new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Project documentation
created with

SIMARIS design
Version: 6.0.0 (25-11-2010) Subrevision: 1852 SIEMENS AG 2010. All rights reserved. http://www.siemens.com/simaris

Master data Project name: Project description: Editor: Planning office: Created at: Changed at: New new Kushtrim MALA Cef Kushtrim MALA Tuesday, April 10, 2012 Tuesday, April 10, 2012 sadik.mustafa@kosovo-nickel.com

Customer data City: Customer: Drenas NEW-CO-FERRONICELI

Comment:

Page 1/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Network parameters:
General Standard Attitude of Site Medium Voltage Rated voltage Ambient temperature Voltage factor c max Voltage factor c min Max./Min short-circuit power Neutral System Relation R1/X1 min Low Voltage Rated voltage System configuration Frequency Tolerable touch voltage Ambient temperature of devices Voltage factor c max Voltage factor c min Base point of voltage drop calulation Relative operating voltage at reference point Max. permissible voltage drop in network 450 V TN-S 50 Hz 50 V 45 C 1.1 0.95 Transformer-primary terminals 100 % 14 % 6 kV 40 C 1.1 1 250 / 100 MVA Low-resistance 0.2 IEC < 1000 m

Page 2/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Defined network modes for calculation and dimensioning:


Operating mode:

Page 3/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

List of devices:
Sources of feeding:
Transformers: Designation Type Sn [kVA] ukr [%] Uprim [kV]/ Usec [V] 6/ 450 Pk [kW] P0 [kW] Vector group u_transf ormer [%] 2.825 Catalog Reference

Transformer 1.1A.1

GEAFOL

100

1.85

0.44

Dyn5

4GB50363DY001AA2

Output u_transformer [%] is independent from defined reference point for voltage drop calculation.

Page 4/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Switches/Fuses:
Medium voltage switch disconnectors: Place LVMD 1.1A.1 Designation MV-SD 1.1A.1 Type Switch-disconnector with fuses, MV Catalog Reference fuse SIB:3009813.20 In fuse [A] 20 In disconnector [A] 200 Quantity 3

Circuit Breaker/Miniature circuit-breaker: Place Designation Catalog Reference In [A] Icu/Icn [kA] Icu/Icn [kA] required Release type / characteristic s ETU10 TM Quantit y

LVMD 1.1A.1 GS 1.1A.1

LV-CB 1.1A.1b CB 1.1A.1a

3VL27161SB330AA0 3VL17121DD330AA0

160 125

25 18

3.016 2.859

1 1

Motor-starter combinations: Place Designation Starter type In motor [A] 25.456 25.456 25.456 25.456 Catalog Reference Device Pmech [kW] 15 15 15 15 Coordinati on type 1 1 1 1 Quantit y 1 1 1 1

GS 1.1A.1 GS 1.1A.1 GS 1.1A.1 GS 1.1A.1

MC-CB-DS 1.1A.1.1a MC-CB-DS 1.1A.1.2a MC-CB-DS 1.1A.1.3a MC-CB-DS 1.1A.1.4a

Direct-on-line starter Direct-on-line starter Direct-on-line starter Direct-on-line starter

3RV10314EA10 3RT10341AP00 3RV10314EA10 3RT10341AP00 3RV10314EA10 3RT10341AP00 3RV10314EA10 3RT10341AP00

Circuit-breaker Contactor Circuit-breaker Contactor Circuit-breaker Contactor Circuit-breaker Contactor

Page 5/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Connections and line distribution:


Cable/Conductor Medium voltage: Designation Type/ Profile [mm] Starting point / Target point Ib [A] Iz [A] Material Length [m] Isolation Installation type ftot u [C] / Ikmax [C] / Ikmin [C] 55 20 80

MV-C/L 1.1A.1

NYFGY 3x25

LVMD 1.1A.1

7.637 105

Cu

40

PVC-cable

Air

Cable/Conductor Low voltage: Designatio n Type/ Profile [mm] Starting point / Target point LVMD 1.1A.1 LVMD 1.1A Ib [A] Iz [A] Material Length [m] Isolation Installatio n type ftot u [%] / u [%] u [C] / Ikmax [C] / Ikmin [C] 55 20 80 Number of runs

LV-C/L 1.1A.1

e.g. NYY, NYCWY, NYCY, NYKY 3x50/50/25 e.g. NYY, NYCWY, NYCY, NYKY 3x35/-/35 e.g. NYY, NYCWY, NYCY, NYKY 3x10/-/10 e.g. NYY, NYCWY, NYCY, NYKY 3x6/-/6 e.g. NYY, NYCWY, NYCY, NYKY 3x10/-/10

101.825 144

Cu

60

PVC70

0.929 3.754

C/L 1.1A.1.1

GS 1.1A.1 M 1.1A.1.1

25.456 119

Cu

200

PVC70

1.069 4.823

55 20 80

C/L 1.1A.1.2

GS 1.1A.1 M 1.1A.1.2

25.456 57

Cu

80

PVC70

1.414 5.168

55 20 80

C/L 1.1A.1.3

GS 1.1A.1 M 1.1A.1.3

25.456 41

Cu

40

PVC70

1.166 4.920

55 20 80

C/L 1.1A.1.4

GS 1.1A.1 M 1.1A.1.4

25.456 57

Cu

70

PVC70

1.237 4.992

55 20 80

Page 6/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Load:
Motors: Designation M 1.1A.1.1 M 1.1A.1.2 M 1.1A.1.3 M 1.1A.1.4 Pmech [kW] In [A] 15 25.456 15 25.456 15 25.456 15 25.456 Un [V] cos 450 0.84 450 0.84 450 0.84 450 0.84 ai 1 1 1 1 Phase connection L1-L2-L3 L1-L2-L3 L1-L2-L3 L1-L2-L3 Ia/In 5 5 5 5 Trip class Class 10 Class 10 Class 10 Class 10 Method of Starting Motor starter combination Motor starter combination Motor starter combination Motor starter combination Ikre 1 1 1 1 0.9 0.9 0.9 0.9 Quant ity 1 1 1 1

Page 7/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Messages
Designation GS 1.1A.1 Message Overload protection not fulfilled. IR = 100A < Ibs = 101.825A

Page 8/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Personal protection against electric shock


All circuits of the project have a permissable break time ta-req > ta-cur and therefor fulfill the requirements for Personal protection against electric shock.

Disclaimer:
Dimensioned protection devices inside tap-off units of busbar trunking systems may not correspond to the actual available devices for those components. Please verify the dimensioning results in the device lists and correct them accordingly.

Page 9/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Symbols legend:
Symbol [Unit] ai cos ftot Ia/In Ib [A] Iz [A] Icu(fuse) [kA] Icu [kA] Icn [kA] Icu/Icn [kA] required Icw 1s [kA] In [mA] Ik1max Ik1min Ik3max Ik3min Ik1D [kA] Ik3D [kA] Ikmax/Ikmin Ikre In [A] P0 [kW] Pk [kW] Pmech [kW] Pn [kW] R0 N [m] R0 PE(N) [m] R0/R1 r1 [%] R1 [m] Sn [kVA] ukr [%] Un [V] Uprim [kV] Usec [V] Description Load factor Power factor Derating factor Inrush current relation Operating current / allowed load capacity Rated ultimate short-circuit breaking capacity - fuse Rated ultimate short-circuit breaking capacity according to IEC 60947-2 Rated short-circuit breaking capacity according to IEC 60898-1 the required breaking capacity of the protection device at installation location Rated short-time withstand current 1s Residual current - RCD Maximum single phase short-circuit current Minimum single phase short-circuit current Maximum three phase short-circuit current Minimum three phase short-circuit current single pole uninterrupted short-circuit current three pole uninterrupted short-circuit current Relation of maximum and minimum short-circuit current Short-circuit current recovery factor Nominal current No-load losses Short-circuit losses mechan. Power Active power Zero phase-sequence resistance phase-neutral conductor Zero phase-sequence resistance phase-PE(N) conductor Resistance relation positive / zero phase-sequence system Relative value of positive phase-sequence resistance Positive phase-sequence resistance Nominal apparent power Short-circuit voltage Nominal voltage Primary voltage Secondary voltage

Page 10/12

new NEW-CO-FERRONICELI X0 N [m] X0 PE(N) [m] X0/X1 X1 [m] xd'' [%] Z1 max Z1 min Zs Zs max Zs min u [%] / u [%] u [C] / Ikmax [C] / Ikmin [C] [] 1 min/max [] 3 min/max [] Zero phase-sequence reactance phase-neutral conductor Zero phase-sequence reactance phase-PE(N) conductor Reactance relation positive / zero phase-sequence system Positive phase-sequence reactance Subtransient reactance Maximum impedance in positive phase-sequence system Minimum impedance in positive phase-sequence system Faulted circuit impedance Maximum faulted circuit impedance Minimum faulted circuit impedance

Apr 10, 2012 / Kushtrim MALA

voltage drop between beginning and end of a section / cumulated voltage drop from the transformer primary/ secondary clamps to the specified point Conductor temperature of MV cable / Conductor temperature of LV cable for voltage drop / on beginning of short circuit / for disconnection Efficiency Phase angle Phase angle at Ik1 min/max Phase angle at Ik3 min/max

Page 11/12

new NEW-CO-FERRONICELI

Apr 10, 2012 / Kushtrim MALA

Standards for computation:


Title Low-voltage electrical installations * Short-circuit currents in three-phase a.c. systems Calculation of currents Short-circuit currents calculation of effects Definitions and calculation methods Low-voltage switchgear and controlgear Circuit-breakers Low-voltage switchgear and controlgear assemblies A method of temperature-rise assessment by extrapolation for partially typetested assemblies (PTTA) of low-voltage switchgear and controlgear Electrical installations of buildings Part 5-52: Selection and erection of electrical equipment Wiring systems Electrical accessories Circuit-breakers for overcurrent protection for household and similar installations Circuit-breakers for a.c. operation High-voltage switchgear and controlgear Alternating Current switch-fuse combinations Electrical installations of buildings Selection and erection of electrical equipment Isolation, switching and control Low-voltage electrical installations Protection for safety Protection against voltage disturbances and electromagnetic disturbances Protection against lightning Part 14 Low-voltage surge protective devices - Surge protective devices connected to low-voltage power systems; Requirements and tests IEC 60364-16 60909 60865 60947-2 60439 60890+C 60364-5-52 60898-1 62271 60364-5-53 60364-4-44 62305-14 61643-11 60364-5-534 60364-4-443 528 S2 384 60898-1 62271 HD 384 60909 60865 60947-2 60439-15 EN DIN VDE 0100 100...710 0102 0103 0660 101 0660 500505 0660 507 0298 4 0641 11 0671 105 0100-534 0100-443 0185 14 0675-6-11

*) Special national conditions and deviations from IEC 60364-4-41: 2005 are not implemented and need to be considered!

Page 12/12