Consumer Meter specification with ABT Feature

Product General Specifications


Model Mk6E Make Wallaby Reference frequency 50Hz, Variation.- 5% Rated voltage - 3x110V Ph-Ph, 3x110V/ 3 Ph-N, Secondary Current : 1. Model A: Class 0.2S, Ib:-/1A, Imax: 2A, 3P4W, Vn: 3 x 63.5V, 50Hz 2. Model B: Class 0.2S, Ib:-/5A, Imax: 10A, 3P4W, Vn: 3 x 63.5V, 50Hz 3. Model C: Class 0.2S, Ib:-/1A, Imax: 2A, 3P3W, Vn: 2 x 110V, 50Hz 4. Model D: Class 0.2S, Ib:-/5A, Imax: 10A, 3P3W, Vn: 2 x 110V, 50Hz Reference frequency 50Hz, Variation.- 5% 4 True Quadrant measurements - Fundamental Integration interval for Load survey are configurable(Default 15mins) User friendly LCD Display configurable. Auxiliary Voltage 110-240VAC/DC Built in calendar and clock.

Measurand (s)
Time, Date, Frequency, Power ON/OFF hours. Instantaneous Voltage, Current Power Factor(Lag/lead) Average Frequency coding for billing (Two Digit code 00 to 99 for frequency from 49.0 to 51.0Hz) Energy parameters kWh, kVArh, kVAh both Imp & Exp, Power (kW, kVAr, kVA) Fundamental Energy, Power kVArh at 103% (High) voltage and 97% (low) voltage Net Wh register during successive 15 mins Block, upto second decimal, with + sign for Export and - sign for Import. Wallaby Metering Systems Pvt. Ltd. Page 1 of 4

Consumer Meter specification with ABT Feature


Cumulative Wh register at each midnight in six digit including one decimal Cumulative VArh register for Voltage High condition at each midnight in six digit including one decimal

Cumulative VArh register for Voltage low condition at each midnight in six digit including one decimal For Model A & C measurement of Wh, Var and VArh will be computed directly in CT and VT secondary quantities. These quantities will be directly recorded, displayed in meter and BCS
For Model B & D measurement of Wh, Var and VArh will be computed directly in CT and VT secondary quantities. These quantities will be directly recorded, displayed in meter but in BCS the active energy will be displayed as one fifth of the Wh computed in CT and VT Secondary quantities.

Compatible Standards o IS 14697:1999 o IEC 62052-11,62053-22 o CBIP Temperature Range o Operating o Storage Communication o o o o o Optical Port- IEC 1107 Remote-Modem(GPRS/GSM) - Internal Modem Power supply RS 232 RS485 (Optional) CMRI ASCII Format Incorporated. : -25 to +60 C : -25 to +80 C

Wallaby Metering Systems Pvt. Ltd.

Page 2 of 4

Consumer Meter specification with ABT Feature


Available Surveys
Load Surveys - Readings are stored every 15 minutes for a period of 40 days. 1 2 3 Record No. Date and Time Net Wh(Fund) 4 Frequency Code 5 Status indication

Status Indication: VT failure - * Time retard - rr Time advanced - aa

Daily Survey - Readings are stored every 1440 minutes (00.00 hours) for a period of 40 days. 1 Net Wh (Fund) Total 2 Cumulative Net Wh (Fund) (6 Digit with 2 Decimal) 3 4 Cum VArh High (6 Digit with 2 Decimal) Cum VArh Low (6 Digit with 2 Decimal)

Event Log - An Event Log records events that occur to the meter and the time at which they occur. A total of 100 entries can be stored. 1 System events 2 Power off/on events 3 Battery/FLASH events 4 Meter Extension events 5 Meter Database events 6 Time events 7 EFA events 8 Firmware Change events 9 Firmware Change events

10 Billing events 11 Automatic billing reset events 12 Manual billing reset events 13 TOU cleared events 14 diagnostic events 15 user events 16 Script events

Wallaby Metering Systems Pvt. Ltd.

Page 3 of 4

Consumer Meter specification with ABT Feature


LCD Display Parameters 2-Line by 16 Character Display with backlight MODE A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Serial No. Current Date Current time NET Wh Previous 15 Mins Avgerage frequency Previous 15 Mins NET Wh Average % Voltage Reactive Power Import VArh High Import VArh Low Export VArh High Export VArh Low Net VArh High Net VArh Low Voltage Healthy 16 17 18 19 20 21 22 23

MODE B
Export Wh Import Wh Export VAh Import VAh Import VArh Lag Import VArh Lead Export VArh Lag EXport VArh Lead

LCD Display Settings Cyclic Rate in Sec(1 to 255 Seconds) Display Revert in Mins(1 to 255 Minutes) Hold time in Secs (0 to 255 Seconds) Back light On time (1 to 254 Secs)

Config 15 Secs 15 Mins 60 Secs Always

Wallaby Metering Systems Pvt. Ltd.

Page 4 of 4