Professional Documents
Culture Documents
Office
Lighting
8-double 36 watt fluorescent lights
Power
8- double10A single phase outlets
1- single 10A single phase outlet
Step 1
Divide the installation into circuits and
distribute these circuits across the three
phases
Calculate the maximum demand of the
installation
The maximum demand of the sub- mains
is the load on the heaviest loaded phase
Office
MD Sub-mains
using table C2
Factory
Circuit
no
1
2
3
4
5
6
7
8
Load
group
Load
calculation
4 x 1.5 = 6
4 x 1.5 = 6
0.12 3 .36
0.36
500
2.72
230 0.8
2.72
Bi
Bi
Bi
6
0.8
1000
3 750
14.14
230
1000
3 750
14.14
230
1000
3 750
14.14
230
14.14
14.14
14.14
Load
group
Load
calculation
9
10
11
12
B (iii)
Full load
20
20
20
B (iii)
15
15
15
B (iii)
15
15
15
Full load
15
15
15
office
13
14
15
8 0.78 6.24
B (i)
B (i)
6 750
19.56
230
6 750
16
B (i)
Maximum D
230
6.24
19.56
19.56
19.56
5 750w
16.3
230
16.3
104.7
104.7
105.6
Sub-mains
Vd
Vc L I 1.62 38 106
6.52 Volts
1000
1000
So 25mm X90 SDI Cables in separate conduits will satisfy both current and
voltage drop requirements.
Unit 1 has the longest run (38 metres) so 25mm will satisfy units 2 and 3
Installation load
Installation load
Power
42 double 10A single phase outlets
3 single 10A single phase outlets
9 20A three phase outlets
3 3 phase HWS
load
Calculation
8 x 1.5 = 12
12
12
12
6.24
6.24
6.24
24 2x36W Fluorescent
Luminaires (8 per phase)
8 0.78 6.24
4 x 0.05 = 0.2
0.2
0.2
0.2
2 x 0.3 = 0.6
0.6
0.6
0.6
0.12 x 3 =.36
0.12 x 2 = .24
0.36
0.36
0.24
2.71
2.71
2.71
3 500W
500
2.71
230 0.8
1000 28 750
95.65
230
95.65
95.65
95.65
20 + 8 x 15 =140
140
140
140
3 x 15 = 45
45
45
45
302.8
302.8
302.7
MD
The consumer mains are X90 SDI cables installed in conduit U/G for a
length of 40 metres
Determine the cable size to suit current and voltage drop requirements
Table 2.4 item 2 refers to Table 7/16
150mm = 330A The cable can carry the MD current
Check for voltage drop.
Table 41 Vc for 150mm conductors = 0.309mV/Am (60C) The cable
is rated at 90C and by choosing a Vc value at 60C this allows for
temperature rise under Short circuit conditions
0.309 40 303
3.745
1000
1000
10 metres
20 metres
MSB
DB
unit3
DB
Unit 2
38 metres
Sub-main voltage drop 6.52 volts
3.745 Volts
6.52 Volts
DB
Unit 1
Sub-main
Final sub-circuits
6.52 volts
10.265 10.265
5.93 Volts
1
.
73
3
Circuit arrangements
Cable
Maximum Installation Parameters
Designation demand
AZ/NZS
3008/1/1
Table No
column
Consumers
mains
302 A
XLPE (X90)
SDI enclosed UG
Table 2.4
Table 7
4
16
Sub-mains
106 A
Table 2.4
Table 7
4
18
4x250W MV
6A
Lamp Factory
2 circuits
Table 2.1
Table 9
Table 24
4
2
8
10A outlets
Factory
Table 2.1
Table 9
Table 24
4
2
8
16A
Cable
Maximum
designation demand
Installation
parameters
AS/NZS
3008
Table no
3 phase
outlets
Table 2.1
Table 12
Table 24
4
2
8
EF + Battens 0.8A
In Toilets
TPS unenclosed
3 other circuits on
cable tray up wall
from switchboard
Table 2.1
Table 9
Table 24
De-rate 0.88
4
2
8
HWS
15
TPS unenclosed
3 other circuits on
cable tray up wall
with 3 other circuits
Table 2.1
Table 12
Table 24
De-rate 0.88
4
2
8
500W SV
2.8A
TPS installed
enclosed U/G
Table 2.4
Table 9
20A
Column
no
4
16
Mains
U/G
turret
Determine the cable size for
the 20A 3 phase outlets 1
per circuit, longest run 38
metres The cable is 3core
TPS V 90 installed enclosed
in air. No de-rating for this
section. Unenclosed in air
spaced on perforated tray up
wall above switchboard 4
circuits
20
24.4
0.82
Table 12/4 a 4mm 2 cable 29A
Unit 1
DB
MSB
20A
3 outlet
1000 Vd
Vc
L I
1000 9.735
38 20
12.8mV / Am
Mains
U/G
turret
MSB
Determine the cable size for the 20A 3 phase outlets 1 per circuit,
Route length 25 metres
Current carrying capacity is the limiting factor in this circuit
20A
3 outlet
To satisfy Current carrying capacity, a
4mm TPS cable is required
Unit 1
DB
Mains
U/G
turret
MSB
Unit 1
DB
20A
3 outlet
14.65mV/A.m
L I
38 10
convert to three phase
14.65 0.86 12.69mV/A.m
Therefore from Table 42, 4mm cable is required for volt drop
Cable enclosed in conduit on wall with 3 0ther circuits spaced
( 4 circuits )
Table 9/6 4mm cable = 26A
De-rating Table 22 (0.9) 26 x 0.87 = 23.4A
18.56mV/A.m
L I
30 10
convert to three phase
18.56 0.86 16.07 mV/A.m
29.316mV / A.m
L I
38 5
convert to three phase Vc 0.866
29.31 0.866 25.39mV / A.m
25.328mV / A.m
L I
44 5
convert to three phase Vc 0.866
25.318 0.866 21.925mV / A.m
39.78mV / A.m
L I
28 5
convert to three phase Vc 0.866
39.78 0.866 34.45mV / A.m
318.28V / A.m
L I
50 .36
convert to three phase Vc 0.866
318.28 0.866 275.63mV / A.m
127.98mV / A.m
L I
16 2.72
convert to three phase Vc 0.866
127.98 0.866 110 .8mV / A.m
23.17mV/Am
L I
28 15
Table 41 (2.5mm = 15.6mm)Therefore 2.5mm Cable
Office
8-2x36W(0.78A) fluorescent one circuit
Route length 40m Use 10A MCB
Rule 3.6.2 50.% circuit protective device for voltage drop
27.85mV / A.m
L I
40 5
convert to three phase Vc 0.866
27.85 0.866 24.118 mV / A.m
Table 42 1.5mm = 28.6mV/Am.
Use 1.5mm cable
25.318mV / A.m
L I
22 10
convert to three phase Vc 0.866
25.318 0.866 21.925mV / A.m
Table 42
2.5mm = 15.6mV/Am
2.5mm Cable for all socket outlet circuits in the office.
Distributor's network
POS
MEN
Neutral
Bar
Main Earth
Faulty equipment
Soil resistance high between
electrodes
MCBS
L L L L L P P P P P
P HW L P P P
10 10 10 10 10 16 16 16 20 20 20 16 10 16 16 16