Process control

Systems

30 November 2017 By Eng. Hesham A. Selim


AUTOMATIC
PROCESS
CONTROL

30 November 2017 By Eng. Hesham A. Selim


DEFINITION

Any operation that regulates some internal physical


characteristic that is important to a living organism
Example:
natural regulation in humans include body
temperature, blood pressure, and heart rate

30 November 2017 By Eng. Hesham A. Selim


Process Control Variables

DISTURBACES

MANIPULATED CONTROLLED
VARIABLES PROCESS VARIABLES

30 November 2017 By Eng. Hesham A. Selim


Element of process control

The purpose of this control


system is to maintain the
liquid level at some
prescribed height (H)
above the bottom of the tank
Element of process control

1-Process
2-Measurement
3-Evaluation
4-Control

30 November 2017 By Eng. Hesham A. Selim


General Requirements of a
Control System
The primary requirement of a control system is that it be reasonably stable.

1. SYSTEM ERROR
The system error is the difference between the value of
the controlled variable set point and the value of the
process variable maintained by the system
e(t) = PV(t) SP(t)

30 November 2017 By Eng. Hesham A. Selim


SYSTEM RESPONSE
-under damped (cyclic response)
-damped.

30 November 2017 By Eng. Hesham A. Selim


Intuitive Approach to Process
Control Concepts
The practice of process control arose long
before the theory or analytical methods
underlying it were developed. Processes
and controllers were designed using
empirical methods that were based on
intuition (feel) and extensive process
experience. Most of the reasoning involved
was nonmathematical. This approach was
unscientific trial and error, but it was a
successful control method.
30 November 2017 By Eng. Hesham A. Selim
Intuitive Approach to Process Control Concepts

we can obtain the desired temperature, Td.


A further process requirement is that the level of the tank must
neither overflow nor fall so low that it exposes the heater coils.

30 November 2017 By Eng. Hesham A. Selim


On/Off Control

This on/off type of control can be


expressed mathematically as follows:
e = PV SP

30 November 2017 By Eng. Hesham A. Selim


Proportional Control

30 November 2017 By Eng. Hesham A. Selim


Proportional Control (continue)

Proportional control can be described mathematically as follows:


V = Kce + m

where
V = is the control valve position
Kc = is the adjustable proportional gain of a typical process
controller
m = is a constant, which is the position of the control valve when
the system error (e) is zero.
Proportional control can be illustrated by using the three graphs
in Figure 1-12 and setting the proportional constant to three
different values (i.e., Kc = 1, Kc <1, and Kc >1).

30 November 2017 By Eng. Hesham A. Selim


Proportional Control (continue)

30 November 2017 By Eng. Hesham A. Selim


Proportional Control (continue)
This definition can be related to proportional gain Kc by

noting the following equation

PB=(1/Kc) .100

30 November 2017 By Eng. Hesham A. Selim


Proportional Control (continue)

Process response with proportional control

30 November 2017 By Eng. Hesham A. Selim


Proportional & Integral
Control
On what basis should the manual reset
be automated?

30 November 2017 By Eng. Hesham A. Selim


Proportional & integral Control (continue)
After the initial upset the reset action returns the error to zero and there is no offset.
Recognizing that the reset action moves the control valve at a rate proportional
to error, this control mode is described mathematically as follows:

where
dV/dt = the derivative of the valve position
with respect to time (t)
Ki = an adjustable constant

30 November 2017 By Eng. Hesham A. Selim


Proportional & integral Control (continue)
Valve equations:-

30 November 2017 By Eng. Hesham A. Selim


Proportional & integral Control (continue)

One problem with PI control bears


mentioning. If a control loop is using PI
control, the possibility exists with the
integral (reset) mode that the controller
will continue to integrate and change the
output even outside the operating range of
the controller. This condition is called
reset windup.
For example, the heat exchanger

30 November 2017 By Eng. Hesham A. Selim


Proportional & integral Control (continue)

30 November 2017 By Eng. Hesham A. Selim


Reset windup control

30 November 2017 By Eng. Hesham A. Selim


Proportional& Derivative
(PD) Control

30 November 2017 By Eng. Hesham A. Selim


Proportional-Integral-
Derivative Control

-Deciding which control action (i.e., PD, PID, etc.) should be used in a control
system will depend on the characteristics of the process being controlled.
-By understanding these concepts you will be better able to select the proper
control action type for effective control.

30 November 2017 By Eng. Hesham A. Selim


Table 1-1. Guidelines for
Selecting Controller Modes

30 November 2017 By Eng. Hesham A. Selim


What Is Good Control?
Purpose Of Automatic Control
Single-loop Feedback Control
Process Controllers
Time Elements of a Feedback Loop
Sensor Time Response
Types of Control
Combinations of Control Functions
Tuning Control Loops
Ziegler-Nichols Tuning Methods
Open Loop Method I.E Process Reaction Curve Method :
Advanced Control Loops

30 November 2017 By Eng. Hesham A. Selim


Purpose Of Automatic Control

The purpose of automatic control is


to provide a means by which any
process operating condition within a
production system can be maintained
in a stable and consistent manner.

30 November 2017 By Eng. Hesham A. Selim


Single-loop Feedback
Control
In a feedback control
loop, the variable to be
manipulated is
measured. This
measured process value
(PV) is then compared
with a set point (SP) to
generate an error signal
(e = PV - SP).

30 November 2017 By Eng. Hesham A. Selim


Process Controllers
There are three types of
controllersmechanical,
pneumatic, and electronic
and they all serve the same
function.
The four common controller
functions are proportional,
proportional plus integral (PI),
proportional plus derivative (PD),
and proportional plus integral
plus derivative (PID).

30 November 2017 By Eng. Hesham A. Selim


Single-loop Feedback
Control

the sensor must be converted into the


same units

30 November 2017 By Eng. Hesham A. Selim


Time Elements of a Feedback
Loop

The time of response of the control loop is the


combination of the responses of the sensor, the
transmitter, the controller, the final control
element, and the process.
it is necessary to understand the concept of
time delays or lags in process control
systems.

30 November 2017 By Eng. Hesham A. Selim


Time Lags

In process control, the term lag means


any relationship in which some result
happens after some cause.
We will start our discussion of time
response and time lag with sensor time
response.

30 November 2017 By Eng. Hesham A. Selim


Sensor Time Response

where
mi = the initial sensor output
measurement
mf = the final sensor output
value
= the sensor time constant
If mi=0

30 November 2017 By Eng. Hesham A. Selim


Sensor Time Response
(continue)
If we wish to find the value of the output exactly
seconds after a sudden change occurs, then
Thus, we see that one time constant (1)
represents the time at which the output value
has changed by 63.2 percent of the total
change. If we solve the Equation for time equal
to 5 or five time constants, we find that
This means that the sensor reaches 99.3 percent
of its final value after five time constants

30 November 2017 By Eng. Hesham A. Selim


Sensor Time Response
The following example illustrates a
typical sensor response application.
The first-order lag is the most common
type of time element encounteredin
process control

30 November 2017 By Eng. Hesham A. Selim


Sensor Time Response (continue)

The system response is called a first-order lag


because the output lags behind the input, and the
differential equation for the system shown in
Figure is a linear first-order differential equation.
Laplace transform method

30 November 2017 By Eng. Hesham A. Selim


Response of a first-order
system to step

30 November 2017 By Eng. Hesham A. Selim


Dead Time Lag

td = t 1 - to .
In this process, the maximum rate of change for the output does not occur
at time zero (to) but at some later time (t1). This is called dead time in
process control:

Dead time is the most difficult condition to overcome in process control.


During dead time, there is no process response and
therefore no information available to initiate corrective action.

30 November 2017 By Eng. Hesham A. Selim


Dead Time Lag(continue)

EXAMPLE
Problem: Determine the dead time for the process shown in Figure 1-9 if the
temperature detector is located 50 meters from the heat exchanger and the
velocity of the process fluid in the discharge pipe is 10 m/s.
Solution: The dead time is given by td = D/v. Since D = 50 m and v = 10 m/s

30 November 2017 By Eng. Hesham A. Selim


Types of Control

There are four basic types of control:


Two-step action,
Proportional action,
Integral action,
Derivative action.

30 November 2017 By Eng. Hesham A. Selim


Combinations of Control Functions

proportional only (P).


proportional plus integral (P + I),
proportional plus derivative (P + D),
proportional plus integral plus derivative (P + I + D).

Deciding which control action (i.e., PD, PID, etc.) should be used in
a control system will depend on the characteristics of the process
being controlled

30 November 2017 By Eng. Hesham A. Selim


Guidelines for Selecting Controller
Modes

There are three important factors to consider when


tuning a PID controller:
1-The characteristics of the process,
2-The selection of controller modes,
3-The performance criteria of the control loop

30 November 2017 By Eng. Hesham A. Selim


Tuning Control Loops
What Is Good Control?

the system's response curve has an amplitude ratio or decay ratio of one-quarter.
A decay ratio of one-quarter means that the ratio of the overshoot of the first
peak in the process response curve to the overshoot of the second peak
is four to one

30 November 2017 By Eng. Hesham A. Selim


What Is Good Control?
In some cases, it is important to tune the
system so that there is no overshoot; in other
cases, a slow and smooth response is
desired; some cases warrant fast response
and significant oscillations are no problem,
etc. The point is you must determine what
control is good for each specific loop.

30 November 2017 By Eng. Hesham A. Selim


The Tuning Concept
The feedback controller is only one
piece of hardware in the entire loop;
there are many other hardware items
connected to form the balance of the
loop. For the purposes of adjusting
the feedback controller, it is
convenient and sufficient to view
everything else

30 November 2017 By Eng. Hesham A. Selim


The Tuning Concept
why controllers cannot be preset at the factory but.
instead, must be individually tuned for individual
loops.
Each of the individual blocks around the feedback
loop represents an algebraic or differential
equation, i.e., it represents a mathematical
statement for that particular piece of hardware
Since all of these blocks are coupled together, all
of these equations represent a simultaneous set
of mathematical equations. If you are able to
determine what you think good control is.

30 November 2017 By Eng. Hesham A. Selim


Advanced Control Loops
Cascade Control Loops
Ratio Control Loops
Override Control

30 November 2017 By Eng. Hesham A. Selim


Cascade Control Loops

In cascade control in Figure


the output from one controller
, the master, is the set point for
another controller commonly
referred to as the slave.
The master will have an independent
plant measurement.

30 November 2017 By Eng. Hesham A. Selim


Ratio Control Loops
ratio is maintained between two or more variables.

Ratio control is often associated with process operations


in which two or more streams must be mixed together
continuously to maintain a steady composition in the resulting mixture

30 November 2017 By Eng. Hesham A. Selim


Override Control

30 November 2017 By Eng. Hesham A. Selim


Ziegler-Nichols Tuning
Methods

This gain is called the


ultimate gain or sensitivity (Su).
The period of these sustained oscillations
is called the ultimate period (Pu).

30 November 2017 By Eng. Hesham A. Selim


Ziegler-Nichols Tuning
Methods
P CONTROL

30 November 2017 By Eng. Hesham A. Selim


Ziegler-Nichols Tuning
Methods
EXAMPLE
Problem: The Ziegler-Nichols ultimate method was used to determine an
ultimate sensitivity of 0.3 psi/ft and an ultimate period of 1 min for a level
control loop. Determine the PID controller settings that are needed for good
control.
Solution: Using the equations for PID control,

30 November 2017 By Eng. Hesham A. Selim


OPEN LOOP METHOD
i.e Process Reaction Curve Method

30 November 2017 By Eng. Hesham A. Selim


OPEN LOOP METHOD
i.e Process Reaction Curve Method

30 November 2017 By Eng. Hesham A. Selim


Thank you.