Elastomeric indoor termination for screened, 1-core polymeric insulated cables with wire screen 10 kV, 15 kV, 20 kV and 35 kV

Dimensions L, D see table

Cable
The termination is designed for 10 kV, 15 kV, 20 kV and 35 kV screened single core polymeric insulated cables with wire screen. For example: NA2XS2Y YHAKXS, , XUHAKXS, AXEKVCE, AXEKVCEY , CXEKVCEY N(A)2XSY XHE 49, XHP 48, , , EHP 48, N(A)2XS(F)2Y .

Design of termination
The screen wires or the earth lead are embedded in sealing mastic. A stress control mastic patch is laid around the end of the screen cut. A highly elastic, non-tracking insulating tubing is slid over the core up to the end of the oversheath. Sealing mastic prevents any moisture ingress at the cable lug.

Nominal voltage Uo /U (kV) 6/10

Cross section (mm2) 25 70 50 185 150 400 25 120 95 300 240 400 25 95 70 240 240 400 35 95 95 185 240 300

Ordering description TFTI-3111 TFTI-3121 TFTI-3131 TFTI-4121 TFTI-4131 TFTI-4141 TFTI-5121 TFTI-5131 TFTI-5141 TFTI-6131 TFTI-6141 TFTI-6151

Dimensions (mm) L D 190 190 190 190 190 190 300 300 300 550 550 550 26 35 41 35 41 46 65 75 85 75 85 95

No. of skirts

8,7/15

12/20

3x1 3x1 3x1 3x5 3x5 3x5

20/35

Note: One termination kit includes material for 3 phases. Longitudinally sealed cable lugs are to be used. Terminations for other cross sections, voltages and cable types are available on request.

32

Elastomeric outdoor termination for screened, 1-core polymeric insulated cables with wire screen 10 kV, 15 kV, 20 kV and 35 kV

Dimensions L, D see table

Cable
The termination is designed for 10 kV, 15 kV, 20 kV and 35 kV screened single core polymeric insulated cables with wire screen. For example: NA2XS2Y YHAKXS, , XUHAKXS, AXEKVCE, AXEKVCEY , CXEKVCEY N(A)2XSY XHE 49, XHP 48, , , EHP 48, N(A)2XS(F)2Y .

Design of termination
The screen wires or the earth lead are embedded in sealing mastic. A stress control mastic patch is laid around the end of the screen cut. A highly elastic, non-tracking insulating tubing is slid over the core up to the end of the oversheath. Sealing mastic prevents any moisture ingress at the cable lug.

Nominal voltage Uo /U (kV) 6/10

Cross section (mm2) 25 70 50 185 150 400 25 120 95 300 240 400 25 95 70 240 240 400 35 95 95 185 240 300

Ordering description TFTO-3111 TFTO-3121 TFTO-3131 TFTO-4121 TFTO-4131 TFTO-4141 TFTO-5121 TFTO-5131 TFTO-5141 TFTO-6131 TFTO-6141 TFTO-6151

Dimensions (mm) L D 190 190 190 190 190 190 300 300 300 550 550 550 61 70 76 61 70 76 65 75 85 75 85 95

No. of skirts 3x1 3x1 3x1 3x3 3x3 3x3 3x5 3x5 3x5 3x8 3x8 3x8

8,7/15

12/20

20/35

Note: One termination kit includes material for 3 phases. Longitudinally sealed cable lugs are to be used. Terminations for other cross sections, voltages and cable types are available on request.