Paralysie respiratoire
Arrt Du cur
-UTE 15127
Rgime TT
Rgime TN Rgime IT
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
PLAN
1. CIRCULATION DU COURANT DE DFAUT
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
PRINCIPE
Schma
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
1 CIRCULATION DU COURANT DE DFAUT
Schma
Id
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
2 SCHMA LECTRIQUE QUIVALENT
Schma
Id L1
Je me trouve en parallle avec quelle rsistance?
Rd
Ra
Rn
Rn
Ra
Rc
Rd
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
2 SCHMA LECTRIQUE QUIVALENT
Schma
Id L1
Je me trouve en parallle avec quelle rsistance?
Rd
Ra
Rn
Rn
Ra
Rc
Rd
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
2 SCHMA LECTRIQUE QUIVALENT
Schma
Id L1 Rd
Ra
Rn
Rc
Uc
Rn
Ra
Rc
Rd
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
3 DTERMINATION DE LA TENSION CORPORELLE On considre : Un rseau 230/400V L1 Une rsistance de mise la terre du neutre de 10
Rd Ra 20 230V Rn
0 Rc Uc 2000
10
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
4 VALUATION DU DANGER
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
5 INTENSIT DU COURANT CORPOREL
Ra
Rn
Ic Rc
Uc 2000
ms 10000
7. PROTECTIONS
5000
2000
1
1000 500
200
3
100
50
20 10 0.1
0.2
0.5
10
20
50
100
200
500
(ma eff)
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
5 INTENSIT DU COURANT CORPOREL
L1 Loi dOhm : Ic = Uc / Rc = 153 / 2000 = 0,0765 A Ic = 76,5mA Effets physiologiques ? Risque de fibrillation cardiaque aprs 1 s V Rd 153V
Ra
Rn
Ic Rc
Uc 2000
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
6 CALCUL DE LINTENSIT COURANT DE DFAUT
Id Rd Ra 0 20 10
230V Rn
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS COUPURE DE LALIMENTATION DS LAPPARITION DU DFAUT Intensit du courant de dfaut Id = 7,65 A Valeur qui sajoute au courant demploi, trop faible pour provoquer le dclenchement dune protection classique (courtcircuit ou surcharge), un rcepteur domestique ou industriel absorbant couramment plus dune dizaine dAmpres.
Solution
Utiliser un appareil de protection capable disoler et de ne mesurer que le courant de dfaut. Dispositif Diffrentiel courant Rsiduel
DDR
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS Principe dun Dispositif Diffrentiel courant Rsiduel Isoler et ne mesurer que le courant dfaut PE L1 L2 L3 N I1 I2 I3 In
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS Principe dun Dispositif Diffrentiel courant Rsiduel Isoler et ne mesurer que le courant dfaut PE L1 L2 L3 N
1) Absence de dfaut
I1
I2 I3 In
I 1 + I2 + I3 + In = 0
1 + 2 + 3 + n = 0
us = 0 Pas de dclenchement
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS Principe dun Dispositif Diffrentiel courant Rsiduel Isoler et ne mesurer que le courant dfaut PE L1 L2 L3 N
I1
I2 I3 In
I 1 + I2 + I3 + In = Id
1 + 2 + 3 + n = d
us > 0 Dclenchement
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS Rgles observer 1)Dans les schmas TT, on assurera la protection par un dispositif diffrentiel courant rsiduel. La sensibilit du dispositif diffrentiel est indiqu par le symbole In. Ce dispositif peut tre un interrupteur ou un disjoncteur. 2)Toutes les masses des matriels protgs par un mme dispositif de protection doivent tre interconnectes et relies par un conducteur de protection une mme prise de terre.
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS Emplacement des dispositifs diffrentiels Toute installation TT doit tre protge au moins par un dispositif diffrentiel courant rsiduel plac lorigine de linstallation.
DDR
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS Emplacement des dispositifs diffrentiels Protections slectives
DDR MS
DDR HS
DDR HS
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS Emplacement des dispositifs diffrentiels Protections slectives
DDR MS
DDR HS
DDR HS
1. CIRCULATION
2. SCHMA
3. TENSION CORPORELLE
4. DANGER?
5. COURANT CORPOREL
6. COURANT DE DFAUT
7. PROTECTIONS
RGIME DU NEUTRE TT
7 PROTECTIONS Emplacement des dispositifs diffrentiels Protections slectives
Rgle Pour une slectivit totale il faut : 1. In sensibilit du dispositif amont 2 x In sensibilit du dispositif aval 2. Temps de dclenchement du dispositif amont > temps de dclenchement du dispositif aval DDR HS
DDR MS
DDR HS
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
PLAN
1. PRINCIPE 2. SITUATION DU PROBLME 3. SOLUTION 4. DIFFRENTS SCHMAS TN 5. CAS OU LA LONGUEUR DES CANALISATIONS DPASSE Lmax
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
1 PRINCIPE T : Neutre la Terre N : Masses au Neutre
Exemple
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
1 PRINCIPE Tout dfaut disolement entre un conducteur actif et une masse est transform dfautDE phase/neutre. CIRCULATION DU en COURANT DFAUT Exemple
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
2 SITUATION DU PROBLME Le courant de dfaut nest limit que par limpdance : des cbles, du dfaut et du transformateur. Cette impdance est trs faible, lintensit du courant de dfaut est trs importante (courtcircuit). La norme attribue arbitrairement 20% de la chute de tension au distributeur dnergie (EDF)
A
E 0,8. Id V D
C
Prise de terre du neutre Prise de terre des utilisations
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
2 SITUATION DU PROBLME
SCHMA LECTRIQUE QUIVALENT
Schma quivalent
F
A
E Id
Rpen
B
0,8.V
Rl3
C
Id
Rl3
0,8.V
Rd
Rpen
Ic
Rc
Uc
C Rd
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
2 SITUATION DU PROBLME
DTERMINATION DE LA TENSION CORPORELLE
Uc = 0,8VxRpen/(Rl3+Rpen+Rd)
Remarque : RC>>Rpen
(Rpen//RC)~Rpen
Rd
Rpen
Ic
Rc
Uc
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
2 SITUATION DU PROBLME
VALUATION DU DANGER
Rd
Rpen
Ic
Rc
Uc
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
2 SITUATION DU PROBLME
INTENSIT DU COURANT CORPOREL
Ic = 46mA
Effets physiologiques ?
Rd
Rpen
Ic
Rc
Uc
ms 10000
7. PROTECTIONS
5000
2000
1
1000 500
200
3
100
50
20 10 0.1
0.2
0.5
10
20
50
100
200
500
(ma eff)
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
2 SITUATION DU PROBLME
INTENSIT DU COURANT CORPOREL
Exemple : Rc =2000 Loi dOhm : Ic = Uc / Rc = 92 / 2000 = 0,046 A Ic = 46mA Effets physiologiques ? Risque de fibrillation cardiaque aprs 3s E
0,8.V
Rd
Rpen
Ic
Rc
Uc
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
2 SITUATION DU PROBLME
CALCUL DE LINTENSIT COURANT DE DFAUT
Id = 0,8 V /(Rl3+Rd+(Rpen//Rc)) Id ~ 0,8 V / (Rl3+Rd+Rpen) Exemple : Rl3 = 40m Rd = 0 Id = 0.8 x 230 / (0,040+0,040) Id = 2300 A E Rpen = 40m
0,8.V
Rd
Rpen
Ic
Rc
Uc
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
3 SOLUTION
PROTECTIONS
disjoncteur, fusible.
Un disjoncteur ou fusible assure la protection des personnes dans un schma TN, condition que le courant de dfaut soit suprieur au courant de fonctionnement du dclencheur magntique. Id > Imag, Ou pour les fusible suprieur au courant assurant la fusion. Id>If
RGIME DU NEUTRE TN
Remarque: Pour que la protection des biens et des personnes soit assure, il faut sassurer que le dispositif de protection ragisse. Pour cela il faut quen cas de dfaut lintensit du courant soit suffisamment importante pour provoquer le dclenchement. Pour rpondre ce problme, la norme impose une longueur maximale des canalisations.
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
3 SOLUTION R= .l/(Sph+Spe) Avec m= Sph/Spe R= .l.(1+m)/Sph sachant que Id > Imag,Id>If pour que la protection des personnes soit assure, on en ddui: Imag(ou If)<0.8V.Sph/ .l.(1+m)
Lmax <
0,8xVxSph
1.PRINCIPE
2.SITUATION DU PROBLME
3.SOLUTION
4. DIFFRENTS SCHMAS TN
5. CAS OU L>Lmax
RGIME DU NEUTRE TN
4 DIFFRENTS SCHMAS TN
TNC
RGIME DU NEUTRE TN
4 DIFFRENTS SCHMAS TN TNS : Le conducteur neutre est spar davec le conducteur de protection
lectrique (Pe). Le conducteur Pe nest pas coup, mais le neutre peut ltre, on utilise un appareillage ttrapolaire.
TNC
TNS
RGIME DE NEUTRE TN
4 DIFFRENTS SCHMAS TN TNS : Un schma TNS peut suivre un schma TNC, mais on ne peut pas reprendre en TNC.
Ce type de schma est autoris pour des sections suprieures 10mm(6mm pour le TNC)
TNC
TNS
1.
3.
4. DIFFRENTS SCHMAS
RGIME DE NEUTRE TN
5 CAS OU LA LONGUEUR DES CANALISATIONS DPASSE Lmax Dans ce cas on peut :- augmenter les sections de cbles - mettre un dispositif diffrentiel ( attention le conducteur Pe doit passer lextrieur du tore, seul le rgime TNS est possible)
TNC
TNS
1.
3.
4. DIFFRENTS SCHMAS
RGIME DU NEUTRE IT
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
PLAN
1. PRINCIPE 2. CAS DUN PREMIER DFAUT 3. CONTRLEUR PERMANENT DISOLEMENT
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
1 PRINCIPE I : Neutre Isol ou Impdant T : Masses la Terre
Schma
Impdance
Z
CPI
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
2 CAS DU PREMIER DFAUT - Calcul de la tension corporelle Circulation du courant de dfaut Schma
Impdance Z
CPI
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
2 CAS DU PREMIER DFAUT - Calcul de la tension corporelle Circulation du courant de dfaut Schma
Impdance
Z
CPI
Id
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
2 CAS DU PREMIER DFAUT - Calcul de la tension corporelle Circulation du courant de dfaut Schma
Schma quivalent
L1
Je me trouve en parallle avec quelle rsistance?
Rd V Ra Rn Rc Uc
Impdance
Z
CPI
Id
Rn
Ra
Rd
Z N
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
2 CAS DU PREMIER DFAUT - Calcul de la tension corporelle Circulation du courant de dfaut Calcul de la tension corporelle Uc = V x (Ra//Rc)
Schma quivalent
L1 Rd V Ra Rn Rc Uc
Rd+(Ra//Rc)+Rn+Z
Avec Ra//Rc = Ra x Rc / (Ra + Rc)
Exemple : Ra = Rn = 10 Rd = 0 Z = 2200 Rc = 1k Ra//Rc = 1000 x 10 / (1000 + 10) = 9,9 Uc = 230 x 9,9 / (9,9 + 10 + 2200) = 1v
Z N
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
2 CAS DU PREMIER DFAUT - Calcul de la tension corporelle
Est-ce quil y a danger ? Uc = 1V Uc<<Us Us tension limite de scurit Us = 12V; 25V; 5OV selon les degrs dhumidit.
L1 Rd V Ra Rn Ic Rc Uc
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
3 CONTROLEUR PERMANENT DISOLEMENT
Le premier dfaut nest pas dangereux et ne ncessite pas la coupure immdiate de linstallation, ce qui nest pas le cas du deuxime dfaut. La rgle impose la signalisation et la localisation du premier dfaut afin den permettre la rparation ds que possible. La continuit de service (principal avantage du schma IT) peut ainsi tre assure. Le Contrleur Permanent dIsolement (C.P.I) permet un signalement automatique du dfaut et peut offrir une aide sa localisation.
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
3 CONTROLEUR PERMANENT DISOLEMENT
Principe
(dfaut)
Relais
Voyant
R
CPI
Gnrateur Klaxon
Mesure disolement
Id
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
4 CAS DUN DEUXIME DFAUT
Schma
Impdance
Z
CPI
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
4 CAS DUN DEUXIME DFAUT Circulation du courant de dfaut Schma
Impdance
Id
Z
CPI
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
4 CAS DUN DEUXIME DFAUT Circulation du courant de dfaut Schma quivalent L2 Rd1 U Ra1 Ra2 Rd2
Impdance Z
Id
L3
Ra2
Rd2
Ra1
Rd1
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
4 CAS DUN DEUXIME DFAUT Circulation du courant de dfaut Schma quivalent L2 Rd1 U Ra1 Impdanc Rc1 e Z
Je me trouve en parallle avec quelle rsistance?
Je me trouve en parallle avec quelle rsistance?
Id
L3
Ra2
Rd2
Ra1
Rd1
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME D NEUTRE IT
4 CAS DUN DEUXIME DFAUT
Schma quivalent L2
Rd1 U Ra1 Ra2 Rd2 Rc1 Rc2
Uc1
Uc2
L3
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
4 CAS DUN DEUXIME DFAUT
Est-ce quil y a danger ? Schma quivalent L2 Rd1 U Ra1 Ra2 Rd2 Rc1 Rc2 Uc 1 Uc 2 Uc1 = Uc2 = 200V Uc>>Us Us tension limite de scurit
DANGER
Calcul de lintensit du courant corporel Ic = Uc / Rc = 200 / 1000 = 0,2A Ic = 200mA DANGER ?
L3
1. PRINCIPE
2. 1re DFAUT
3. CONTRLEUR
3. 2me DFAUT
RGIME DU NEUTRE IT
4 CAS DUN DEUXIME DFAUT Conclusion Schma quivalent L2
Rd1 U Ra1 Ra2 Rd2 Rc1 Rc2 Uc 1 Uc 2 Il faut noter que le Rgime du neutre IT est proscrire si vous ne possdez pas de technicien capable dintervenir 24/24h 7/7h ce qui est obligatoire daprs la norme. Protection : Id = U / R = 400 / 20 = 20A Dispositif diffrentiel courant rsiduel en tte de chaque groupe de masses interconnectes, Et que sa sensibilit : I = Us /R prise de terre
L3
Conclusion