Professional Documents
Culture Documents
iIi
FRAMO Important rules for cargo operation
'-- number
3tart and run only required
of power packs.
Run pump at
approximately 80 - 100 bar.
See technical data. Strip against the lowest
possible back-pressure. Stripping
Remember to stop
the power packs, Empty deck line improves
when the cargo pumps stripping result.
have been stopped.
\.....-
For more specific details,
see Framo Service Manual
(0242-0081-3)
No.: 922
ODJ SERVICE MANUAL Date/sign.: 1OSep.9~
FOR Sect.: 5 Page: 1
FRAMO CLOSED CIRCUIT Rev.:
"-"
5.0 NORMAL OPERATION
Once the system is completed and the ship is in service, the hydraulicsystem
should always be kept pressurized by running one of the feed pumps in lowspeed
when main power packs are not running. The reason for this is to avoid the hydral
system being contaminated by cargo through shaft seals on submerged cargo
pumps or by sea- or freshwater through hydraulic oil cooler. In addition, this willgi
a continuous air venting and cleaning/filtration of the hydraulic oil.
That the speed control valve for all consumers are in dosed position.
Note! Never run hydraulic pumps with pressure below 50 bar (impossible if the
system adjustment is correct).
" "
5.1.3 Set the main hydraulic pressure to approximately 15 bar above the highest
consumer (hydraulic motor) if hydraulic oil temperature is above 20°C.
'-../
If the oil temperature is below 20°C, circulate the oil (through the heating and venting
valve installed in the system) for heating with only one power pack running
according to Fig. 1.
(Based upon hydraulic oil viscosity ISO VG46 according to ISO 3448)
Hydraulic oil
temp. (°C)
70 /
20
- 30
Fig. 1
5.1.5 After operation of the system is completed and the main power packs are not to be
used, the system can be stopped as follows:
Note! Always leave one of the feed pumps running in low speed to maintain over- ~
pressure in the hydraulic system.
' "
Note! One of the feed pumps must always be running in low speed and all valves in
main return line and in front of all cargo pumps and other consumers must be
open.
It is important that emergency stop buttons are used in emergency only and not for
operational stop of the system. An emergency stop stresses the system, and should
be avoided:
Emergency stop buttons should be activated when the following conditions occur:
After a shut-down the error must be located and repaired before restart.
For restart: Reset system. Refill oil if necessary in accordance with normal
procedures. Vent the system thoroughly and start up in
accordance with normal procedures.
After service follow the same routines as described above and in separate
instructions in section 8 for the component and/or part of system that has been
serviced.
'-'
This means that if a cargo pump has been serviced, the system must be started up
as a first time start-up of the cargo pump.
Ifthe hydraulic system has been opened, it is crucial that the system is vented and
that the procedure for fillingand venting is followed.
5.4.1 In case of failure to the control system, a manual override panel is located inside the
control cabinet. This panel to be used in a criticalsituation only. Severe damage to
equipment or in worst case personnel injuries may take place by improper use. This
function is accessed by use of key switches/pulse switches on the manual override
panel. Acceptance to be given by authorized personnel before using the manual
override function. After operation, the failure causing use of this mode to be
corrected before further operation of the system. "-""
Examples:
Sensor on oil tank is indicating shutdown level, and it has been verified that
actualleve! is within normal limits.
A limit switch is indicating closed valve and it has been verified that valve is
fully open.
The system will be automatic reset to normal mode one hour after an override
function has been activated without starting any power pack, and automatic reset.
after stopping all power packs after operation. Hence, operator must reinitiate
manual override mode before restarting the system in this mode. Additionally it is
possible to reset manually by activating the reset button for 5 seconds, but only
when the power packs are not running. "-w/
Mode 2 can be used in case of failure to the PLC (Programmable Logic Control).
Note that this mode disables the entire control system except emergency stop
buttons. The system will follow the mode (normal or manual override) given by
position of key switch.
5.4.2.2 Mode2:
. Visual inspection of hydraulic oil level on system tank.
. Visual inspection of position of critical valves, i.e. before oil cooler and after filtE
local service valves for power packs in operation.
"---" After trouble shooting and identification of failure, decision is to be made whether tl
use Mode 1 or Mode 2.
5.4.3.1 Mode 1:
. Open the door to control cabinet for access to manual override panel.
. After operation, the failure causing use of manual override mode to be correcte
' / immediately to avoid unnecessary use of this mode.
5.4.3.2 Mode 2:
. Open the door to control cabinet for access to manual override panel.
'-../
. Operate consumers.
. After operation, the failure causing use of manual override mode to be corrected
immediately to avoid unnecessary use of this mode. PLC failure must be
reported to Frank Mohn Services immediately.
'-'"
5.5 Manual override of pressure controlvalve
Contact Frank Mohn Services for an immediate service assistance to correct the
problem.
'-../
iIi No.9.1993
"-'" Frank Mohn Services AS
FRAMO
~~M~€ ]B.e~~
MAKE YOU UP TO DATE WITH THE LATEST NEWS FROM FRANK MOHN SERVICES AS
CARGO HEATING
OPERATIONAL
ADVICE.
'-'
Heatingbymeansofdeckmountedheatexchangersandforcedcirculationby
FRAMOsubmergedcargopumps.
Advantages
. Smallheatingsurface
- Highefficiency
. Easymaintenance
. "Clean"tanksurface
- Easytankwashing
~
. .
,
FRAMO
\...}
DEARFRAMO- CUSTOMER
SYSTEMADVANTAGES
COMPARED
TOCOILSINTANK
"Clean"tanksurface- easytankwashing.
~
Easymaintenance- on deckonly.
Forcedcirculation
andhighvelocityofcargothroughheatermeanslowersurfacetemperature
and
riskofcarbonising
avoided.
---
HEATINGREQUIREMENTS
INGENERAL
'-'
Mostsystemsaredesignedfor heatingof HFOfrom44° C to 66° C in 96 hours,ambienttemperatureof
air 2° C andsea5° C.
HEATING
ISEXPENSIVE,
SOTHESAVINGS
ACHIEVED
BYFASTERUNLOADING
BYREDUCING
, VISCOSITY,
AREFARLESSTHANTHEMONEY
SPENT
ONHEATING.
'-'
FRAMO
'-'"
OPERATION
OFTHEHEATINGSYSTEM
TYPICALHEATINGPROCEDUREcFOR-TANKERSWiTH COIL
70.0 HEATING& PUMP ROOM CARGOPUMPS
65,0
60.0
u 55.0
c,
~ 50.0
a.:
i1i .5,0
15
C) .0,0
a:
() 35.0
30,0
25,0
20,0
0 . 10 12 14 18 20 22
STARTOF
'-'" I
IlUTAL SAILINGTIME (days) CARGOHEATING
RUNTHEHYDR.SYSTEMECONOMICAllYDURINGCARGOCIRCULATION.
Runningcargopumpsforcirculation
throughheatersrequirehydr.pressureof 40- 60bar.Many
vesselsareequippedwith"lowpressure"powerpacksforthispurpose,butif the"main"powerpacksto
beused,makesurethatsystempressureissetto correctvalue.
'-'
.
FRAMO
.
v
DONOTCOMBINEHEATINGANDDISCHARGING.
Asmentioned,
thecargotemp.willdropby 1-2 0 C perdayonlywithoutheating,sothetemp.drop
duringunloadingtime of a tank is neglectible.Stopheatingandclosevalveson "heatingline",otherwise
mostof the cargowill passthroughheaterand intotank again.
SPECIALCAREWITHSENSITIVE
CARGOES
Notethatascargoispassingtheheatingsurfaceat highvelocity,thetemperature
of heatingmedium
canbekepthigherthanin coilsintank. -.J
STARTI STOPOFHEATING
Toavoid"overheating",
neverheatwithoutcorrectcargoflowthroughheater.
STARTCARGOPUMPBEFORE
VALVEFORHEATING
MEDIUMISOPENED.
SHUTOFFHEATINGMEDIUMBEFOREPUMPISSTOPPED.
CLEANING
OFHEATERS
Theheatersarefittedwithconnections
forsteamcleaning.Washingwaterusedfortankcleaningcan
alsobe pumpedthroughheater,however:Do IlQ1 useseawaterfor cleaningof,FRAMOI BENDEK
heaterbecausestainlessmaterialis verysensitiveto chloridecorrosionat temperaturesabove600C.
----
Drainheaterproperlyafterwards.
I
Yoursfaithfully
pr.FrankMohnServicesAS
5, s~dL\
...............................
SigmundSmedsvik
Headoffice:FrankMohnAS,P.O.Box98, N-5051 Nesttun,Norway, Phone:+47 55 99 90 00, Telefax:+47 55 99 93 80, Telex:42 078 framo n
FrankMohnFusaAS, P.O.Box10, N-5670 Fusa,Norway,Phone:+4755999600, Telefax:+4755999780, Telex:40417 frafu n
FrankMohnFlat")'AS, Flat")',N-5110Frekhaug,Norway,Phone:+4755999400, Telefax:+4755999581
FrankMohnServicesAS, P.O.Box98, N-5051 Nesttun,Norway,Phone:+4755 99 92 00, Telelax:+4755 99 93 82, Telex:42 927 framon
FramoEngineeringAS, P.O.Box174,N-5049 Sandsli,Norway,Phone:+47 55 92 88 00, Telelax:+47 55 92 8900
FrankMohnNederlandBY,Edisonweg18, P.O.Box305, Nl-3200 AHSpijkenisse, TheNetherlands,phone:+31 181 619311,Telefax:+31 181 611193,Telex:29643 framonl ' ,,/
FrankMohnHoustonInc.,P.O.Box1586, LaPorte,Texas77572-1586,USA,Phone:+ 1 281 471 7920, Telelax:+1 281 842 5450, Telex:68 68 120framouw
FrankMohnSingaporePte.ltd., 16 TuasCrescent,Singapore638710,Republicof Singapore,phone+65 861 4455, Telefax:+65 861 5910, Telex:35446 framors :2
FrankMohnAS SwedenOffice,AskimsIndustrivog1 A, S-43634Askim,Sweden,phone:+46 31 682085,Telelax:+46 31 681862 fi
<0
FrankMohnNipponK.K.,6-3, Chojamachi2 - Chome,Naka-Ku,Yokohama231, Japan,Phone:+81 452537155, Telefax:+81 452537188, Telex:3822767 framoi ~
Z
FrankMohnKoreaOffice,Rm.309, YachtingCenterBldg.,1393,Woo-Dong,Haeundai-Ku,Pusan,Korea,phone:+82 51 743 6942/3, Telelax:+82 51 7436944 «a:
'"
f[j
FRAMO
FrankMohn Services AS
"-"
Pumping Theory
Pump Curves
' /
Positive Pumps
Centrifugal Pumps
'-'
A capacity diagram shows the relationShip between 6.2. THE USE OF THE CAPACITY DIAGRAM AND
capacity, head. speed. hydropressure. efficiency etc. THE CORRECTION CHART FOR LIQUIDS WITH
for a certain type of pump. Normally our diagrams HIGH VISCOCITY (drg. 101-101-2).
show head. speed and hydropressure operating at the
hydr. motor in the pumps as a function of the water A capacity diagram shows pumping capacity against
capacity. (Refer diagrams 258-47-4) and 277-1-4 at the discharge head and the corresponding hydr pressure
end of chapter 6). The diagram is based on water pumping (sP. g. 1.0).
When liquids with other sp. g. and/or viscosities shall
6.1. THE DIFFERENCE BETWEEN A POSITIVE be pumped. the data on the diagram must be correct
PUMP, AND A CENTRIFUGAL PUMP. according to the correction charg. drg. no 101-101-2.
To illustrate the use of the capacity diagram see the
The difference between a positive pump (screw pump, diagram in fig. 6.2. which is an example chosen at
piston pump) and a centrifugal pump is shown in d ia- random.
gram 6.1. A and 6.1. B.
As shown in fig. 6.1A the capacity of a positive pump is
almost constant and independent of the head. The
decrease in capacity is very small when the back pres-
sure rises. and this is due to small internal leakages "-'"
in the pump itself.
When looking at fig. 6.1. B. it is seen that the capacity
of a centrifugal pump varies very much with the head.
If the head is very low (when pumping justover the
rail for example) the capacity is large. But if the head
is very high. the capacity reaches zero.
H-Q
'--"
CAPACITY CAPACITY ~
FIG 6.1A FIG.6.1.8.
POSITIVE PUMP CENTRIFUGAL PUMP
'-6.3 RUNNING OF CENTRIFUGAL PUMPS IN Diagr 6.3. B. will do if the pumps are running at the
PARALLEL same speed and if the oillevel in the cargo tanks are
If running two identical centrifugal pumps in parallel almost the same. But if one pump is working under
(ie. on common cargo line) one should believe that worse conditions than the other ones you will have a
the capacity would be.twice as much as for one pump. situation as indicated in diagram 6.3.C
and if running three pumps the capacity would be three
times greater than for one pump and so on, as indi- As you will see the increase in the total capacity is less
cated in diagram 6.3.A. for each pump you connect to the common line than
shown in fig. 6.3.A.
But this is not really true. The reason is that pressure If you connect many pumps to the line. the profit for
losses in the cargo line. which is a function of the the last ones will be almost zero.
capacity, is added to the static head (i.e. the height
between the ship and the cargo tanks ashore) as
shown in diagr. 6.3. B.
a
«
UJ
:r:
STATIC HEAD
I
I
I
I
I
I I
I I
I I
I 1.. L ...
en en en CAPACITY
a.. a.. a.. a..
~ ~ ~ ~
::> ::> ::> ::>
a.. a.. a.. a..
N M '"
FIG.6.3.A.
a
«
UJ
:r:
'-. 5fo<l;<'-
~ HEAD
en en en CAPACITY
a.. a.. a.. a..
~ ~ ~ ~
::> ::> ::> ::>
a.. a.. a.. a..
N M '"
FIG 6.3.8.
r
'-"
"-"
'0
<t:
lJ.J
:r:
STATIC HEAD
0 0- (/) (/)
0-
CAPACITY
z ::2 0-
::J ::2 ::2
z 0- ::J ::J
Z 0- 0-
::J N M
a:
0-
::2
::J
0-
6.3.C.
~.
" '
";"
p o. sOXga
';'
' ,
SG:ilb-l
"/ . , ,i":';~t.
, ,
'
FRAMOPERFORMANCE
DIAGRAMS
',:N.5051.~~E~nUN ~~ORWA V 1400.030 GB
, '
..... , ' : I
PERFORMANCE
DIAGRAM
100
: I"':" "".., .1. ,.., .~,
+"~"';,o"o',;
!:
1;0 and viscosity 1,0 Cst.
Manometer reading at s.g. 1.3 will be: 105 x 1,3 = 13,4 bar}
10.2
minus static head in tank, and cargo pipe lasses.
'--'" 1
I f capacity is increased, speed will drop and capacity and head will fo 11ow a
curve as indicated by curve (B). approx. parallell to the drop Curve (A) for
] fresh water.
1
i
Performance Diagram for FRAMO Pump Drcwrrg no. 0169-0936-4
,.... Pump type : SO 100-4 Order no.: 611586-87/1 No. (rpm) (1<g/dmJ] (cSt)
I 4101. 0.75 I.CO
Imp. (mm] : 220. Construct: 05.1 0.98/HeS 2 4101 I.CO ICO
Driver 3 '110 I - 1 .o.J2 {.o
Remarks : A2FIv12361 S Released : ()~'.10 ..:fi'/#J
. &.A: 21.t7r.,,!'?/j-/<:.-~
(4~~JS4.,,<. W'~r C""""-<..)
8
("")
8
i/ ("")
~ --I
a ./ I
8- ./ I?, ar:
.2
a
"-' £8 aa04
004
s I ~
~ \.o1 ."../.
_..---
150 bar
8 8
~ I
(j'-
~l-- I ! I I ! I l~
g
~~-~
8
'~ ~ '<~~I~- I
- L- - I r.~
8
- I- ~
~ ~
~ ~
a
~ 1 "'! ~ ~ ~I ~I ~' ~
200bar
248 bar i t~a
~~ i I ~I ~~! ~1.0
04 '- I I' 150 ber 04
'--' I D~...,i
0 25
l
50
!..IOO,bC1""!"",,.,lo
75 100 125 150
Flow Q (m3/h)
Performance Diagram for FRAMO Pump Drcwingno. 0169-0937-4
./ Pump type: so 150-5 Order no. : 611586-87/1 ,'\Jo. (rpm) (kg/emJ) (cSt)
t 2857. 0.75 I.CO
Imp. (mm) : 320. Construct: 05.10.98/HeS 2 2857 Ice LCO
Driver : A2FM90 61 3 ~ 1.00
Released: O"!J-.lo.CftJ/#d
Remarks
l2~v. A: 21ooto'H/Jle§" 2351 - '(§)
(A/t:4/ s~ w.c..4t" cf/rv.A.)
8 ,8
C'J
I
i
I
'' I
- ,
a ---
I I
I. fn
8- 246 ber
§ I
I
0
£8
0('1
I
8
('I
150 bar
8 8
0 a
6 50 100 150 200 250 300 350 400 450
Flow Q (m3/h)
-It) It)
U('l ('I
g~
It
\J .......... I
0
~8 I' !8
246 bar
I-'
I
It)
r--.
I
246bar
' I I r--.
It)
0 I I I ILa
It) It)
i,
. . It)
I
i ,I
:t
J 1[('1
I
I
../
I 'I' , , .
II ' , , , , , , 'I
I
I
'" I ' "" ~a
a 50 100 150 300 350 400 450
Flow Q (m3/h)
Performance Diagram for FRAMO Pump Drawing no. 0169-0938-4
"-./. Pump type: so 300-3 Order no.: 611586-87/1 No.
I
(rpm)
1971.
(kg/dm3)
0.75
(cSt)
LCO
Imp. (mm) : 460. Construct: 05.10.98/HeS 2 1971. LCO I.CO
Driver : A2F355.60 3 Iqj1 - \.0.25 ;.0
Remarks Released : C}::.~/o.'f£,/#J
R~J/.A: 23.o~.9'1 H'~s:
(A //.e../ S.t:A .va..f.< r, I./rv'-<.)
8 8
("j
(")
/3~ /'"
~
I I/' /"
0 /' /'" I
I
I/'i
~ 252 bdr
2-
.2
0
>=
?Ii a
~ ci:8 a
oC'j C'j
150 bar
8 8
I
I
i
!
I
--@
0 0
LO LO
0J 0J
is
8,8 8
00J 0J
0
E
"-" Q
o~ ~
8 8
~ ~
0 0
6 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750
Flow Q (m3/h)
~
(]
E
-0
Dn 0
a n
<D
I
0 0
0J 0J
- -
01 I I 1 I I -, '\.1 10
I
I
------I I
I I I
INP5Hj3>
I
I '
'-'" I
a -I ' , , , : ' , , , : ' , , , ' , ,
: . ' , , , , ' , , , ' , , , , ' ,
! ! ., 1 ' , , , ; , , ,, I ' , , , o
0 250 500 750 1ceo 1250 1500 1750 2000 2250 2500 2750
Flow Q (m3/h)
Performance Diagram for FRAMO Pump Drawing
no. 0 169-0940-4
'--/ Pump type: MA 200/150 Order no. : 611586-87/1 No. (rpm) (kg/dmJ) (cSi)
1 26J6. 1.02 ICO
Imp. (mm) : 3CO. Construct: 05.10.98/HeS
Driver:
Remarks A2FM80 61 Released: ,:)!:./"""?,;;/~d
- -@)
8~ I !,
I , I 0
<.0
- -I____L
~
a
~
8-
.28 I I 0
o~ 0
~
E
'-../ ci
0
8 8
8 8
8 8
0 0
6 50 100 150 200 250 300 350 400
<.0 Flow Q (m3/h)
~ , . <.0
0J
"---'"
u
g8 0
a
u~
0
Q) I
<.0
r--.
I
1-
J
i
<.0
r--.
i"'-
0 0
<.0 <.0
<.0 <.0
~ ~
"'--"
0, , i 0
0 50 100 150 200 250 300 350 400
Flow Q (m3/h)
Performance Diagram for FRAMO Pump Drawing no. 0169-0935-4
"-../ Pump type: TK150 Order no. : 611586-87/1 NO. (rpm) (Kg/cmJ) (cSt)
1 J4.38. 0.75 1.00
Imp. (mm) : 225. Construct: 05.10.98/HeS 2 J4.38. 100 1.00
Driver : A2F 56
Remarks Released : Oj~.lo.c??/#~
I I 2
I
~8 I I I I I
8
~C"J C"J
0
0
E 1
"-../ ci
°s;s I I I I f?S
8 8
s;s s;s
a I 0
6 50 100 150 200 250 300 350 460 450
Flow Q (m3/h)
~
u
g<.() <.()
D" "
0
<D
I
a a
<.() <.()
<.() <.()
C"J C"J
""---" .
o. a
a 50 100 150 200 250 300 350 400 450
Flow Q (m3/h)