8800HO0601 4/2006
Display Status: Displays default settingsthe drives state, active control channels, frequency reference, and LOC/REM (T/K key status). The Display Status content can be configured. Menu line: Displays the name of the current menu or submenu. Submenus: Lists the submenus of the current menu. Scroll boxes: Indicates (by arrow direction) whether there are additional submenus or levels to access. A blank box indicates that there are no additional submenus or levels to access. Status line displays the functions assigned to function buttons F1F4. Code = F1, << = F2, >> = F3, and T/K = F4. See the descriptions below. Function buttons F1 displays the code of the selected parameter or contextual Help. F2 provides navigation to the left / returns to the previous menu or submenu F3 provides navigation to the right / advances to the next menu or submenu F4 command and reference via the terminal Stop/Reset buttonstops the drive controller and resets the faults ESC buttonexits a menu or parameter, or cancels a value to return to the previous value in the memory Run buttonruns the motor with the current setting. Starts the drive controller if in HMI command mode. Navigation button/dialpressing the button saves a value or enters a menu or parameter. Turning the dial clockwise increases a value. Turning the dial counter-clockwise advances to the next menu item or line, or decreases the reference (if terminal control is active). FWD/REV buttonreverses the rotation direction of the motor (if configured to allow reverse for HMI command mode).
C D D E F
1 DRIVE MENU 1.1 SIMPLY START 1.2 MONITORING 1.3 SETTINGS 1.4 MOTOR CONTROL 1.5 INPUTS / OUTPUTS CFG
E F G
Code
<<
>>
T/K
G H H I
PROGRAMMING PARAMETERS
Example of accessing the acceleration ramp setting
RDY Term +0.00 Hz REM 1 DRIVE MENU 1.1 SIMPLY START 1.2 MONITORING 1.3 SETTINGS 1.4 MOTOR CONTROL 1.5 INPUTS / OUTPUTS CFG Code << >> T/K Term +0.00 Hz 1.3 SETTINGS Ramp increment: Acceleration Deceleration: Acceleration 2: Deceleration 2: Code << >> RDY REM 01 9.51 s 9.67 s 12.58 s 13.45 s T/K RDY
NOTE: Refer to the Altivar 61 (ATV61) programming manual for detailed information about the display terminal operations.
Changing a parameter
Term +0.00 Hz Acceleration REM
1. 2. 3. 4.
ENT ESC
ENT ENT or
Min = 0.01
9.51 s
Max = 99.99 << >> T/K
ESC
5.
Use the navigation dial to vertically scroll the DRIVE MENU list, press ENT (navigation button) to select the submenu. Select the parameter to change and press ENT. Use F1 and F2 to scroll horizontally, then select the digit to change (the digit is highlighted). Turn the navigation dial clockwise to increase the digit or counter-clockwise to decrease the digit. Press ENT to save the change or press the ESC button to cancel the change.
TYPICAL CONNECTIONS
[Pumps.Fans]
[Ref.1 channel]
3a
[Start/Stop]
[Ref.1 channel]
[Gen. Use]
[Ref.1 channel]
[PID regul.]
[Ref.1 channel] (PID reference) [PID feedback] [Motor freq.] [No drive flt] [No] [Forward] [Fault reset] [PID integral reset] [2 preset PID ref.] [4 preset PID ref.] [No] Stop [Forward] [Fault reset] [PID integral reset] [2 preset PID ref.] [4 preset PID ref.] [No] [No] [No] [No] [No] [I motor] [PID Output] [No] [No]
[Network C.]
[Ref.2 channel] ([Ref.1 channel] = integrated Modbus) [No] [Motor freq.] [No drive flt] [No] [Forward] [Fault reset] [Ref. 2 switching] [Forced local] [No] [No] Stop [Forward] [Fault reset] [Ref. 2 switching] [Forced local] [No] [No] [No] [No] [No] [No] [I motor] [No] [No] [No]
AI2 AO1 R1 R2 LI1 (2-wire) LI2 (2-wire) LI3 (2-wire) LI4 (2-wire) LI5 (2-wire) LI6 (2-wire) LI1 (3-wire) LI2 (3-wire) LI3 (3-wire) LI4 (3-wire) LI5 (3-wire) LI6 (3-wire) LI7 to LI14 LO1 to LO4 R3/R4 AI3, AI4 RP AO2 AO3 F1 key F2, F3 keys F4 key
[No] [Motor freq.] [No drive flt] [No] [Forward] [Fault reset] [No] [No] [No] [No] Stop [Forward] [Fault reset] [No] [No] [No] [No] [No] [No] [No] [No] [I motor] [No] [No] [No] [T/K] (Control via graphic display terminal)
[Summing ref. 2] [Motor freq.] [No drive flt] [No] [Forward] [Reverse] [Jog] [Fault reset] [Torque limitation] [No] Stop [Forward] [Reverse] [Jog] [Fault reset] [Torque limitation] Option cards [No] [No] [No] [No] [No] [I motor] [No] [No] [No] [T/K] (Control via graphic display terminal)
R1B
R2A
R / L1
S / L2
T / L3
R2C
PWR PC / -
[Freewheel] [Ref 1B switching] [Fault reset] [No] [No] Stop [Forward] [Freewheel] [Ref 1B switching] [Fault reset] [No] [No] [No]
PWR +24 A1 ATV61Hppppp
Q1
W / T3
PA / +
U / T1
V / T2
M 3a
W1
U1
V1
PB
P0
+24
[Forward]
A1
COM
AI1+
[No] [No] [I motor] [No] [No] [No] [T/K] (Control via graphic display terminal)
0V
[T/K] [T/K] (Control via graphic (Control via graphic display terminal) display terminal)
NOTE: The graphic display terminal is standard on the ATV61 high horsepower (hp) drive controllers and is optional on the low hp drive controllers. ATV61 low hp drive controllers are equipped with a 7-segment, 4-digit integrated display terminal.
AI 2
LI1
LI5
LI2
LI3
LI4
LI6
[No]
+10
0 10 V or X-Y mA
COM
AI1-
AO1
8800HO0601 4/2006
1 DRIVE MENU
1.1 SIMPLY START 1.2 MONITORING 1.3 SETTINGS 1.4 MOTOR CONTROL 1.5 INPUTS/OUTPUTS CFG 1.6 COMMAND 1.7 APPLICATION FUNCT. 1.8 FAULT MANAGEMENT 1.9 COMMUNICATION 1.10 DIAGNOSTICS 1.11 IDENTIFICATION 1.12 FACTORY SETTINGS 1.13 USER MENU 1.14 PROGRAMMABLE CARD
1.3 SETTINGS GS
Ramp increment Acceleration Deceleration Low Speed High Speed Mot.therm. Current Speed prop. Gain Speed time integral. K speed loop filter IR compensation Slip compensation Auto DC inj. Level 1 Auto DC inj. Time 1 Auto DC inj. Level 2 Auto DC inj. Time 2 Switching freq. Current Limitation Motor fluxing Low speed time out Current threshold Low | Threshold Freq. threshold Low Freq. Threshold Freq. threshold 2 2 Freq. Threshold Motor therm. level High Freq. Ref. Thr. Low Freq. Ref. Thr. Skip Freq. Skip Freq. 2 3rd Skip Frequency : 0.1 : 3.00s : 3.00s : 0.0Hz : 50.0Hz : 2.0A : 40% : 100% : 0 : 100% : 100% : 1.6A : 0.5s : 1.1A : 0.0s : 12.0kHz : 2.7A : No : 0.0s : 2.3A : 0.0A : 50.0Hz : 0.0Hz : 50.0Hz : 0.0Hz : 100% : 0.0Hz : 0.0Hz : 0.0Hz : 0.0Hz : 0.0Hz
CONFIG.
7 DISPLAY
CONFIG.
2 ACCESS LEVEL
Basic Standard Advanced Expert
4 PA PASSWORD RD
Status PIN code 1 PIN code 2 Upload rights Download rights : Unlocked : OFF : OFF : Permitted : Unlock drv
S SELECT MONITORING T
Alarm groups Frequency ref. Output frequency Motor current Motor speed Motor voltage Motor power Motor torque Mains voltage Motor thermal state Drv. Thermal state DBR thermal state Input Power Consumption Run time Power on time IGBT alarm counter PID reference PID feedback PID error PID Output Config. Active Utilized param. Set Local / Remote
6 MONITORING CN G CNFG
6.1 PARAM. BAR EFFECT 6.2 MONITOR SCREEN TYPE 6.3 COM MAP. CONFIG.
7 DISPLAY CONFIG
7.1 USER PARAMETERS 7.2 USER MENU 7.3 PARAMETER ACCESS
1.11 IDENTIFICATION I
ATV61H075N4 0.75kW / 1HP 380 / 480V Appl. Software V1.1 IE 02 MC Software V1.1 IE 05 6W054100156 Product V1.1 IE02 OPTION 1 No option OPTION 2 No option GRAPHIC TERMINAL GRAPHIC S V1.1E04 12WOP4200 ENCODER No
1.6 COMMAND
Ref.1 channel RV Inhibition Stop Key priority Profile Ref.2 switching Ref.2 channel Copy channel 1<>2 F1 key assignment F2 key assignment F3 key assignment F4 key assignment HMI cmd. : AI1 : No : Yes : Not separ. : ch1 active : No : No : No : No : No : T/K : Bumpless
NOTE:
The key drive settings to monitor are highlighted in yellow. Refer to the ATV61 programming manual for additional programming instructions. All menu levels are accessible through the Expert access level.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 2006 Schneider Electric All Rights Reserved Schneider Electric USA 8001 Knightdale Blvd Knightdale, NC 27545 1-888-SquareD (888-778-2733) / www.us.Telemecanique.com