KVA of a single phase transformer = V x A KVA of a three phase transformer = V x A x 1.732, where 1.732 = the sq. root of 3. The square root of 3 is introduced for the reason that, in a three phase system, the phases are 120 degrees apart and, therefore, can not be added arithmetically.

Transformer Short Circuit Test


A convenient method to measure the shortcircuit impedance of a transformer is the voltmeter-ammeter method. This method is applicable to testing either single-phase or three-phase transformers. An AC power source, with a rated frequency of the transformer being tested, is used to drive a current through the impedance. The current and the voltage across the impedance are measured simultaneously. The impedance is then given by the ratio of the measured voltage and current.

Transformer Short Circuit Test


The purpose of this test is to determine the series branch parameters of circuit

Transformer Short Circuit Test


Make sure that the autotransformer can handle the rated current of the primary winding of the transformer under test. Keep the autotransformer output at its lowest setting at the beginning. You need a fairly low voltage to set up the rated current in the primary when the secondary is short-circuited. Adjust the input voltage to the primary winding by adjusting the autotransformer setting until the current in the primary winding is equal to its rated value. Record the voltmeter, ammeter and wattmeter readings.

Transformer Short Circuit Test


Conductors used for short-circuiting the transformer windings should be low-impedance conductor having a cross-section equal or greater than No.1 AWG. They should be as short as possible and be kept away from magnetic masses. This is to minimize the loading effect of the connecting wires to the impedance the transformer being measured.

Transformer Testing
R Y B N R

3 PHASE RECTIFIER

CHOKE + IGBT CHOPPER

3 PHASE IGBT POWER INVERTER

Y B

NI Based Measurement System

+
NI cDaq

NI Based Measurement System


NI cDAQ-9178 NI Compact DAQ 8-Slot Chassis Built-in BNC connections for external clocks and triggers (up to 1 MHz) Run analog input modules at different rates with multiple timing engines Four general-purpose 32-bit counter/timers built into chassis (access through digital module) NI-DAQmx driver with LabVIEW SignalExpress LE Windows 7 OS support Hi-Speed USB with NI signal streaming technology

NI Based Measurement System


NI 9215 4-Channel, 100 kS/s, 16-bit, 10 V Simultaneous Sampling Analog Input Module 4 simultaneously sampled analog inputs, 100 kS/s -40 to 70 C operating range NIST-traceable calibration Hot-swappable operation 16-bit resolution

NI Based Measurement System


NI 9265 4-Channel, 100 kS/s, 16-Bit, 0 to 20 mA Analog Output Module

0 to 20 mA output range, 16-bit resolution Open-loop detection with interrupt, 0.0 mA power-on Hot-swappable operation 4 analog outputs, 100 kS/s, simultaneously updated -40 to 70 C operating range NIST-traceable calibration

NI Based Measurement System


NI 9474 8-Channel 5 to 30 V, 1 s, Sourcing Digital Output Module 8-channel, 1 s high-speed digital output 5 to 30 V, sourcing digital output -40 to 70 C operating range Extreme industrial certifications/ratings Hot-swappable operation

Transformer Testing - Costing


NI 9215 NI 9265 NI 9474 cDaq 9178 NI 9901 Freight Application Software 30690.00 23320.00 18480.00 67540.00 3080.00 1200.00 144310.00 135000.00 279310.00

NI Based Measurement System


CONTACT VI AUTOMATION (P) LTD C/2, APNA GHAR HOUSING SOCIETY, SHANKARSHETH ROAD, PUNE 411042 PH: + 91 20 6400 2256 / 7 FAX: + 91 20 2645 1554 www.viapl.com kaustubh@viapl.com

You might also like