September 2010

Iris Control Damper (ICD)

Iris Control Damper (ICD)


For adjustment and measuring of airflow

Features

G Quick and simple installation and maintenance G Extended spigot connections G 100% opening capacity G Low noise generation G Air tightness to DW144 Class C G Linear choking for simple operation G High accuracy and excellent adjustment properties

Iris Control Damper (ICD)

Iris Control Damper (ICD)


Introduction Quick and simple installation and maintenance. Balancing the airflow is normally a time consuming operation when commissioning a ventilation system. The linear choking characteristics of the Actionair Iris Control Damper (ICD), simplifies this operation. Adjustment and measuring is carried out in the same operation, reducing the on site time to achieve correct airflow. The result is a permanent comfortable indoor climate. The Actionair ICD is delivered locked in the fully open position, facilitating pressure testing of the system. A graduated scale of 'K' factors is located on the outer edge of the damper so as not to be obscured by insulation and each damper is supplied with full mounting and adjustment instructions to make the installation quick and simple. Every Actionair ICD is factory calibrated. Extended spigot connections are a standard feature to avoid damage to the seal when riveting to ducting. 100% Opening capacity The ICD can be fully opened. Low Noise Generation The design of the adjustment function together with the geometry of the ICD, results in low noise generation under volume control. A conventional damper will increase the air velocity along the duct walls resulting in high generated noise under volume control.The 'Iris' aperture is close to ideal from a flow technology aspect. The Iris Control Damper (ICD) increases the air velocity with low levels of noise generation provided the instructions are followed in relation to the location of bends and junctions. The correct properties The construction is simple, but gives excellent adjustment properties. The ICD is manufactured to air tightness class C and can work equally well with the airflow in either direction, eliminating the risk of incorrect installation.

Quick, silent and efficient is the simple summary of the features of the Actionair Iris Control Damper (ICD) for the adjustment and measuring of airflow.

Function The Actionair ICD is an iris damper for measuring and adjusting the air flow. The ICD has the following specifications: low noise level, centrically-formed air flow and fixed test points for precise measurements. The damper also has an adjustment aperture which can be opened completely. Available in sizes 100 to 630mm diameters. Maximum temperature for ICD is 70 C. Design The damper is manufactured from galvanised sheet steel and is fitted with a rubber seal tested for air-tightness. Exhaust ventilation Using the ICD damper for exhaust Ventilation by diffusion offer many advantages over other forms 2 www.actionair.co.uk

of ventilation and one of them is the simplicity in design and layout of exhaust air. The dynamics of an extracted air flow is independent of geometry and direction at all distances greater than a couple of diameters from the opening. As long as the extracted air volume equals the supply air volume it doesn't matter where the extract opening is located nor does the number of openings applied. When you are using dampers with good control abilities and enough pressure drop like ICD, these can be combined with a supply diffuser to form functional exhaust installations. By using the same diffuser for supply and exhaust you can achieve an aesthetic ceiling profile.

Mounting The ICD adjustment damper must be installed in accordance with the distances required to minimise air-flow deviation. The ICD enables the taking of precise air-flow measurements at all points including points close to duct deviations such as T junctions and bends and points in front of other supply air devices. Protective distance before bends 1 x Diameter. after bends 1 x Diameter. before T-pipes 3 x Diameter. after T-pipes 1 x Diameter. before supply-air devices 3 x Diameter.

Specification Actionair ICD The Actionair ICD Iris Control damper, housed in a galvanised sheet steel casing with circular extended spigots for ease of duct connection. The simplicity of the Actionair ICD design with linear choking, provides quick and efficient airflow adjustment and measurement with low noise generation. Note: Maximum damper differential pressure is as indicated on Performance Data charts, pages 4, 5 and 6.

Iris Control Damper (ICD)

Sound Power Level


Sound power level, Lw
Lw (dB) = LwA + Kok (LwA = diagram Kok = table) correction factor Kok Mid-frequency band, Hz ICD Size 100 125 150 160 200 250 315 400 500 630 Tolerance 63 11 7 8 9 9 6 3 3 14 12 6 125 10 8 7 6 5 1 1 1 8 6 5 250 3 2 1 1 1 4 4 4 2 1 2 500 2 4 5 5 5 3 4 4 3 3 2 1K 8 11 11 11 12 12 9 9 11 8 2 2K 16 19 18 18 17 17 14 13 17 11 2 4K 24 27 27 27 24 24 23 19 26 14 3

Dimensions
60
20

60

ICD Size d

D Part Number Weight Kg

30

100 125 150 160 200


d

99 124 149 159 199 249 314 399 499 629

54 63 54 60 62 62 63 70 60 60

163 210 230 230 285 333 406 560 644 811

XSGR05101 XSGR05102 XSGR05103 XSGR05104 XSGR05105 XSGR05106 XSGR05108 XSGR05109 XSGR05110

0.80 1.09 1.30 1.30 1.81 2.70 3.42 7.33 8.33

250 315 400 500 630

XSGR05111 10.00

40

40

The compact measurements of the Actionair ICD, are an advantage as space is often limited. www.actionair.co.uk 3

Iris Control Damper (ICD)


The diagram shows Air volume (l/s and m 3/h), static pressure (Pa) and sound power level [dB(A)], including aperture damping.

Performance Data
100
0 250 Pt [Pa] 55dB(A) 200 50 150 45 150 100 40 35 50 30 30 0 10 20 30 40 35 0 50 60 70 80 90 I/s 0 50 30 100 40 45 50 55 100 50 45 40 35 30 35 40 150 45 50 Pt [Pa] 50 100 150 200 250 300 m3/h 300 250 300 50

160
0 200 55dB(A) 400 600 800 m3/h

55

200

250 I/s

125
0 400 Pt [Pa] 55dB(A) 350 300 250 200 150 100 50 0 0 20 40 30 50 100 200 300 400 500 m3/h Pt [Pa] 200 180 160 140 120 45 40 35 30 40 35 80 100 120 140 I/s 55 50 45 100 80 60 40 20 0

200
54 200 400 600 800 1000 1200 1400 m3/h

55dB(A)

50 45 40 35 30 50 35 15 65 115 165 40 45 55

60

215 265 315 365 415 I/s

150
0 350 Pt [Pa] 300 250 50 200 150 100 50 0 0 50 45 40 35 30 35 40 45 55 100 150 55dB(A) 200 400 600 800 m3/h 250 Pt [Pa]

250
0 500 55dB(A) 200 50 45 40 35 30 50 30 35 0 200 250 I/s 0 100 200 300 400 500 600 I/s 40 45 50 50 55 1000 1500 2000 m3/h

30 100

150

www.actionair.co.uk

Iris Control Damper (ICD)

Performance Data
315
0 180 Pt [Pa] 160 140 120 100 80 60 40 20 0 0 30 35 35 30 45 40 0 0 200 400 600 30 35 40 50 55 50 45 50 500 55dB(A) 50 45 40 100 1000 1500 2000 2500 3000 m3/h 250 Pt [Pa]

500
0 1000 55dB(A) 2000 3000 4000 5000 m3/h

200

45 40 35 30

150

100 200 300 400 500 600 700 800 900 I/s

800 1000 1200 1400 1600 I/s

400
0 300 Pt [Pa] 250 200 150 100 50 0 0 Pt [Pa] 55dB(A) 1000 2000 3000 4000 5000 m3/h 250

630
0 2000 55dB(A) 200 45 150 40 100 35 50 30 35 40 45 50 55 0 0 500 1000 30 30 40 1500 2000 45 4000 6000 8000 10000 m3/h

30 30 30 30 30

50

200 400 600

800 1000 1200 1400 1600 I/s

2500 3000 I/s

Ordering Information
Example Quantity 10 Size 100 Description ICD PART No. XSGR05101

www.actionair.co.uk

Iris Control Damper (ISD)

Iris Shut Off Damper (ISD)


Specification Actionair ISD The Actionair ISD Iris Shut Off Damper, housed in a galvanised sheet steel casing with circular extended spigots for ease of duct connection. The simplicity of the Actionair ISD design with linear choking, provides quick and efficient airflow adjustment and measurement, low noise generation and more choking ability than Actionair ICD. When using the Actionair ISD we recommend the installation of the Actionair Access/Shield CDS Access Door with the unit.

Sound power level, Lw


Lw (dB) = LwA + Kok (LwA = diagram Kok = table) correction factor Kok ISD Size 160 200 250 315 400 Tolerance Mid-frequency band, Hz 63 9 9 6 3 3 6 125 6 5 1 1 1 5 250 500 1 1 4 4 4 2 1K 5 5 3 4 4 2 2K 4K 11 12 12 9 9 2 18 17 17 14 13 2 27 24 24 23 19 3

Dimensions

60
30
20

60

d D

40

40

The compact measurements of the Actionair ISD, are an advantage as space is often limited.

ISD Size 160 200 250 315 400

d 159 199 249 314 399

C 60 62 62 63 70

D 230 285 333 406 560

Part Number XSGR05131 XSGR05132 XSGR05133 XSGR05135 XSGR05136

Weight Kg 1.50 1.91 2.80 3.63 7.56

www.actionair.co.uk

Iris Control Damper (ISD)

Performance Data
SPM 160 0 140 Pt [Pa]
Pt [Pa]

SPM 315 100 200 300 400 500 m3/h 200 45 180 160 140 120 100 0 200 400 600 800 1000 1200 1400 1600 1800 m3/h

120

45 40

100 80

60 45 40 35 20 30 25dB(A) 40

80 60 40 20 0 25 0 50 30 35 40 dB(A) l/s 45

0 0 20 40 60 80 100 120 140 I/s

100 150 200 250 300 350 400 450 500

SPM 200
0 120 Pt [Pa] Pt [Pa] 45 100 40 80 35 60 100 30 40 40 20 30 25dB(A) 0 0 20 40 60 80 100 120 140 160 180 200 l/s 0 35 45 50 150 200 100 200 300 400 500 600 700 m3m

SPM 400 0 500 1000 1500 2000 2500 3000 m3/h

45

40

35 30 25

dB(A) 0 100 200 300 400 500 600 700 800 900 l/s

SPM 250 0 140 Pt [Pa] 200 400 600 800 1000 1200 1400 1600 m3/h

120

100

80 60

Ordering Information
45dB(A)

40

Example Quantity 10 Size 250 Description ISD Part Number XSGR05133

20 25 0 50 100 150 200 30 250 35

40

300

350

400

450 l/s

www.actionair.co.uk

Iris Control Damper (ICD)

Options
Actionair ICD-M (Motorised) Where the ventilation requirements are variable, dependent on say temperature or CO2 , the Actionair ICD-M, motorised unit may be used.The motor will receive a signal from the installed sensor and vary the air supply accordingly. The maximum/minimum opening position can be adjusted manually using the release button on the unit. Once set the damper will return to automatic operation.

ICD-M 24V On/Off Part Number Weight Kg Size 100 125 160 200 250 315 NM24A NM24A NM24A NM24A SM24A SM24A XSGR05113 XSGR05116 XSGR05119 XSGR05122 XSGR05125 XSGR05128 2.20 2.50 3.20 4.00 4.95 5.20

Motor Options 240V On/Off NM230A NM230A NM230A NM230A SM230A SM230A Part Number Weight Kg 24V Modulating Part Number Weight Kg On/Off NM24A-SR NM24A-SR NM24A-SR NM24A-SR SM24A-SR SM24A-SR XSGR05115 XSGR05118 XSGR05121 XSGR05124 XSGR05127 XSGR05130 2.20 2.50 3.00 3.20 3.50 3.80

XSGR05114 XSGR05117 XSGR05120 XSGR05123 XSGR05126 XSGR05129

2.20 2.50 3.20 4.00 4.95 5.20

Ordering Information
Example Quantity 10 Size 100 Description ICD-M Motor Option NM24A-SR PART No. XSGR05115

www.actionair.co.uk

Iris Control Damper (ICD)

Actionair ISD-M (Motorised) Where the ventilation requirements are variable, dependant on say temperature or CO2, and complete closing is required, the Actionair ISD-M motorised unit may be used. The motor will receive a signal from the installed sensor and vary the air supply accordingly. The maximum/minimum opening position can be adjusted manually using the release button on the unit. Once set the damper will return to automatic operation. When using the Actionair ISD-M we recommend the installation of the Actionair CDS Access Door with the unit.

ICD-M 24V On/Off Part Number Weight Kg Size 160 200 250 315 NM24A NM24A SM24A SM24A XSGR05137 XSGR05140 XSGR05143 XSGR05146 2.40 3.90 5.80 7.80

Motor Options 240V On/Off NM230A NM230A SM230A SM230A Part Number Weight Kg 24V Modulating Part Number Weight Kg On/Off NM24A-SR NM24A-SR SM24A-SR SM24A-SR XSGR05139 XSGR05142 XSGR05145 XSGR05148 3.40 4.30 5.80 7.80

XSGR05138 XSGR05141 XSGR05144 XSGR05147

2.40 3.90 5.80 7.80

Ordering Information
Example Quantity 10 Size 160 Description ISD-M Motor Option NM24A-SR PART No. XSGR05139

www.actionair.co.uk

Iris Control Damper (ICD)

Accessories

40

Actionair MR Constant Airflow Device The Actionair MR Constant airflow device housed in a galvanised sheet steel casing with silicon bellows with a polycarbonate centre, dimensioned so as to maintain a constant air volume. The Actionair MR can be vertically or horizontally mounted, either within an Actionair Access/Shield CDS access door or spiral ductwork. For use with air volumes up to 200 l/s. Operating temperatures 30 to +60 C Adjustment is made by setting dividers into 1 of 10 different positions.

MR Size 100 125 160 200 250

D 98 121 156 196 247

A 80 137 137 155 172

Part Number XSGR05149 XSGR05150 XSGR05151 XSGR05152 XSGR05153

Weight Kg 0.20 0.45 0.50 0.90 1.50

10

www.actionair.co.uk

Iris Control Damper (ICD)

Accessories
Actionair AccessShield CDS The access door can be easily opened without tools. The door is fitted with a sealing gasket. Manufacture is from galvanised mild steel and is available in sizes 100mm diameter to 400mm.

CDS Size 100 125 160 200 250 315 400

A 290 395 405 445 480 480 480

H (hole) 100 150 160 180 200 200 200

D 100 125 160 200 250 315 400

Part Number XSGQ05155 XSGQ05156 XSGQ05157 XSGQ05158 XSGQ05159 XSGQ05160 XSGQ05161

Weight. 0.60 1.10 1.40 1.85 3.20 3.90 4.30

40

40

Ordering Information
Example Quantity 10 Size 100 Description CDS PART No. XSGQ05155

www.actionair.co.uk

11

Iris Control Damper (ICD)

Ruskin Air Management Limited is a ISO 9001 and 14001 registered company.
The statements made in this brochure or by our representatives in consequence of any enquiries arising out of this document are given for information purposes only. They are not intended to have any legal effect and the company is not to be regarded as bound thereby. The company will only accept obligations which are expressly negotiated for and agreed and incorporated into a written agreement made with its customers. Due to a policy of continuous product development the specification and details contained herein are subject to alteration without prior notice.

Comprehensive and detailed information is available for all Actionair products. Visit our website at www.actionair.co.uk

Ruskin Air Management Limited


South Street, Whitstable, Kent CT5 3DU England. Tel: 01227 276100 Fax: 01227 264262 Email: sales@actionair.co.uk Website: www.actionair.co.uk
LNNN00313