You are on page 1of 92

Medium Voltage Distribution

PIX High

Air-insulated switchgear 1217.5 kV ( 50 kA)

Assembly Operation Maintenance Technical Manual


No. AGS 531 502-02 Edition 03/2010

www.schneider-electric.com

Schneider Electric 35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France www.schneider-electric.com Manufacturer: Schneider Electric Energietechnik Sachsenwerk GmbH Service: Should you have any queries regarding our Service, please do not hesitate to contact: Schneider Electric Energietechnik Sachsenwerk GmbH

Schneider Electric All rights for this Technical Manual reserved. Reproduction and distribution of this Technical Manual - completely or partially - to third parties is prohibited. Only reproduction of this Technical Manual in full is admissible subject to the written approval of Schneider Electric Energietechnik GmbH Sachsenwerk Mittelspannung. Electronic copies, e.g. in pdf format or as a scanned version, have the status for information only. The Technical Manuals which are exclusively valid are always supplied by the manufacturer together with the product in question.

PIX

Content

Remarks on this manual......................................................................... 6 Purpose and target group ......................................................................... 6 Reference documents ............................................................................... 6 Terms and symbols used .......................................................................... 7 Any questions or suggestions? ................................................................. 7 1 2 Safety provisions ........................................................................... 8 Design and description ................................................................. 9

2.1 Panel design..................................................................................... 9 2.2 Panel variants..................................................................................11 2.2.1 Branch-circuit panels with switching devices..............................11 2.2.2 Metering panel / bus riser .......................................................... 12 2.2.3 Panels for bus section coupler .................................................. 13 2.3 Dimensions and weights ................................................................ 14 2.4 Applied standards........................................................................... 15 2.5 Environmental and operating conditions ........................................ 15 2.6 Design data of the PIX High series ................................................ 16 2.7 Nameplate ...................................................................................... 16 2.8 Technical data of electrical control and operating devices............. 17 2.9 Intended use................................................................................... 18 2.10 Disposal after the end of service life .............................................. 18 3 3.1 3.2 3.3 Packaging, transport, storage .................................................... 19 Shipping units ................................................................................. 19 Transport ........................................................................................ 20 Warehousing .................................................................................. 20

4 Access to the main circuit compartments 21 4.1 Safety provisions and important information .................................. 21 4.2 Access to the circuit-breaker compartment .................................... 21 4.2.1 Opening and closing the front door ........................................... 21 4.2.2 Removing and connecting the low-voltage connector ............... 22 4.2.3 Removing the truck from the panel ........................................... 23 4.2.4 Inserting the truck into the panel ............................................... 24 4.3 Access to cable connection compartment ..................................... 26 4.3.1 Removing cable compartment cover ......................................... 26 4.3.2 Access via the circuit-breaker compartment (optional) ............. 26 4.4 Access to the busbar compartment ............................................... 27 5 Assembly ...................................................................................... 28 5.1 Safety provisions ............................................................................ 28 5.2 Important instructions for assembly ............................................... 28 5.3 Requirements regarding the switchgear room ............................... 29 5.4 Transport of the panels and trucks on the construction site .......... 33 5.5 Mounting the switchgear end plates .............................................. 35 5.6 Aligning and fastening panels ........................................................ 36 5.7 Screw-fastening the panels to one another ................................... 38 5.8 Busbar assembly ............................................................................ 40 5.8.1 Access to the busbar compartment ........................................... 40 5.8.2 Busbar compartment section segregation (optional) ................. 40 5.8.3 Busbar assembly ....................................................................... 41 5.9 Mounting the earth bar ................................................................... 45 5.10 Mounting the fan ............................................................................ 46 5.11 Mounting the deflectors .................................................................. 47 5.12 Assembly of the pressure relief duct .............................................. 49

AGS 531 502-02

PIX

Content (contd.)

6 6.1 6.2 6.3 6.4 7 7.1 7.2 8 8.1 8.2 8.3 8.4 9 9.1 9.2 9.3 9.4

High-voltage connection ............................................................. 50 Overview of cable connection variants .......................................... 50 Overview for fully insulated busbar connection.............................. 51 Mounting the high-voltage cables .................................................. 52 High-voltage connection on rear side of switchgear panel (optional) .... 54 Low-voltage terminal ................................................................... 56 Connection of the ring circuits in the low-voltage cabinet.............. 56 Placing external cables in the switchgear panel ............................ 56 Commissioning ............................................................................ 57 Final steps ...................................................................................... 57 Checking switching functions and interlocks ................................. 58 Power frequency test of busbar (optional) ..................................... 58 Cable test after assembly............................................................... 60 Voltage Detecting Systems (VDS) .............................................. 61 Pluggable voltage detection system............................................... 61 Integrated voltage detection system IVIS (optional) ...................... 61 Voltage detection system VOIS+ (optional) ................................... 62 Phase comparators ........................................................................ 62

10 Operation ...................................................................................... 63 10.1 Operating interface of the panel..................................................... 63 10.2 Trucks for PIX High Panels ............................................................ 64 10.3 Operation accessories.................................................................... 66 10.4 Interlocks ........................................................................................ 67 10.4.1 Internal mechanical interlocks in the panel ............................... 67 10.4.2 Electromagnetic interlocks (optional) ......................................... 67 10.4.3 Interlock with padlock ................................................................ 68 10.4.4 Interlock with cylinder lock (optional) ......................................... 69 10.5 Operating specifications ................................................................. 70 10.6 Operating the circuit-breaker .......................................................... 70 10.6.1 Charging the circuit-breakers energy storing device ................ 70 10.6.2 Switching the circuit-breaker manually ...................................... 71 10.6.3 Switching the circuit-breaker electrically.................................... 72 10.6.4 Position indicators on circuit-breaker and possible operating sequences.................................................................................. 72 10.7 Move truck into operating/disconnected position ........................... 73 10.7.1 Racking-in the truck from disconnected into service position ... 73 10.7.2 Racking-out the truck from service into disconnected position . 73 10.8 Vacuum contactor CVX .................................................................. 74 10.9 Operating the earthing switch manually ......................................... 76 10.9.1 Switching earthing switch ON .................................................... 76 10.9.2 Switching the earthing switch OFF ............................................ 76 10.10 Standard switching operations ................................................... 77 10.10.1 Operating the outgoing feeder cable ......................................... 77 10.10.2 Earthing the outgoing feeder cable............................................ 77 10.10.3 Coupling busbar sections using the bus section coupler ......... 78 10.11 Earthing the busbar ................................................................... 79 10.11.1 Earthing a busbar section by means of the bus section coupler .....79 10.11.2 Earthing the busbar with the circuit-breaker of a branchcircuit panel .......................................................................................... 80 10.11.3 Earthing the busbar with busbar earthing switch....................... 80 10.12 Panel with fan attachment ......................................................... 81

AGS 531 502-02

PIX

Content (contd.)

11 11.1 11.2 11.3 11.4 11.5 11.6 11.7 11.8

Maintenance .................................................................................. 82 Safety provisions ............................................................................ 82 Maintenance and servicing specifications ...................................... 82 Cleaning ......................................................................................... 83 Avoiding condensation ................................................................... 83 Corrosion protection ....................................................................... 83 Replacement of components and panels....................................... 83 Lubrication instructions................................................................... 84 Replace fuses for voltage transformer ........................................... 85

12 Annex ............................................................................................ 86 12.1 Auxiliary products ........................................................................... 86 12.2 12.3 12.4 12.5 12.6 How to treat the contact surfaces .................................................. 86 Specifications for screw connections ............................................. 87 Required tools (not included in the scope of supplies) .................. 87 Transport trolley for truck ............................................................... 88 List of assembly drawings .............................................................. 89

Notes....................................................................................................... 90

AGS 531 502-02

PIX

Remarks on this manual

As our products are subject to continuous further development, we reserve the right to make changes regarding standards, illustrations and technical data. All dimensions specified in this manual are in millimeters.

Purpose and target group


This Technical Manual describes installation, operation and maintenance of airinsulated medium-voltage switchgear units of the series PIX High. It is exclusively intended for use by the manufacturers staff or by persons certified for the PIX High series (training certificate). The work described in this manual may only be performed by specialist electricians with proven experience regarding the PIX High series (training certificate) all relevant safety provisions. This Technical Manual is an integral part of the product and must be stored such that it is at all times readily accessible for and can be used by persons who are to work on the switchgear. If the switchgear is relocated to another site, this Technical Manual must be passed on to the new operators along with the unit. This Technical Manual cannot describe every imaginable individual case or every customer-specific version of the product. For information which is not included in this manual, please contact the manufacturer. This Technical Manual does not include information regarding the safety of buildings in case of internal faults (pressure load of the switchgear room and necessary pressure relief ports). Pressure calculations for switchgear rooms incl. recommendations regarding pressure relief ports can be provided on request against a fee. For further details, please contact the manufacturer.

Reference documents
The following additional documents must be complied with: Purchase agreement containing the stipulations on the specific equipment of the switchgear and the legal details the switchgear-specific circuit diagrams / documentation the operating manuals of the low-voltage devices installed in the switchgear (e.g. voltage presence indicating systems, devices in lowvoltage cabinet) the assembly drawings supplied with the switchgear the Operating Instructions of the trucks used: Circuit-breaker HVX (No. AGS 531 461-01) Metering truck MTX (No. AGS 531 361-01) Isolating truck UTX (No. AGS 531 361-01) Vacuum contactor CVX (12kV) (No. NTV 133 2E) the Assembly Instructions of the manufacturer of the cable connection systems to be connected to the switchgear

AGS 531 502-02

PIX

Remarks on this manual (contd.)

Terms and symbols used


This manual uses certain terms and symbols. They warn about dangers or provide important information which must be complied with in order to avoid danger to persons and damage to equipment:

Danger! This danger symbol warns about dangerous electrical voltage. Contact with voltage may result in fatal injury! Warning! This danger symbol warns about the risk of injury. Please comply with all the provisions identified by this symbol in order to avoid death or serious injury. Warning! This danger symbol warns about the risk of falling. Important:

This instruction symbol is used for information which is important to avoid material damage.

Any questions or suggestions?


Do you have any questions or suggestions regarding this manual, or do you require further information? We always strive to provide you with the best-possible information for optimum, safe use of our products. Thus, do not hesitate to contact us if you have any recommendations, amendments or proposals for improvement.

AGS 531 502-02

PIX

Safety provisions

The work described in this manual may only be performed by specialist electricians who have proved their experience with the PIX High series and the applicable safety provisions. Please read the whole manual carefully before working on the switchgear.

Applicable standards and regulations:


Metal-enclosed AC switchgear for rated voltages > 1 kV up to including 52 kV: IEC 62271-200 The locally applicable accident prevention, operating and work instructions must be complied with. Assembly and maintenance: IEC 61936-1/HD 637 S11 Operation of electrical equipment: EN 50110-11 1 The national standards applicable in the country where the equipment is to be installed must be complied with. Before performing work on the panel, it is essential that you comply with the following instructions:

Danger! Risk of fatalities due to high voltage. Isolation from high voltage and earthing must always be ensured before performing assembly or maintenance work. Warning! After the removal of covers from a switchgear unit, operator safety regarding internal arcs may be reduced unless the switchgear is isolated from the power supply. Optimum operator safety is only ensured if the switchgear is completely isolated from the power supply and earthed during assembly or maintenance work. Danger! Risk of fatalities due to supply voltage. Isolation from supply voltage before must always be ensured before performing assembly or maintenance work. Warning! Risk of injury due to movable parts in mechanical drives. For maintenance work, - isolate from supply voltage - release the circuit-breakers energy storing device by switching it OFF-ON-OFF - close via the make-proof earthing switch. Behaviour in case of incidents or accidents
For the case of an internal fault, the PIX High switchgear features pressure relief ports which prevent the panels and the switchgear unit from bursting. In case of fire or of internal faults, toxic and caustic decomposition products may be produced. Comply with the locally applicable accident and safety provisions. In case of personal injury, take first-aid measures or cause them to be taken.

AGS 531 502-02

PIX

Design and description

2.1 Panel design

Fig. 1 Branch-circuit panel PIX High with circuit-breaker truck HVX 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Low-voltage cabinet Circuit-breaker truck HVX Front door with nameplate Earthing switch position indicator Voltage detection system Operator interface of the earthing switch Cable compartment cover Voltage transformer (optional) Cable connection compartment Current transformer Make-proof earthing switch Shutter Busbar compartment Circuit-breaker compartment

AGS 531 502-02

PIX

Design and description (contd.)

Panel description
10

9 1

8 7 2

6 5 4

Fig. 2 Branch-circuit panel with circuit-breaker truck HVX 1 2 3 4 5 6 7 8 9 10 Busbars Earthing switch Current transformer Voltage transformer (optionally with fuses) Cable compartment cover Cable connections Door of circuit-breaker compartment Circuit-breaker truck HVX Low-voltage cabinet Fan (Ir = 4000 A)
12 11

Fig. 3 Panel with internal arc classification (IAC) 11 Deflector 12 Pressure relief duct 10 AGS 531 502-02

PIX

Design and description (contd.)

2.2

Panel variants

The illustrations show the panel types with their respective basic equipment without pressure relief duct or deflectors. Customized models or add-on elements are described in the switchgear-specific documentation.

2.2.1 Branch-circuit panels with switching devices


Single Line Sectional view Panel Description

Branch-circuit panel Circuit-breaker truck HVX (1) optional voltage transformer (2) with fan for Ir = 4000 A (not shown)

1 2

Branch-circuit panel Isolating truck UTX (1) Earthing switch (2) optional current and voltage transformers (not shown)

Motor Control Center (only 12 kV) Vacuum contactor CVX (1) optional current transformer (2)

AGS 531 502-02

11

PIX

Design and description (contd.)

2.2.2 Metering panel / bus riser


Single Line Sectional view Panel Description

Metering panel Metering truck MTX (1) optional busbar earthing switch (2)

Bus riser optional earthing switch (1) optional current transformer (2) optional voltage transformer (3)
1 2 3

12

AGS 531 502-02

PIX

Design and description (contd.)

2.2.3 Panels for bus section coupler


Single Line Sectional view Panel Description

2 3

Bus section coupler panel Circuit-breaker truck HVX (1) optional earthing switch (2) optional current transformer (3) with fan for Ir = 4000 A (not shown)

Bus section coupler panel Isolating truck UTX (1) optional earthing switch (2) optional current transformer (3)

2 3

Bus section coupler panel with riser Metering truck MTX (1)

Bus section coupler panel with riser

AGS 531 502-02

13

PIX

Design and description (contd.)

2.3

Dimensions and weights


B 1590 1590 760

630/730

Fig. 4 Dimensions of PIX High Panels

Panel type

Branch current [A]1


630 1250 1600 2000 2500 2500 3150 4000 < 2500 > 2500 < 2500 > 2500 < 400 -

Width B [mm]
800 800 800 800 800 1000 1000 1000 800 1000 800 1000 800 -

approx. weight [kg]2


< 1000 < 1000 < 1200 < 1200 < 1300 < 1400 < 1500 < 1600 < 650 < 750 < 750 < 850 < 900 + approx.120

Panel with circuit-breaker truck HVX

Direct bus riser panel without truck Panel with isolating truck UTX or metering truck MTX Panel with vacuum contactor CVX (only 12 kV) 3x voltage transformer (optional)
1 2

Busbar rated current max. 4000 A incl. low-voltage cabinet with average extent of equipment mounted, incl. shutters or pressure relief duct The busbars have been taken into consideration with a maximum weight at 4000 A.

2330/2430

2900/3000

2820

2840

14

AGS 531 502-02

PIX

Design and description (contd.)

2.4

Applied standards

Switchgear units of the PIX High series are metal-enclosed; loss of service continuity category acc. to IEC 62271 200: LSC 2B-PM type-tested tested for internal faults (qualification IAC AFLR) dimensioned for indoor installation

PIX High switchgear units meet the following standards and regulations:

Designation
Switchgear Internal arc classification (IAC) Circuit-breaker Earthing switch Isolating truck Current transformer Voltage transformer Voltage detection systems Protection against accidental contact, foreign bodies and water Vacuum contactor High-voltage fuse link

IEC standard
IEC 62271-200 IEC 62271-1

EN standard
EN 62271-200 EN 62271-1

IEC 62271-200 IEC 62271-100 IEC 62271-102 IEC 62271-102 IEC 60044-1 IEC 60044-2 IEC 61243-5 IEC 60529 IEC 60470 IEC 60644 IEC 60282

EN 62271-200 EN 62271-100 EN 62271-102 EN 62271-102 EN 60044-1 EN 60044-2 EN 61243-5 EN 60529 EN 60470 EN 60644 EN 60282

Degree of protection against accidental contact and foreign objects


Degrees of protection against accidental contact and foreign objects according to IEC 62271-200 and IEC 60529
Degree of protection of switchgear enclosure Degree of protection of the accessible claddings in the panel
1

IP3X1 IP2X

other values available on request

2.5 Environmental and operating conditions


PIX High is an indoor switchgear and may only be operated under normal conditions in acc. with IEC 62271-1. Operation under conditions deviating from these is only admissible subject to consultation with and written approval from the manufacturer.

Temperature class Min./max. ambient temperature Average value over 24 hours Average rel. humidity: 24 hour/1 month Installation altitude above sea-level
1

Ambient conditions in accordance with IEC 62271-1


C C % m Minus 5 indoors1 5/+401 351 95/ 90 10001

other values available on request

AGS 531 502-02

15

PIX

Design and description (contd.)

2.6

Design data of the PIX High series


[kV]
[kV] [kV] [A] [A] [A] [kA] [kA] [kA] [Hz]

Rated voltage Ur

12
75 28 (422)

17,5
95 38 (452)

Rated lightning impulse withstand voltage Up Rated power frequency withstand voltage Ud Busbar Rated normal current Ir Branch-circuit panel Vacuum contactor

<3150/40001/50002 <3150/40001/50002 <400 A <130 <50 <50 (3 s) 50 (602) -

Rated peak withstand current Ip Rated short-circuit breaking current Isc Rated short-time current Ik Rated frequency fr
1 2

with fan on request

2.7

Nameplate

The type designation of the switchgear panels on the nameplate Fig. 5 specifies essential technical data. When submitting enquiries to the manufacturer or ordering spare parts, the following information is required: Type designation Serial number Year of construction

1 2 3

Fig. 5 Nameplate on panel front 1 2 3 4 Type designation Serial number Year of construction Technical data

16

AGS 531 502-02

PIX

Design and description (contd.)

2.8 Technical data of electrical control and operating devices


The switchgear panels have been designed on principle so as to permit manual operation. The drive mechanisms of the individual switching devices can be equipped, depending on the specific customers model, with additional electrical control and operating devices. These are defined in the switchgear-specific circuit diagram (see switchgear documentation). Component fitting options: Motor drive for actuation of the earthing switch Blocking coil The blocking coil prevents manual actuation of the earthing switch. If the supply voltage has failed or is shut off, all blocking coils are in blocked position. Auxiliary switches Auxiliary switches are always actuated directly by the truck or by the switch shaft via an intermediate linkage. Their position always corresponds to that of the main contacts. The switching functions have been set in the factory according to the circuit diagram. Micro switches are used depending on the customized panel models.

Overview of rated supply voltages


Overview of rated supply voltages
Direct voltage DC Alternating voltage AC [V] [V] 24 48 (110)/120 60 110 125 (220)/230 220

Power consumption
Device
Blocking coil Motor for earthing switch

Power consumption
DC approx. [W]
12 150

AC 50/60 Hz approx. [VA]

Information about the power consumption of solenoids and the motor is available from the manufacturer. The supply voltage data is required to this effect.

Technical data - auxiliary switch for earthing switch


Rated supply voltage
Switching capacity (NC contact) Time constant T = L/R

[V DC]
[A] [ms]

220
2 20

Truck
Electrical control and operating devices of trucks are described in the appropriate Technical Manuals (see Reference documents on page 6). Circuit breaker HVX: see Technical Manual AGS 531 461-01 Isolating truck UTX/Metering truck MTX: see Technical Manual AGS 531 361-01 Vacuum contactor CVX: see Technical Manual NTV 133-2E

AGS 531 502-02

17

PIX

Design and description (contd.)

2.9

Intended use

Air-insulated medium-voltage switchgear units of the PIX High series are designed exclusively for switching and distributing electrical power. They may only be used in the scope of the specified standards and the switchgear-specific technical data. Any other utilization constitutes improper use and may result in dangers and damage.

Disclaimer of liability
The manufacturer shall not be held responsible for damage which occurs if instructions in this Technical Manual are not complied with; the switchgear is not operated according to its intended use (see above); the switchgear is assembled, connected or operated improperly; accessories or spare parts are used which have not been approved by the manufacturer; the switchgear is converted without the manufacturers approval, or if inadmissible parts are added. No liability is accepted for parts provided by customers, e.g. current transformers.

2.10

Disposal after the end of service life

A material and recycling data sheet can be provided on request for the disposal of switchgear units of the PIX High series at the end of their service life. Disposal is performed as a service by the manufacturers Service Center and is subject to a fee.

18

AGS 531 502-02

PIX

3 Packaging, transport, storage


3.1 Shipping units

The conditions and types of transport have been stipulated in the contract details. The type of packaging depends on the type of transport and the storage conditions. The panels are delivered individually and are fastened on pallets. The standard accessories are included. In the case of panels with a width of 800 mm, the trucks can be delivered within the panels. They are in disconnected position. With 1000 mm wide panels, the trucks are delivered in separate packaging. The panels are delivered in upright position.

Important:

The weight of the entire transport unit is indicated on the packaging.

Packaging
If packed exclusively for truck transport, the panels are delivered on a pallet with PE protective film (Fig. 6). For sea transport, the units are packed in sealed aluminium foil with desiccant and in a closed wooden case with tightly closed wooden base (also for container transport, Fig. 7). In case of air transport, the panels are packaged in wooden crates with a protective PE film hood (dust protection) or in wooden crates, also with closed wooden bases, however without protective hoods (dust protection, Fig. 7).

Fig. 6 Packed in PE protective film on a pallet

Fig. 7 Packed in a wooden case AGS 531 502-02 19

PIX

3 Packaging, transport, storage (contd.)


3.2 Transport
Warning! Danger due to load tipping over. Transport units must be secured sufficiently during transport to prevent slipping and tipping over. Transport using a forklift truck
The panel may only be transported on a pallet. The entire length of the forks must be placed under the transport unit (Fig. 9).

Fig. 8 Transport units must not be allowed to tip over

Fig. 9 Transport using a forklift truck

Delivery
Handle shipping units carefully when unloading and unpacking them. Shipping units must be checked upon receipt. Any damage which may have occurred in transit must be recorded and reported to the manufacturer immediately. Check completeness of consignment based on the transport documents. The supplier must be notified in writing without delay about any possible deviations.

3.3
40 C

Warehousing
Warning! Risk of accidents. Sufficient stability and evenness of the supporting area (floor) must be ensured.

-5 C

Fig. 10 Schematic diagram of storage conditions for PIX High panels 20

If the panels are not installed immediately after delivery, they can be stored under the following conditions: Panels must be stored in vertical position, and must not be stacked. Storage only admissible indoors. Switchgear panels and accessories must be sealed with desiccant in aluminium foil and be packed in a wooden crate (storage for max. two years after the date of packaging).
AGS 531 502-02

PIX

4 Access to the main circuit compartments


4.1 Safety provisions and important information
Warning! Risk of injury due to non-respect of the safety provisions in Chapter 1, page 8.
The panels may be equipped with additional cylinder locks to lock the cable compartment cover and the front door. In this context, refer also to Chapter 10.4.4 as of page 69 Interlocks with cylinder lock.

Important:

4.2 Access to the circuit-breaker compartment


Danger! Risk of fatalities due to high voltage. The front door may only be opened if the truck is in disconnected position (see Chapter 10.7.2, page 73).

4.2.1 Opening and closing the front door


Opening the front door
Insert the door handle into the door opening and turn it upwards (Fig. 11). The door is lifted. To open the door, swing it to the left (Fig. 12).

Fig. 11 Insert the door handle and turn it upwards

Fig. 12 To open the door, swing it to the left

Closing the front door


Close the door completely. Turn the handle downwards; the door is lowered. Pull door handle off and stow it in the tool tray of the trolley (see Chapter 12.5 as of page 88).

AGS 531 502-02

21

PIX

4 Access to the main circuit compartments (contd.)


4.2.2 Removing and connecting the low-voltage connector
Important:
The low-voltage connector can only be removed or inserted while the truck is in its disconnected position.

Removing the low-voltage connector


Pull interlocking slide of low-voltage connector forward and remove the connector (Fig. 13). Stow low-voltage connector in storage tray above the truck (Fig. 14).

Fig. 13 1 Interlocking slide

1 2

Fig. 14 1 2 Storage tray Low-voltage connector

Connecting the low-voltage connector


Remove low-voltage connector from the tray above the truck. Insert low-voltage connector into the truck and press interlocking slide forward.

22

AGS 531 502-02

PIX

4 Access to the main circuit compartments (contd.)


4.2.3 Removing the truck from the panel
3

Fig. 15 Coupling the trolley to the panel 1 Adjust the trolley to the appropriate panel width 800/1000 (see Chapter 12.5 on page 88). 2 Turn the lever on the trolley clockwise in order to lift the table. 3 Push the trolley right up to the panel.

Fig. 16 4 Turn the lever counter-clockwise in order to lock the trolley to the panel. Ensure it is locked. 5 Turn the interlocking lever on the truck upwards by 90 in order to unlock the truck in the panel. 6 Pull the truck carefully onto the trolley to its stop.

AGS 531 502-02

23

PIX

4 Access to the main circuit compartments (contd.)

Fig. 17 7 Turn the interlocking lever on the truck back to the right in order to lock the truck to the trolley. 8 Turn the lever on the trolley clockwise in order to lift the transport table. 9 Remove the trolley from the panel.

Now the truck can be raised by means of a crane, if required, and deposited. Additional information is also given in Chapter 5.4. as of page 33. For further information regarding lifting and transporting the trucks (HVX, UTX, MTX, CVX), please refer to the appropriate Operating Instructions.

4.2.4 Inserting the truck into the panel


Important:
Optionally, trucks and panels can be given matching coding. This is to prevent a truck from being racked completely into a panel if the ratings do not match.

Fig. 18 Moving the truck to the front of the panel using the trolley 1 Turn the lever on the trolley clockwise in order to lift the transport table. 2 Push the trolley right up to the panel.

24

AGS 531 502-02

PIX

4 Access to the main circuit compartments (contd.)

Fig. 19 3 Turn the lever on the trolley counter-clockwise in order to lock the trolley to the panel. Ensure it is locked. 4 Turn the interlocking lever on the truck upwards by 90 in order to unlock the truck on the trolley. 5 Rack the truck carefully into the panel.

Fig. 20 6 Turn the interlocking lever to the right in order to lock the truck in the panel. 7 Turn the lever on the trolley clockwise in order to lift the transport table. 8 Remove the trolley from the panel.

AGS 531 502-02

25

PIX

4 Access to the main circuit compartments (contd.)


4.3 Access to cable connection compartment
Danger! Risk of fatalities due to high voltage. The cable connection compartment may only be opened if the earthing switch is ON (see Chapter 10.9.1, page 76).

4.3.1 Removing cable compartment cover


Release the securing bolts and keep them in a safe place (Fig. 21, item 3). Lift and remove the cable compartment cover (4). The cable connection compartment is now accessible from the front.

Mounting the cable compartment cover


After completing assembly work, place cable compartment cover onto the panel, lower it and re-fasten it using the securing bolts.

4.3.2 Access via the circuit-breaker compartment (optional)


Remove truck from the panel (see Chapter 4.2.3, page 23). Remove the base plate from the circuit-breaker compartment: Release all securing bolts from the base plate (1). Remove the base plate carefully (2). The cable connection compartment underneath is now accessible from the top.

Fig. 21 Access to cable connection compartment 1 Remove the 15 self-locking screws 2 Remove the base plate 3 Release the bolts from the cable compartment cover 4 Lift and remove the door

Re-mounting the base plate


After completion of assembly work, re-insert the base plate and fasten it by means of the bolts.
26 AGS 531 502-02

PIX

4 Access to the main circuit compartments (contd.)


4.4 Access to the busbar compartment
Danger! Risk of fatalities due to high voltage. The busbar compartment may only be opened if the busbar is earthed (see Chapter 10.11, page 79).
Open the front door and remove the truck from the panel (see Chapter 4.2, page 21). De-mount cladding between busbar compartment and circuit-breaker compartment (Fig. 22 and Fig. 24). The busbar compartment is now accessible.

Fig. 22 Remove truck (1) and partition plate (2)

Fig. 23 Posture of worker during busbar mounting and panel fastening

Fig. 24 De-mounting the cladding between busbar compartment and circuit-breaker compartment 1 Release all securing bolts. 2 Tilt the cladding and remove it in forward direction.

Re-mounting the partition plate


After completion of assembly work, re-insert the partition plate and fasten it by means of the bolts.
AGS 531 502-02 27

PIX

Assembly

5.1

Safety provisions

The switchgear panels may only be installed and assembled by the manufacturers staff or by persons who have been certified for this work. PIX High panels are delivered with the earthing switch ON. In the case of panels with a width of 800 mm, the trucks can be delivered within the panels. They are in disconnected position. The circuit breakers are always shipped in open state (OFF) with the energy storing device released.

Warning! Risk of injury due to movable parts in mechanical drives. The circuit-breakers energy storing device and the earthing switch must not be tensioned during assembly. Warning! Risk of accidents! Watch out for floor openings in the switchgear room Warning! The top sides of the panels are not meant to be walked on. Persons may fall through them, get injured or may damage the panel. When work has to be performed on the panel top - e.g. assembly of deflectors, fans or pressure relief ducts - temporarily position a solid base plate to step on. Warning! Risk of injury in case of non-compliance with the safety instructions on page 6.

5.2

Important instructions for assembly


Important:
- Condensation, dirt and dust during assembly should be avoided on all accounts, in order to prevent damage to the panels. - For assembly, observe the assembly drawings supplied with the equipment. Read them before you commence assembly work. The drawing numbers are specified in this manual in the description of the assembly work in question. - For all screw connections, refer to the tightening torques specified in the Annex.

28

AGS 531 502-02

PIX

Assembly (contd.)

5.3 Requirements regarding the switchgear room


Before installing the switchgear panels, make sure that the switchgear room is checked according to the switchgear documentation (Fig. 25). Observe the minimum distance between the switchgear and the wall of the building. The load-bearing capacity of the fastening areas must correspond to the weight of the switchgear (perform a stress analysis of the building). Check base frame (if used) for dimensions and positional tolerances. Check position of floor openings for high-voltage and low-voltage cables. Before the swichgear is positioned at its site of installation, check that the fastening points are level. Unevenness must not exceed 2 mm/meter and 6 mm difference in height over the entire switchgear width.

Important:

Observe switchgear-specific space assignment plan.

100

35

35

1000
Fig. 25

1000

800

800

860

Dimensions in the switchgear room (example) 1 2 3 Deflectors Panels Switchgear room

AGS 531 502-02

29

PIX

Assembly (contd.)

Switchgear with rear wall-mounting and deflectors

200

1590

1500(1900) 1

Fig. 26
1

For panel replacement, 1900 mm are required.

Switchgear for free-standing installation within the room, with deflectors

2330 2890 3500


1000 1590 1500(1900)1

Fig. 27
1

For panel replacement, 1900 mm are required.

Switchgear with rear wall-mounting, deflectors and installation face-to-face

200

2300

2890

1590

2000

3500

2330 2890

3500

1590

200

Fig. 28 30 AGS 531 502-02

PIX

Assembly (contd.)

Switchgear with rear wall-mounting and pressure relief duct

2330

2820 2
2 1500(1900)
2330 3300 1

200

1590

1500 (1900)

Fig. 29
1 2

lower room height on request For panel replacement, 1900 mm are required.

Switchgear for free-standing installation within the room, with pressure relief duct

800

2820

1590

Fig. 30
1 2

lower room height on request For panel replacement, 1900 mm are required.

AGS 531 502-02

1 3300

31

PIX

Assembly (contd.)

100

35 100

1 820 620

35 4
1550

50

1000 1

800 2 3

152

140

275
105 105 105

275
1533 105 105 105

210 1/2 3/4 5/6 7/8

210
1590

1 2 3 4 70

1590

490

70
200

90

30

20

200

30

490

680

67

480
20

30

50

50

40

2 1000

2 800

Fig. 31 Dimensions of the site of installation in the switchgear room (example) 1 2 3 4 5 6 7 8 Bore-holes for fastening of panel Opening for routing external low-voltage cables Opening for routing high-voltage cables Further dimensional diagrams for cable or fully insulated bus connector versions are available on Switchgear end plate Base frame, width: 100 mm Base frame, width: 50 mm Rear gap cover Front gap cover 32

40

request.

AGS 531 502-02

435

525

200

PIX

Assembly (contd.)

5.4 Transport of the panels and trucks on the construction site


Warning! Make sure the rope or chain is strong enough to bear the weight of the panel and the trucks. Comply with the relevant provisions for hoisting equipment. Warning! On lowering the panels and the trucks, make sure that the supporting platform is sufficiently stable and even. Warning! Risk of accidents. Pay attention to floor openings! Transport of panel by means of a crane
Take the four jack rings for crane transport (included in the accessories) out of their packaging (Fig. 32). Remove transport packaging and protective film from the panel. Insert the jack rings on the four fastening points at the top of the panel and secure with one bolt each (Fig. 32). Attach 4 crane ropes/chains (observing minimum carrying capacity and length, Fig. 33). Lift the panel carefully. Release the screw-fastenings between the lateral fixing brackets on the pallet and on the panel. Deposit the panel carefully on the floor at the intended site of installation.

1.5 m

1 2
Fig. 32 Jack rings for crane transport and fastening points at the panel Fig. 33

The ropes must have the following minimum lengths/release the screwfastenings between the fixing brackets and the panel 1 2 Fixing brackets Pallet

AGS 531 502-02

33

PIX

Assembly (contd.)

Transport of the panel on the floor


If the panel needs to be moved on the floor: Use three rollers with a minimum diameter of 30 mm (Fig. 34). Evenness and stability of the supporting area (floor) must be ensured. Move the panel on the rollers to its final site of installation.

Fig. 34 Transport on rollers

Transport of the trucks


Lift circuit-breaker acc. to Fig. 35. To this effect, three ropes (no metallic steel ropes) of 1215 mm or straps are required.

Fig. 35 Lifting and depositing the HVX circuit-breaker AGS 531 502-02

34

PIX

Assembly (contd.)

5.5

Mounting the switchgear end plates


Important:
If the switchgear is to be placed in the corner of a room, the appropriate end plate must be mounted first.

Assembly drawing: AGS C73040-01

The left-hand and the right-hand end plates are mounted identically. First mount the rear, then the front end plate, as shown in Fig. 36.

Fig. 36 Mounting the end plates (shown: mounting the end plates on the left-hand switchgear end) 1 2 Front switchgear end plate Rear end plate

AGS 531 502-02

35

PIX

Assembly (contd.)

5.6 Aligning and fastening panels


Important:
The position of the first panel is decisive for placement of the subsequent panels, thus it is essential that measuring is effected with the utmost precision! Position first panel on the foundations in accordance with the switchgearspecific space assignment plan. Remove cable compartment cover (see Chapter 4.3.1, page 26). Align panel. Check the panel front for correct horizontal and vertical position. If applicable, lift the panel and place shims in the direct vicinity of the fastening areas, until the horizontal position has been reached. Screw-fasten the panel to the two fastening points provided on the front and to at least one fastening point on the rear (see also Fig. 31 on page 32).

Fastening on concrete foundations


(Assembly drawing: SEM 102 173-01) Hex. bolt M 10 x 30 + dowel pin

Sectional drawing

1 2 3

4 5 Top view

Fig. 37 Fastening of panels on concrete foundations 1 2 3 4 5 Hex. bolt M 10 x 30 Lock washer ES 10 Washer ES 12 Dowel pin 0, 1 or 2 shims

36

AGS 531 502-02

PIX

Assembly (contd.)

Fastening on base frame


Screws, bolts and accessories are not included in the scope of supplies. Drill boreholes ( 8.5 mm) into the base frame at the intended panel fastening points (Fig. 38). Cut threads M 10 in the boreholes. Screw-fasten panel to the frame.

Sectional drawing

1 2 3

4 Top view

Fig. 38 Panel fastening on base frame 1 2 3 4 5 6 Hex. bolt M 10 Lock washer ES 10 Washer ES 12 0, 1 or 2 shims Base frame Fastening points

Additional fastening variants


Further fastening variants are available on request. Please contact the manufacturer. Panel fastening with seismic qualification or vibration-proof characteristics can be supplied on request. For further details, please contact the manufacturer.

AGS 531 502-02

37

PIX

Assembly (contd.)

5.7

Screw-fastening the panels to one another

Assembly drawing: AGS C73038-01 Position the next panel next to the previous one in accordance with the assignment plan and align it.

Connecting points
Screw-fasten the two rear connecting links from the inside of the busbar compartment to the two panels (Fig. 39). Access to the busbar compartment: see Chapter 4.4 page 27. Screw-fasten the panels to one another at the front using 7 self-locking screws M 8. Screw-fasten low-voltage cabinets to one another using self-locking screws M 8.

3 4

Fig. 39 Screw-fastening the switchgear panels 1 2 3 4 Thread cutting screw M 8 Connecting piece Hex. bolt M 6 with lock ring Hex. bolt M 8

38

AGS 531 502-02

PIX

Assembly (contd.)

Upper gap cover


Assembly drawing: AGS C73 479-01 Fasten one cover plate on the top between the panels with 6 bolts M 6 respectively (Fig. 40).

Rear gap cover (only if IAC AFLR is to be ensured)


Assembly drawing: AGS C73 483-01 Fasten one cover plate on the rear between the panels with 24 bolts M 8 respectively.

Fig. 40 Gap cover between panels 1 2 3 Upper gap cover Rear gap cover Bolt M 6

AGS 531 502-02

39

PIX

Assembly (contd.)

5.8

Busbar assembly

5.8.1 Access to the busbar compartment


See Chapter 4.4 page 27.

5.8.2 Busbar compartment section segregation (optional)


The section segregation for the busbar compartment and for the bus section coupler is mounted to the right-hand panel side (except for the right-hand end panel) (Fig. 41). Normally, the busbar segregation plate is pre-assembled in the factory. Mounting the bushings:

Type of busbar
Ir (busbar) 1250 A (2 x 80 x 10) 1600 A Ir (busbar) 2500 A (3 x 80 x 10) 3150 A Ir (busbar) 4000 A (4 x 80 x 10)

Assembly drawing
AGS C73044-01 AGS C73044-02 AGS C73044-03

2 3

Fig. 41 Busbar compartment section segregation 1 2 3 4 5 Lock ring Fastening Partition plate Bushing Right-hand panel side platee

40

AGS 531 502-02

PIX

Assembly (contd.)

5.8.3

Busbar assembly

Assembly drawings for busbar assembly

Switchgear panel

Branch-circuit panel
Ir (panel) 1250A or metering panel

Branch-circuit panel
In (busbar) 1250A (2x80x10) 1600A Ir (busbar) 2500A (3x80x10) 3150A Ir (busbar) 4000A (4x80x10) 1600A Ir (busbar) 2500A (3x80x10) 3150A Ir (busbar) 4000A (4x80x10) 3150A Ir (busbar) 4000A (4x80x10) Ir (busbar) 1250A (2x80x10) 1600A Ir (busbar) 2500A (3x80x10) 3150A Ir (busbar) 4000A (4x80x10) 1600A Ir (busbar) 2500A (3x80x10) 3150A Ir (busbar) 4000A (4x80x10) 3150A Ir (busbar) 4000A (4x80x10) Ir (busbar) 1250A (2x80x10) 1600A Ir (busbar) 2500A (3x80x10) 3150A Ir (busbar) 4000A (4x80x10) Ir (busbar) 1250A (2x80x10) 1600A Ir (busbar) 2500A (3x80x10) 3150A Ir (busbar) 4000A (4x80x10)

Assembly drawing
AGSC73032-01 AGSC73032-02 AGSC73032-03 AMT003246-02 AMT003246-03 AGSC73032-07 AGSC73032-04 AGSC73032-05 AGSC73032-06 AMT003246-08 AMT003246-09 AGSC73032-08 AMT003246-07 AGSC73753-02 AMT003246-08 AGSC73753-02 AGSC73032-08 AGSC73753-01 AMT003246-07 AMT003246-08 AGSC73032-08

Center panel

1600A Ir (panel) 3150A 4000A Ir (panel) 5000A Ir (panel) 1250A or metering panel

End panel

1600A Ir (panel) 3150A 4000A Ir (panel) 5000A

Bus section coupler

Bus riser; bus riser with UTX or MTX

Arrangement of busbars in branch-circuit panels

Number of busbars per phase


2
1 Number of outgoing feeder bars per phase 2 3150 A
4000 A

L1

L2/L3

AGS 531 502-02

41

PIX

Assembly (contd.)

Important:

- Comply with the specifications on treatment of contact surfaces and the tightening torques for busbar screw fastening in the Annex. - Remove transport spacers Fig. 42. - Comply with the position and direction of screws and nuts as shown in the diagram (Fig. 43).
1

Fig. 42 1 Remove transport spacers

L1

L2

L3

Fig. 43 Illustrated: Busbar fastening in the left-hand end panel Ir busbar: 16002500 A Ir branch-circuit panel: 16003150 A

42

AGS 531 502-02

PIX

Assembly (contd.)

Busbar link

L1

4 6

4 5 3

L2 2 L3

Fig. 44 Busbar link in a center panel Ir busbar: 31504000 A Ir branch-circuit panel: 16003150 A 1 2 3 4 5 6 7 Busbar Intermediate copper layer Hex. socket bolt M 10 Washer Lock washer Nut M 10 Outgoing feeder bar

AGS 531 502-02

43

PIX

Assembly (contd.)

L3 L2 L1

6 2 4 5

Fig. 45 Busbar assembly in a bus section coupler Example: Ir busbar: 31504000 A 1 2 3 4 5 6 Busbar Intermediate copper layer Hex. socket bolt M 10 Washer Lock washer Outgoing feeder bar

44

AGS 531 502-02

PIX

Assembly (contd.)

5.9

Mounting the earth bar

(Assembly drawing: AGS C73 030-03) The earth bars are screw-fastened from panel to panel by means of connecting bars (Fig. 46 and Fig. 47).

Important:

Comply with the specifications on treatment of contact surfaces and the tightening torques for screw fastenings in the Annex. Clean all contact areas of the connecting bar and the appropriate earth bar in the switchgear panels and coat them with synthetic lubricant (see Chapter 12.2, page 86). Slip the connecting bar into the adjacent panels supporting structure through the cutout in the panel. Screw-fasten connecting bar on both sides to the earth bar in question. Connect earth bus to the earthing system of the switchgear building. (Connecting lines and screw accessories are not included in the scope of supplies).

Important:

Observe the specific standards referring to earthing systems which apply in the country in question.

Fig. 46 Connecting the earth bars 1 2 Connecting bar Screw connection: Bolt M 10 + lock washer + washer

Fig. 47 Connection of the switchgears earth bus to the building earth 1 2 3 AGS 531 502-02 Connecting bar Connection points for the building earth End plate with marked cutout

45

PIX

Assembly (contd.)

5.10

Mounting the fan

Assembly drawing: AGS C73 488-01 The fan with capacitor, air flow sensor and supporting frame is pre assembled. The pre-assembled fan is included in the standard accessories. Fasten the pre-assembled fan above the opening in the panel top by means of self-locking screws, as shown in Fig. 48. Connect the cabling in the low-voltage cabinet, as shown in the assembly drawing.

2 5 4 3

Fig. 48 1 2 3 4 5 Fan Securing bolts Supporting frame Air flow sensor (in the supporting frame) Cabling

46

AGS 531 502-02

PIX

Assembly (contd.)

5.11

Mounting the deflectors

Deflectors are required to ensure operator safety in the case of internal faults in accord. with IEC 62271-200. IAC: Internal arc classification

Fig. 49 Example 1: the switchgear is positioned in the left-hand corner of the switchgear room. It is accessible on the front and on one side (in this case the right-hand side). IAC: AFL

Fig. 50 Example 2: the switchgear is positioned at the wall of the switchgear room, accessible on the front and on both sides. IAC: AFL

Fig. 51 Example 3: the switchgear is positioned in the center of the switchgear room, accessible on the front, on the rear and on both sides. IAC: AFLR

AGS 531 502-02

47

PIX

Assembly (contd.)

Assembly drawings for mounting the deflectors: Switchgear front and rear side: Switchgear side: Gap covers between switchgear and building wall: Lateral deflector adjustment in the case of elevated low-voltage cabinet: AGS C73 566-01 AGS C73 566-02 AGS C73 566-02 AGS C73 566-03

Important:

Check the correct position of deflectors and the gap covers in the switchgear documentation before mounting them. The deflectors and gap covers are mounted identically on the left-hand and the right-hand sides.

Fig. 52 Lateral gap cover on a switchgear without lateral access (illustrated showing the left-hand side)

Fig. 53 Lateral deflector and gap cover on a laterally accessible switchgear (in this example: on the right side)

48

AGS 531 502-02

PIX

Assembly (contd.)

5.12 Assembly of the pressure relief duct


The pressure relief duct on the upper side of the panel ensures operator safety in accordance with IEC 62271-200 in the case of internal faults. With a pressure relief duct installed, the switchgear can be accessible on general from the front, the rear and both sides. IAC (= Internal arc classification): AFLR.

Important:

Before mounting the pressure relief duct, comply with the appropriate specifications in the customer-specific switchgear documentation. Each panel must be equipped with the pressure relief duct matching the panel width (800 or 1000 mm). Assembly drawings: AGS C73 475-01 Connection between two channel sections: AGS C73 478-01 Left-hand or right-hand channel end plate: AGS C73 476-01 Extension of the pressure relief duct (identical on the left and right): Left-hand or right-hand connecting piece: Mounting the extension duct (depending on the length: 400/800/1000 mm): Pressure relief flap at the end of the pressure relief duct: or connecting piece for connection of a customer-specific pressure relief duct:
AGS C 74 010-01 (optional) AGS C 73 475-01

AGS C73 480-01 AGS C73 481-XX AGS C73 012-03 AGS C74 010-01

AGS C 73 476-01

AGS C 73 478-01

Extension duct (400, 800, 1000 mm) Bottom of the extension duct AGS C 73 012-03

AGS C 73 481-XX

AGS C 73 480-01

Fig. 54 Assembly of the pressure relief duct

AGS 531 502-02

49

PIX

High-voltage connection

6.1

Overview of cable connection variants


In panel [A]
630 1250 1600/2000 2500 3150 4000

Panel width [mm]


800 800 800 800 1000 1000 1000

Cables per phase


1/2/3/4 2/3/4 3/4 1 / 2 / 3 / 4 (5-8)1 6/8 6/8 8

Special attachment

Fig. 55 Panel illustration

Overview of connecting brackets available for cable connection


1-4 cables per phase max. 500 mm2 cable
50

534.5
6-8 cables per phase max. 500 mm2 cable
50 50

6-8 cables per phase max. 630 mm2 cable


125

17

17

17

20

20

20

13

(534.5)

(534.5)

13

50

13

(534.5)

75

50

AGS 531 502-02

PIX

High-voltage connection

(contd.)

6.2 Overview for fully insulated busbar connection


Technical specifications and assembly
For the customized technical design of a fully insulated busbar connection, please consult the manufacturer. Assembly is effected in accordance with the specifications of the manufacturer of the fully insulated busbars.

Fig. 56 Busbar connection in the front of the cable connection compartment

Panel width: 800 mm; rated current 2500 A


Panel illustration Connecting brackets
80

Base plate

200

200

40

14

(522)

45
482

745

Panel width: 1,000 mm; rated current 4,000 A


Panel illustration Connecting brackets
100
275

Base plate
275

14

19

130

(522)

40

745
715

160

20-40

55

715

AGS 531 502-02

482

170

19

51

PIX

High-voltage connection

(contd.)

6.3
67

Mounting the high-voltage cables

Clamping assemblies for high-voltage cables, screws, bolts and plastic sleeves are included in the accessories.

Access to cable connection compartment


See Chapter 4.3, page 26.

Preparation
1

Remove the base plates (Fig. 57).

Fig. 57 1 Base plates in the cable connection compartment

Mounting the cable box Warning! Danger due to contact corrosion in case of inadmissible matching of materials! Do not use aluminium cable lugs for the cable connection.
Route the individual cables outwards through the cable connection compartment of the panel to enable assembly of the cable ends (Fig. 58). Cut the plastic sleeves to fit the cable diameter, and slip them onto the cables. Strip cable ends and assemble the cable box as specified by the cable manufacturer.

Fig. 58 Cable routing

52

AGS 531 502-02

PIX

High-voltage connection

(contd.)

Connecting the cables


- Unless otherwise specified by the cable manufacturer: Comply with the specified tightening torques and pre-coat contact areas (see Chapter 12.2, page 86). - Observe the phase grouping of the switchgear panel. Fasten the individual cables to the appropriate connection surfaces (Fig. 59, item 1). Re-mount the base plates (3). Fasten high-voltage cables to the floor opening using clamping assemblies (Fig. 59, item 2, and Fig. 60/Fig. 61). Connect the ground wires to the panel rack (4).

Important:

Fig. 59 High-voltage connection 1 2 3 4 Cable connection on the panel Clamping assembly for the cables Base plates Connection of the ground wires to the panel

Clamping assembly for the cables

Fig. 60 Clamping assembly for cables with a diameter of 40 mm

Fig. 61 Clamping assembly for cables with a diameter of < 40 mm AGS 531 502-02 53

PIX

High-voltage connection

(contd.)

6.4 High-voltage connection on rear side of switchgear panel (optional)


Panels can be extended optionally by a metal-clad rear cable connection compartment (Fig. 62 to Fig. 65). This rear connection compartment permits connection to high voltage behind the panel. High-voltage cables or external conductor bars can be routed in from the top or from the bottom alike. The variants of the cable connection options (depending on the rated nominal current) correspond to the explanations in Chapter 6.1, page 50.

Important:

Please clarify further technical details and design specifications with the manufacturer, as required. A dimensional drawing (AGSC73653-05) can be provided on request.

Basic design of the rear cable connection compartment

Fig. 62 Rear connection module (example: high-voltage cable routed from the top) 1 2 3 4 5 6 High-voltage cables Rear cable connection compartment Cable connections Terminal contacts Conductor bars Current transformer

The connection of the rear cable connection compartment to the panel was designed symmetrically and, on principle, does not depend on whether cables or fully insulated busbars are routed from the top or from the bottom. In both versions, turning by 180 on site is possible, if required. The preassembled sheet metal housing of the rear cable connection compartment is screw-fastened to the panel on the construction site.

54

AGS 531 502-02

PIX

High-voltage connection

(contd.)

The current transformers in the cable connection compartment (Fig. 62, item 6) are located in the same position as they are in the standard panel. The conductor bars (5) are routed from the current transformer to the rear and coupled to the appropriate terminal contacts (4) for the high-voltage connection in the rear cable connection compartment. The front earth bus has an outgoing feeder to the rear into the rear cable connection compartment, where a separate earth bar for earth connectors is located. In the case of several adjoining rear cable connection compartments, these rear earth bars must be connected to one another.

Further variants:

Fig. 63 Rear cable connection compartment with high-voltage cables routed from the bottom

Fig. 64 Rear cable connection compartment with fully insulated conductor bar connection from the top

Conductor bar connection from the rear


Rear metal housing and supply conductor bars are not included in the scope of supplies. A dimensional drawing incl. the specified connecting points for conductor bars and metal housings can be provided on request.

Fig. 65 Rear cable connection compartment with conductor bar connection. Only schematic illustration, as the components specified are not included in the standard range of products 1 AGS 531 502-02

Supply conductor bars


55

Metal housing

PIX

Low-voltage terminal

7.1 Connection of the ring circuits in the low-voltage cabinet


Route the ring circuits for the interpanel wiring through the lateral openings of the low-voltage cabinet (Fig. 66). Connect ring circuits to the appropriate terminal strips in the low-voltage cabinet according to the circuit diagram.

2 2 2 1 2

2
Fig. 66 Connection of low-voltage cable 1 2 Terminal strip Openings for ring circuits in the low-voltage cabinet

7.2 Placing external cables in the switchgear panel


Customized low-voltage cables for control and measuring purposes can be placed for each panel on the left inside of the panels to the lowvoltage cabinet (Fig. 67). Remove the metal cable duct covers on the left inside of the panel (3, 4). Route external cables (5) from the cable basement through the cutout in the panel floor (6) and route them in the cable duct to the low-voltage cabinet. Fasten cables to the panel using cable clamps (2). Connect external cables to the terminal strip in the low-voltage cabinet according to the circuit diagram (1). Reposition cable compartment covers.

5 6

Fig. 67 Placing external cables in the switchgear panel 1 2 3,4 5 6 Connection to terminal strip in the low-voltage cabinet Cable clamp Cable duct covers Bus riser in cable duct Cutout in the panel floor

Important:

If the cables are to be routed into the low-voltage cabinet from above, the cable fastening and protection equipment must be provided by the customer.

56

AGS 531 502-02

PIX

Commissioning

8.1

Final steps
Danger! The high-voltage supply must not be connected. All active parts must be earthed. Important:

Whenever you detect anomalies, faults or malfunctions, do not commission the switchgear, but inform the manufacturer.

Cleaning the panel and checking panel assembly


Clean the switchgear, removing contamination resulting from assembly work. Remove all the attached information tags, cards, brochures and instructions no longer needed. Check the tightening torques of all screw fastenings and connections established on the site of installation: High-voltage connection Earth conductor Panel screw fastenings Busbar links Deflector fastening Special attachments

Damaged paint
The panels are powder-coated. Minor damage to the paint can be repaired using commercially available paint (standard colour RAL 7044 or corresponding colour).

Re-mounting the covers


Secondary cable duct cover (see Chapter 7.2, page 56) Remove cable compartment cover (see Chapter 4.3.1, page 26). Remove temporary base from the panel top, if such a base has been used. Re-mount cladding between busbar compartment and circuit-breaker compartment.

Inspection
Check the switchgear for damage which might be due to transport or assembly work. Compare data on nameplate to the required ratings. Check the connected cables for phase coincidence (see Chapter 9.4, page 62).

Racking-in the trucks


Rack the following components into the panel: Circuit-breaker truck HVX Isolating truck UTX Metering truck MTX Vacuum contactor CVX Close front doors (see Chapter 4.2.1, page 21).

AGS 531 502-02

57

PIX

Commissioning (contd.)

8.2 Checking switching functions and interlocks


Danger! The high-voltage supply must not be connected. All active parts must be earthed. Important:

- For switching operations, comply with Chapter 10 as of page 63 (Operation). - In case supply voltage is not available, blocking coils (optional; lock circuit-breaker button and/ or truck in disconnected position) are in locked position, thus blocking manual switching operations; there is a dropped-out undervoltage release in the circuitbreaker (optional). - The energy-storing device of the circuit-breaker drive is charged autonomously as soon as the supply voltage is applied.

Apply supply voltage. Perform several manual test operations with each switching device. Check switch position indicators. Check electrical functions of control and operating devices: Closing and opening releases for circuit-breaker Optional motor-operated drives for the truck and the earthing switch Check switch position indicators and interlocks (see Chapter 10 as of page 63).

8.3 Power frequency test of busbar (optional)


Warning! Comply with the safety provisions in Chapter 1, page 8.
A test unit and a test adapter (not included in scope of supplies) are required for the power frequency test.

Preparation
All panels must be isolated from the power supply and earthed (see Chapter 10.10, page 77). Busbar: Disconnect voltage transformer (MTX) and surge arrester. Earth voltage detection systems. Incoming feeder panel for voltage test: Remove cable connection compartment cover and disconnect voltage transformer and surge arrester. Earth voltage detection systems.

Important:

Make sure that no high-voltage cables are connected. Observe the assembly and operating instructions for the test unit and the test adapter.

58

AGS 531 502-02

PIX

Commissioning (contd.)

Perform the power frequency test of the busbar on the feeder panel: Connect test unit to the test cable. Switch the earthing switch OFF. Move circuit-breaker truck HVX into service position and switch circuit-breaker ON. Perform the power frequency test successively for all three phases (L1, L2, L3) in accordance with the specifications of the test unit manufacturer.

Important:

Observe admissible test values for the switchgear and the admissible test values for power-frequency tests after installation of the switchgear in accordance with IEC 62271-200.

5 1
Fig. 68 Switch position during the power frequency test (example: five panels) 1 2 3 4 5 Branch-circuit panels Incoming feeder panel for test voltage Busbar Test unit (e g. high-voltage source, test transformer) Test cable

After the power frequency test


After the power frequency test: Switch circuit-breaker OFF and put circuit-breaker truck to disconnected position; switch earthing switch ON. Remove test unit and test cables. Reconnect disconnected voltage transformers and surge arresters.

AGS 531 502-02

59

PIX

Commissioning (contd.)

8.4

Cable test after assembly


Warning! Comply with the safety provisions in Chapter 1, page 8.

A test unit and a test adapter (not included in scope of supplies) are required for cable testing.

Important:

The assembly, operating and testing instructions for cable fittings, connectors and the test unit must be taken into consideration. During the cable test, the busbar can be operated at rated voltage (see nameplate). For qualification of the current transformers for cable tests, enquire at the appropriate manufacturers.

Preparation
Isolate outgoing feeder cable of the panel to be tested (see Chapter 10.10.1, page 77). Isolate outgoing feeder cable in remote station. Earth outgoing feeder cable of the panel to be tested (see Chapter 10.10.2, page 77). Remove cable compartment cover (see Chapter 4.3.1, page 26). Disconnect voltage transformer and surge arrester; earth voltage detection systems.

Performing the cable test


Connect the test adapter to a free cable connection in the panel and on the test unit. To this effect, observe the specifications of the test units manufacturer.

Important:

Make sure that the metallic components of the test adapter are at a sufficient distance from the earthed switchgear components (e.g. housing). Set switchgear panel to test position: Switch earthing switch: OFF. Circuit-breaker: OFF Truck: in disconnected position Earthing switch: OFF Perform cable test according to the cable manufacturers specifications. When doing so, do not exceed the admissible limits (see Table below).

After the cable test


Earth outgoing feeder cable again. Remove test set. Reconnect voltage transformer, surge arrester and voltage detection systems or de-earth them. Reposition cable compartment cover.

Admissible limits for the switchgear in case of cable tests with high-voltage cables connected:

DC test voltage [kV] max. 15 min


PIX 12 PIX 17 34 42

Admissible limits for the switchgear in case of cable tests with a testing frequency of 0.1 Hz available on request from the manufacturers.

60

AGS 531 502-02

PIX

Voltage Detecting Systems (VDS)


Important:

Refer to the operating manual of the voltage detection system concerned.

9.1

Pluggable voltage detection system

The system voltage or the zero voltage state of the outgoing feeders is detected via a separate voltage detection system according to IEC 61243-5. Socket-contacts for the indicator units are located on the panel front (Fig. 70). Capacitive voltage indicators in accordance with IEC 61243-5 can be used for high-resistance measuring systems.(Fig. 69).

Fig. 69 Voltage indicator (Type HR-ST, Horstmann GmbH)

Important:

All three phases L1, L2 and L3 must always be checked together. Close non-used socket-contacts using caps.

Fig. 70 Socket-contacts for HR system on the panel front

9.2 Integrated voltage detection system IVIS (optional)


IVIS is an integrated voltage detecting system with an integrated display unit used to verify zero voltage according to IEC 61243-5. The IVIS system has been designed for maximum operating reliability. It does not require supply from an external source. It features climateproof encapsulated electronics and is maintenance-free due to permanent monitoring of the indication thresholds. Flash arrow symbols on the indicators display the mains voltage still existing within the defined response thresholds (Fig. 71). The IVIS system does not require the electrical repeat tests common for voltage detection systems. For a description of all functions and messages of the IVIS system, please refer to the separate Operating Manual IVIS (No. AGS 531 751-01).

Fig. 71 IVIS display unit

AGS 531 502-02

61

PIX

9 Voltage Detecting Systems (VDS)


(contd.)

9.3 Voltage detection system VOIS+ (optional)


VOIS+ (Fig. 72) is a capacitive three-phase voltage detection system with an integrated display unit used to determine voltage or zero voltage in accordance with IEC 61243-5. It does not require a battery or external power supply. Flash arrow symbols on the display indicate the applied voltage within the defined response thresholds. VOIS+ has a 3-phase measuring point geared to the LRM conditions in accord. with VDE 0682 part 415 for phase comparison and determining the rotary field direction.

Fig. 72 Voltage detection system VOIS+ (Manufacturer: Kries Energietechnik GmbH & Co. KG)

9.4 Phase comparators


Important:
Before connecting live switchgear components for the first time, always check phase coincidence. If IVIS is used, phase comparison can be performed by means of the phase comparator MS 100 (Fig. 73, ref. no. AGS C26320-01). Phase comparators are optionally available and not included in the scope of supplies.

Fig. 73 Phase comparator MS 100

62

AGS 531 502-02

PIX

10

Operation

10.1

Operating interface of the panel


1 2 3 4 5 6 7 8 9 Switching circuit-breaker OFF (shown with operating rod; optionally: via push-button) Opening for door handle Interlocking slide for the actuating port, for racking the truck in/out manually Cylinder lock mechanism of cable compartment cover (optional) Earthing switch position indicator Voltage detection system Cable compartment cover Interlocking lever for the actuation port of the earthing switch Insertion opening for manual actuation of earthing switch

10 Cylinder lock mechanism of truck (optional) 11 Cylinder lock mechanism of earthing switch (optional) 12 Opening for racking the truck in/out manually 13 Truck position indicator 14 Opening for manual charging of the circuit-breakers energy storing device 15 Inspection glass 16 Switching circuit-breaker ON (shown with operating rod; optionally: via push-button) 17 Nameplate 18 Low-voltage cabinet

Fig. 74 Operating interface of a PIX High Panel

AGS 531 502-02

63

PIX

10

Operation (contd.)

10.2
1 2 3 4 5 6 7 8 9 10 11 12 13

Trucks for PIX High Panels

Fig. 75 Circuit-breaker truck HVX

Pole partitions Moving contacts Vacuum interrupter chamber Press rod (transfer of ON/OFF switching movement) Truck Truck rollers Slide for opening the insertion opening (8) for racking the truck in and out manually Insertion opening for racking the truck in/out manually Lever for locking/unlocking the truck in the panel Position indicator - truck in disconnected position Position indicator - truck in service position Operator interface Low-voltage terminal

1 2 3 4

Moving contacts Truck Truck rollers Slide for opening the insertion opening (5) for racking the truck in and out manually 5 Insertion opening for racking the truck in/out manually 6 Lever for locking/unlocking the truck in the panel 7 Position indicator - truck in disconnected position 8 Position indicator - truck in service position 9 Cover plate with nameplate 10 Low-voltage terminal

Fig. 76 Isolating truck UTX

1 2 3 4 5 6

Moving contacts High-voltage fuse Voltage transformer Truck Truck rollers Slide for opening the insertion opening (7) for racking the truck in and out manually 7 Insertion opening for racking the truck in/out manually 8 Lever for locking/unlocking the truck in the panel 9 Position indicator - truck in disconnected position 10 Position indicator - truck in service position 11 Cover plate with nameplate 12 Low-voltage terminal
Fig. 77 Metering truck MTX

64

AGS 531 502-02

PIX

10

Operation (contd.)

1 2 15

14 13 12 11 10 9 8 7 6

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

4 5

Fig. 78 Vacuum contactor CVX (only for 12 kV version)

Moving contacts Fuse Vacuum interrupter chambers with magnetic drive Truck Truck rollers Slide for opening the insertion opening (7) for racking the truck in and out manually Insertion opening for racking the truck in/out manually Lever for locking/unlocking the truck in the panel Position indicator - truck in disconnected position Position indicator - truck in service position Indicator - vacuum contactor ON/ OFF Fuse status indicator Handles for racking out/in Operations counter (optional) Low-voltage terminal

1 2 3 4
9 1 8 7 6 5 4

5 6 7 8 9

Moving contacts Truck Truck rollers Slide for opening the insertion opening (5) for racking the truck in and out manually Insertion opening for racking the truck in/out manually Lever for locking/unlocking the truck in the panel Position indicator - truck in disconnected position Position indicator - truck in service position Cover plate with nameplate

2 3

Fig. 79 Truck with jumper

AGS 531 502-02

65

PIX

10

Operation (contd.)

10.3

Operation accessories
Important:
These accessories are supplied with the panel. The panel may only be operated by means of these accessories.

Fig. 80 Handle for opening and closing the door Item no. SEM 101120-01

Fig. 81 Standard double-bit key to lock/unlock the door of the low-voltage cabinet Item no. SEM 101137-02

Fig. 82 Crank to charge the circuit-breakers energy-storing device Item no. AGS H30498-01

Fig. 83 Lever for racking the truck in/out manually Item number AGS C66911-01

Fig. 84 Control lever for actuation of the earthing switch Item number AGSC74270-01

Fig. 85 Operating rod to switch the circuitbreaker ON and OFF Item no. AGS H35446-01 AGS 531 502-02

66

PIX

10

Operation (contd.)

10.4

Interlocks
Important:
Complete switchgear interlocking can only be ensured with complete locking devices.

10.4.1 Internal mechanical interlocks in the panel


Interlock
Switch cannot be racked in unless the lowvoltage connector Between truck and is inserted and locked low-voltage The low-voltage connector connector can only be inserted or removed while the truck is in its disconnected position The truck cannot be moved into service position while the earthing switch of the switchgear panel is in Between truck and ON position earthing switch The earthing switch cannot be switched on once the truck has left its disconnected position Circuit-breaker cannot be racked in or out while it is switched on Circuit-breaker cannot Between the be switched on unless circuit-breaker and it has completely the truck Between reached its the disconnected or circuit-breaker and service position and the truck the operating crank for the rack-in mechanism has been removed The cable Between the cable compartment cover compartment cover can only be removed if and the earthing the earthing switch is switch (optional) ON.

Function of interlock

Method of operation of interlock


The opening for the moving crank handle is locked The interlock for the low-voltage connector on the drive end has been activated

The opening for the moving crank handle is locked.

The opening for the earthing switch lever is locked. The opening for the moving crank handle is locked

The circuit-breaker cannot be switched ON or OFF

The cable compartment cover is locked mechanically by means of a sheet metal plate.

10.4.2 Electromagnetic interlocks (optional)


Electromagnetic blocking coils can be used for inter-panel as well as intra-panel interlocks: The circuit-breakers ON and OFF pushbuttons are blocked. Manual actuation of the isolating truck is blocked. Manual actuation of the earthing switch is blocked.

Important:

Fig. 86 1 Symbol for blocking coil on the earthing switch AGS 531 502-02

- In case of failure of the supply voltage, all electrical interlocks are in their locked position. Action: Re-establish power supply. - Please note the purchase contract and the switchgear-specific circuit diagram as regards the design of the interlocking systematics.
67

PIX

10

Operation (contd.)

10.4.3

Interlock with padlock

The holes are designed so that the shackles of padlocks with a diameter of max. 8 mm can pass through them.

Fig. 87 Earthing switch locked by padlock with short shackle

Fig. 88 Manual racking-in of truck locked by padlock

Fig. 89 Manual switching ON of circuit-breaker locked by padlock

Fig. 90 Manual switching OFF of circuit-breaker locked by padlock


1

Fig. 91 Padlocks blocking opening of shutters

1 2

Opening the upper shutter is blocked. Opening the lower shutter is blocked.

Fig. 92 Optional: Cover flaps on ON/OFF pushbutton for circuit-breaker can be locked by means of a padlock. 68 AGS 531 502-02

PIX

10

Operation (contd.)

10.4.4 Interlock with cylinder lock (optional)

Fig. 93 Overview of possible mechanical lock-out mechanisms with cylinder locks 1 2 3 4 5 6 Cylinder lock for front door (locks the door handle) Cylinder lock for cable compartment cover Cylinder lock to lock the earthing switch in OFF position Cylinder lock to lock the earthing switch in ON position Slide to block manual actuation of the earthing switch Cylinder lock to lock the truck in disconnected position (blocks the interlocking slide used to open the insertion port for racking the truck in/ out manually)
90

90

Fig. 94 Handling of cylinder locks 1 2 3 Key can be remvoved: cover/actuation locked Turning the key to the right by 90: locking mechanism unlocked Turning or removing the key not possible: cover opened/switching device in unlocked position, or operating crank/lever inserted

Fig. 95 1 2 Slide to the right Key-locking the earthing switch

AGS 531 502-02

69

PIX

10

Operation (contd.)

10.5

Operating specifications

The switchgear unit may only be operated by specialist electricians who have proven experience (training certificate) in conjunction with the PIX High series and all the relevant safety standards. Refer also to the safety provisions in Chapter 1, page 8.

Warning! To rule out faulty switching operations, the operating sequences described below must be complied with. Each switching operation must be completed.

Check whether the supply voltage is ON.

Important:

- While the power supply is not available, blocking coils (locking the interrogation slides and circuit-breaker push-buttons, depending on design), are in locked position. An undervoltage release (optional) has dropped out. Measure: Re-establish the supply voltage. - After each switching operation for which you have used a crank or a lever, remove this tool and store it in the tool board.

10.6

Operating the circuit-breaker

10.6.1 Charging the circuit-breakers energy storing device


Initial situation:
- Circuit-breaker - Energy-storing device OFF released

Charging by hand
Open the cover (Fig. 97, item 1) and insert the crank (Fig. 96 and Fig. 97, 2). Turn in direction of arrow (3) until the charge drive mechanism is uncoupled (sound). The energy storing device indicates the charged condition (4). Remove crank.

4 1 2 3

Fig. 96 Charging the circuit-breakers energy storing device

Fig. 97 Charging the circuit-breakers energy storing device

Charging via motor


The energy-storing device is charged automatically as soon as the motors supply voltage is applied. The position indicator of the energy storing device indicates the charged condition (Fig. 97, 4).

70

AGS 531 502-02

PIX

10 Operation (contd.)

10.6.2 Switching the circuit-breaker manually


Variant description

Fig. 98 Switching the circuit-breaker via the operating rod

Fig. 99 Switching the circuit breaker via pushbutton is only possible in service position!

Switching ON via the operating rod


Insert the operating rod (Fig. 98 and Fig. 100, item 1) into the left-hand guide mechanism of the door and press it rearward to its stop. The circuitbreaker is switched ON; the position indicator indicates ON (2). The energy storing device can be charged immediately after switching ON (manually or by motor). If supply voltage is present, the energy storage device is charged automatically.

Switching OFF via the operating rod


Insert the operating rod into the left-hand guide of the door (Fig. 101, item 1) and press it rearward to its stop. The circuit-breaker is switched OFF. The position indicator indicates OFF (2).

1
2

Fig. 100 Switching the circuit-breaker ON via the operating rod

Fig. 101 Switching the circuit-breaker OFF via the operating rod

Switching ON via pushbutton (optional)


Press the left-hand lever down (Fig. 102, item 1). For switching ON, press the black right-hand pushbutton (Fig. 99 and Fig. 102, items 1, 2). Circuitbreaker is switched OFF. The position indicator indicates ON (3). The energy storing device can be charged immediately after switching ON (manually or by motor). If supply voltage is present, the energy storage device is charged automatically.
AGS 531 502-02 71

PIX

10

Operation (contd.)

Switching OFF via pushbutton (optional)


Press the left-hand lever down (Fig. 103, item 1). To switch OFF, press the red left-hand pushbutton (2). Circuit-breaker is switched OFF. The position indicator indicates OFF (3).

2 3

2 3

Fig. 102 Switching circuit-breaker ON via pushbutton

Fig. 103 Switching circuit-breaker OFF via pushbutton

10.6.3 Switching the circuit-breaker electrically


Switching ON (Closing)
Actuate closing release via bay computer or remote control. The energy storing device can be charged immediately after switching ON (manually or by motor). If voltage is applied to the motor, charging is performed automatically.

Switching OFF (Opening)


Actuate the opening release via the bay computer or the remote control Undervoltage release or Secondary release

10.6.4 Position indicators on circuit-breaker and possible operating sequences


Item Position indicator Energy-storing device (closing spring)
released charged released charged
O = Opening (OFF)

Position indicator ON/OFF switch position


OFF ON OFF ON

Possible operating sequence

1 2 3 4
C = Closing (ON)

none C-O O O-C-O

72

AGS 531 502-02

PIX

10

Operation (contd.)

10.7 Move truck into operating/ disconnected position


Warning! Isolating truck UTX and truck with jumper may only be racked in or out if busbar and outgoing feeder cable are in de-energized condition.
Initial situation: - Circuit-breaker - Earthing switch OFF OFF

10.7.1 Racking-in the truck from disconnected into service position


Press the slide (Fig. 104, item 1) to the left and hold it. Insert crank through the opening in the door onto the drive shaft of the truck (2). Turn crank clockwise until the truck has been racked in (Fig. 105). Remove crank. Check position indicator; to this effect, turn the button (3) to the left. Position indicator (4) must now indicate service position (I).
3 1 2 4

Fig. 104 Moving the truck from disconnected into service position

Fig. 105 Truck racked-in in service position

10.7.2 Racking-out the truck from service into disconnected position


Press the slide (Fig. 106, 1) to the left and hold it. Insert crank through the opening in the door onto the drive shaft of the truck (2). Turn crank counter-clockwise until the truck has been racked out (Fig. 107). Remove crank. Check position indicator; to this effect, turn the button (3) to the left. Position indicator (4) must now indicate disconnected position (O).
3 1 2 4

Fig. 106 Moving the truck from service into disconnected position AGS 531 502-02

Fig. 107 Truck racked-out in disconnected position 73

PIX

10

Operation (contd.)

10.8

Vacuum contactor CVX

Position indicator
Whether the vacuum contactor CVX is switched ON or OFF is indicated directly on the device (Fig. 108 and Fig. 109).

CVX
1
2

CVX

Fig. 108 1 Vacuum contactor switched ON

Fig. 109 2 Vacuum contactor switched OFF

Switching
The vacuum contactor CVX is switched ON and OFF by means of a remote control device or the control and protection unit GEMSTART (see switchgear documentation).

Switching OFF manually (optional)


This feature is only available for mechanically latched vacuum contactors CVX. In this case, the vacuum contactor CVX can be switched off directly on the panel (Fig. 111 and Fig. 110). Insert operating rod through the guide hole in the front door until the vacuum contactor switches OFF (Fig. 111). Check position indicator (Fig. 109).

Fig. 110 Switching OFF the vacuum contactor CVX by means of an operating rod

Fig. 111 Switching OFF the vacuum contactor CVX by means of an operating rod

74

AGS 531 502-02

PIX

10

Operation (contd.)

Alternatively: switch OFF via push-button (Fig. 113 and Fig. 112). To this effect, move the lever (1) downwards to its stop and press pushbutton OFF (2). Check position indicator (Fig. 109).

Fig. 112 Switching OFF the vacuum contactor CVX via push-button (only possible in service position)

Fig. 113 Switching OFF the vacuum contactor CVX by means of a push-button 1 2 Press lever down Press O push-button

Fuse tripping
The inspection port of the vacuum contactor on the panel front indicates the fuse tripping status:

CVX

CVX

Fig. 114 1 Indicator green: no fuse tripped

Fig. 115
2 3 Indicator red: one or several fuses have tripped Position indicator: vacuum contactor has switched off automatically

Measures to be taken in case of fuse tripping


Put vacuum contactor to disconnected position and rack it out of the panel. This approach corresponds to the description in Chapter 10.7.2 on page 73 with the HVX truck. Always exchange all three fuses. Fuse replacement is described in the Operating Manual of the vacuum contactor CVX (no. NTV 133 2E).

AGS 531 502-02

75

PIX

10

Operation (contd.)

10.9 Operating the earthing switch manually


10.9.1 Switching earthing switch ON
Initial situation: - Circuit-breaker - Earthing switch - Truck OFF OFF (Fig. 119) in disconnected position

Push the slide (Fig. 116 , item1) upwards and insert the control lever of the earthing switch with the lever rod pointing down (2). Turn the lever upwards clockwise by 180 (3). The earthing switch is ON. Check position indicator (Fig. 117); it must indicate that the earthing switch is ON. Remove crank.

Fig. 116 Switch earthing switch ON

Fig. 117 Earthing switch ON

10.9.2 Switching the earthing switch OFF


Initial situation: - Earthing switch ON (Fig. 117) Push the slide upwards (Fig. 118, item 1) and insert the control lever of the earthing switch with the lever rod pointing upwards (2). Press the lever downwards counterclockwise by 180 (3). The earthing switch is OFF. Check position indicator (Fig. 119); it must indicate that the earthing switch is OFF. Remove crank.

3 2 1

Fig. 118 Switch the earthing switch OFF

Fig. 119 Earthing switch OFF

76

AGS 531 502-02

PIX

10

Operation (contd.)

10.10

Standard switching operations

Important:

Observe switching provisions (Chapter 10.5, page 70) and interlocking conditions (Chapter 10.4, page 67).

10.10.1 Operating the outgoing feeder cable


Initial situation:

1 2

- Circuit-breaker - Truck HVX - Earthing switch

OFF in disconnected position OFF

Switching outgoing feeder cable ON


Move truck into service position (Fig. 120, item 1). Switch circuit-breaker ON (2).

Switching outgoing feeder cable OFF


Switch circuit-breaker OFF. Move truck into disconnected position.

Fig. 120 Switching outgoing feeder cable ON

10.10.2 Earthing the outgoing feeder cable


Initial situation: - Circuit-breaker - Truck HVX - Earthing switch OFF in disconnected position OFF

Earthing the outgoing feeder cable


Check the branch circuit for zero voltage Switch the earthing switch ON (Fig. 121, item 1).

De-earthing
Switch the earthing switch OFF

Fig. 121 Earthing the outgoing feeder cable

AGS 531 502-02

77

PIX

10

Operation (contd.)

10.10.3 Coupling busbar sections using the bus section coupler


With HVX and UTX truck
Initial situation: - Circuit-breaker - both trucks (HVX, UTX) OFF in disconnected position

Coupling busbar sections


Move both trucks into service position (Fig. 122, item 1). Switch circuit-breaker ON (2).

Fig. 122

1 2

Coupling busbar sections via bus section coupler

Uncoupling
Switch circuit-breaker OFF. Move both trucks into disconnected position.

With HVX truck and direct bus riser


Initial situation: - Circuit-breaker - Truck HVX OFF in disconnected position

Coupling busbar sections


Move truck into service position (Fig. 123, item 1). Switch circuit-breaker ON (2).

1 2

Fig. 123 Coupling busbar sections via bus section coupler

Uncoupling
Switch circuit-breaker OFF. Move truck into disconnected position.

78

AGS 531 502-02

PIX

10 Operation (contd.)

10.11

Earthing the busbar

Important:

- Observe switching provisions (Chapter 10.5, page 70) and interlocking conditions (Chapter 10.4, page 67). - Check the busbar for zero voltage.

10.11.1 Earthing a busbar section by means of the bus section coupler


This version is only available if the bus section coupler panels are equipped with earthing switches (optional). Initial situation: - Circuit-breaker HVX - both trucks (HVX, UTX) - both earthing switches OFF in disconnected position OFF

Earthing the left-hand busbar


Move left-hand truck into service position (Fig. 124, item 1). Switch circuit-breaker ON (item 2). Switch right-hand earthing switch ON (item 3).

1 2

Fig. 124 Earthing the left-hand busbar via the bus section coupler

De-earthing
Switch right-hand earthing switch OFF. Switch circuit-breaker OFF. Move left-hand truck into disconnected position.

Earthing the right-hand busbar


Move right-hand truck into service position (Fig. 125, item 1). Switch left-hand earthing switch ON (item 2).

Fig. 125 Earthing the right-hand busbar via the bus section coupler

De-earthing
Switch the earthing switch OFF. Move right-hand truck into disconnected position.
AGS 531 502-02 79

PIX

10

Operation (contd.)

10.11.2 Earthing the busbar with the circuitbreaker of a branch-circuit panel


The earthing device can be connected to a free cable terminal in the cable connection compartment (access: see Chapter 4.3 on page 26). If necessary, remove cable. Earthing devices and earthing adapters are not included in the scope of supplies. Please comply with the manufacturers specifications for the earthing devices and, if applicable, the earthing adapters. Initial situation: Outgoing feeder cable - Earthing switch - Circuit-breaker - Truck HVX EARTHED ON OFF in disconnected position

3 4

Earthing the busbar:


Connect earthing device in cable connection compartment (Fig. 126, 1). Switch earthing switch OFF (2). Move truck into service position (3). Switch circuit-breaker ON (4).

2 1
Fig. 126 Earthing the busbar with the circuit-breaker of a branch-circuit panel

De-earthing:
Switch circuit-breaker OFF. Move truck into disconnected position. Switch the earthing switch ON. Remove the earthing device.

10.11.3 Earthing the busbar with busbar earthing switch


Initial situation: Busbar earthing switch OFF

Earthing the busbar


1
Fig. 127 Earthing the busbar with busbar earthing switch

Switch the earthing switch ON (Fig. 127, item 1).

De-earthing
Switch the earthing switch OFF

80

AGS 531 502-02

PIX

10

Operation (contd.)

10.12

Panel with fan attachment

Bus section couplers with circuit-breaker truck HVX or incoming feeder panels can be equipped on their top with a fan attachment for ventilation and consequently for cooling the circuit-breaker compartment (Fig. 128). This ventilation system is used for circuit breakers with high currents or in case of ambient temperatures 40 C. The fan is switched on automatically if the current exceeds an adjustable threshold (see Table). The ventilation system operates with a radial fan and is protected against accidential contact. The service life of the fan is approx. 30 00040 000 hours, depending on the ambient conditions. Settings for ambient conditions in accordance with Chapter 2.5, page 15:

Degree of protection (IEC 60529)


IP3X IP4X IP3X1 IP4X1
1

ON threshold of the fan [A]


2950 2750 2550 2500

OFF threshold of the fan [A]


2850 2650 2450 2400

Switchgear with pressure relief duct

Air flow sensor


To ensure the required cooling effect, the fan is monitored by an air flow sensor located directly in the air outlet. If the air flow is interrupted, the sensor issues a signal.

Measures to be taken in case of failure of the fan


Reduce maximum normal current to the ON threshold of the fan (see Table). Contact the manufacturers Service Center. Replacement of the fan can be performed by staff certified accordingly. Assembly drawing: AGS C73488-03

Warning! Risk of injury due to non-respect of the safety provisions in Chapter 1, page 8.

Fig. 128 Panels with fan attachment 1 2 AGS 531 502-02 Fan attachment Pressure relief duct 81

PIX

11

Maintenance

11.1

Safety provisions

Maintenance and repair work may only be performed by specialist electricians who have proved their experience with the PIX High series and the applicable safety provisions..

Warning! Comply also with the safety provisions in Chapter 1, page 8.

11.2 Maintenance and servicing specifications


PIX High series indoor switchgear units have been designed for normal operating conditions in accordance with IEC 62271-1. It is recommended to check the panels visually at regular intervals depending on the strain they are subject to during operation and in accordance with the national regulations.

Important:

In case of frequent condensation or air pollution (dust, smoke or corrosive gases), the maintenance intervals must be adapted to the actual conditions. A visual inspection includes a complete check of the panels for contamination, condensation and damage, to be performed by certified staff. If there are traces of contamination or condensation, the panels must be cleaned in expert fashion (see Chapter 11.3, page 83, and Chapter 11.4, page 83) and subsequently the drives, interlocks and position indicators checked for proper functioning (see Chapter 10, page 63). If damage is detected on the panels, these must be repaired or components be replaced (see Chapter 11.5, page 83, and Chapter 11.6, page 83). In case of ambiguities or irregularities, please contact the manufacturers Service Center immediately.

Mantenance interval

Work to be carried out

Qualification / Work performed by

12 years

Clean and grease drives and movable main current contacts Staff who have been (see Chapter 11.7, certified for this work page 84) Check releases and blocking coils for proper function Revision of the switching device in question Service Center of the manufacturer

After 1,000 actuations of the truck or the earthing switch Truck Circuit-breaker HVX Metering truck MTX Isolating truck UTX Vacuum contactor CVX

refer to the applicable instruction manual for the truck concerned: AGS 531 461-01 AGS 531 361-01 AGS 531 361-01 NTV 133 2E

82

AGS 531 502-02

PIX

11

Maintenance (contd.)

11.3

Cleaning
Warning! Risk of injury: the drives must not be disassembled for service and maintenance work.

To ensure the specified insulating level, the insulating components must be clean. On principle, cleanliness deserves utmost attention. When deposited dirt is detected, the panels must be cleaned in an expert fashion. When cleaning, make sure that the lubrication in the drive mechanisms is not removed. If the drive mechanisms are no longer sufficiently lubricated, new lubrication must be applied.

Use a dry cleaning cloth to remove slight soiling:


Clean using a dry, lint-free cloth. Depending on the degree of soiling, replace cloth as often as necessary.

Use cleaning agents for severe soiling:


Cleaning agent, 1 l can (see Chapter 12.1, page 86). The use of other cleaning agents is not admissible. Wear protective gloves Use cleaning agent according to manufacturers instructions Soak the cloth thoroughly and wipe the insulating components. Keep duration of exposure as short as possible. Expose the cleaned surface to the air for at least two hours.

11.4 Avoiding condensation


To ensure the specified insulating level, the switchgear panels especially their insulating components must not be exposed to condensation.

Measures to take in case of condensation:


Should condensation be detected in or on the panels, clean the panels in accordance with Chapter 11.3, page 83). Installation or inspection of panel heating. It must provide a sufficient heating performance to prevent condensation on the panels. Condensation can also be prevented by ensuring suitable ventilation and heating of the station or by using de-humidification devices.

11.5

Corrosion protection

Drive mechanisms and covers have a long-term protection against corrosion. Any damage to the paint, scratches and other damage must be repaired immediately to avoid corrosion.

11.6 Replacement of components and panels


The drive mechanisms, current transformers and voltage transformers as well as the testing and monitoring systems can be replaced if necessary. Also, entire panels can be replaced. Should you have any queries regarding replacement of components or panels, please contact the manufacturers Service Center. The data on the nameplate are relevant for replacement of components or panels or in case of any queries (see also Chapter 2.7, page 16).

AGS 531 502-02

83

PIX

11

Maintenance (contd.)

11.7

Lubrication instructions
Important:
- The bearings and joints must not be washed out by the cleaning agent. - The following elements must not be lubricated: Motor Ball bearings Auxiliary releases Push switches Blocking coils Auxiliary switches. - Only approved lubricants may be used (see Chapter 12.1, page 86).

Preparation
Remove truck from the panel (see Chapter 4.2.3, page 23). To get access to the fixed contacts behind the shutters, use the shutter lifter (Fig. 129). Handling of the shutter lifter in accordance with the standard trucks (HVX, UTX). Clean lubrication points using a lint-free cloth; use cleaning agent in case of serious contamination (see Annex). Use cleaning agents sparingly; lubricating points must only be moistened.

Fig. 129 Shutter lifter for panel width 800: AGS C71 802-03 for panel width 1000: AGS C71 800-02

Lubrication

Lubrication points (see also Fig. 130, page 85)


Sliding contact surfaces All accessible friction points and sliding surfaces

Lubricants (refer to Annex)


Synthetic lubricant Synthetic lubricant

Lubrication procedure
Apply a thin and uniform film of lubricant. Clean lubrication points with lint-free cotton cloth; apply a thin film of lubricant (using e.g. a paintbrush). Pour drops of liquid lubricant (oil can, drip feed lubricator) into the bearing gap. Liquid lubricant gets between the bearing surfaces due to the capillary effect. In case of inaccessible lubrication points, use an extension tube or spray.

Bearings and joints

Liquid lubricant

Once maintenance work is complete


Remove all the tools and auxiliary equipment used. Reinsert truck into the panel (see Chapter 4.2.4, page 24). Reposition covers, close doors and check switching functions (see Chapter 8 Commissioning as of page 57).

84

AGS 531 502-02

PIX

11 Maintenance (contd.)

3 9 4

Fig. 130 Points of lubrication/maintenance 1 2 3 4 5 6 7 8 9 Fixed contacts for the truck Earthing switch contacts Earthing switch drive High-voltage fuse of the voltage transformer (optional), see Chapter 11.8, page 85 Tracks for the truck Shutter mechanism Fan attachment (for details, see Chapter 10.12, page 81) Truck (lubricate in accordance with lubricating instructions in the appropriate operating manual HVX/UTX/MTX/CVX) Trolley, handling: see Chapter 12.5, page 88.

11.8

Replace fuses for voltage transformer

Voltage transformer in outgoing feeder cable


Isolate outgoing feeder cable from the power supply and earth it. Remove cable compartment cover (see Chapter 4.3.1, page 26). Pull fuse (Fig. 130, item 4) carefully out of the clamping contact. Coat all contact areas (see Annex) and insert new fuses. Mount cable compartment cover again.

Voltage transformer on metering truck MTX


See Operating Manual AGS 531 361-01.

High voltage fuses for voltage transformers:

Rated voltage
12 kV 17,5 kV

Ref. no.
AGS C61689-01 AGS C13478-01

AGS 531 502-02

85

PIX

12

Annex

12.1 Auxiliary products


The auxiliary products are available from the manufacturer. The use of alternative auxiliary products is not permissible.

Warning! Risk of injury in case of inappropriate handling. Observe the safety data sheets of the manufacturers of the auxiliary products.

Auxiliary products
Cleaning agent Synthetic lubricant, 0.5 kg can Liquid lubricant FL, 0.5 kg can Touch-up pen RAL 7044, silk-grey, 50 ml

Ref. no.
S 008 152 ST 312-111-835 S 008153 S 009 561

Touch-up pen, special paint (specify colour shade) S 009 562

12.2

How to treat the contact surfaces


Important:
- Caution when handling bars insulated by heat-shrinkable sleeves: The heat-shrinkable sleeve must not get into contact with lubricant (swelling). - Contact areas coated with synthetic lubricant should not be touched, if possible. - Contact areas must be subjected to preliminary treatment before screwfastening (see Table). - Immediately after the pre-treatment, coat the contact surfaces sparingly with a thin and uniform film of synthetic lubricant so that the space between the contact surfaces is completely filled once the screws have been fastened.

Material of contact surfaces Pre-treatment


Silver-plated Nickel-plated Copper or copper alloy Aluminium Steel Zinc-plated steel Hot-galvanized sheet-metal
1

Clean1 Remove passivation layer4 Clean1, expose metallic surface2 Clean1, expose metallic surface2 Clean1, expose metallic surface2 Remove passivation, not, however, the zinc layer3 Clean1, passivation need not be removed

Clean by means of lint-free cloth; use cleaning agent in case of serious contamination 2 Expose metallic surface

3 4

using a brass brush, steel brush rub slightly by hand using Scotchbrite abrasive agent (Ni layer must not be reduced)

by treating the entire surface with emery cloth or a rotating grinding tool (grain size 100 or 80) or using a wire brush which is clearly marked for use exclusively for aluminium or exclusively for copper

86

AGS 531 502-02

PIX

12 Annex (contd.)

12.3

Specifications for screw connections


Important:
- The threads of screws and bolts must generally not be pretreated! - Max. tolerance for the effective tightening torques: 15% - The nut must correspond in strength to the grade of the screw/bolt used or be of better quality.

General screw connections

Grade or material
Screw/bolt Plastics 8.8 10.9

Thread
M4 M5 M6 M8 M 10 M 12 M 16 M 20

0,25 0,5 0,8 1,8 3,5 6,0 12

Tightening torques [Nm]


2,6 5,0 8,8 21,0 42,0 70,0 170 330

Self-locking screw 8.8

7,0 12,3 30,0 59,0 97

Screw fastening for power transmission


Screws and bolts: Grade 8.8

Conductor material: copper


Thread
M6 M8 M 10 M 12 M 16

Tightening torques [Nm]


6,5 17 35 68 135

Screw connection for terminal strips


M 2.5 (M 2.6) M3 M 3.5 M4 M5

Thread

Tightening torques [Nm]


0,5 0,7 1,0 1,5 2,5

12.4 Required tools (not included in the scope of supplies)


Cutter Nail puller approved torque wrenches with different bits for hexagon socket screws and socket-head screws and nuts; bits for screw and nut grades M 5, M 6, M 8, M 10, M 12 Screwdriver and Philips screwdriver Cutting pliers 4 crane straps/chains of L 2000 mm each, capacity 1500 kg lint-free, clean rags

AGS 531 502-02

87

PIX

12

Annex (contd.)

12.5
1

Transport trolley for truck

4 2

Fig. 131 Transport trolley for truck (item number AMT 003412-01) 1 2 3 4 Tracks for the truck Lever to lock / unlock the transport trolley on the panel Storage tray for instruction manuals Tool tray

The trolley can be used for panel widths of 800 and 1000 mm. Adjusting the track width from 1000 to 800 mm: Release the two securing bolts (Fig. 132, item 1). Push the two tracks to the inside to their stop. Check distance: 631 1.5 mm (Fig. 133). Re-tighten the six screws. The track width has now been adjusted to 800 mm panel width. For adjusting from 800 to 1000 mm, proceed accordingly. largeur de cellule de 800 mm.
83 1.5 1
63 1 1.5

.5

Fig. 132 1 88 Release screws

Fig. 133 Push tracks to the inside AGS 531 502-02

PIX

12

Annex (contd.)

12.6

List of assembly drawings

List of all assembly drawings specified in Chapter 5, page 28 Assembly. This does not apply to special modules or customer-specific special designs. According to the switchgear configuration in question, only such drawings from the list are supplied by the factory as are actually required.

Description
Mounting the switchgear end plates Fastening on concrete foundations Screw-fastening the switchgear panels Mounting the upper gap cover Mounting the rear gap cover Busbar compartment section segregation Ir (busbar) 1250 A (2 x 80 x 10) Busbar compartment section segregation 1600 A Ir (busbar) 2500 A (3 x 80 x 10) Busbar compartment section segregation 3150 A Ir (busbar) 5000 A (4 x 80 x 10) Busbar assembly Mounting the earth bar Mounting the fan Mounting deflector on panel front and rear side Mounting deflector on panel side Mounting gap covers between switchgear and building wall Mounting the lateral deflector adjustment in the case of elevated low-voltage cabinet Mounting the pressure relief duct Mounting the link between two pressure relief duct sections Mounting the pressure relief duct end plate Mounting the link for extension of the pressure relief duct Mounting the pressure relief duct extension Mounting the pressure relief flap at the end of the pressure relief duct Mounting the connecting piece for the connection of a customized pressure relief duct

Assembly drawing
AGS C73040-01 SEM 102 173-01 AGS C73038-01 AGS C73 479-01 AGS C73 483-01 AGSC73044-01

Chapter
5.4 5.5

5.6

AGSC73044-02

5.7.2

AGSC73044-03 see Chapter 5.7.3 AGS C73 030-01 AGS C73 488-01 AGS C73 566-01 AGS C73 566-02 AGS C73 566-02 AGS C73 566-03 AGS C73 475-01 AGS C73 478-01 AGS C73 476-01 AGS C73 480-01 AGS C73 481-XX AGS C73 012-03 AGS C74 010-01 5.11 5.10 5.7.3 5.8 5.9

AGS 531 502-02

89

Appendices

Notes

90

AGS 531 502-02

Appendices

Notes

AGS 531 502-02

91

Schneider Electric 35, rue Joseph Monier CS 30323 92506 Rueil-Malmaison Cedex, France RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com AGS 531 502-02

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Design: Schneider Electric Printing: 01-2011

2011 Schneider Electric - All rights reserved

You might also like