You are on page 1of 30

TRX and T-Doble

comparison

Jozef Levi
Application Engineer
Doble Engineering Company
TRXField and TRX

 Office software TRX and field software TRXField


 TRX operate with data base software
 TRXField for testing with TDR9000
T-Doble
 One software for office and field use
 Data base software incorporated
 Uploading and down loading of data to DTAWeb
 Horizontal pan function
 Two axis zoom
 Scaling function
 Transducer scaling
 Virtual channel
 Multiple new calculations
 Shock absorber time
T-Doble

 TRIP and CLOSE coil current calculations


 Copy plot data to clip board
 Copy data to Excel
 Report generator
T-Doble as data base

 Test results and plans can be arranged By File


location
type

Clicking tabs test results and plans are arranged


T-Doble as data base

 Tabs can be rearranged By test date

Arranged by test date


T-Doble as data base

 Use of filters

Library test plan filter


T-Doble as data base

 Filter function

Filter by location name


T-Doble - TRXField

 TRXField screen

Line thickness can


not be changed
T-Doble - TRXField

 T-Doble screen

Line thickness
changed in preferences
T-Doble - TRXField

 TRXField – two cursor no color change


T-Doble - TRXField

 T-Doble up to 8 cursors
T-Doble - TRXField

 T-Doble – horizontal pan function

Two
Pan function
test results
brings
are them
overlaid
to same
with different
beginningbeginning
T-Doble - TRXField

 Zoom function

Great tool for test result analyze

TRXField has one dimensional zoom


T-Doble has two axis zoom
T-Doble scaling function

 T-Doble
 Shunt is used to measure current
 Voltage drop is measured in voltage units - V
 Scaling function allows to enter correlation between
voltage and current
 Test results are presented in current unit - A

2 V at shunt output corresponds to 2000 A


T-Doble transducer scaling

 Motion test are done in degrees


 Motion at contacts are in mm
 Transducer scaling allow user to change degrees to mm
after test is done
T-Doble transducer scaling

 Motion units - degrees


T-Doble transducer scaling

 Value at contacts changed to 150 mm

Motion units are changed to Linear


Value at contacts changed to 150 mm
T-Doble transducer scaling

 Results are in mm
T-Doble – virtual channel

 Transducer output in – V graphics in - A


T-Doble – virtual channel

 Virtual channel

Voltage drop

Current

Two analog channels


T-Doble – virtual channel

 Virtual channel

Voltage drop

Current

Voltage drop
Resistance = -----------------
Current
T-Doble calculations

 Shock absorber reaction time calculation on TRIP

fully open position

velocity change

Cursors are positioned at moment when velocity is


changed rapidly and when travel reach fully open position for first time
Shock absorber travel = 55.2 mm
Shock absorber time = 165.3 ms
T-Doble calculations

 TRIP and CLOSE coil current calculations

First maximum current

Maximum
current

t t – total on time
t t – Time to Max
t t – Pickup time
T-Doble

 Copy plot data to clip board

Data transferred to Excel


T-Doble

 Copy picture

Picture transferred to Word


T-Doble

 Reports

Print to pdf or other printer


T-Doble

 Reports
T-Doble