EST Catalog u Strobes, Horns, Bells, Chimes

Harsh Environment Strobes


405-3A, -5A, -6A, -7A -8A CS405-7A, -8A
MEA Patented

405 Series

Overview
405 Series strobes are specially designed for use with compatible life safety communication and control equipment to alert the hearing impaired of a life safety event. Strobes are available with 15 cd, 15/75 cd, 30 cd, 60 cd, and 110 cd effective flash intensity. They are fully compatible with Genesis signals. 405 Series strobes exceed UL synchronization requirements (within 10 milliseconds other over a two-hour period) when used with a separately-installed G1M Signal Master, or SIGA-CC1S Synchronization Module, or when powered by suitably enabled booster power supplies and control panels. The flash from 405 Series strobes can be noticed from almost any position in the room, corridor, or large open space. 405 Series strobes are UL 1971 listed with both wall and ceiling cd intensity ratings (see Specifications). This is useful in areas where the Authority Having Jurisdiction (AHJ) permits ceiling-mount strobes. 405 Series strobes are designed for 16 to 33 Vdc operation and must be connected to signal circuits that output a constant (not pulsed) voltage. A diode is used to allow full signal circuit supervision and polarized connections are made to terminals that accept up to #12 AWG (2.5mm) wire. The strobe front plate is of steel construction finished with durable baked epoxy polyester powder-coat paint.

Standard Features
UL 1971-listed synchronizing strobe Integrity strobes synchronize to the latest UL 1971 requirements when used with a synchronization source. Genesis-compatible All Genesis and Integrity strobes on the same circuit meet UL 1971 synchronization requirements when used with an external control module. Approved for public and private mode applications UL 1971-listed as signaling devices for the hearing impaired and UL 1638-listed as protective visual signaling appliances. Rugged red or white steel front plate Ideal for outdoor or harsh environments. Rated for wall or ceiling installation Field changeable field markings Lens language or standard FIRE marking is easily changed with optional LKW and LKC series lens kits. Fits 4-inch square flush box Ideal for retrofit and renovation projects. UL/ULC rated outdoor option

Page 1 of 4

D ATA S H E E T Not to be used for installation purposes. Issue 8

85001-0305

Application
NOTE: The installation of visible signals are subject to national and local standards, codes, and ordinances. Consult your Authority Having Jurisdiction for device installation requirements, application standards, and minimum performance specifications.

Edwards strobes are UL 1971-listed for use indoors as wall-mounted public-mode notification appliances for the hearing impaired. Prevailing codes require strobes to be used where ambient noise conditions exceed specified levels, where occupants use hearing protection, and in areas of public accommodation. Consult with your Authority Having Jurisdiction for details. As part of the Enhanced Integrity line of products, 405 Series strobes exceed UL synchronization requirements (within 10 milliseconds other over a two-hour period) when used with a synchronization source. Synchronization is important because a small portion of the population have a condition which may cause them to become disoriented from multiple random flashes of light. Integrity strobes minimize this risk. Integrity strobes are fully compatible with Edwards Genesis signals.

NOTE: The flash intensity of some visible signals may not be adequate to alert or waken occupants in the protected area. Research indicates that the intensity of strobe needed to awaken 90% of sleeping persons is approximately 100 cd. Edwards recommends that strobes in sleeping rooms be rated at at least 110 cd. WARNING: These devices will not operate without electrical power. As fires frequently cause power interruptions, further safeguards such as backup power supplies may be required.

Operating Current (RMS)


UL Rating 16 Vdc 16 Vfwr Typical Current 24 Vdc 24 Vfwr 15 cd 109 150 15 cd 69 108 15/75 cd 150 210 15/75 cd 90 128 30 cd 130 189 30 cd 89 134 60 cd 269 359 60 cd 158 229 110 cd 329 420 110 cd 180 260

Installation and Mounting


All models fit to a standard flush mounted, North American four inch electrical box, 1-1/2 inch (38 mm) deep minimum. Optional Edwards weatherproof, surface mount boxes are available. The strobes must be connected to signal circuits which output a constant (not pulsed) voltage. Edwards recommends that these strobes always be installed in accordance with the latest recognized edition of national and local fire alarm codes.
0.25 (6 mm)

Vdc: Volts direct current, regulated and filtered Vfwr: Volts full wave rectified

Current Draw Notes and Comments


1. Current values are shown in mA. 2. UL Nameplate Rating can vary from Typical Current due to measurement methods and instruments used. 3. Edwards recommends using the Typical Current for system design including NAC and Power Supply loading and voltage drop calculations. 4. Use the 16 Vdc RMS current ratings for filtered power supply and battery AH calculations. Use the 16 Vfwr RMS current ratings for unfiltered power supply calculations. 5. Fuses, circuit breakers and other overcurrent protection devices are typically rated for current in RMS values. Most of these devices operate based upon the heating affect of the current flowing through the device. The RMS current determines the heating affect and therefore, the trip and hold threshold for those devices.

*Changeable Lens Marking, LKW or LKC Series.

SIDE VIEW, CEILING MOUNTED

1.9 (48 mm)

Countersunk Philip head screws are provided to secure unit onto electrical box. 5.5 (140 mm) Two Plastic Caps are provided for indoor mounting.

Typical Wiring - 24 Vdc


(+) UL/ULC Listed 24V dc Fire Alarm Control Panel (signal circuit) (-) Place an end-ofline resistor on the last device (resistor supplied with control panel)

5.5 (140 mm)

S Strobe

S Strobe

Page 2 of 4

D ATA S H E E T Not to be used for installation purposes. Issue 8

85001-0305

Light Distribution
15 cd (-5A) Series Strobes 15/75 cd (-7A) Series Strobes 30 cd (-3A) Series Strobes
Horizontal Output Horizontal Output Horizontal Output
eg ees ddegeees degrrr es

s Strobes es Strobes

15/75 cd (-7A) Series Strobes 75 cd (-4A) Series Strobes 30 cd (-3A) Series Strobes
Horizontal Output Horizontal Output Horizontal Output
ddeggreeess deegr reees

110 cd (-4A) Series Strobes 75 cd (-8A) Series Strobes 30 (-3A)


Horizontal Output Horizontal Output Horizontal Output
ge s ddeggeeess dee rrr ee

110 cd (-4A) Series Strobes 75 (-8A)


Horizontal Output Horizontal Output
degrrees deg e es

110 cd (-8A)

tput tput

Horizo
-15

5 5

30 30 45 45 60 60

75 75 90 90 050 20 30 100

-15 00 15 -15 -15 0 15 15 30 30 -30 30 -30 -30 45 45 -45 45 -45 -45 60 60 -60 60 -60 -60 75 75 75 -75 -75 -75 90 90 -90 90 -90 -90 10 cd 20 100 60 40 50 cd 20 50 60 30 100 20 20 cd 10 40 30

-15 0 15 -15 0 15 -15 0 15 30 30 -30 -30 30 -30 45 45 -45 -45 45 -45 60 60 -60 -60 60 -60 75 75 75 -75 -75 -75 90 90 -90 -90 90 -90 20 cd 40 100 140 100 50 cd 60 100 140 60 40 60 cd 20 50 60 100

-15 00 15 -15 0 15 -15 15 30 30 30 -30 -30 -30 45 45 45 -45 -45 -45 60 60 60 -60 -60 -60 75 75 75 -75 -75 -75 90 90 90 -90 -90 -90 200 100 60 cd 60 100 200 60 140 40 20 cd 20 40 140 60 100 cd 100

-15 0 -15 0 -30 -30 -45 -45 -60 -60

15 15 30 30 45 45 60 60

-30 -45 -60 -75 -90 200

75 75 -75 -75 90 90 -90 -90 200 100 60 cd 60 100 200 140 100 cd 100 140

100

put put

Vertical Output Vertical Output Vertical Output


-90 -75 -90 100 -75 -60 30 -60 60 -45 -45 20 40 -30 -30 50 -15 -15 10 20

Vertical Output Vertical Output Vertical Output


-90 -75 -90 140 -75 -60 100 -60 60 -45 -45 100 40 -30 -30 50 -15 -15 20 60

Vertical Output Vertical Output Vertical Output


-90 -75 -90 140 -75 -60 -60 150 60 -45 -45 100 40 100 -30 -30 -15 -15 20 60 50

Vertical Output Vertical Output


-90 -75 -90 140 -75 -60 -60 150 -45 -45 100 100 -30 -30 -15 -15 60 50

Vertic
150 100
50
degrees

-90-7

30 -15 0

egrees degrees

e egrees degrees degre s

degrees d degrees

degrees

cd cd
10 20 50 20 40

00

cd
60 20 50 100 40

00

cd cd
50 60 20

0 0 15 15 30 30 45 45

cd cd
50 60

Vertical -90

0 0

cd
50

15 30

15 15 30 30 45 45 60 60 30 60 90 75 10090 75
Average Average Average UL min UL min UL min

15 15 30 30 45 45 60 60 140 60 90 75 10090 75
Average Average Average UL min UL min UL min

100 100 40 140 150 90 75 60 90 75


Average Average Average

100 100
90 140 150 90 75 90 75 Horizontal

60 60

15 15 -90 30 30 45 45 60 60
UL min UL min

100

150 90 7

min min

UL min UL min UL min

Average Average
90

Averag

Vertical -90

Vertical -90 -90 -90

Vert -90

Specifications
Catalog Number UL 1638/ULC S526 Rated Strobe Output UL 1971 Rated Strobe Output Strobe Flash Rate Synchronization Sources Strobe Operating Volts Operating Environment Lens Markings Wire Connections Flash Tube Enclosure Strobe Plate, Finish Mounting Agency Listings 405-5A 15cd 405-3A 30cd
90 90 Horizontal

405-6A 60cd

90 405-7A Horizontal

90 405-8A, CS405-8A

Horizontal

15/75cd
90

110cd
90

15cd 30cd wall 60cd wall 15cd wall 110cd wall (wall only) 15cd ceiling 30cd ceiling 15cd ceiling 60cd ceiling Synchronized at one flash per second. External control module necessary to meet UL 1971 synchronization requirements of 10 milliseconds over a two-hour period. G1M-RM, SIGA-CC1S, SIGA-MCC1S, BPS6, BPS10 Continuous 16 to 33 Vdc or 16 to 33 Vfwr INDOOR: 30 C @ 85% RH; 32 - 120 F (0 - 49 C) ambient temperature. OUTDOOR (CS models only): 30 C @ 93% RH; -40-150 F (-40-66 C) ambient temp 7A (17.7cd @ -35 C per UL @ -40 C per ULC) and; 8A (70.7cd @ -35C per UL @ -40C per ULC) models only Supplied with LKW-1 FIRE red letters, vertical both sides (Wall Mount) - see LKW and LKC series for ceiling style and optional markings Terminals - polarized input, #12 AWG (2.5mm) max wire size Clear LEXAN CRS steel - 5 in (140mm) square, red or white baked epoxy polyester powder-coat finish INDOOR: North American 4 in square electrical box; OUTDOOR: 449 series weatherproof surface box UL 1971, UL 1638, ULC S526, CE, FM, CSFM, MEA (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule)

Page 3 of 4

D ATA S H E E T Not to be used for installation purposes. Issue 8

85001-0305

Ordering Information
Catalog Number 405-5A-T 405-5A-TW 405-7A-T 405-7A-TW 405-3A-T 405-3A-TW 405-6A-T 405-6A-TW 405-8A-T 405-8A-TW Description Strobe, 15 cd, Red Strobe, 15 cd, White Strobe, 15/75, Red Strobe, 15/75, White Strobe, 30 cd, Red Strobe, 30 cd, White Strobe, 60 cd, Red Strobe, 60 cd, White Strobe, 110 cd, Red Strobe, 110 cd, White Ship Wt. lb (kg)

Detection & alarm since 1872


U.S. T 888-378-2329 F 866-503-3996 Canada Chubb Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T : +65 6391 9300 F : +65 6391 9306 India T : +91 80 4344 2000 F : +91 80 4344 2050 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T +32 2 725 11 20 F +32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 utcfireandsecurity.com 2010 UTC Fire & Security. All rights reserved.

1 (0.4)

Outdoor Listed Strobes CS405-7A-T Strobe, 15/75, Outdoor, Red CS405-8A-T Strobe, 110 cd, Outdoor, Red

1 (0.4)

Synchronization Sources G1M-RM Genesis Signal Master Remote Mount (1-gang) Synchronization Output Module (Standard Mount) - UL/ULC SIGA-CC1S Listed SIGA-MCC1S Synchronization Output Module (UIO Mount) - UL Listed BPS6A 6.5 Amp Booster Power Supply BPS10A 10 Amp Booster Power Supply Mounting Accessories
449 LKW-1 LKW-1R LKW-2 LKW-3 LKW-4 LKW-5 LKW-6 LKW-7 LKW-8 LKW-9 LKC-1 LKC-2 LKC-3 LKC-4 LKC-5 LKC-6 LKC-7 LKC-8 Surface Mount Box, Gray, Outdoor, (CS models only) FIRE - Wall Orientation (supplied) FIRE - Wall Orientation, red with white letters FEU - Wall Orientation FIRE/FEU - Wall Orientation SMOKE - Wall Orientation HALON - Wall Orientation CO2 - Wall Orientation EMERGENCY - Wall Orientation ALARM - Wall Orientation FUEGO - Wall Orientation FIRE - Ceiling Orientation FEU - Ceiling Orientation FIRE/FEU - Ceiling Orientation SMOKE - Ceiling Orientation HALON - Ceiling Orientation CO2 - Ceiling Orientation EMERGENCY - Ceiling Orientation ALARM - Ceiling Orientation

0.2 (0.1) 0.5 (0.23) 0.18 (0.08) 13 ( 5.9) 13 ( 5.9)


1 (0.4)

0.2 (0.1)

Strobes are shipped with standard wall mount style FIRE lens markings.

05-18-11

Page 4 of 4

D ATA S H E E T Not to be used for installation purposes. Issue 8