You are on page 1of 25

PTHVP - Page 1

Application ITs

Why Instrument
Transformers?

Instrument Transformers in general

PTHVP - Page 2

Application and selection parameters

Example of an 132/20 kV S/S


Two line bays

Single busbar

132 kV

PTHVP - Page 3

Two transformer bays


132/20 kV

PTHVP - Page 4

Protection system - General purpose

Detect all electrical faults and some


abnormal operating conditions.

Protect human beings and properties


around the power network.

Protect apparatus, power lines etc


from unnecessary damage.

Disconnect minimum possible part of


the power network.

Restore normal operation

Protection system
Fault
analysing
equipment

Protection

Instrument
Transformers

relays
Station
building

PTHVP - Page 5

Communication
Equipment

Power
System
Circuit
breaker

Different types of protections


Two line bays
Earth fault

Single busbar

132 kV

Bus bar fault

PTHVP - Page 6

Two transformer bays


132/20 kV

Protection - Lines
Earth fault

Lightning

132 kV

The transmission lines are


the least protected parts of
the system from
environmental influences.

REL 511
Line protection
C
E

PTHVP - Page 7

Among the most important


protection system in the
power system.

Line fault clearing is subject to authority


regulations due to the risk for damage to
general public and equipment not
belonging to the power system.

Protection - Lines

Z = U/I

Z<

PTHVP - Page 8

132 kV

Z<

132 kV

Over current protection

Overload

132 kV
REL 511
Line protection
C

PTHVP - Page 9

Busbar protection

I1

Kirchhoffs law 1
I1 + I 2 + I 3 + I 4 = 0

I2

Single busbar

132 kV
To actual Circuit Breaker

I3

RAD 55
Busbar
protection
C

PTHVP - Page 10

132/20 kV

I4

Busbar fault

Transformer protection

C
E

PTHVP - Page 11

Example of transformer protection


Pressure guard
Overload
Over-current
Ground fault
Differential

RADSB
Transformer
differential
protection

Signal from MV
current
transformer

Voltage transformer on busbar


Often measurement in one phase

Synchronizing

Over voltage protection

PTHVP - Page 12

C
E

Ex. No load line

Under voltage protection

Synchronizing
relay

Phase position

Ex. Overloaded line

Voltage indication

Metering

Wactive = U . I. cos kWh

Energy Meters
kWh
kVAr

Numerical
Energy calculation
VT

kWh
kVAr

CT

Tomorrow
Today

Electronic
Analogue Integrator
Yesterday

PTHVP - Page 13

kWh
kVAr

Mechanical
Integrator

METER
Rb
A/D conversion
Computer

Energy output

Ancient

PTHVP - Page 14

Why Instrument Transformers?

Transform high currents and voltages


to levels suitable for instruments and
relays.
Standardised secondary currents and
voltages
Ex 1 or 5 A, 100 or 110 V

Insulate secondary circuits from


primary net.

The instrument transformer must, at


every moment be able to correctly
sense and transmit the currents and
voltages of the network!
The relays are deaf and blind!

Instrument Transformers

PTHVP - Page 15

Important parameters when selecting instrument transformers

Project and customer

Standard / Customer
specification

Insulation data

Thermal data

Core / windings data

Important parameters when selecting ITs

PTHVP - Page 16

Insulation data

Highest voltage for equipment (Um)

(Ex 145 kV)

Rated system voltage (Ex 132 kV)

Test voltages
Lightning impulse 1.2/50 s (Simulating lightning, Ex 650 kV)
Power frequency dry/wet
(Ex 275 kV)
Switching surge 250/2500 s
(For Um > 300 kV, wet. Replace power
frequency test)

Creepage distance
(Based up on Um)
Pollution, Salt spray ?
(We have often as standard >25 mm/kV)

Altitude above sea level


Over/under 1000 m
(Capacitance for CVTs)

Problem with high altitudes ? >1000m a.s.l.

Outer insulation dielectric strength is


reduced due to:

Inner insulation is not affected due to:

PTHVP - Page 17

lower air pressure


lower density of air
we must dimension for outer flashover
distance, i.e. longer porcelain.

internal pressure is constant

High altitudes >1000m a.s.l.

PTHVP - Page 18

Technical data required for quoting and ordering

Normal system and test voltages according to


IEC standard when 1000m a.s.l.

Actual altitude above sea level.

We take care of the rest!

Important parameters when selecting current transformers

Thermal data

Rated currents
Primary/secondary
Primary/secondary reconnection

Rated continuous thermal current (Rf)

Short time current, Ith

PTHVP - Page 19

(Ex 25 kA/1sek)

Dynamic current, Idyn

1.0 , 1.2 , 1.5 , ......... (IEC)

(2.5 x Ith)

Ambient temperature

To high temp. destroy insulation material

Important parameters when selecting current transformers

Core data

Primary/secondary reconnection

Number of cores

Metering / Protection

Burden / class Examples

PTHVP - Page 20

20 VA cl 0.2, FS 5
30 VA cl 5P20
FS and ALF are valid at rated burdens
(Class X)
Ekn V

Rct Ohm

I0 mA

Important parameters when selecting voltage transformers

Thermal data

Rated voltages
Primary/secondary

(Ex: 132 000/V3:110/V3:110/3 V)

Voltage factor (Vf)


Type

of system earthing
Effectively earthed - 1.5/30 sec
Not effectively earthed - 1.9/30 sec (8h)

Thermal limit output


not be > Vf 2 x Sn
(Sn = Total rated burden)

PTHVP - Page 21

Can

Ambient temperature

Voltage Transformer windings

da

da

Open delta winding for earth fault


detection

dn

PTHVP - Page 22

Y-windings for metering


(and protection purpose)

da

dn

Metering

dn

Open delta

Important parameters when selecting voltage transformers

Winding data

Number of secondary windings

Metering / protection / earth fault

Burden / class
30 VA cl 0.2
A rated burden around 1.3-1.5 times the
connected burden, will give maximum
accuracy at connected burden.
100 VA cl 3P

Simultaneous burden
Metering and protection windings are seen as
continuously loaded.
Earth fault winding is seen as loaded only at faults.

PTHVP - Page 23

Modern Relays and Energy meters

Consumes very little power.


Typical < 5 VA
All consumption in cables
A/D conversion in relay

Secondary currents from earlier 5 A


towards 1 A.
kWh

Standard burden cos 0.8

PTHVP - Page 24

(Reality cos 1.0)

PTHVP - Page 25

You might also like