INTRODUCTION

 Alarm’s are used to monitor the site in case of any fault occur then
alarm panel automatically generate the alarm for corresponding fault
occurred at site.

AMIT MISHRA 2
 Why alarm’s are used at site?

 External alarm is important at BTS site because in case of any fault occur
then as a maintenance engineer it will be easier for us to identify the
problem and rectify it accordingly.
 We can check at DDF, where termination of alarm is done.
 It provide security and stability to whole BTS site.

AMIT MISHRA 3
 TYPES OF ALARM AT BTS SITE

BTS
SITE

ALARM

INTERNAL EXTERNAL
ALARM ALARM

AMIT MISHRA 4
 PARAMETER OF EXTERNAL ALARM

 These are parameter which may differ according to manufacturer.

ALARM NAME
ALARM
OR SYNTAX ALARM NO
TYPE(NO/NC)
OR TITLE

ALARM PORT
ALARM SEVERITY NO/PIN NO

ROUTE ROOT
COLOUR CODE OF CAUSE OF
CAUSE OF
ALARM ALARM
ALARM

AMIT MISHRA 5
 ALARM NAME OR SYNTAX OR TITLE

 It define the name of the alarm at BTS site.


 It may differ according to the operator.
 Depending upon BTS used syntax or title can change.
 Some of the example of name of alarm operator are as follow’s..

BTS NAME ALARM NAME

 NOKIA FLEXI BTS  DG FAIL’S TO START


 MAIN’S FAILURE

 ERICSSION RBS 2964  DG FAIL’S TO STOP


 DOOR OPEN

AMIT MISHRA 6
 PARAMETER DESCRIPTION CONTINUED

 ALARM NO

 Every operator decide a particular alarm no for it’s BTS site and accordingly
series of alarm is decided.

for eg-7401 in NOKIA flexi BTS case.

ALARM TYPE

 Type of alarm mean’s that either alarm will be normally


Closed or normally open.
 Normally open mean’s that state of alarm in NORMALLY NORMALLY
normal condition is OPEN. OPEN CLOSED
 Normally closed mean’s that state of alarm in
normal condition is closed.

ALARM TYPE

AMIT MISHRA 7
 PARAMETER DESCRIPTION
CRITICAL

SEVERITY
CRITICAL
MAJOR

 Critical mean’s that ,it require immediate attention, MINOR


if on BTS site any alarm is critical defined that mean’s
that level of alarm severity is high.
for eg : LLOP- low lubricant oil pressure.

MAJOR

 Major mean’s that ,it’s severity level is lesser than critical but it is also needed
attention as soon as possible.
for eg: low fuel level
MINOR

 Minor mean’s that ,it’s severity level is lesser in compare to other alarm and site
may not get affected as much as in case of critical and major.
for eg- site on DG.

AMIT MISHRA 8
ALARM PORT
PORT
NO/PIN
NO
 Alarm port or pin no is decided by operator
itself . OPERATOR
SPECIFIC

COLOUR
COLOUR CODE CODE

 The colour code of alarm wire is decided by


operator itself.
 Always it will exist in pair for PCM cable’s used.

AMIT MISHRA 9
 ROUTE OF ALARM

 It decide the route of alarm or we can say that where alarm connection start
till termination of that alarm.

 ROOT CAUSE

 Root cause mean’s the exact cause of fault which led to the alarm at the site.

ROUTE
• IT DECIDE ROUTE OF
of
ALARM
ALARM

ROOT • IT DECIDE THE CAUSE


CAUSE OF ALARM

AMIT MISHRA 10
 ALARM CABLE CONNECTION  Alarm cable are PCM cable.
 They exist in pair’s.
 Each alarm will be connected to ddf with
these cable.(two wire is one pair)
 37 pin D-type connector.
 Alarm ddf installed on shelter wall.
 Alarm’s are connected to sensor’s.

25 PAIR PCM CABLE

AMIT MISHRA 11
 For connection of alarm these are needed.

D TYPE 37 PIN

DDF ALARM CONNECTION

AMIT MISHRA 12
 TYPE OF EXTERNAL ALARM’S 1. DOOR OPEN
2. HIGH TEMPERATURE
3. DG FAIL’S TO START
4. DG FAIL’S TO STOP
5. LOW FUEL LEVEL
6. FIRE OR SMOKE
7. LOW LUBRICATION OIL PRESSURE
8. LOAD ON DG
9. AC FAIL’S TO START(AC-1/AC-2)
10.RECTIFIER MODULE PAIR FAIL’S
11.LOW BATTERY VOLTAGE
12.SITE ON DG
13.AC -1 FAIL’S
14.AC-2 FAIL’S
15.DG RUNNING WITHOUT LOAD

AMIT MISHRA 13
 TO ELABORATE ABOVE DESCRIPTION TAKE EXAMPLE OF NOKIA FLEXI BTS

 There are 12 external alarm for nokia flexi BTS.


 For 12 alarm connection ,we need 37 pin D connector in which 24 pin’s
will be used.
 For each alarm , we require one pair E1 cable having two wire.
 Termination of these cable is done on DDF i.e from BTS to DDF and from
alarm sensor to DDF.

AMIT MISHRA 14
SYNTAX- ALARM NO- ALARM TYPE-
SEVERITY-
MAIN’S 7401/ALARM NORMALY
MINOR
FAILURE NO1 OPEN

COLOR
CODE-
PIN NO-7/25
GREEN&
GREEN/WHITE

 ROUTE OF ALARM PIU/AMF DDF BTS

ROOT CAUSE -MAIN’S FAILURE

AMIT MISHRA 15
 ALARM CONFIGURATION CONTINUED

SYNTAX-
ALARM NO- ALARM TYPE-
RECTIFIER SEVERITY-
7402/ALARM NORMALY
MODULE MINOR
NO2 OPEN
FAILURE

COLOR
PIN NO-8/26 CODE-BLUE&
BLUE/WHITE

POWER
 ROUTE OF ALARM DDF BTS
PLANT

ROOT CAUSE -RECTIFIER FAILURE

AMIT MISHRA 16
 ALARM CONFIGURATION CONTINUED

SYNTAX-BATTERY AT ALARM NO- ALARM TYPE-


SEVERITY-
47V/LOW BATTERY 7403/ALARM NORMALY
CRITICAL
VOLTAGE NO3 OPEN

COLOR CODE-
PIN NO-9/27 VOILET&
WHITE
VOILET

POWER
 ROUTE OF ALARM DDF BTS
PLANT

ROOT CAUSE -BATTERY VOLTAGE IS BELOW -48V

AMIT MISHRA 17
 ALARM CONFIGURATION CONTINUED

SYNTAX- ALARM NO- ALARM TYPE-


SEVERITY-
LOAD ON 7404/ALARM NORMALY
MAJOR
BATTERY NO4 OPEN

COLOR
PIN NO-
CODE-GREY&
10/28
WHITE GREY

 ROUTE OF ALARM
POWER
DDF BTS
PLANT

ROOT CAUSE -ALL RECTIFIER IN P.P FAILED

AMIT MISHRA 18
 ALARM CONFIGURATION CONTINUED

ALARM NO- ALARM TYPE-


SYNTAX- SEVERITY-
7405/ALARM NORMALY
LOAD ON DG MINOR
NO5 OPEN

PIN NO- COLOR


11/29 CODE-PINK&
BLACK/RED

 ROUTE OF ALARM
PIU/
DDF BTS
AMF

 ROOT CAUSE-MAIN’S FAILURE

AMIT MISHRA 19
 ALARM CONFIGURATION CONTINUED

ALARM NO- ALARM TYPE-


SYNTAX-DG SEVERITY-
7406/ALARM NORMALY
LLOP CRITICAL
NO6 OPEN

COLOR CODE-
PIN NO- LIGHTGREEN&
12/30 BLACK/
GREEN

 ROUTE OF ALARM LLOP


PIU/AMF DDF BTS
SENSOR

 ROOT CAUSE-WHEN LUBRICANT OIL PRESSURE IN ENGINE


GOES BELOW SPECIFIED LEVEL

AMIT MISHRA 20
 ALARM CONFIGURATION CONTINUED

ALARM NO- ALARM TYPE-


SYNTAX-LOW SEVERITY-
7407/ALARM NORMALY
FUEL LEVEL MINOR
NO7 OPEN

COLOR
PIN NO-
CODE-LIGHT
13/31
BLUE&BLACK

FUEL
 ROUTE OF ALARM PIU/AMF DDF BTS
SENSOR

ROOT CAUSE -WHEN THE FUEL IN TANK GOES BELOW 40%.

AMIT MISHRA 21
 ALARM CONFIGURATION CONTINUED

SYNTAX-DG ALARM NO- ALARM TYPE-


FAIL TO 7408/ALARM NORMALY SEVERITY-
START NO8 OPEN MAJOR

COLOR
PIN NO-
CODE-WHITE
14/32
BLACK/WHITE

PIU/
 ROUTE OF ALARM DDF BTS
AMF

 ROOT CAUSE-DG DOESN’T START AFTER 3 ATTEMPT’S BY PIU/AMF

AMIT MISHRA 22
 ALARM CONFIGURATION CONTINUED

ALARM NO- ALARM TYPE-


SYNTAX-AC SEVERITY-
7409/ALARM NORMALY
FAIL’S MAJOR
NO9 OPEN

COLOR CODE-
PIN NO- LIGHT GREY&
15/33 LIGHT GREY
/BLACK

MICRO
 ROUTE OF ALARM- DDF BTS
CONTROLLER

 ROOT CAUSE-BOTH AC FAIL’S

AMIT MISHRA 23
 ALARM CONFIGURATION CONTINUED

SYNTAX- ALARM N0- ALARM TYPE-


DOOR 7410/ALARM SEVERITY-
NORMALY
OPEN NO10 MINOR
CLOSED

COLOR
PIN NO- CODE-
16/34 GREEN&
GREEN/WHITE

DOOR
 ROUTE OF ALARM- PIU/AMF DDF BTS
SENSOR

 ROOT CAUSE -WHEN SHELTER DOOR IS OPEN.

AMIT MISHRA 24
 ALARM CONFIGURATION CONTINUED

SYNTAX-
ALARM NO- ALARM TYPE-
HIGH SEVERITY-
7411/ALARM NORMALY
TEMPERATUR MAJOR
NO11 OPEN
-E

COLOR CODE-
PIN NO- ORANGE/
17/35 RED&ORANGE/LI
GHT GREY

MICRO
 ROUTE OF ALARM- DDF BTS
CONTROLLER

 ROOT CAUSE -WHEN TEMPERATURE REACHES ALARMING LEVEL.

AMIT MISHRA 25
 ALARM CONFIGURATION CONTINUED

ALARM NO- ALARM TYPE-


SYNTAX- SEVERITY-
7412/ALARM NORMALY
FIRE/SMOKE CRITICAL
NO12 OPEN

COLOR CODE-
PIN NO- ORANGE
18/36 /BLACK&ORA-
NGE/GREEN

FUEL
 ROUTE OF ALARM- PIU/AMF DDF BTS
SENSOR

 ROOT CAUSE -WHEN TEMPERATURE REACHES ALARMING LEVEL.

AMIT MISHRA 26
 APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S

SYNTAX-DG ALARM NO- ALARM TYPE-


SEVERITY-
FAIL’S TO OPERATOR NORMALLY
MINOR
STOP SPECIFIC CLOSED

COLOUR
PIN NO-
CODE-
OPERATOR
OPERATOR
SPECIFIC
SPECIFIC

 ROUTE OF ALARM- PIU/AMF DDF BTS

 ROOT CAUSE-WHEN PIU OR AMF NOT ABLE TO STOP DG AFTER 3 ATTEMPT.

AMIT MISHRA 27
 APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S

ALARM NO- ALARM TYPE-


SYNTAX-AC- SEVERITY-
OPERATOR NORMALLY
1 FAIL’S MINOR
SPECIFIC OPEN

PIN NO – COLOUR CODE-


OPERATOR OPERATOR
SPECIFIC SPECIFIC

MICRO
 ROUTE OF ALARM- CONTROLLER
DDF BTS

 ROOT CAUSE-WHEN AC-1 FAIL’S

AMIT MISHRA 28
 APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S

ALARM NO- ALARM TYPE-


SYNTAX-AC- SEVERITY-
OPERATOR NORMALLY
2 FAIL’S MINOR
SPECIFIC OPEN

PIN NO – COLOUR CODE-


OPERATOR OPERATOR
SPECIFIC SPECIFIC

MICRO
 ROUTE OF ALARM- CONTROLLER
DDF BTS

 ROOT CAUSE-WHEN AC-2 FAIL’S

AMIT MISHRA 29
 LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

 Ericsson RBS2954  DG on
 DG fail’s to start
 Main fail’s
 DG fuel level
 LLOP
 DG fails to stop
 Cabinet temperature
 Fire & smoke
 Door smoke
 BFU fault
 Spare
 SMPS input fail
 Battery low voltage
 DC disconnected alarm
 Battery breaker off
 Battery disconnected

AMIT MISHRA 30
 LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

 Ericsson RBS2964  DG on
 DG fail’s to start
 Main fail’s
 DG fuel level
 LLOP
 DG fails to stop
 Cabinet temperature
 Fire & smoke
 Door open
 BFU fault
 Spare
 SMPS input fail
 Battery low voltage
 DC disconnected alarm
 Battery breaker off
 Battery disconnected

AMIT MISHRA 31
 LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

 HUAWEI 3900  Intruder


 A/C failure
 High room temperature
 Fire alarm
 Fire fighting
 Main’s failure
 Generator failure
 Generator run
 Rectifier high voltage
 Tower light failure
 Rectifier 2/more failure
 Tower amplifier fail
 Rectifier low voltage
 Rectifier common alarm
 GN auto mode
 Low fuel in main tank

AMIT MISHRA 32
 LIST OF DIFFERENT OPERATOR EXTERNAL ALARM

 ZTE ZXG 10

AMIT MISHRA 33
 ALARM DEFINED IN ERICSSON SITES:

Sl. No External Alarms ID Breaking Closing Level


1 DG ON 0 Closing 2
2 DG fail to Start 1 Closing 1
3 Mains Fail 2 Closing 1
4 High Shelter 3 Closing 1
Temperature
5 DG Fuel Level Low 4 Closing 1
6 LLOP 5 Closing 2
7 DG Fail to Stop 6 Closing 1
8 Fire and Smoke 7 Closing 1
9 Door Open 8 Closing1
10 AC 1 - OFF 9 Closing 1
11 AC 2 – OFF A Closing 1
12 Spare B
13 Battery Fuse Fail C Closing 1
14 Rectifier Fail D Closing 1
15 Battery Low Voltage E Closing 1
16 SMPS Input Fail F Closing 1

AMIT MISHRA 34
 EXTERNAL ALARMS FOR BTS (RBS 2954) SITES:

Port ID External Alarms Closing/Breaking Level


1 0 DG ON Closing 2
2 1 DG FAIL TO START Closing 1
3 2 MAINS FAIL Closing 1
4 3 DG FUEL LEVEL LOW Closing 1
5 4 LLOP Closing 2
6 5 DG FAIL TO STOP Closing 1
7 6 CABINET TEMPERATRE Closing 1
HIGH
8 7 FIRE AND SMOKE Closing 1
9 8 BBS DOOR OPEN Closing 1
10 9 BFU FAULT Closing 1
11 10 SPARE
12 B SMPS INPUT FAIL Closing 1
13 C BATTERY LOW VOLTAGE Closing 1
14 D DC DISCONNECTED ALARM Closing 1
15 E BATTERY BREAKER OFF Closing 1
16 F BATTERY DISCONNECTED Closing1

AMIT MISHRA 35
 BELOW MENTIONED COLOUR CODE OF RBS(2954)-

S/N TTSL Requirement Node colour code


1 AC mains fail blue-white
2 High room temperature Orange-white
3 fire alarm Green-white
4 Battery Discharge Brown-white
5 rectifier fail Blue-red
6 intruder Orange-red
7 DG low fuel Red-green
8 DG running Brown-red

After we connect the cable on krone block we


will give loop with krone tool one by one and
check weather alarm get disappear in OMCR or
not.
Same way we have to check for all the 8 ports.

AMIT MISHRA 36
 EXTERNAL ALARM IN HUAWEI 3900 BTS AND COLOUR CODE-

KRONE NO:1 KRONE NO:2

NO: port SLOT DDF ALARM NO: port SLOT DDF ALARM
RECTIFIER
1 0 18 1 INTRUDER 9 0 19 1 HIGH
VOLTAGE
TOWER
A/C
2 1 18 2 10 1 19 2 LIGHT
FAILURE
FAILURE
HIGH
RECTIFIER
ROOM
3 2 18 3 11 2 19 3 2/MORE
TEMPERA
FAILURE
TURE
TOWER
FIRE
4 3 18 4 12 3 19 4 AMPLIFIE
ALARM
R FAIL
RECTIFIER
FIRE
5 4 18 5 13 4 19 5 LOW
FIGHTING
VOLTAGE
RECTIFIER
MAINS
6 5 18 6 14 5 19 6 COMMON
FAILURE
ALARM
GENERAT
GN AUTO
7 6 18 7 OR 15 6 19 7
MODE
FAILURE
LOW FUEL
GENERAT
8 7 18 8 16 7 19 8 IN MAIN
OR RUN
TANK

AMIT MISHRA 37
HUAWEI EXTERNAL ALARMS(COLOURS)

EXTERNAL ALARM COLOUR CODES

CABLE NO: PAIR COLOUR


WHITE
1 1
ORANGE
2 1 ORANGE
WHITE
3 2
GREEN
4 2 GREEN
WHITE
5 3
BLUE
6 3 BLUE
WHITE
7 4
BROWN
8 4 BROWN

AMIT MISHRA 38
 INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

 LIST OF ALARM’S (1)RECTIFIER & BTS DOOR CABINET ALARM


(2)RECTIFIER MAJOR ALARM
(3)RECTIFIER MINOR ALARM
(4)LOW DC VOLTAGE
(5)HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY)
(6)TEMPERATURE ALARM(FOR FAN COOL CABINE ONLY)

 CORRESPONDING ALARM NO-


 ALARM NO1
 ALARM NO2
 ALARM NO3
 ALARM NO4
 ALARM N05
 ALARM NO7

AMIT MISHRA 39
 INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

 LIST OF COLOUR CODE OF ABOVE ALARM

 ALARM
NO1-RECTIFIER & BTS DOOR CABINET ALARM- GREEN & WHITE GREEN
 ALARM
NO2-RECTIFIER MAJOR ALARM-BLUE & WHITE BLUE
 ALARM
NO3-RECTIFIER MINOR ALARM-VIOLET & WHITE VIOLET
 ALARM
NO4-LOW DC VOLTAGE-GREY & WHITE GREY
 ALARM
NO5-HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY)-BLUE/BLACK
&BLACK BLUE
 ALARM NO7-TEMPERATURE ALARM(FOR FAN COOLED CABINET ONLY)-LIGHTBLUE
&LIGHT BLUE/ BLACK

AMIT MISHRA 40
 INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

 MATERIAL REQUIREMENT-  ALARM CABLE


 KRONE
 RACK
 CAT-5 CABLE 7-9 METER
 SOLDERING IRON
 OTHRE BASIC TOOL’S

AMIT MISHRA 41
 INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

 INSTALLATION PROCESS-  Initial step before installation-

(1)Alarm cable is too long so cut it into two pieces.

(2)1st cable will be used to take alarm from rectifier


smart pack i/o ports to crone.

(3)2nd cable with connector at one end will be used for


taking alarms from krone to BTS EAC port(2G cabinet).

AMIT MISHRA 42
 INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE

 INSTALLATION PROCESS CONTINUE-

 STEP-1 KRONE INSTALLATION

 Install the krone on rack and fix this rack in rectifier cabinet.
 Use proper size bolt’s and washer.

AMIT MISHRA 43
 INSTALLATION PROCESS CONTINUE-

 Alarm cable installation(BTS – KRONE)

 Connect the alarm cable connector on EAC port at BTS(2G cabinet)


 Bring the other end of alarm cable to rectifier through roxtec.
 Punch the alarm cable on the lower side of krone according to the alarm’s sequence.
 The alarm cable should be fixed properly with ties and properly routed.

AMIT MISHRA 44
 INSTALLATION PROCESS CONTINUE-

Route this cable properly with ties and fix it near the Rectifier I/O
ports

• Connect Green & White Green (Alarm nu 1) with Pins 8 & 9 of CON1
(X1)

• Connect Grey & White Grey (Alarm nu 4) with Pins 9 & 10 of CON2
(X2)

• Connect Violet & White Violet (Alarm nu 3) with Pins 15 & 16 of


CON2 (X2)

• Connect Blue & White Blue (Alarm nu 2) with Pins 18 & 19 of CON2
(X2)

• Connect Light Blue & Light Blue Black (Alarm nu 7) with Pins 12 & 13
of CON2 (X2) (Only for Fan Cool Rectifier Cabinets)

AMIT MISHRA 45
CON 2
( X2 )

CON 1
( X1 )

AMIT MISHRA 46
 INSTALLATION PROCESS CONTINUE-

 HEAT MANAGEMENT ALARM

 Air condition in the door usually


has Red & Yellow cable for Air
Condition Alarm.
 This cable is connected to Pins 3
& 4 on CON1.
 Remove this cable from there &
punch it on Krone.

AIR CON ALARM CABLE

AMIT MISHRA 47
 INSTALLATION PROCESS CONTINUE-

 Remove this cable from pins &


punch it on Krone as shown

Air Con Alarm cable

AMIT MISHRA 48
 INSTALLATION PROCESS CONTINUE-

 TESTING HEAT MANAGEMENT ALARM-

To test Heat Management Alarm cover


the AC from outside with plastic
so that no air can go through as shown
below

Air Condition covered with plastic


sheet

AMIT MISHRA 49
 INSTALLATION PROCESS CONTINUE-

 900 BTS CABINET DOOR SENSOR

The BTS Cabinet door sensor cable is very


small so we have to extend it

Take 1 pair from CAT-5 Cable and solder
it with the sensor wires in BTS (900
Cabinet)

Route this cable properly and fix it near
Smart Pack I/O ports

Connect this pair with pins 3 & 4 of
CON 2

BTS Cabinet door


Sensor

AMIT MISHRA 50
 INSTALLATION PROCESS CONTINUE-

 RECTIFIER CABINET DOOR SENSOR Rectifier Door Sensor

Usually Rectifier door Sensor cables are


already connected to the
CON 1 (X1)•

If it is not connected then connect


Rectifier Door Alarm Cable with
pins 1 & 2 of CON 1 (X1)

Rectifier Door cable connected to


pins 1 & 2 of CON 1

AMIT MISHRA 51
SUMMARY

 Overall summary is that on any BTS site external alarm’s are important.
 Alarm’s make fault finding easy.
 External alarm’s make BTS site safer and easy to maintain.
 Each alarm has it’s own importance cannot be neglected.

AMIT MISHRA 52