Company Name Project Author

Project Name Project Part

Spread footing verification Input data


Project Date : 2.11.2005 Basic soil parametres No. 1 2 Silty sand Sandstone Name Pattern ef [] 31.50 45.00 cef [kPa] 0.00 100.00 [kN/m3] 17.50 22.00 su [kN/m3] 7.50 12.00 [] 0.00 0.00

Soil parametres to compute pressure at rest No. 1 2 Silty sand Sandstone Name Pattern Type calculation cohesive cohesive [] [-] 0.30 0.20 OCR [-] Kr [-] -

Soil parameters Silty sand Unit weight : Angle of intern. friction : Cohesion of soil : Deformation modulus : Poisson's ratio : Coeff. of structural strength : Saturated unit weight : Sandstone Unit weight : Angle of intern. friction : Cohesion of soil : Deformation modulus : Poisson's ratio : Coeff. of structural strength : Saturated unit weight :

g = jef = cef = Edef = n = m = gsat = g = jef = cef = Edef = n = m = gsat =

17,50 kN/m 3 31,50 0,00 kPa 21,00 MPa 0,30 0,30 17,50 kN/m 3 22,00 kN/m 3 45,00 100,00 kPa 1000,00 MPa 0,20 0,30 22,00 kN/m 3

Foundation Foundation type: centric spread footing Depth from ground surface hz = 2.00 m Depth of footing bottom d = 1.20 m Foundation thickness t = 0.40 m Incl. of finished grade s1 = 0.00 Incl. of footing bottom s2 = 0.00 Unit weight of soil above foundation = 20.00 kN/m 3 Geometry of structure Foundation type: centric spread footing 1
[Geo 5 - Spread footing | version 5.1.7.0 | hardware key 4001 / 1 | FINE TESTTT | Copyright (c) FINE Ltd. 1990-2005 | www.fine.cz]

Company Name Project Author Spread footing length Spread footing width Column width in the direction of x Column width in the direction of y Spread footing volume Name : Geometry x y cx cy = = = = = 1.50 1.50 0.40 0.40 0.90 m m m m m3 Stage : 1

Project Name Project Part

0.550

+x

0.40 1.50

0.550 +y 0.550 0.40 1.50

0.550

Material of structure Unit weight g = 23.00 kN/m 3 Analysis of concrete structures carried out according to the standard CSN 73 1201 R. Concrete : Concrete B 20 Compressive strength Tensile strength Elastic modulus Rbd = 11.50 MPa 0.90 MPa Rbtd = Eb = 27000.00 MPa

Longitudinal steel : Reinf.bars 10 216 E Tensile strength Rsd = 190.00 MPa Compressive strength 190.00 MPa Rscd = Elastic modulus Es = 210000.00 MPa Transverse steel: Reinf.bars 10 216 E Tensile strength Rsd = 190.00 MPa Compressive strength 190.00 MPa Rscd = Elastic modulus Es = 210000.00 MPa Geological profile and assigned soils Layer No. Assigned soil [m] 1 2 7.00 Silty sand Sandstone

Pattern

2
[Geo 5 - Spread footing | version 5.1.7.0 | hardware key 4001 / 1 | FINE TESTTT | Copyright (c) FINE Ltd. 1990-2005 | www.fine.cz]

Company Name Project Author Load No. 1 2 3 4 Load new change YES YES YES YES Name Zaten slo: 1 Zaten slo: 2 Zaten slo: 3 Zaten slo: 4 Type Design Design Service Service N [kN] 910.00 820.00 700.00 700.00 Mx [kNm] -2.00 0.00 0.00 100.00 My [kNm] 70.00 -100.00 0.00 0.00

Project Name Project Part

Hx [kN] 14.00 0.00 100.00 0.00

Hy [kN] 5.00 0.00 0.00 0.00

Surface surcharges in the vicinity of footing Surcharge No. Name new change 1 YES Surcharge No. 1

xs ys x y [m] [m] [m] [m] 3.00 0.00 2.00 2.00

q [kPa] 0.00

[] 15.00

h [m] 0.00

Ground water table The ground water table is at a depth of 4.00 m from the original terrain. Analysis settings Type of analysis - Analysis for drained conditions Analysis of vertical bearing capacity - CSN 73 1001 Analysis of settlement - Analysis using oedometric modulus (CSN 73 1001) Bounding of influence zone - based on structural strength Soil parameteres are reduced according to CSN 73 1001.

Verification No. 1

Analysis carried out with an automatic selection of the most unfavorable load cases. Computed weight of spread footing G = 22.77 kN Computed weight of overburden Z = 43.47 kN Vertical bearing capacity check Parameters of slip surface below foundation: Depth of slip surface zsp = 2.51 m Length of slip surface lsp = 7.77 m Design bearing capacity of found.soil Rd = 520.10 kPa Extereme contact pressure s = 475.73 kPa Bearing capacity in the vertical direction is SATISFACTORY Horizontal bearing capacity check Earth resistance: at rest Spd = 3.86 kN Design magnitude of earth resistance Friction angle foundation-footing bottom y = 31.50 Cohesion foundation-footing bottom a = 0.00 kPa Horizontal bearing capacity Rdh = 512.06 kN Extreme horizontal force H = 14.87 kN Horizontal bearing capacity is SATISFACTORY Foundation bearing capacity is SATISFACTORY

3
[Geo 5 - Spread footing | version 5.1.7.0 | hardware key 4001 / 1 | FINE TESTTT | Copyright (c) FINE Ltd. 1990-2005 | www.fine.cz]

Company Name Project Author Name : Bearing cap.

Project Name Project Part Stage : 1; Analysis : 1

Delta = 0.87

1.37

1.50

+x

1.50

1.50

Verification No. 2

Analysis carried out for the load case No. 1. (Zaten slo: 1) Computed weight of spread footing G = 22.77 kN Computed weight of overburden Z = 43.47 kN Vertical bearing capacity check Parameters of slip surface below foundation: Depth of slip surface zsp = 2.51 m Length of slip surface lsp = 7.77 m Design bearing capacity of found.soil Rd = 520.10 kPa Extereme contact pressure s = 475.73 kPa Bearing capacity in the vertical direction is SATISFACTORY Horizontal bearing capacity check Earth resistance: at rest Spd = 3.86 kN Design magnitude of earth resistance Friction angle foundation-footing bottom y = 31.50 Cohesion foundation-footing bottom a = 0.00 kPa 4
[Geo 5 - Spread footing | version 5.1.7.0 | hardware key 4001 / 1 | FINE TESTTT | Copyright (c) FINE Ltd. 1990-2005 | www.fine.cz]

+y

Company Name Project Author Horizontal bearing capacity Rdh = 512.06 kN Extreme horizontal force H = 14.87 kN Horizontal bearing capacity is SATISFACTORY Foundation bearing capacity is SATISFACTORY

Project Name Project Part

Verification No. 1
Settlement and rotation of foundation - input data Analysis carried out with an automatic selection of the most unfavorable load cases. Analysis carried out with accounting for coefficient k1 (influence of foundation depth). Stress at the footing bottom considered from the finished grade. Computed weight of spread footing G = 20.70 kN Computed weight of overburden Z = 33.44 kN Settlement of mid point of edge x - 1 Settlement of mid point of edge x - 2 Settlement of mid point of edge y - 1 Settlement of mid point of edge y - 2 Settlement of foundation center point Settlement of characteristic point = = = = = = 5.5 5.5 6.2 4.8 9.6 6.5 mm mm mm mm mm mm

(1-max.compressed edge; 2-min.compressed edge) Settlement and rotation of foundation - results Foundation stiffness: Computed weighted average modulus of deformation Edef = 21.00 MPa Foundation in the longitudinal direction is rigid (k=24.38) Foundation in the direction of width is rigid (k=24.38) Overall settlement and rotation of foundation: Foundation settlement = 6.5 mm Depth of influence zone = 2.86 m Rotation in direction of x = 0.961 (tan*1000) Rotation in direction of y = 2.285 (tan*1000)

5
[Geo 5 - Spread footing | version 5.1.7.0 | hardware key 4001 / 1 | FINE TESTTT | Copyright (c) FINE Ltd. 1990-2005 | www.fine.cz]

Company Name Project Author Name : Settlement

Project Name Project Part Stage : 1; Analysis : 1

OG

FG 2.00

1.20

0.40

2.86

Sigma,z Sigma,or mSigma,or

Dimensioning No. 1

Analysis carried out with an automatic selection of the most unfavorable load cases. Verification of longitudinal reinforcement of foundation in the direction of x Bar diameter = 22.0 mm = 10.00 Number of bars Reinforcement cover = 35.0 mm Cross-section width = 1.50 m 6
[Geo 5 - Spread footing | version 5.1.7.0 | hardware key 4001 / 1 | FINE TESTTT | Copyright (c) FINE Ltd. 1990-2005 | www.fine.cz]

Company Name Project Author Cross-section depth = 0.40 m

Project Name Project Part

Reinforcement ratio 0.63 % > 0.16 % = mst,min mst = Position of neutral axis xu = 0.04 m < 0.19 m = xu,lim Ultimate moment Mu = 229.87 kNm > 132.76 kNm = Md Cross-section is SATISFACTORY.

Verification of longitudinal reinforcement of foundation in the direction of y = 22.0 mm Bar diameter = 8.00 Number of bars Reinforcement cover = 35.0 mm Cross-section width = 1.50 m Cross-section depth = 0.40 m Reinforcement ratio 0.51 % > 0.16 % = mst,min mst = Position of neutral axis xu = 0.03 m < 0.19 m = xu,lim Ultimate moment Mu = 186.20 kNm > 121.09 kNm = Md Cross-section is SATISFACTORY.

Spread footing for punching shear failure check = 820.00 kN Column normal force = 524.80 kN Force transmitted into found.soil Force transmitted by shear strength of SRC = 295.20 kN Maximum shear force Qd = 136.37 kN/m Outline of critical cross-section 3.20 m Shear force transmitted by concrete Qbu = 194.25 kN/m Qd < Qbu => Reinforcement is not required Spread footing for punching shear is SATISFACTORY

7
[Geo 5 - Spread footing | version 5.1.7.0 | hardware key 4001 / 1 | FINE TESTTT | Copyright (c) FINE Ltd. 1990-2005 | www.fine.cz]