Professional Documents
Culture Documents
• Bus arrangements
• Bus components
• Bus protection techniques
• CT Saturation
• Application Considerations:
High impedance bus differential relaying
Low impedance bus differential relaying
Special topics
2
GE Consumer & Industrial
Multilin
21-Nov-18
Single bus - single breaker
ZONE 1
1 2 3 ---- n-1 n
3
GE Consumer & Industrial
Multilin
21-Nov-18
Multiple bus sections - single breaker with
bus tie
ZONE 2
ZONE 1
ZONE 2
ZONE 1
TRANFER BUS
ZONE 2
7
GE Consumer & Industrial
Multilin
21-Nov-18
Double bus - double breaker
ZONE 1
ZONE 2
ZONE 2
TB1
B1 B2
TB1
L3 L4
BUS 2
ISO 1 ISO 2
CB 1
ISO 3
BYPASS
11
GE Consumer & Industrial
Multilin
SF6, EHV & HV - Synchropuff 21-Nov-18
Disconnect switches & auxiliary contacts
BUS 1
BUS 1
BUS 2
+
ISOLATOR 1
7B 7A
BUS 1
ISOLATOR 1
+
CB 1
7B 7A
ISO 3
BYPASS
ISOLATOR 1 CLOSED
F1a Contact Input F1a On
F1c Contact Input F1c On
F1b
- 12
GE Consumer & Industrial
Multilin
21-Nov-18
Current Transformers
BUS 1
BUS 2
ISO 1 ISO 2
• Interlocking schemes
• Overcurrent (“unrestrained” or “unbiased”)
differential
• Overcurrent percent (“restrained” or “biased”)
differential
• Linear couplers
• High-impedance bus differential schemes
• Low-impedance bus differential schemes
15
GE Consumer & Industrial
Multilin
21-Nov-18
Interlocking Schemes
• Blocking scheme typically
used
• Short coordination time
required
50
• Care must be taken with
BLOCK
possible saturation of feeder
CTs
50 50 50 50 50
• Blocking signal could be sent
over communications ports
(peer-to-peer)
• This technique is limited to
simple one-incomer
distribution buses
16
GE Consumer & Industrial
Multilin
21-Nov-18
Overcurrent (unrestrained) Differential
• Differential signal formed by
summation of all currents feeding
the bus
• CT ratio matching may be
required
51 • On external faults, saturated CTs
yield spurious differential current
• Time delay used to cope with CT
saturation
• Instantaneous differential OC
function useful on integrated
microprocessor-based relays
17
GE Consumer & Industrial
Multilin
21-Nov-18
Linear Couplers
59
0V
40 V 10 V 10 V 0V 20 V
External
Fault
If = 8000 A
18
GE Consumer & Industrial
Multilin
2000 A 2000 A 0A 4000 A 21-Nov-18
Linear Couplers
Esec= Iprim*Xm - secondary voltage on relay terminals
where,
Iprim – primary current in each circuit
Xm – liner coupler mutual reactance (5V per 1000Amps => 0.005 @ 60Hz )
ZR – relay tap impedance
ZC – sum of all linear coupler self impedances
40 V 59
0V 10 V 10 V 0V 20 V
19
GE Consumer & Industrial
Multilin
21-Nov-18
0A 2000 A 2000 A 0A 4000 A
Linear Couplers
20
GE Consumer & Industrial
Multilin
21-Nov-18
High Impedance Differential
• Operating signal created by
connecting all CT secondaries in
parallel
o CTs must all have the same ratio
o Must have dedicated CTs
• Overvoltage element operates on
voltage developed across resistor
59 connected in secondary circuit
o Requires varistors or AC shorting
relays to limit energy during faults
• Accuracy dependent on secondary
circuit resistance
o Usually requires larger CT cables to
reduce errors higher cost
23
GE Consumer & Industrial
Multilin
21-Nov-18
Digital Differential Algorithm Goals
• Improve the main differential algorithm operation
o Better filtering
o Faster response
o Better restraint techniques
o Switching transient blocking
• Provide dynamic bus replica for reconfigurable bus bars
• Dependably detect CT saturation in a fast and reliable manner,
especially for external faults
• Implement additional security to the main differential algorithm to
prevent incorrect operation
o External faults with CT saturation
o CT secondary circuit trouble (e.g. short circuits)
24
GE Consumer & Industrial
Multilin
21-Nov-18
Low Impedance Differential (Distributed)
• Data Acquisition Units (DAUs)
installed in bays
52 52 52
• Central Processing Unit (CPU)
processes all data from DAUs
DAU DAU DAU
• Communications between DAUs
and CPU over fiber using
proprietary protocol
• Sampling synchronisation
between DAUs is required
CU • Perceived less reliable (more
hardware needed)
copper
fiber
• Difficult to apply in retrofit
applications
25
GE Consumer & Industrial
Multilin
21-Nov-18
Low Impedance Differential (Centralized)
26
GE Consumer & Industrial
Multilin
21-Nov-18
CT Saturation
27
GE Consumer & Industrial
Multilin
21-Nov-18
CT Saturation Concepts
28
GE Consumer & Industrial
Multilin
21-Nov-18
CT Saturation
No DC Offset
• Waveform remains fairly
symmetrical
With DC Offset
• Waveform starts off being
asymmetrical, then
symmetrical in steady
Ratio Current CT Current
state
29
GE Consumer & Industrial
Multilin
21-Nov-18
External Fault & Ideal CTs
differential
t1
t0 restraining
• Fault starts at t0
• Steady-state fault conditions occur at t1
Ideal CTs have no saturation or mismatch errors thus
produce no differential current 30
GE Consumer & Industrial
Multilin
21-Nov-18
External Fault & Actual CTs
differential
t1
t0 restraining
• Fault starts at t0
• Steady-state fault conditions occur at t1
Actual CTs do introduce errors, producing some differential
current (without CT saturation) 31
GE Consumer & Industrial
Multilin
21-Nov-18
External Fault with CT Saturation
t2
differential
t1
t0 restraining
• Fault starts at t0, CT begins to saturate at t1
• CT fully saturated at t2
CT saturation causes increasing differential current that
may enter the differential element operate region. 32
GE Consumer & Industrial
Multilin
21-Nov-18
Some Methods of Securing Bus Differential
33
GE Consumer & Industrial
Multilin
21-Nov-18
High-Impedance
Bus Differential
Considerations
34
GE Consumer & Industrial
Multilin
21-Nov-18
High Impedance Voltage-operated Relay
External Fault
• 59 element set above max possible voltage developed across
relay during external fault causing worst case CT saturation
• For internal faults, extremely high voltages (well above 59
element pickup) will develop across relay
35
GE Consumer & Industrial
Multilin
21-Nov-18
High Impedance Voltage Operated Relay
Ratio matching with Multi-ratio CTs
• Application of high impedance differential relays with CTs of
different ratios but ratio matching taps is possible, but could
lead to voltage magnification.
• Voltage developed across full winding of tapped CT does not
exceed CT rating, terminal blocks, etc.
36
GE Consumer & Industrial
Multilin
21-Nov-18
High Impedance Voltage Operated Relay
Ratio matching with Multi-ratio CTs
• Use of auxiliary CTs to obtain correct ratio matching is also
possible, but these CTs must be able to deliver enough voltage
necessary to produce relay operation for internal faults.
37
GE Consumer & Industrial
Multilin
21-Nov-18
Electromechanical High Impedance Bus
Differential Relays
• Single phase relays
• High-speed
• High impedance voltage sensing
• High seismic IOC unit
38
GE Consumer & Industrial
Multilin
21-Nov-18
P -based High-Impedance Bus Differential
Protection Relays
39
GE Consumer & Industrial
Multilin
21-Nov-18
High Impedance Module for Digital
Relays
41
GE Consumer & Industrial
Multilin
21-Nov-18
High Impedance Bus Protection - Summary
• Fast, secure and proven
• Requires dedicated CTs, preferably with the same CT ratio
and using full tap
• Can be applied to small buses
• Depending on bus internal and external fault currents, high
impedance bus diff may not provide adequate settings for
both sensitivity and security
• Cannot be easily applied to reconfigurable buses
• Require voltage limiting varistor capable of absorbing
significant energy
• May require auxiliary CTs
• Do not provide full benefits of microprocessor-based relay
system (e.g. metering, monitoring, oscillography, etc.)
42
GE Consumer & Industrial
Multilin
21-Nov-18
Low-Impedance
Bus Differential
Considerations
43
GE Consumer & Industrial
Multilin
21-Nov-18
P-based Low-Impedance Relays
• No need for dedicated CTs
• Internal CT ratio mismatch compensation
• Advanced algorithms supplement percent differential
protection function making the relay very secure
• Dynamic bus replica (bus image) principle is used in
protection of reconfigurable bus bars, eliminating the need
for switching physically secondary current circuits
• Integrated Breaker Failure (BF) function can provide optimal
tripping strategy depending on the actual configuration of
a bus bar
44
GE Consumer & Industrial
Multilin
21-Nov-18
Small Bus Applications
2-8 Circuit Applications
• Up to 24 Current Inputs • Different CT Ratio Capability for
• 4 Zones Each Circuit
• Zone 1 = Phase A • Largest CT Primary is Base in
• Zone 2 = Phase B Relay
• Zone 3 = Phase C
• Zone 4 = Not used
45
GE Consumer & Industrial
Multilin
21-Nov-18
Medium to Large Bus Applications
9-12 Circuit Applications
• Relay 1 - 24 Current Inputs • Relay 2 - 24 Current Inputs
• 4 Zones • 4 Zones
• Zone 1 = Phase A (12 currents) • Zone 1 = Not used
• Zone 2 = Phase B (12 currents) • Zone 2 = Not used
• Zone 3 = Not used • Zone 3 = Phase C (12 currents)
• Zone 4 = Not used • Zone 4 = Not used
• Different CT Ratio Capability for Each Circuit
• Largest CT Primary is Base in Relay
CB 11 CB 12
46
GE Consumer & Industrial
Multilin
21-Nov-18
Large Bus Applications
87B phase A
87B phase B
87B phase C
Logic relay
(switch status,
optional BF)
47
GE Consumer & Industrial
Multilin
21-Nov-18
Large Bus Applications
For buses with up to 24 circuits
48
GE Consumer & Industrial
Multilin
21-Nov-18
Summing External Currents
Not Recommended for Low-Z 87B relays
• Relay becomes combination
CT-1
CT-4
differential currents
• Associated feeders must be radial
I3 = 0
49
GE Consumer & Industrial
Multilin
21-Nov-18
Definitions of Restraint Signals
iR i1 i2 i3 ... in “sum of”
iR i1 i2 i3 ... in
1
“scaled sum of”
n
50
GE Consumer & Industrial
Multilin
21-Nov-18
“Sum Of” vs. “Max Of” Restraint Methods
51
GE Consumer & Industrial
Multilin
21-Nov-18
Bus Differential Adaptive Approach
Region 2
(high differential
currents)
differential
Region 1
(low differential
currents)
restraining
52
GE Consumer & Industrial
Multilin
21-Nov-18
Bus Differential Adaptive Logic Diagram
DIFL
AND
DIR
OR
OR
87B BIASED OP
SAT
AND
DIFH
53
GE Consumer & Industrial
Multilin
21-Nov-18
Phase Comparison Principle
• Internal Faults: All fault (“large”) currents are approximately in
phase.
Secondary Current of
Faulted Circuit
• No Voltages are required or needed (Severe CT Saturation)
54
GE Consumer & Industrial
Multilin
21-Nov-18
Phase Comparison Principle Continued…
Ip Ip
imag imag
ID I p OPERATE ID I p
OPERATE
BLOCK BLOCK
Ip Ip
ID - Ip real ID - Ip real
Ip ID I p ID I p
Ip
BLOCK
BLOCK
OPERATE OPERATE
55
GE Consumer & Industrial
Multilin
21-Nov-18
CT Saturation
t2
differential
t1
t0 restraining
• Fault starts at t0, CT begins to saturate at t1
• CT fully saturated at t2
56
GE Consumer & Industrial
Multilin
21-Nov-18
CT Saturation Detector State Machine
NORMAL
SAT := 0
The differential
current below the saturation
first slope for condition
certain period of
time EXTERNAL
FAULT
SAT := 1
The differential-
The differential restraining trajectory
characteristic out of the differential
entered characteristic for
certain period of time
EXTERNAL
FAULT & CT
SATURATION
SAT := 1
57
GE Consumer & Industrial
Multilin
21-Nov-18
CT Saturation Detector Operating
Principles
• The 87B SAT flag WILL NOT be set during internal faults,
regardless of whether or not any of the CTs saturate.
• The 87B SAT flag WILL be set during external faults,
regardless of whether or not any of the CTs saturate.
• By design, the 87B SAT flag WILL force the relay to use
the additional 87B DIR phase comparison for Region 2
59
GE Consumer & Industrial
Multilin
21-Nov-18
CT Saturation Example – External Fault
200
150
100 ~1 ms
50
current, A
0
-50
-100
-150
-200
0.06 0.07 0.08 0.09 0.1 0.11 0.12
time, sec
Despite heavy CT
saturation the
external fault current
The element is seen in the
The
does not opposite direction
directional flag
maloperate 60
is not set
GE Consumer & Industrial
Multilin
21-Nov-18
CT Saturation – Internal Fault Example
The
The element directional
operates in flag is set
10ms 61
GE Consumer & Industrial
Multilin
21-Nov-18
Applying Low-Impedance Differential
Relays for Busbar Protection
Basic Topics
• Configure physical CT Inputs
• Configure Bus Zone and Dynamic Bus Replica
• Calculating Bus Differential Element settings
Advanced Topics
• Isolator switch monitoring for reconfigurable buses
• Differential Zone CT Trouble
• Integrated Breaker Failure protection
62
GE Consumer & Industrial
Multilin
21-Nov-18
Configuring CT Inputs
• For each connected CT circuit enter Primary rating and
select Secondary rating.
• Each 3-phase bank of CT inputs must be assigned to a
Signal Source that is used to define the Bus Zone and
Dynamic Bus Replica
65
GE Consumer & Industrial
Multilin
21-Nov-18
Configuring the Bus Differential Zone
Bus Zone settings defines the boundaries of the Differential
Protection and CT Trouble Monitoring.
66
GE Consumer & Industrial
Multilin
21-Nov-18
Dual Percent Differential Characteristic
High Set
(Unrestrained)
High Slope
Low Slope
High
Breakpoint
68
GE Consumer & Industrial
Multilin
21-Nov-18
Calculating Bus Differential Settings –
Minimum Pickup
69
GE Consumer & Industrial
Multilin
21-Nov-18
Calculating Bus Differential Settings –
Low Slope
70
GE Consumer & Industrial
Multilin
21-Nov-18
Calculating Bus Differential Settings –
Low Breakpoint
• Defines the upper limit to restraint currents that will be
biased according to the Low Slope setting
• Should be set to be above the maximum load but not more
than the maximum current where the CTs still operate
linearly (including residual flux)
• Assumption is that the CTs will be operating linearly (no
significant saturation effects up to 80% residual flux) up to
the Low Breakpoint setting
71
GE Consumer & Industrial
Multilin
21-Nov-18
Calculating Bus Differential Settings –
High Breakpoint
72
GE Consumer & Industrial
Multilin
21-Nov-18
Calculating Bus Differential Settings –
High Slope
• Defines the percent bias for the restraint currents IRESTHigh
Breakpoint
• Setting determines the stability of the differential element
for high current external faults
• Traditionally, should be set high enough to accommodate
the spurious differential current resulting from saturation of
the CTs during heavy external faults
• Setting can be relaxed in favour of sensitivity and speed as
the relay detects CT saturation and applies the directional
principle to prevent maloperation
• Range: 50% to 100% in 1%. increments
73
GE Consumer & Industrial
Multilin
21-Nov-18
Calculating Unrestrained Bus Differential
Settings
74
GE Consumer & Industrial
Multilin
21-Nov-18
Dual Percent Differential Characteristic
High Set
(Unrestrained)
High Slope
Low Slope
High
Breakpoint
CT-1 CT-7
CT-2 B-2 CT-3 B-3 CT-4 B-4 CT-5
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
CT-1 CT-7
CT-2 B-2 CT-3 B-3 CT-4 B-4 CT-5
B-7
CT-6
CT-8
B-6
S-2 S-4 S-6
SOUTH BUS
81
GE Consumer & Industrial
Multilin
21-Nov-18
Switch Status Logic and Dyanamic Bus
Replica
Isolator Open Isolator Closed Isolator Position Alarm Block Switching
Auxiliary Auxiliary
Contact Contact
Off On CLOSED No No
On Off OPEN No No
82
GE Consumer & Industrial
Multilin
21-Nov-18
Differential Zone CT Trouble
• Each Bus Differential Zone may a dedicated CT Trouble
Monitor
• Definite time delay overcurrent element operating on the
zone differential current, based on the configured Dynamic
Bus Replica
• Three strategies to deal with CT problems:
1. Trip the bus zone as the problem with a CT will likely
evolve into a bus fault anyway
2. Do not trip the bus, raise an alarm and try to correct
the problem manually
3. Switch to setting group with 87B minimum pickup
setting above the maximum load current.
83
GE Consumer & Industrial
Multilin
21-Nov-18
Differential Zone CT Trouble
• Strategies 2 and 3 can be accomplished by:
Using undervoltage supervision to ride through the period
from the beginning of the problem with a CT until declaring a
CT trouble condition
Using an external check zone to supervise the 87B function
Using CT Trouble to prevent the Bus Differential tripping (2)
Using setting groups to increase the pickup value for the 87B
function (3)
84
GE Consumer & Industrial
Multilin
21-Nov-18
Differential Zone CT Trouble – Strategy #2
Example
87B operates
Undervoltage condition
CT OK
Breaker Failure
elements configured
here
88
GE Consumer & Industrial
Multilin
21-Nov-18
Example Architecture – Breaker Failure
Tripping Trip
90
GE Consumer & Industrial
Multilin
21-Nov-18
91
GE Consumer & Industrial
Multilin
21-Nov-18