example, provided the HVdc current loop bandwidth this can result in short-time motoring mode of the DFIG, but
is 40 Hz, by the time when DFIGs start to reduce the output help to reduce windfarm output much quicker.
power in response on fault detection signal (τd = 10 ms), the During our studies, we also found few other measures that
STATCOM will already have to absorb approximately 95% of allowed reducing total STATCOM apparent power demand dur-
delivered by generators power (less losses). This can also be ing faults. For example, HVdc dc-link controller designed for
illustrated using simplified phasors diagram as it is shown in normal operation in standard benchmark model does not pro-
Fig. 7. vide good performance during faults, and dc-link current does
Before fault occurs, the DFIGs deliver current IG to the off- not follow the reference signal. This is due to the fact that the
shore grid, and the HVdc rectifier absorbs the current ICO . The HVdc current loop gain became too low when α ≈ 90◦ and

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.
BOZHKO et al.: LARGE OFFSHORE DFIG-BASED WIND FARM WITH LINE-COMMUTATED HVDC CONNECTION TO THE MAIN GRID 125

Fig. 8. Enhanced system performance during a solid three-phase fault in the onshore grid and fault recovery.

some adaptation is necessary. In our studies, a simple twofold


increase of both proportional and integral gains of PI current
controller results in much better quality of current control dur-
ing faults. Within a reasonable compromise regarding quality
of ac grid control, lowering the bandwidth of voltage/frequency
control loops reduces the STATCOM rating. In our investiga-
tions, the bandwidth of voltage controller was reduced to 50 Hz
for voltage controller and to 30 Hz for grid frequency controller
with acceptable grid control quality during fault. In addition to
all earlier considered measures, one can also impose the hard
limits on STATCOM ac current.
All the considered measures have been implemented in the
Fig. 9. Development of STATCOM apparent power for different values of
PSCAD/EMTDC model similar to one shown in Fig. 4. The communication delay.
performance of proposed enhanced control system has been
verified according to the worst-case fault scenario: three-phase
solid fault occurs in the onshore grid when the wind farm oper- while the HVdc dc-link current loop has an equivalent time
ates at maximum wind speed of 1.3 p.u., duration of fault is 8 constant of 4.5 ms. The discrepancy can be explained by far
cycles (0.16 s), and communication delay is 10 ms. Simulation nonideal performance of the HVdc current loop and noncon-
results are shown in Fig. 8. stant grid voltage during a fault as it was assumed in theoretical
As one can see, the aforementioned proposed enhancements analysis. As one can conclude from Fig. 9, the STATCOM rat-
provide significant reduction of STATCOM rating demanded to ing can be significantly reduced if communication delay is less
handle the faults (peak apparent power demand is reduced from then 4 ms. For example, if τC = 2 ms, the STATCOM apparent
2.1 p.u. in original system down to 1.0 p.u. in the enhanced one. power demand is as little as 0.37 p.u. in peak.
It means that in order to handle the worst-case fault condition The STATCOM dc-link capacitor in the enhanced system is
in the studied power system, the STATCOM should be rated at subject of significantly lower overvoltage (94% in the original
0.5 p.u. assuming standard short time (up to 2s), 200% current system and 23% in the enhanced one). The offshore grid voltage
overloads are allowed. and frequency are kept well below the limits that can lead to
Fig. 9 shows STATCOM apparent power development for the wind farm tripping out. Fault recovery is proceeding quite
different values of communication delay τC . The results con- smoothly: generated from wind and transmitted to the onshore
firm the theoretical study given earlier (13): the general curve grid power increases gradually and no commutation failure in the
behavior is exponential-like with visible effect of 11th and 13th HVdc inverter occurs. Effectiveness of the proposed engineering
harmonics, and with a time constant of approximately 2.5 ms solutions is demonstrated.

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.
126 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 23, NO. 1, MARCH 2008

VI. CONCLUSION [7] P. Cartwright and L. Xu, “The integration of large scale wind power
generation into transmission network using power electronics,” presented
This paper has considered a large offshore wind farm with at the CIGRE Gen. Session, Paris, France, 2004.
an LCC HVdc connection to the main onshore network. The [8] S. V. Bozhko, R. Blasco-Gimenez, R. Li, J. C. Clare, and G. M. Asher,
“Control of offshore DFIG-based windfarm grid with line-commutated
proposed control system provides high-performance control of HVDC connection,” IEEE Trans Energy Convers., vol. 22, no. 1, pp. 71–
the offshore ac grid and guarantees the transfer of generated 78, Mar. 2007.
wind power into the main onshore grid. Engineering issues of [9] R. Pena, J. C. Clare, and G. M. Asher, “Doubly fed induction generator
using back-to-back PWM converters and its application to variable speed
STATCOM sizing are considered and confirmed using simu- wind-energy generation,” Inst. Electr. Eng. Proc.-Electr. Power Appl.,
lations in PSCAD/EMTDC, and recommendations for control vol. 143, no. 3, pp. 231–241, May 1996.
system enhancement are given. The control system studied in [10] M. Szechtman, T. Wess, and C. V. Thio, “First benchmark model for
HVDC control studies,” Electra, vol. 135, pp. 55–73, 1991 (CIGRE
this paper can be a satisfactory solution for integrating large Committee 14).
offshore DFIG-based wind farms into existing ac networks. [11] S. Muller, M. Deicke, and R. W. De Doncker, “Doubly fed induction
generator systems for wind turbine,” IEEE Ind. Appl. Mag., vol. 8, no. 3,
pp. 26–33, May/Jun. 2002.
APPENDIX I [12] PSCAD v.4.1: The professional tool for power system simulation, Mani-
tobe HVDC Research Centre, Winnipeg, MB, Canada, 2004.
POWER SYSTEM PARAMETERS
STATCOM: CS = 20 000 µF; ESo = 35 kV.
STATCOM transformer: 200 MVA; 10/132 kV; 0,12 p.u.
Collector bus transformer: 1100 MVA; 33/132 kV; 0,15 p.u.
HVdc rectifier transformers:
TC 1 : 604 MVA; 33/213 kV; Y/∆; x = 0,18 p.u. Serhiy Bozhko (M’96) received the M.Sc. degree
TC 2 : 604 MVA; 33/213 kV; Y/Y; x = 0,18 p.u. in electrical engineering and the Ph.D. degree in
electrotechnology from the National Technical Uni-
HVdc Link: R0 = 5 Ω; L0 = 1.836 H; I0 = 2 kA. versity of Ukraine, Kiev, Ukraine, in 1987 and 1994,
AC Filters: 250 MVAr at third harmonic; 250 MVAr at 11th/13th respectively.
harmonics and 125 MVAr capacitance bank. Since 1995, he has been a Senior Lecturer in the
Department of Electrical Drives and Automation, Na-
tional Technical University of Ukraine, where since
APPENDIX II 1987, he was a Research Assistant and a Lecturer.
Since December 2000, he has been with the Univer-
CONTROL DESIGN PARAMETERS sity of Nottingham, Nottingham, U.K., where he is
currently a Research Fellow at the School of Electrical and Electronic Engi-
neering. His current research interests include stability of power systems with
DESIGNED CLOSED LOOP NATURAL FREQUENCIES AND PI CONTROLLER distributed generation, intelligent control systems, and variable speed drives.
PARAMETERS

Greg Asher (SM’02–F’07) received the B. Eng.


degree in electrical and electronic engineering from
Bath University, Bath, U.K., in 1976, and the Ph.D.
degree in bond graph structures and general dynamic
systems from Bath University, in 1979.
He was appointed a Lecturer in control in the
School of Electrical and Electronic Engineering, Uni-
versity of Nottingham, Nottingham, U.K., in 1984,
where he developed an interest in motor drive sys-
tems, particularly the control of ac machines. He is
currently the Head in the School of Electrical and
Electronic Engineering, Nottingham, where in 2000, he was appointed as a Pro-
fessor of electrical drives. He is the author or coauthor of over 180 published
research papers, and has received over $5M in research contracts.
Dr. Asher was a member of the Executive Committee of European Power
REFERENCES Electronics (EPE) Association until 2003. He is an Associate Editor of the
IEEE INDUSTRIAL ELECTRONICS SOCIETY, and is currently the Chair of the
[1] European Wind Energy Association. Wind force 12. (2005). [Online]. Power Electronics Technical Committee for the Industrial Electronics Society.
Available: http://www.ewea.org/
[2] N. M. Kirby, L. Xu, M. Luckett, and W. Siepman, “HVDC transmission
for large offshore wind farms,” IEEE Power Eng. J., vol. 16, no. 3,
pp. 135–141, Jun. 2002.
[3] J. Arrillaga, High Voltage Direct Current Transmission, 2nd ed. London, Risheng Li received the B.Eng. degree in measure-
U.K.: Institution of Electrical Engineers, 1998. ment and control in 2002 from Zhejiang University,
[4] P. Cartwright, L. Xu, and S. Sasse, “Grid integration of large offshore wind Hangzhou, China, and the M.Sc. degree in elec-
farms using hybrid HVDC transmission,” presented at the Nordic Wind trical engineering in 2003 from the University of
Power Conf., Chalmers University of Technology, Göteborg, Sweden, Nottingham, Nottingham, U.K., where he is currently
Mar. 1–2, 2004. working toward the Ph.D. degree.
[5] L. Xu and B. R. Andersen, “Grid connection of large offshore wind farms His current research interests include wind farm
using HVDC,” Wind Energy, vol. 9, no. 4, pp. 371–382, 2006. power systems dynamics, control of doubly fed in-
[6] B. R. Andersen and L. Xu, “Hybrid HVDC for power transmission to duction generators (DFIGs), and interaction between
island network,” IEEE Trans. Power Del., vol. 19, no. 4, pp. 1884–1890, a wind farm and a power system when connected to
Oct. 2004. the main grid through high-voltage dc (HVdc) link.

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.
BOZHKO et al.: LARGE OFFSHORE DFIG-BASED WIND FARM WITH LINE-COMMUTATED HVDC CONNECTION TO THE MAIN GRID 127

Jon Clare (M’90–SM’04) was born in Bristol, U.K. Liangzhong Yao received the M.Sc. and Ph.D. de-
He received the B.Sc. and Ph.D. degrees in electrical grees from Tsinghua University, Beijing, China, in
engineering from the University of Bristol, Bristol, 1989 and 1993, respectively, all in electrical power
U.K., in 1979 and 1991, respectively. engineering.
From 1984 to 1990, he was a Research Assistant From 1995 to 1999, he was a Research Associate
and a Lecturer at the University of Bristol, where at Manchester Centre for Electricity Energy, Univer-
he was engaged in teaching and research in power sity of Manchester (formerly UMIST), Manchester,
electronic systems. Since 1990, he has been with U.K., and from 1999 to 2004, he was a Senior Power
the Power Electronics, Machines and Control Group, System Analyst in the Network Consulting Group,
University of Nottingham, Nottingham, U.K., where ABB Ltd., U.K. He is currently a Technology Con-
he is currently a Professor of power electronics and sultant and a Programme Manager at the AREVA
the Head of the Research Group. His current research interests include power T&D Technology Centre, Stafford, U.K., where he is engaged in wind farm grid
electronic converters and modulation strategies, aerospace electrical systems, connections, network engineering design, and consulting for transmission and
variable speed drive systems, and electromagnetic compatibility. distribution systems.
Prof. Clare is a member of the Institution of Electrical Engineers. Dr. Yao is a Chartered Engineer and a member of the Institute of Electrical
Engineers (IEE).

Authorized licensed use limited to: University of Reading. Downloaded on December 4, 2009 at 06:17 from IEEE Xplore. Restrictions apply.

You might also like