LOT-1 CALABAR PLANT TECHNICAL DETAILS

PLANT TOTAL CAPACITY : 563.37 MW Gas Turbines 5 nos Make Model Site Rated Capacity Air Intake Filters Stack Height Generators 5 nos Make Rating Voltage/Amps Step up Transformers 5 nos Make Rating Voltage Cooling Make Rating Voltage Cooling GE GE 9171E DLN 112.674 MW @ 31degC DONALDSON 40meters Brush Electrical Machines Ltd 141.250 MVA 15kV / 5437 Amps / 0.8 pf GE PROLEC 90 / 143 MVA 15 kV / 330 kV ONAN / ONAF Daihen Electric Co Ltd 6 / 8 MVA 15kV / 6.9 kV ONAN / ONAF

Unit Aux Transformers

5 nos

BOP Transformers

1 nos

Make Rating Voltage Cooling

Daihen Electric Co Ltd 150 MVA 330 kV / 132 kV ONAN / ONAF1 / ONAF2

1 nos

Make Rating Voltage Cooling

Daihen Electric Co Ltd 40 / 50 / 60 MVA 132 kV / 33kV ONAN / ONAF1 / ONAF2

Fuel Gas Station

Supplier REPCO S.p.A Emergency Shutdown Valve 2x100% Filter Separators Gas Flow Meter 2x100% Pressure Reducing Station Heating Station (Water Bath Heaters) 2x100% Coalescing Filters Cold Vent Stack Nitrogen Skid Gas Chromatograph Safety Valves / Overhead Crane

Emergency Diesel Gen

2 nos

Make Model Rating Voltage Level

UNATRAC - CATERPILLAR C-18 500 kVA / 400kW 1500 rpm / 415V / 50HZ

Black Start Diesel Gen

2 nos

Make Model Rating Voltage Level Make Model Rating Air Receiver Tanks Air Drier Units

UNATRAC - CATERPILLAR 3516 B HD 2275 kVA / 1820kW 1500 rpm / 6.9 kV / 50HZ INGERSOLL RAND IRN37K-OF 180 Nm3 / hr 2 nos 5m3 each 2 nos 50 Nm3/hr each

Air Compressors

2 x 100 %

Water Treatment Plant

Storage Tanks

Pumps

Raw Water Storage Tank 570 m3 Fire Water Storage Tank 570 m3 Filtered Water Storage Tank 215 m3 Demin Water Storage Tank 10 m3 Potable Water Tank 3 m3 (Admin Bldg) 2 m3 (Control Bldg) 1.2 m3 (Water Treatment Plant) Raw Water Transfer Pumps 2x100% (37m3/hr each) Service Water Transfer 2x100% (13m3/hr each) Pumps Potable Water Transfer 2x100% (30.5m3/hr each) Pumps 2x100% trains One train 30m3/cycle 5 m3 /day

Demin Water Plant

Waste Water System

VENDOR SALCON PTE LIMITED BSDG / EDGs Oily Water Catchment Basin GSU Transf 1 to 3 Oily Water Catchment Basin GSU Transf 4 to 5 Oily Water Catchment Basin 150 & 60 MVA Tranf Stack Drain Pits Washing Water Recovery Pit Back Wash Drain Pit Neutralization Pit Central Waster water monitoring basin

0.6 m3 110.9 m3 110.9 m3 90.9 m3

250 m3

Diesel Oil System

Storage Tanks

Main Storage Tank Fire Water Pump House Black Start Diesel Generator Emergency Diesel Generator 2x100% transfer pumps Unloading pump Jockey Pump Electrical Driven Pump Diesel Engine Driven Pump Hydro Pneumatic Tank Air Compressor Hydrant System Sprinkler system

34 m3 1 m3 4 m3 0.6m3 each (two tanks)

Pumps

13 m3/hr each 8 m3/hr 30 m3/hr 283 m3/hr 283 m3/hr

Fire Fighting System

CRANES

GTG- 1 to 3 GTG 4 to 5 BSDG House EDG House Water Treatment Plant Fire Fighting Pump House Workshop & Warehouse Central Control Building Administration Building EDG Building BSDG Building Fire Water Pump House Fire Truck Station Canteen Workshop & Warehouse Switchyard Control Bldg Guard House

40 Tons 40 Tons 5 Tons 2 Tons (2 nos) 1 Ton 1.5 Tons 10 Tons 30x30x11.7m 36x13.6x9.45m 13.7x8.5x6.75m 26.2x11.5x9.59m 11.4x12x6.2m 17x11.5x7.95m 30x15x4.3m 50x15x8.3m 45.6x13.4x5.15m 9x6x4.3m

Buildings

Housing Estate

Area 2 bed room houses 3 bed room houses 4 bed room houses Canteen Club house First aid station Fire truck station Shops Tennis Court Foot Ball Pitch

200 x 250 m = 50,000 SQM = 5 hectors 28 nos 20 nos 2 nos

Water Storage

Ground Tank Overhead Tank Yokogawa Centum CS 3000 Transtel (PA/Telephone/Clock systems) Available (SELTA PPC) Available (SELTA PPC) ABB Chloride Not Available

Misc

DCS Communication System NCC Communication Tele Protection system MV & LV Switchgear DC & UPS System Security Towers & Cameras

LOT 1 CALABAR POWER STATION OVERVIEW

Total Plant Capacity : 564.37 MW Gas Turbines: 5 nos GE 9171E, DLN (each 112.87 MW as per site conditions) Each Gas Turbine having one Unit Auxiliary Transformer rated 6/8 MVA which step down voltage from 15kV to 6.6kV. Each Gas Turbine having one Generator Stepup Transformers (GSU) of capacity 143MVA which step up voltage from 15kV to 330kV and feed to the power station switchyard. Switchyard: 1. Consists Switchyard control building equipped with protection panels, metering panels, communication panels & DC System. 2. 4 circuits of 330kV out going lines (Calabar-1, Calabar-2, Ikot Ekpene 1, Ikot Ekepene -2) 3. 150MVA transformer step down from 330 to 132kV 4. 60MVA transformer step down from 132kV to 33kV and feed to 33kV switchyard. 5. 33kV switchyard consists 4 outgoing feeders provision to nearby communities.

The Balance of Plant Consists 1. Fuel gas station receives gas from Plant Metering station (NIPP/NGC). Fuel gas station consists emergency shut of valve , two filter separators, two pressure reducing stations, two water bath heaters, condensate tank etc., 2. 3 nos of Black Start Diesel Generators of capacity each 1.82 MW which is mainly used for start up of generators when the grid is off. 3. 2 nos of Emergency Diesel Generators of capacity each 400 KW which is mainly used to feed emergency power to Gas Turbine and its auxiliaries for plant safe rundown during power out.

4. 2 nos of Air Compressors (276 m3/hr each) which supplies service as well as instrument air to plant equipment. 5. Diesel oil System consists of storage tank and transfer pumps which transfers from tank to individual storage tanks located at EDG and BSDG house. 6. Fire Fighting Pump House: Consists jockey pump, motor driven pump and diesel engine driven pump which maintains constant pressure in the hydrant lines. The hydrant lines are distributed throughout the plant includes Transformers Sprinklers Spray System. And also it consists of water storage tank capacity around 570 m3. 7. Plant Water System consists of raw water tank (570 m3), filtered water tank (220 m3) and demin water tank (10m3), Potable water tanks for Control bldg / Admin bldg/ Switchyard Bldg. 8. Waste water treatment system collects used chemical treated water and also sometimes oil which will treat at the plant before disposal. 9. Fire Truck Station consists of Fire truck equipped with water and foam discharges as well as other types of fire extinguishers. 10. Central Control Building located between two turbine shelters. CCB consists low voltage (415 V) & medium voltage (6.6kV) switch gear rooms in the ground floor. In the first floor consists plant DCS (distributed control system) panels and central control room includes monitoring, control stations from there operator can operate the plant. 11. Administration building 12. Ware house and Work Shop: Sufficient space to store spare parts and work shop equipments like lathe machines, grinding, milling machines etc., 13. Canteen Building 14.

Employers Accommodation: Area: 200 x 250 m = 50,000 SQM = 5 hectors Total No. of Houses: 50 2 bed room-28 / 3 bed room 20 / 4 bed room - 2