Professional Documents
Culture Documents
Application ITs
Why Instrument
Transformers?
PTHVP - Page 2
Single busbar
132 kV
PTHVP - Page 3
PTHVP - Page 4
Protection system
Fault
analysing
equipment
Protection
Instrument
Transformers
relays
Station
building
PTHVP - Page 5
Communication
Equipment
Power
System
Circuit
breaker
Single busbar
132 kV
PTHVP - Page 6
Protection - Lines
Earth fault
Lightning
132 kV
REL 511
Line protection
C
E
PTHVP - Page 7
Protection - Lines
Z = U/I
Z<
PTHVP - Page 8
132 kV
Z<
132 kV
Overload
132 kV
REL 511
Line protection
C
PTHVP - Page 9
Busbar protection
I1
Kirchhoffs law 1
I1 + I 2 + I 3 + I 4 = 0
I2
Single busbar
132 kV
To actual Circuit Breaker
I3
RAD 55
Busbar
protection
C
PTHVP - Page 10
132/20 kV
I4
Busbar fault
Transformer protection
C
E
PTHVP - Page 11
RADSB
Transformer
differential
protection
Signal from MV
current
transformer
Synchronizing
PTHVP - Page 12
C
E
Synchronizing
relay
Phase position
Voltage indication
Metering
Energy Meters
kWh
kVAr
Numerical
Energy calculation
VT
kWh
kVAr
CT
Tomorrow
Today
Electronic
Analogue Integrator
Yesterday
PTHVP - Page 13
kWh
kVAr
Mechanical
Integrator
METER
Rb
A/D conversion
Computer
Energy output
Ancient
PTHVP - Page 14
Instrument Transformers
PTHVP - Page 15
Standard / Customer
specification
Insulation data
Thermal data
PTHVP - Page 16
Insulation data
Test voltages
Lightning impulse 1.2/50 s (Simulating lightning, Ex 650 kV)
Power frequency dry/wet
(Ex 275 kV)
Switching surge 250/2500 s
(For Um > 300 kV, wet. Replace power
frequency test)
Creepage distance
(Based up on Um)
Pollution, Salt spray ?
(We have often as standard >25 mm/kV)
PTHVP - Page 17
PTHVP - Page 18
Thermal data
Rated currents
Primary/secondary
Primary/secondary reconnection
PTHVP - Page 19
(Ex 25 kA/1sek)
(2.5 x Ith)
Ambient temperature
Core data
Primary/secondary reconnection
Number of cores
Metering / Protection
PTHVP - Page 20
20 VA cl 0.2, FS 5
30 VA cl 5P20
FS and ALF are valid at rated burdens
(Class X)
Ekn V
Rct Ohm
I0 mA
Thermal data
Rated voltages
Primary/secondary
of system earthing
Effectively earthed - 1.5/30 sec
Not effectively earthed - 1.9/30 sec (8h)
PTHVP - Page 21
Can
Ambient temperature
da
da
dn
PTHVP - Page 22
da
dn
Metering
dn
Open delta
Winding data
Burden / class
30 VA cl 0.2
A rated burden around 1.3-1.5 times the
connected burden, will give maximum
accuracy at connected burden.
100 VA cl 3P
Simultaneous burden
Metering and protection windings are seen as
continuously loaded.
Earth fault winding is seen as loaded only at faults.
PTHVP - Page 23
PTHVP - Page 24
PTHVP - Page 25