You are on page 1of 8

Technical Specification - Item 10 Characteristic Product name Country of origin Rated power Insulation Liquid Primary voltage Primary

tappings (OFFLOAD) Secondary voltage at no load Primary insulation level Secondary insulation level Frequency Number of phases Vector group Ambient temperature max./monthly/annual average Max. average temperature rise (Oil/Winding) Surface treatment Altitude (a.s.l.) Location Performance values Standards Impedance No load losses Load losses at 75 C Preliminary dimensions and weight Length Width Height Roller distance (c/c) [mm] [mm] [mm] [mm] 1550 1100 1500 x [%] [W] [W] IEC 60076 6(+-10%) 1200(+15%) 6750(+15%) [m] [V] [kV] [kV] [Hz] [V] [kVA] Liquid-Filled Groundmount Transformer; 3PH, 630 kVA, HV 6300D , LV 690yn Turkey 630 Mineral Oil 6300 +2 -2 2.5% 690 LI 60 / AC 20 / Um 7.2 LI - / AC 3 / Um 1.1 50 3 Dyn5 40 / 30 / 20 60 / 65 Painted, RAL 7033 <1000 Indoor/Outdoor

C [C/C]

ABB ELEKTRK SANAY A..


Yukar Dudullu, Organize Sanayi Blgesi 2. Cadde No:16 34776 Umraniye-Istanbul-TURKEY 1/8 Fax: +90.216.365 29 21 Phone:+90.216.528 22 00

Oil Weight Total weight Type of design Tank construction Cooling Primary winding conductor material Secondary winding conductor material Standard Features/Accessories - Item 10 Off-Load Tap Changer DIN type HV and LV bushings Wheels Integrated Safety Detector Pressure Relief Valve

[kg] [kg]

X 1750

Corrugation, Hermetically sealed ONAN Al Al


Technical Specification - Item 20 Characteristic Product name Country of origin Rated power Insulation Liquid Primary voltage Primary tappings () Secondary voltage at no load Primary insulation level Secondary insulation level Frequency Number of phases Vector group Ambient temperature max./monthly/annual average Max. average temperature rise (Oil/Winding) Surface treatment Altitude (a.s.l.) Location Performance values Standards Impedance No load losses Load losses at 75 C Preliminary dimensions and weight Length Width Height Roller distance (c/c) [mm] [mm] [mm] [mm] 1700 1150 1600 x [%] [W] [W] IEC 60076 6(+-10%) 1700(+15%) 10500(+15%) [m] [V] [kV] [kV] [Hz] [V] [kVA] Liquid-Filled Groundmount Transformer; 3PH, 1000 kVA, HV 6300D , LV 690yn Turkey 1000 Mineral Oil 6300 +-2x2.5% 690 LI 60 / AC 20 / Um 7.2 LI - / AC 3 / Um 1.1 50 3 Dyn5 40 / 30 / 20 60 / 65 Painted, RAL 7033 <1000 Indoor/Outdoor

C [C/C]

ABB ELEKTRK SANAY A..


Yukar Dudullu, Organize Sanayi Blgesi 2. Cadde No:16 34776 Umraniye-Istanbul-TURKEY 3/8 Fax: +90.216.365 29 21 Phone:+90.216.528 22 00

Oil Weight Total weight Type of design Tank construction Cooling Primary winding conductor material Secondary winding conductor material Standard Features/Accessories - Item 20 Off-Load Tap Changer DIN type HV and LV bushings Integrated Safety Detector Pressure Relief Valve Wheels

[kg] [kg]

X 2650

Corrugation, Hermetically sealed ONAN Al Al


Technical Specification - Item 30 Characteristic Product name Country of origin Rated power Insulation Liquid Primary voltage Primary tappings (OFFLOAD) Secondary voltage at no load Primary insulation level Secondary insulation level Frequency Number of phases Vector group Ambient temperature max./monthly/annual average Max. average temperature rise (Oil/Winding) Surface treatment Altitude (a.s.l.) Location Performance values Standards Impedance No load losses Load losses at 75 C Preliminary dimensions and weight Length Width Height Roller distance (c/c) [mm] [mm] [mm] [mm] 1800 1150 1650 x [%] [W] [W] IEC 60076 6(+-10%) 2100(+15%) 13500(+15%) [m] [V] [kV] [kV] [Hz] [V] [kVA] Liquid-Filled Groundmount Transformer; 3PH, 1250 kVA, HV 6300D , LV 690yn Turkey 1250 Mineral Oil 6300 +2 -2 2.5% 690 LI 60 / AC 20 / Um 7.2 LI - / AC 3 / Um 1.1 50 3 Dyn5 40 / 30 / 20 60 / 65 Painted, RAL 7033 <1000 Indoor/Outdoor

C [C/C]

ABB ELEKTRK SANAY A..


Yukar Dudullu, Organize Sanayi Blgesi 2. Cadde No:16 34776 Umraniye-Istanbul-TURKEY 5/8 Fax: +90.216.365 29 21 Phone:+90.216.528 22 00

Oil Weight Total weight Type of design Tank construction Cooling Primary winding conductor material Secondary winding conductor material Standard Features/Accessories - Item 30 Off-Load Tap Changer DIN type HV and LV bushings Wheels Integrated Safety Detector Pressure Relief Valve

[kg] [kg]

X 2900

Corrugation, Hermetically sealed ONAN Al Al


Technical Specification - Item 40 Characteristic Product name Country of origin Rated power Insulation Liquid Primary voltage Primary tappings (OFFLOAD) Secondary voltage at no load Primary insulation level Secondary insulation level Frequency Number of phases Vector group Ambient temperature max./monthly/annual average Max. average temperature rise (Oil/Winding) Surface treatment Altitude (a.s.l.) Location Performance values Standards Impedance No load losses Load losses at 75 C Preliminary dimensions and weight Length Width Height [mm] [mm] [mm] 1995 1220 1785 [%] [W] [W] IEC 60076 6(+-10%) 2600(+15%) 17000(+15%) [m] <1000 Indoor/Outdoor [V] [kV] [kV] [Hz] [V] [kVA] Liquid-Filled Groundmount Transformer; 3PH, 1600 kVA, HV 6300D , LV 690yn Turkey 1600 Mineral Oil 6300 +2 -2 2.5% 690 LI 60 / AC 20 / Um 7.2 LI - / AC 3 / Um 1.1 50 3 Dyn5 40 / 30 / 20 60 / 65

C [C/C]

ABB ELEKTRK SANAY A..


Yukar Dudullu, Organize Sanayi Blgesi 2. Cadde No:16 34776 Umraniye-Istanbul-TURKEY 7/8 Fax: +90.216.365 29 21 Phone:+90.216.528 22 00

Roller distance (c/c) Oil Weight Total weight Type of design Tank construction Cooling Primary winding conductor material Secondary winding conductor material Standard Features/Accessories - Item 40 Off-Load Tap Changer DIN type HV and LV bushings Wheels Pressure Relief Valve Terminal Box

[mm] [kg] [kg]

x 645 3345

Corrugation, Hermetically sealed ONAN Al Al