Professional Documents
Culture Documents
US: most sized for cooling load oversized for heating Europe: most sized for base load heating US: 2,000 full-load heating hours/yr
CF = 0.23
(2,200 hours typical) CF = 0.23 to 0.68
Country MWt GWh/yr Number Canada 1,111 2,360 92,600 China 5,210 8,060 434,000 France 1,000 2,800 83,300 Germany 2,230 2,880 185,800 Netherlands 1,394 2,890 116,200 Norway 3,300 7,000 275,000 Sweden 4,460 12,580 371,700 Switzerland 1,017 1,830 84,800 USA 12,000 13,200 1,000,000
largest installation in the USA 600 hotel rooms 100 apartments 960,000 ft of office space Total 1,740,000 ft
Using 2,800 gpm from 4 wells @ 57F Provides 15.8 MW cooling, 19.6 MW heating Energy approx. 53% of similar non-GHP building Saving approx. $25,000 per month
Work done pump used to describe Refrigeration unit reversible Heat absorbed = source Heat delivered = sink Difference in temperature = lift The greater the lift greater power input
Uses geothermal resource between 40 and 90F Either removes heat from a low temperature resource to a higher temperature reservoir (heating) Or removes heat from a high temperature resource to a lower temperature reservoir (cooling)
Lowest when heating demand is highest, and Highest when cooling demand is highest Thus, supplemental energy (electric) source needed
They consume less energy to operate They tap a constant temperature resource They do not require supplemental energy during extreme outside air temperature They use less refrigerant Simpler in design and maintenance Does not require a unit outside exposed to the weather Longer equipment life
Higher initial cost due to excavation for piping or drilling of a well Lack of trained and experienced designers and installers Lack of understanding by government regulators Shallow horizontal heat exchangers are affected by surface (air and sun) temperature variations thus, requiring 30 to 50% more pipe in the ground
General terms:
Geoexchange
Used by Geothermal Heat Pump Consortium
Ground-coupled or earth-coupled (closed loop) tubing network directly buried in the ground - generally a thermally-fused plastic pipe (HDPE) with water or antifreeze (20% propylene glycol) solution circulated through the tubing
Horizontal Vertical Spiral coil in vertical hole Slinky in a horizontal trench Encased in a foundation pile Direct expansion (no heat exchanger)
Groundwater or water-source (open loop) systems use well or lake water. Water quality may be a problem due to calcium carbonate (hardness) and/or iron bacteria causing scaling or fouling of the heat exchangers
Well water Lake water Mine water Tunnel water Standing column
vertical
horizontal slinky
two well
single well
indirect
direct
pond pond
USA experience
1,000,000 total installations (estimated) Mainly in midwestern and eastern states 100,000 to 120,000 installed annually
45% horizontal closed loop (mainly residential) 45% vertical closed loop (mainly commercial/institutional) 10% water-source open loops
Spiral slinky
That is: for a COP of 4, for every unit of electrical input, the system puts out 4 units of heat energy
Denver (Stapleton): 924F-days cooling (>65F), 6,282F-days heating <65C) System Cooling Heating DHW Total (kWh) (kWh) (kWh) (kWh) Electric 3,910 17,640 4,120 25,670 ASHP 1,960 8,820 4,120 14,900 GHP 1,220 4,650 2,510 8,380
For a 2000 ft home, newly constructed with desuperheater: est. annual savings @ 8/kWh = $1,385 (electric vs GHP), and $522 (ASHP vs GHP)
Steamboat Springs, CO: 300F-days cooling (>65F), 7,300F-days heating <65C), the annual loads are: System Cooling Heating DHW Total (kWh) (kWh) (kWh) (kWh) Nat. Gas 520 25,400 5,150 31,070 Electric 500 20,300 4,120 24,920 ASHP 400 10,150 4,120 14,670 GHP 340 5,400 3,150 8,890
For a 2000 ft home, newly constructed with desuperheater: est. annual savings @ 8/kWh = $1,280 (electric vs GHP), and $462 (ASHP vs GHP). For natural gas at $12/million Btu, the annual savings would be $910 compared to GHP.
Steamboat Springs, CO: 750 FLH cooling (>65F), 750 FLH heating heating <65F) annual loads System Cooling Heating DHW Total (kWh) (kWh) (kWh) (kWh) Nat. Gas 47,100 137,500 10,000 194,600 Electric 45,000 110,000 8,000 163,000 ASHP 30,000 55,000 8,000 93,000 GHP 23,550 27,500 4,000 55,050 For a 10,000 ft commecial building with desuper-heater: est. annual savings @ 8/kWh = $8,640 (electric vs GHP), and $3,040 (ASHP vs GHP). For natural gas at $12/million Btu the annual savings would be = $5,700 compared to GHP = 8 year payback for new construction for 35 tons and 16 years for retrofit.
Costs more than conventional system; however, savings are greater Costs depend upon:
The availability and experience of contractors Cost of drilling or trenching (or well)
Total installed cost (10.5 kW 3 tons) for a 2000 ft home with duct work and controls
ASHP and Gas with AC ~ US$ 4 to 5,000 ($1300 1,700/ton) GW GHP ~ US$ 7,000 (+ well cost) ($2,450/ton) Ground-coupled GHP ~ US$ 8 to 9,000 ($2,700 3,000/ton)
Ground coupled horizontal: $750/ton Ground coupled slinky: $900/ton Ground coupled vertical: $1,025/ton Ground water (3 ton): $570/ton (w/o well)
8.8 kW (2.5 tons): 10.5 kW (3.0 tons): 14.1 kW (4.0 tons): $2,750 ($1,100/ton) $3,000 ($1,000/ton) $3,600 ($900/ton)
Substantial variations possible. Ref: Kavanaugh & Gilbreath (1995), and Rafferty (2008)
4x for electric resistance 3x for propane 2x for ASHP 2x for fuel oil 2x for natural gas
Assuming a rebate by local government of $200/kW ($2,000 per home) 5 kW reduction in peak heating demand 2.5 kW reduction in peak cooling demand 200,000 new homes produce 1000 MW savings Power plants installed cost = $3,000/kW Thus, cheaper to provide rebates than build newer power plant ($200 vs $3,000/kW) Rebates offered in USA and Switzerland ($500 to $2,000 per home) to installed heat pumps
Cooling demand usually the largest Using central or multiple control units Groundwater systems the oldest and most widely used approach with two wells, often reversing source from winter to summer Multiple ground-coupled system becoming popular vertical bore holes 100 to 400 ft. deep in large fields under parking lots Ref: Kavanaugh & Rafferty, ASHRAE, 1997