Professional Documents
Culture Documents
2010
Cascade control
2010
Cascade Control
d S y d1 S1 d2 S2 decomposed process d3 S3 y3 y u u
y2
Undecomposed process
Cascade control is employed for controlling large and complex processes, where performance of a single controller is not acceptable due to (i) slow closed loop response and/or (ii) high sensitivity to plant gain changes and load/disturbances. In order to employ Cascade Control, there should be at least one measurable intermediate (secondary) variable which affect the primary process variable.
Such processes are called cascade decomposable
Cascade Control-II
The process equation y = f(u,d)
Where u= input, y= primary PV and d is disturbance
May be decomposable as follows y=f3(y3,d3)=f3{f2(y2,d2),d3} = f3[f2 {f1 (u, d1), d2},d3] y2 and y3 are intermediate variables which, in a cascade form, affects y, the primary PV,
d1 S1 d2 S2 d3 S3 y3 y
y2
2010
Cascade Control-III
Cascade control can substantially improve the performance of the controlled system over single-loop control whenever
(1) Disturbances affect the intermediate or secondary process or (2) the gain of the secondary process, including the actuator, is nonlinear.
In the first case, a cascade control system can limit the effect of the disturbances entering the secondary variable on the primary output. In the second case, a cascade control system can limit the effect of gain variations in the actuator or the secondary process on the closed loop performance.
Such gain variations usually arise from changes in operating point due to set point changes or sustained disturbances.
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
Cascade control-IV
The structure of a (two loop) cascade controlled system with two controllers is shown below
Effect reduced by inner loop (2ry controller)
Effect of gain variation reduced by inner loop PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu 2010 (2ry controller)
Cascade control-V
We note the following:
The process is decomposed in two parts sometimes called the main/primary process and the inner/secondary process There are two feedback loops, two controllers and two transmitters The primary controller supplies the set point to the secondary controller - and are in cascade More than two controllers may similarly be cascaded
2010
Cascade control-VI
Official definition:
A cascade control system is a multiple-loop system where the primary variable is controlled by adjusting the setpoint of a related secondary variable controller.
Cascade control-VII
Only one controller, one control loop, one transmitter The sole controller has to take care of the lag and nonlinearity of the valve actuator and that of the heat exchanger
SET POINT
2010
Cascade control-VIII
SETPOINT
2010
10
Cascade control-IX
The secondary loop controls steam flow by directly manipulating the valve The primary loop controls the temperature of the process fluid by demanding appropriate flow of steam from the secondary controller One flow transmitter, one temperature transmitter, one temperature controller and a flow controller are required
SETPOINT
2010
11
Cascade control-X
The input to the FCE can be limited, either at the input or at the output of the 2ry controller. By moving the limiter to the input of the 2ry controller, the secondary PV can also be limited, if desired.
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
12
Effect of gain variations in the secondary part of the process are contained within its own loop. The secondary loop permits an exact manipulation of the flow of mass or energy by the primary controller.
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
13
Advantages-II
With proper tuning of parameters cascade control generally provides faster and more robust performance, without using complex compensators By applying strong (with adequate proportional gain) inner loops the outer loop becomes
less dependent on the plant parameters and nonlinearities Not unduly affected by disturbances of the inner loop
With the use of limiters, the intermediate PVs may be kept within safe limits Cascade control usually provides more meaningful interpretation of the set point variable and the controller outputs.
This helps in understanding as well as applying feedforward compensation.
E.g. in the level control system, the output can be fed forward to the inflow controller
2010
14
Advantages revisited
Better control of the primary variable Primary variable less affected by disturbances Faster recovery from disturbances Reduction of rise time, increased speed of response of the CL system Easier tuning of dynamic performance Provide limits on the secondary variable
2010
15
2010
16
Plants where cascade control is possible The plant can be modelled as a sequence of two or more subsystems each providing the excitation for the next The excitation variable should be measurable Each subsystem should have only one excitation and possible disturbances
2010
17
2010
18
PV
Traditionally feed forward control used the setpoint point signal to directly control the valve, bypassing the controller.
Hence the name Acted as a SP proportional bias Rarely used nowadays
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
19
2010
20
10
Feed Forward-II
Now feed forward mostly uses measurable load and disturbance signals to actuate the FCE Very common in industrial control Used often with cascade control
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
21
The FF controller receives the disturbance measurement, computes control actions to counter its impending impact on the measured process variable, and transmits the result to the FCE. Feed forward is useful when load and measurable disturbances cause substantial change in the PV
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
22
11
Disadvantages
Load must be measurable More transmitters required Cannot be used as stand alone CLAW except for trivial systems
FF gain needs to be changed with change in plant parameter
23
Configuration-1
Measures outlet flow Q2 and adjusts inlet valve by a feed forward controller In an attempt to match the two flows
24
FF
Flow Xmitter omitted for clarity
Q2
12
FF
Q2
25
Q1
FC
Limitation
though the level would remain constant, its exact value is undetermined. The matching cannot be perfect because of
Measurement errors There may be transient mismatch due to valve positioning loop and flow loop.
FF
Q2
2010
26
13
Q1, P1
FT
FC
SP2
FF LC Q2 SP
27
Ratio Control
Ratio control is used to ensure that two or more flows are kept at the same ratio even if the flows are changing. Applications of ratio control:
Maintaining correct air and fuel mixture to combustion. Blending two or more flows to produce a mixture with specified composition for chemical reaction (feed). Blending two or more flows to produce a mixture with specified physical properties. e.g. in lubricant Blending two or more flows to produce a mixture with specified test or flavour
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
28
14
Ratio Control-II
Inflows: Q1 Mixing Or Reaction
Q3 Qn
Q(n+1)
n number of input flows Each assumed to be measurable One input flow cannot be controlled by the ratio control system One outflow
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
29
Ratio Control-III
Several cases may arise for ratio control, for example:
The composition of the mixture may not be measurable with reasonably costly transmitter.
One has to use feed forward control
One of the flows cannot be controlled because the flow is dictated by other conditions (wild flow).
This occurs in neutralizing application, where the quantity of the acidic flow is dictated by production volume. The wild flow is usually not constant and so it must be measured. Only the other (n-1) flows need to be controlled on the basis of measurements
2010
30
15
Ratio Control-V
Flow following configuration The wild flow is measured and this information is used to provide the set-point of the other flow through a flow controller. Requires manual setting of the ratio
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
31
Ratio Control-VI
Configuration with feed back and cascade control. Also called Ratio Relay Control or automatic ratio adjustment The output composition is measured and from this the suitable ratio is inferred by the feed forward controller. From the desired ratio and quantity of wild flow, the set point for the other flow is determined.
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
32
16
2010
33
2010
34
17
2010
35
To Conclude
When designing a control system, be aware of the control objective
Also foresee any possible conflicts
Using a combination of feedback, feed forward, ratio, and cascade control, one can design flexible control systems More complex control systems are harder to tune and model, Complex loop structures are justified where
Performance is important. The complex loop outperforms simpler architectures
2010
PIC Lecture 2010 Prof. T.K.Ghoshal and Prof. Smita Sadhu
36
18